Revised Dwg S301.pdf
PDF 510 KB Posted
- Solicitation number
- 36C24421R0046
About this file
This document contains construction drawings and details for a federal solicitation to renovate inpatient pharmacy spaces at a Department of Veterans Affairs medical center. The solicitation seeks general construction and alterations services to renovate existing compounding, office, file, and mechanical rooms to provide two chemotherapy mixing labs (non-hazardous and hazardous), a hazardous chemical room, new office space, and relocated dry drug storage. Work includes structural steel framing, ductwork, and building systems. Bidders must confirm site visit attendance by contacting the contracting officer by phone or email due to COVID-19 protocols limiting groups to two individuals. The bid due date is not provided.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24421R0046 0003.docx | DOCX document | |
| Revised Dwg AE 111.pdf | ||
| Revised Dwg ES101.pdf | ||
| Addnl Dwg AE 111.1.pdf | ||
| Camera Spec.pdf | ||
| 36C24421R0046 0002.docx | DOCX document | |
| 36C24421R0046 0001.docx | DOCX document | |
| IP for CM - Full Set of Specifications.pdf | ||
| 36C24421R0046.docx | DOCX document | |
| IP for CM - Full Set of Drawings.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEVEL 4 T/SLAB
102' - 11"
I
HSS 3 1/2 x 1 1/2 x 1/4"
WELDED FRAME AT 7'-1"
MAX. SHOP ASSEMBLE.
MINIMUM 50 KSI STUDS
SECTION 1
1/2" x 1'-0" x 2'-6" PL W/(4) 1/2" DIA. CONC.
ANCHORS W/ 3 1/2" EMBEDMENT. SPA 2'-0"
C/C.
SECTION 1A
1/2" x 7" x 10" PL W/ (4) 1/2" DIA. CONC.
ANCHORS W/ 3 1/2" EMBEDMENT.
SPA 7" C/C .
L 8x4x7/16" NS/FS COL
ENCLOSURE (TYP)
AT SECTION 1 ONLY
EXIST. COLUMN
EXIST. CONCRETE
ENCASED BEAM
EXIST. SLAB
C 6 x 13
3/8" PL WELDED TO BOTH HSS AND C6
9 13/16" +/-
1/4
1/4
3/16
TYP
/2
SECTION 1A SIMILAR
COORDINATE DUCT ENCLOSURE
HSS FRAME DIMENSIONS WITH
ARCHITECTURAL AND MECHANICAL
WORK. SHOP ASSEMBLE TO
GREATEST EXTENT POSSIBLE. HSS
FRAME TO BE ALL WELDED
CONSTRUCTIONS
3/16
3/16
ADDL
TYP
CONTINUOUS
/4 " 3" 3"
(4) 3/4" DIA ADHESIVE CONC
ANCHORS W/4 3/4" EMBEDMENT
COLUMN ENCASEMENT
W /A
R C
H
C O
O R
D
3/16
3/16
TYP 3 SIDES
1/4
(TYP)
2"
L 8X4 CONNECTION TO EXIST COLUMN ENCASEMENT DETAIL
L 8x4 (TYP)
(2) CONC. ANCHOR
(TYP)
EXISTING TIE BAR
DO NOT DAMAGE
LEVEL 4 T/SLAB
102' - 11"
I
W8X18
COORD DUCT
LOCATION W/ MECH
CONTRACTOR
EX COLUMN
(4) 3/4" DIA. ADHESIVE
ANCHORS
W/ 4 3/4" EMBEDMENT
M
IN5
6 1/2" 6" 1 1/2"1 1
SECTION 1-1
L3x3x3/8 (TYP)
1/2" PLATE
3/4" x 4" PLATE
1/4
3 SIDES
1/4
1/4
F
IE
L D
D E
T E
R M
IN
E
M
IN3
1" PLATE
STIFF PL
1/4
3/4" DIA
BOLTS (TYP)
/4
/4
W8x18
LEVEL 4 T/SLAB
102' - 11"
I
W8X18 (TYP)
DUCT.
SEE MECH. DWGS
EXISTING CONC. ENCASED BEAM
SECTION AT DUCT TRANSITION
CANTILEVERED
W8X18 HUNG
FROM W8 ABOVE
W8X18X6" LONG
FOR DUCT SUPPORT
C8 INFILL
W8X18 (TYP)
DO NOT CONNECT
TO EX WALL
3/8" STIFF PL
NS/FS
(TYP)
2 3/4" EA WAY3/4" DIA
BOLTS (TYP)
LEVEL 4 T/SLAB
102' - 11"
I
W8X18 (TYP)
UPPER DUCT.
SEE MECH. DWGS
L 3 x 3 x 3/8"
EXISTING CONC.
ENCASED BEAM
EXISTING BRICK WALL
EXISTING COLUMN
W8X18
C8X11.5 (TYP)
(2) 1/2" DIA. ADHESIVE CONC ANCHORS
W/ 3 1/2" EMBEDMENT 2'-0" C/C
3/8" x 3" x 8" PLATE
DUCT (BEYOND)
COORD W/ MECH CONTRACTOR TO
CLEAR C8. HANG FROM SUPPORTS
DUCT TRANSITION
BEYOND
3/4" x 1'-1" x 2'-6" PLATE
(4) 1/2" DIA ADHESIVE CONC
ANCHORS W/ 3 1/2" EMBED 2'-0" C/C
3/16
3/16
TYP
3/8" GUSSET PL
1/4
1/4
TYP
C8x11.5
SEE SECTION 2
FOR CONNECTION INFORMATION
3/8" x 8" x 2'-6" PLATE
1/4
1/4
F
IE
L D
V E
R
IF
Y
M
IN
1/4
M
IN7
F
IE
L D
L O
C A
T E
M
IN
V E
R
IF
Y
EX STRAP @ 3'-0" O.C.
EX CONTINUOUS ANGLE
LEVEL 4 T/SLAB
102' - 11"
LEVEL 5 T/SLAB
115' - 6 1/4"
/4
/4
S301
S301
S301
S302
1/2" STL. PLATE W/ (4) 1/2" DIA. CONC.
ANCHORS AT EACH FLOOR LEVEL TYP
EA HSS END. REFER TO SECTION 10
T/SLAB
EXIST. BEAM
HSS 3 1/2 x 3 1/2 x 1/4"
HSS 3 1/2 x 3 1/2 x 1/4"
AT EA FLOOR LEVEL
REFER TO SECTION 10 FOR CONN
FOR METAL STUD INFILL
REFER TO ARCH DWGS
10 10
LEVEL 4 T/SLAB
102' - 11"
HSS 3 1/2 x 1 1/2 x 1/4"
HORIZONTAL (TYP)
DUCT. SEE MECH.
DWGS
FACE OF
EXIST BRICK
EXIST. BEAM
EXIST. CONC. SLAB
HSS 3 1/2 x 3 1/2 x 1/4"
(TYP)
1' - 0 1/2" +/-
HSS 3 1/2 x 1 1/2 x 1/4"
VERTICAL (TYP)
SEE SECTION 1
THIS SHEET
FOR PLATE DETAILS
HSS 3 1/2 x 1 1/2 x 1/4"
BRACE (TYP)
HSS 3 1/2 x 1 1/2 x 1/4"
HORIZONTAL (TYP)
DUCT. SEE MECH. DWGS
W8, HUNG FROM BEAM
ABOVE (TYP)
L 3x3x3/8 HANGER
@ EA W8
STL PLATE
H
MECH. ROOM ROOF
T/STL
106' - 4 1/8"
S301
DUCT.
SEE MECH. DWGS
EXISTING WALL
EX 12x26
(3) L 3 1/2x 3x5/16" (GALV)
W/ 1/4" PLATE BELOW
PORTION OF
EXISTING WALL
TO BE REMOVED
L3x3x3/8 (A36) HANGER
@ EA W8
3/8" PLATE (A36)
REMOVE EXIST
BRICK AND CMU
AS NEEDED TO
INSTALL BEAMS.
REPLACE AND
GROUT SOLID.
BEAM PER PLAN
1/4
1/4
3 SIDES
1/4 6
1/4 6
TYP EA END
3/8"x6"x6" (A36)
PLATE
1/4
1/4
1/4
1/4
3 SIDES
3/8" STIFF
PLATE NS/FS
KEY PLAN
AREAS OF WORK
N
I
S301
S101
9 7/8" +/-4 1/2" +/-
1' - 2 3/8" +/-
/2
F A
C E
O F
B R
IC
K
E D
G E
O F
C O
N C
HSS 3 1/2 x 3 1/2 x 1/4"
CONTINUOUS POST
HSS 3 1/2 x 1 1/2 x 1/4" (TYP)
TYP
1/4
TYP
1/4
1/4
TYP
1/2"x10"x10" PLATE W/(4) 1/2" DIA
ADHESIVE CONC ANCHORS SPACED
7"x7" W/ 3 1/2" EMBEDMENT (TYP)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMP
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ENGINEER
SCALE:
533 6TH AVENUE, BETHLEHEM, PA
POC: DEMIKO RICHARDSON
drichardson@cbdg-ae.com
H.F. LENZ COMPANY
1407 Scalp Avenue Johnstown, PA 15904
Phone: 814-269-9300 FAX: 814-269-9301 cadd@hflenz.com www.hflenz.com Engineers - Planners - Surveyors
1As indicated
Philadelphia VA Medical Center 3900 Woodland. Ave., Philadelphia, PA 19104
08/27/20
642-17-100
JAMAMH
Renovate Inpatient Pharmacy for Chemotherapy I.V. Mixing
BID SETSECTIONS AND DETAILS
S301
SCALE: 3/4" = 1'-0"1
SECTION
SCALE: 1" = 1'-0"2
SECTION
SCALE: 1" = 1'-0"3
SECTION
SCALE: 1" = 1'-0"4
SECTION
SCALE: 1/2" = 1'-0"5
SECTION
SCALE: 1" = 1'-0"6
TYPICAL FRAMING DETAIL AT VERTICAL DUCT
SCALE: 1" = 1'-0"7
FRAMING DETAIL AT DUCT ELBOW
SCALE: 1" = 1'-0"8
SECTION
SCALE: 3/4" = 1'-0"9
SECTION
SCALE: 1" = 1'-0"10
SECTION
NOTES:
1. SEE SHEET S001 FOR GENERAL NOTES.
2. REFERENCE ELEVATIONS ARE BASED ON INFORMATION OBTAINED FROM AVAILABLE EXISTING DRAWINGS. CONTRACTOR
SHALL VERIFY ALL ELEVATIONS PRIOR TO START OF CONSTRUCTION AND FABRICATION.
3. WORK THIS DRAWING WITH ARCHITECTURAL DRAWINGS FOR DUCT ENCLOSURE DETAILS.
4. WORK THIS DRAWING WITH MECHANICAL DRAWINGS FOR DUCT LOCATIONS.
5. WORK THIS DRAWING WITH ARCHITECTURAL AND MECHANICAL DRAWINGS FOR LOCATIONS OF WALL PENETRATIONS.
6. GC SHALL COORDINATE NEW DUCT SUPPORTS WITH EXISTING DUCTS, CONDUITS, WINDOW LOCATIONS, AND EXISTING
CONDITIONS PRIOR TO START OF FABRICATION AND INSTALLATION.
7. REFER TO PLANS FOR MEMBER SIZES NOT SHOWN HERE.
8. FOR CONNECTIONS TO EXISTING CONCRETE ENCASEMENT, REMOVE EXISTING BRICK AND TILE AS NEEDED TO INSTALL
NEW WORK. REPLACE AFTER CONSTRUCTION. PACK SOLID WITH GROUT. SEAL WATERTIGHT.
REMOVE EXISTING BRICK AND TILE BLOCK AS NEEDED
TO INSTALL SUPPORTS. REPALCE AFTER
CONSTRUCTION. GROUT SOLID. SEAL WATERTIGHT.
AMENDMENT #3 4/29/2021
| Sheets |
| S301 - SECTIONS AND DETAILS |
File details come from the government source that posted it. Updated .