Revised Dwg ES101.pdf

PDF 281 KB Posted

Attached to
Z2DA--642-17-100 | Renovate Inpatient Pharmacy for Chemo I. V. Mixing
Solicitation number
36C24421R0046
Issued by

About this file

This solicitation is for general construction and alterations services to renovate an inpatient pharmacy at the Philadelphia VA Medical Center. The scope of work includes renovating existing spaces to provide two chemotherapy mixing labs, one for hazardous materials and one for non-hazardous, a hazardous chemical room, new office space, and a relocated dry drug storage cabinet room. Interested contractors must contact the contracting officer representative by March 23, 2021 to confirm attendance at the mandatory site visit scheduled for that day beginning at 9 AM local time due to COVID-19 social distancing requirements. The solicitation number is 36C24421R0046 and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4 for the project located at 3900 Woodland Ave., Philadelphia, PA 19104.

View the file

Other files

File Type Posted
36C24421R0046 0003.docx DOCX document
Revised Dwg AE 111.pdf PDF
Addnl Dwg AE 111.1.pdf PDF
Revised Dwg S301.pdf PDF
Camera Spec.pdf PDF
36C24421R0046 0002.docx DOCX document
36C24421R0046 0001.docx DOCX document
IP for CM - Full Set of Specifications.pdf PDF
36C24421R0046.docx DOCX document
IP for CM - Full Set of Drawings.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S FA

S FA

S FA

REX

R E

X

REX

DC

ML

DS

DS

DR

D S

D S

DS

DS

D R

DR

M K

D C

DC

M L

ML

IAM

DRD

R

DR

F

F

F

ETR

ETR

WAP

WAP

WAP

AB

FOR PHARMACY DOOR

INTERLOCKING SYSTEM.

ACTIVATION OF THE FIRE ALARM

WILL UNLOCK ALL DOORS

CONNECTED TO THIS SYSTEM

OFFICE

2D135r

OFFICE

2D135t

HD STORAGE

2D135u

PASSAGE

2D135s

STERILE HD

COMPOUNDING

2D135w

STERILE

COMPOUNDING

2D135x

ANTE-ROOM

2D135v

ORDER ENTRY

2D135q

ANTE-ROOM

2D135n

IV CLEAN ROOM

2D135m

FILES

2D135j

VAULT

2D135h

COORDINATE FINAL CAMERA

LOCATION W/ COR IN FIELD

BEOFRE INSTALLATION OF

CAMERA (TYPICAL)

DISCONNECT FROM CEILING &

RE-INSTALL TO ALLOW FOR

NEW CEILING WORK

H

U V WT

F

E

G

13.3

13.2

SECOND FLOOR

DC

ML

R E

X

DS DRMK

DOOR 2D135v

DOOR INTERLOCK

POWER SUPPLY

SEE DRAWING EP101

FINISHED

ACCESSIBLE CEILING

J

DS

DOOR STAUS ON EITHER

SIDE OF DOOR (TYPICAL)

REQUEST TO EXIT IN DOOR

FRAME/LEVER (TYPICAL)

DC

ML

R E

X

DS DR

DOOR 2D135w

J

DS

DC

ML

R E

X

DS DR

DOOR 2D135x

J

DS

TO EX FIRE ALARM SYSTEM

120V

1"C W/ PULLCORD

3/4"C.

OVERHEAD

JUNCTION BOX

(TYPICAL)

IAM

SEQUENCE OF OPERATION

THE ABOVE IS A THREE DOOR INTERLOCKING SYSTEM. OPENING ANY OF

THE THREE DOORS AUTOMATICALLY LOCKS THE OTHER TWO DOORS.

THE KEYSWITCH WILL TURN THE SYSTEM ON OR OFF. REQUEST TO EXIT

SWTICH IN THE LOCK DISABLES THE ELECTROMAGNETIC LOCK.

GENERAL NOTES

1. ALL WORK INVOLED WITH SYSTEM SHALL BE COORDINATED

BETWEEN ALL TRADES INVOLVED.

2. GENERAL HARDWARE ITEMS ARE AS FOLLOWS,

A. 24V DC SURFACE MOUNTED MAGNETIC DOOR LOCKS

B. LED DOOR STATUS INDICATOR

C. DP SWITCH

D. KEYSWITCH

E. PUSHBUTTONS

F. POWER SUPPLY

3. ALL ITEMS ASSOCIATED WITH DOORS MUST BE COORDINATED W/

THE ARCHTECT

1 1

KEY PLAN

AREAS OF WORK

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P

M

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT OF RECORD STAMP

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ENGINEER

SCALE:

533 6TH AVENUE, BETHLEHEM, PA 18018

POC: DEMIKO RICHARDSON

drichardson@cbdg-ae.com

H.F. LENZ COMPANY

1407 Scalp Avenue Johnstown, PA 15904

Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors

As indicated

Philadelphia VA Medical Center 3900 Woodland Ave., Philadelphia, PA 19104

08/27/2020

642-17-100

RJDRGM

Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing

BID SETELECTRICAL FLOOR PLANS - SIGNAL

NEW WORK

ES101

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

PARTIAL SECOND FLOOR PLAN - SIGNAL

NOT TO SCALE

PHARMACY DOOR INTERLOCK SYSTEM

AMENDMENT #3 04/28/2021

MEP-2019-0132x01-2017_rdorich
ES101 - ELECTRICAL FLOOR PLANS - SIGNAL NEW WORK