This is a building permit document for electrical improvements to Ochoa Park (also referred to as Ochoa Sports Complex) located at 3450 North Fairview Avenue, Tucson, Arizona 85705, prepared by the City of Tucson Parks and Recreation Department in coordination with design professionals including Norris Design, GLHN Architects & Engineers, Dibble Corporation, Ninyo & Moore, and Schneider Structural Engineers. The permit, dated December 20, 2024, with project identifier TD-DEV-1223-00486 and TC-COM-0724-01300, encompasses comprehensive electrical infrastructure work including new LED sports field lighting systems, lighting control cabinets, branch circuitry, conduit installation, and associated demolition of existing electrical equipment. The project involves two distinct work areas with electrical site plans showing demolition of existing lighting fixtures and installation of new sport LED lamps mounted on poles with new lighting control cabinets and branch circuits. Design development and completion dates spanned from March 2023 (30% completion) through October 2024, with the permit issued at 100% completion in December 2024. The work includes compliance with National Electrical Code 2017 requirements, installation of ground fault circuit interrupter receptacles, emergency lighting and battery packs, and underground conduit with proper warning tape and trench specifications.

The electrical scope includes new panelboard installations rated at 225 amperes, 277/480 volts, three-phase, four-wire configurations with main circuit breakers and branch circuit protection. Multiple pull boxes and junction boxes are specified throughout the site for continuous wire pulls in underground conduit systems, with contractor responsibility for field verification of exact routing and distances. Existing underground utilities, including irrigation systems, must be protected or repaired at no additional cost to the owner. The permit requires lighting fixture calculations to be submitted to the City of Tucson's permitting department as a deferred submittal package, with final fixture calculations subject to city approval. All electrical work must comply with local codes and requirements, and the contractor is responsible for proper grounding with either UFER ground or copper-clad steel rods meeting National Electrical Code section 250 specifications. The project includes provisions for bee-proof ventilation screening on electrical equipment enclosures and tamper-resistant hardware for cabinet security.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FD-1 FD-1

VA

VA

VA

VA

VA VA

PB

PB

PB

PB PB

PB

PB

PB

PB

PB

PB

PBPB

PB

PB

PB

PB PB PB

PB

PB

PB

PB

PB

PB

PB

PB

PB

PB

PB

J

J

J

J

J

J

J

J

J

PB

J

P

26'-11"

'-4

L1.0

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

R

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00486, TC-COM-0724-01300

02.23.24 100% CD

03.07.24 100% CD

100% CD05.17.24

100% CD07.01.24

100% CD10.07.24

IFC12.20.24

NORTH

OCHOA PARK IMPROVEMENTS - BUILDING PERMIT

NORRIS DESIGN

418 N. TOOLE AVENUE

TUCSON, AZ 85701

PH: (520) 622-9565

WWW.NORRIS-DESIGN.COM

ATTN: JASON KUKLINSKI

JKUKLINSKI@NORRIS-DESIGN.COM

CITY OF TUCSON

PARKS AND RECREATION

DEPARTMENT

900 S. RANDOLPH WAY

TUCSON, AZ 85781

PHONE: (520) 837-8037

ATTN: JOE BARR

JOE.BARR@TUCSONAZ.GOV

GLHN ARCHITECTS & ENGINEERS, INC.

2939 E BROADWAY BLVD.

TUCSON, AZ 85716

PHONE: (520) 881-4546

ATTN: THEODORE MOELLER, PE, LEED AP

TMOELLER@GLHN.COM

DIBBLE

177 N CHURCH AVE, SUITE 1000

TUCSON, AZ 85701

PHONE: (520) 495-4065

ATTN: GREG VEGA, PE

GREG.VEGA@DIBBLECORP.COM

3450 NORTH FAIRVIEW AVE

TUCSON, AZ 85705

PROJECT OVERVIEW

SCALE: 1" = 200'

OWNER / DEVELOPER LANDSCAPE ARCHITECT ELECTRICAL ENGINEERCIVIL ENGINEER

SHEET INDEX

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

R

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00486, TC-COM-0724-01300

02.23.24 100% CD

03.07.24 100% CD

100% CD05.17.24

100% CD07.01.24

100% CD10.07.24

IFC12.20.24

COVER

SHEET

NINYO & MOORE

2939 E BROADWAY BLVD.

TUCSON, AZ 85716

PHONE: (520) 577-7600

FRED NARCAROTI

FNARCAROTI@NINYOANDMOORE.COM

GEOTECHNICAL ENGINEER

SCHNEIDER STRUCTURAL ENGINEERS

435 E 9TH ST.

TUCSON, AZ 85705

PHONE: (520) 512-8183

ATTN: RON SCHNEIDER

RSCHNEIDER@SASTRUCTURAL.COM

STRUCTURAL ENGINEER

N

FA

IR

VI

EW

NORTH

3450 NORTH FAIRVIEW AVE

TUCSON, AZ 85705

SCALE: 3" = 1 MILE

LOCATION MAP

PROJECT

LOCATION

N

OR

AC

LE

R D

W PRINCE RD

W MIRACLE MILE

SHEET DESCRIPTION

L1.0 COVER SHEET

E-001 ELECTRICAL SYMBOLS AND ABBREVIATIONS

E-002 ELECTRICAL OVERALL CODE COMPLIANCE SITE PLAN

E-003 ELECTRICAL COMPLIANCE CODE LIGHTING CALC

ES101-ES102 ELECTRICAL SITE PLAN DEMOLITION

ES201-ES202 ELECTRICAL SITE PLAN

E-501 ELECTRICAL DETAILS

E-601 ELECTRICAL SINGLE LINE DIAGRAM

A.P.N. 106-07-008B

1007 W. PRINCE RD.

ZONED: MH-1

A.P.N. 106-07-008C

(NO ADDRESS)

ZONED: MH-1

ZO

NE

D:

R

-1

A.P.N. 106-08-003A

3165 N. ORACLE RD.

ZONED: R-2

ZONED: R-1

A.

P.

N.

6-

-0

A

W

. P

RI

NC

E

RD

ZO

NE

D:

M

H-

OCHOA SPORTS COMPLEX SCOPE

OF WORK UNDER THIS SUBMITTAL

JACOBS PARK WORK

UNDER SEPARATE

SUBMITTAL

APN 106-08-002D

3450 N FAIRVIEW AVE

CITY OF TUCSON

DKT 8439, PG 1624

ZONED: C-2

APN 106-07-0030

CITY OF TUCSON

DKT 10451, PG 209

ZONED: R-1

APN 106-07-0380

CITY OF TUCSON

DKT 10451, PG 209

ZONED: R-1

DIAGRAM SYMBOLSABBREVIATIONS

1' -6

8' -0

M A

X 6'

-7

6"

EN

C

LO

SE

D C

IR

C

UI

T

BR

EA

KE

R

D

IS

C O

N N

EC

T

PA

N

EL

BO

A

RD

EM

ER

G

EN

C Y

LI

G

HT

S

A N

D B

A

TT

ER

Y

PA

C

KS

C

LO

C K

RE

C

EP

TA

C

LE

A

BO

V E

C O

UN

TE

R

RE

C

EP

TA

C

LE

RECEPTACLE

TYPICAL MOUNTING HEIGHTS

SW

ITC

HE

S

3' -6

A, AMP AMPERE

AC ABOVE COUNTER

AF AMP FUSE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

C CONDUIT

CAB CABINET

CAT CATEGORY

CKT CIRCUIT

CU COPPER

DIA DIAMETER

DL DAMP LABEL

DWG DRAWING

EA EACH

ELEC ELECTRICAL

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EP EMERGENCY POWER

EPO EMERGENCY POWER OFF

(E) EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOT CANDLES

FIXT FIXTURE

FLEX FLEXIBLE METALLIC CONDUIT

G GROUND

GA GAUGE

GALV GALVANIZED

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GRS GALVANIZED RIGID STEEL CONDUIT

HD HEAVY DUTY

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HT HEIGHT

HZ HERTZ

IEEE INSTITUTE OF ELECTRICAL & ELECTRONICS ENGINEERS

ISO INTERNATIONAL ORGANIZATION FOR

STANDARDIZATION

J-BOX,JB JUNCTION BOX

kAIC THOUSAND AMPS INTERRUPTING CAPACITY kHz KILOHERTZ kVA, KVA KILOVOLT AMPERES kW, KW KILOWATTS kWH, KWH KILOWATT HOURS

LSI LONG TIME, SHORT TIME, INVERSE

LSIG LONG TIME, SHORT TIME, INVERSE, GROUND FAULT

LT LIGHT

LV LOW VOLTAGE

LED LIGHT EMITTING DIODE

MA MILLIAMPERE

MAX MAXIMUM

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MH MANHOLE OR METAL HALIDE

MHz MEGAHERTZ

MIN MINIMUM

MLO MAIN LUGS ONLY

MV MEDIUM VOLTAGE

N/A NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRIC MANUFACTURERS

ASSOCIATION

NEUT, N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO. NUMBER

NTS NOT TO SCALE

P POLE

PB PULLBOX

PH,Ø PHASE

PNL PANEL

PWR POWER

REC RECEPTACLE

REQ REQUIRED

RGS RIGID GALVANIZED STEEL

RPM REVOLUTIONS PER MINUTE

SES SERVICE ENTRANCE SECTION

SHT SHEET

SPEC SPECIFICATION

SQ SQUARE

SURF SURFACE

SWBD SWITCHBOARD

TBD TO BE DETERMINED

TP TAMPER PROOF

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

V VOLT OR VOLTS

VA VOLT AMPS

VFD VARIABLE FREQUENCY DRIVE

W WATT OR WIRE

W/ WITH

W/O WITH OUT

WP WEATHERPROOF

XFMR TRANSFORMER

NEW EQUIPMENT ENCLOSURE

DA 1a

DA 1a

DA 1a

DA 1a

AA 1

EM

WA 1a

AA 1

a

R

MA

MA

J 1

J 1 a

XB 1

XA 1

PA 1a

PA 1a

LIGHTING PLAN SYMBOLS COMMON PLAN SYMBOLS

LINE TYPES

P

WALL MOUNTED SWITCH. LETTER INDICATES AS

FOLLOWS:

a - INDICATES SWITCH LEG

2 - 2 POLE SWITCH

3 - 3-WAY SWITCH

4 - 4 WAY SWITCH

D - DIMMER

F - SWITCH UNIT EQUAL TO BUSS SSU OR STY

K - KEY OPERATED

L - LIGHTED HANDLE

LM - LOW VOLTAGE MASTER

M - MOTOR RATED SWITCH. NUMBER OF

POLES AS REQUIRED

Mo - LIGHTING CONTROL MOTION DETECTOR

SWITCH

P - PILOT LIGHT SWITCH

T - TIME OPERATED

WP - WEATHERPROOF

XP - EXPLOSIONPROOF

JUNCTION BOX MOUNTED EXPOSED OR ABOVE

CEILING. 4"x4"xDEPTH PER SPECIFICATIONS, UON.

JUNCTION BOX MOUNTED FLUSH IN WALL, UON.

4"x4"xDEPTH PER SPECIFICATIONS WITH 2-GANG

PLASTER RING, UON. NUMBER INDICATES BRANCH

CIRCUIT.

JUNCTION BOX MOUNTED FLUSH IN FLOOR, UON.

CONDUIT AND WIRE CONCEALED ABOVE CEILING

OR IN WALLS. REFER TO ELECTRICAL WIRING

SPECIFICATIONS FOR SIZE AND TYPE. SEE SINGLE-LINE

DIAGRAM AND/OR PANEL SCHEDULES.

CONDUIT AND WIRE BURIED BELOW GRADE OR

SLAB. REFER TO ELECTRICAL WIRING SPECIFICATION

FOR SIZE AND TYPE. SEE SINGLE-LINE DIAGRAM

AND/OR PANEL SCHEDULES.

CONDUIT AND WIRE HOME RUN TO PANEL SHOWN.

REFER TO ELECTRICAL WIRING SPECIFICATION FOR

SIZE AND TYPE.

CEILING RECESSED FIXTURE. SEE FIXTURE SCHEDULE

FOR TYPE. NUMBER INDICATES BRANCH CIRCUIT,

UPPER CASE LETTERS INDICATE FIXTURE TYPE, LOWER

CASE LETTER INDICATES SWITCH CONTROL.

SURFACE OR PENDANT MOUNTED FIXTURE. SEE

FIXTURE SCHEDULE FOR TYPE AND MOUNTING.

NUMBER INDICATES BRANCH CIRCUIT, UPPER CASE

LETTERS INDICATE FIXTURE TYPE, LOWER CASE LETTER

INDICATES SWITCH CONTROL.

CHANNEL OR STRIP TYPE FIXTURE. SEE FIXTURE

SCHEDULE FOR TYPE. NUMBER INDICATES BRANCH

CIRCUIT, UPPER CASE LETTERS INDICATE FIXTURE TYPE,

LOWER CASE LETTER INDICATES SWITCH CONTROL.

SURFACE MOUNTED FIXTURE. SEE FIXTURE SCHEDULE

FOR TYPE. NUMBER INDICATES BRANCH CIRCUIT,

UPPER CASE LETTERS INDICATE FIXTURE TYPE, LOWER

CASE LETTER INDICATES SWITCH CONTROL.

SURFACE MOUNTED DIRECTIONAL FIXTURE. SEE

FIXTURE SCHEDULE FOR TYPE. NUMBER INDICATES

BRANCH CIRCUIT, UPPER CASE LETTERS INDICATE

FIXTURE TYPE, LOWER CASE LETTER INDICATES SWITCH

CONTROL.

RECESSED FIXTURE. SEE FIXTURE SCHEDULE FOR TYPE.

NUMBER INDICATES BRANCH CIRCUIT, UPPER CASE

LETTERS INDICATE FIXTURE TYPE, LOWER CASE LETTER

INDICATES SWITCH CONTROL.

RECESSED DIRECTIONAL FIXTURE. SEE FIXTURE

SCHEDULE FOR TYPE. NUMBER INDICATES BRANCH

CIRCUIT, UPPER CASE LETTERS INDICATE FIXTURE TYPE,

LOWER CASE LETTER INDICATES SWITCH CONTROL.

EMERGENCY BATTERY PACK WITH DIRECTIONAL

LAMPS. SEE FIXTURE SCHEDULE FOR TYPE. NUMBER

INDICATES BRANCH CIRCUIT, LETTERS INDICATE

FIXTURE TYPE.

SHADING INDICATES LIGHTING FIXTURE WITH

EMERGENCY BATTERY PACK MOUNTED IN FIXTURE,

OR CONNECTED TO EMERGENCY POWER SOURCE.

WALL MOUNTED FIXTURE. SEE FIXTURE SCHEDULE FOR

TYPE. NUMBER INDICATES BRANCH CIRCUIT, UPPER

CASE LETTERS INDICATE FIXTURE TYPE, LOWER CASE

LETTER INDICATES SWITCH CONTROL.

CEILING/WALL EXIT SIGN, SHADING INDICATES

FACES. SEE FIXTURE SCHEDULE FOR TYPE. NUMBER

INDICATES BRANCH CIRCUIT, LETTERS INDICATE

FIXTURE TYPE. PROVIDE DIRECTIONAL ARROWS AS

SHOWN.

LIGHTING TRACK AND TRACK LIGHT. SEE FIXTURE

SCHEDULE FOR TYPE. NUMBER INDICATES BRANCH

CIRCUIT, UPPER CASE LETTERS INDICATE FIXTURE TYPE,

LOWER CASE LETTER INDICATES SWITCH CONTROL.

ONE FIXTURE MOUNTED ON POLE. SEE FIXTURE

SCHEDULE FOR TYPE. NUMBER INDICATES BRANCH

CIRCUIT, UPPER CASE LETTERS INDICATE FIXTURE TYPE,

LOWER CASE LETTER INDICATES SWITCH CONTROL.

TWO FIXTURES MOUNTED ON POLE. SEE FIXTURE

SCHEDULE FOR TYPE. NUMBER INDICATES BRANCH

CIRCUIT, UPPER CASE LETTERS INDICATE FIXTURE TYPE,

LOWER CASE LETTER INDICATES SWITCH CONTROL.

CONTROL RELAY. NUMBERS INDICATE AMPS/POLES.

LIGHTING CONTROL MOTION DETECTOR,

NON-DIRECTIONAL. SEE SPECIFICATIONS FOR TYPE.

A - AUTO ON / AUTO OFF

V - MANUAL ON / AUTO OFF

LIGHTING CONTROL MOTION DETECTOR,

DIRECTIONAL. SEE SPECIFICATIONS FOR TYPE

A - AUTO ON / AUTO OFF

V - MANUAL ON / AUTO OFF

EXISTING

DEMOLITION

NEW

EXISTING UNDERGROUND

DEMOLITION UNDERGROUND

NEW UNDERGROUND

AA 1a

AA 1a

CA 1a

CONTINUATION

SPORTS FIELD PARK LIGHTS

CONDUIT STUB

CONDUIT RISE/FALL

TIME SWITCH

LIGHTING PHOTO CONTROL

POLE MOUNTED POST TOP LIGHT

P CEILING MOUNT CLOSED LOOP DAYLIGHT SENSOR

STEP LIGHT

RC

NB

LIGHTING ROOM CONTROLLER

LIGHTING NETWORK BRIDGE

WALL MOUNTED CHANNEL OR STRIP TYPE FIXTURE.

SEE FIXTURE SCHEDULE FOR TYPE. NUMBER INDICATES

BRANCH CIRCUIT, UPPER CASE LETTERS INDICATE

FIXTURE TYPE, LOWER CASE LETTER INDICATES SWITCH

CONTROL.

DA 1a

DA 1a

EXISTING EQUIPMENT ENCLOSURE

DEMOLISHED EQUIPMENT ENCLOSURE

AA 1

EM

XC 1

J

BOLLARD LIGHT

PANEL

AA

G

M

M

J

N G

P

DRY-TYPE TRANSFORMER. LETTERS DENOTE NAME,

POWER RATING, PRIMARY/SECONDARY VOLTAGE,

PHASE, AND WIRES. SEE SPECIFICATIONS.

CIRCUIT BREAKER PANELBOARDS. SEE SCHEDULES

FOR NUMBER AND SIZES OF BREAKERS, PANEL SIZE,

VOLTAGE, AND INTERRUPTING DUTY.

GENERATOR. NUMBERS INDICATE POWER RATING,

VOLTAGE, POLES, AND WIRES. SEE SPECIFICATIONS.

SWITCH. NUMBERS INDICATE AMPERES/POLES. SEE

SPECIFICATIONS FOR TYPE.

FUSE. NUMBERS INDICATE AMPERE/TRIP RATING. SEE

SPECIFICATIONS FOR TYPE.

CIRCUIT BREAKER. NUMBERS INDICATE TRIP

RATING/POLES. SEE SPECIFICATIONS FOR TYPE.

DRAW-OUT CIRCUIT BREAKER. NUMBERS INDICATE

TRIP RATING AND POLES. SEE SPECIFICATIONS FOR

TYPE.

METER AND CURRENT TRANSFORMERS. SEE

SPECIFICATIONS FOR SIZE AND TYPE.

VOLTMETER OR DIRECT-COUPLED AMMETER. SEE

SPECIFICATIONS FOR TYPE.

CONTACTOR OR CONTROL RELAY CONTACT.

NUMBER INDICATES NEMA SIZE. SEE SPECIFICATIONS

FOR TYPE.

VARIABLE FREQUENCY DRIVE (VFD). SEE

SPECIFICATIONS FOR TYPE.

BUS DIAGRAM SYMBOL

NON-FUSED DISCONNECT DIAGRAM SYMBOL

FUSED DISCONNECT DIAGRAM SYMBOL

NON-FUSED SWITCH STARTER DIAGRAM SYMBOL

FUSED SWITCH STARTER DIAGRAM SYMBOL

MOTOR

CONNECTION POINT

POLE-MOUNTED UTILITY TRANSFORMER. LETTERS

DENOTE NAME, POWER RATING, PRIMARY /

SECONDARY VOLTAGE, PHASE, AND WIRES. SEE

SPECIFICATIONS.

JUNCTION BOX

NEUTRAL/GROUND BUS BARS

PAD-MOUNTED UTILITY TRANSFORMER. LETTERS

DENOTE NAME, POWER RATING, PRIMARY /

SECONDARY VOLTAGE, PHASE, AND WIRES. SEE

SPECIFICATIONS.

PHOTOCELL CONTROL

DUPLEX RECEPTACLE DIAGRAM SYMBOL

(2) DUPLEX RECEPTACLES DIAGRAM SYMBOL

SPECIAL RECEPTACLE DIAGRAM SYMBOL

FAULT SYMBOL

SWITCH DIAGRAM SYMBOL

ELECTRICAL FEEDER ID CALLOUTID

T

AUTOMATIC MOTOR STARTER DIAGRAM SYMBOL

SURGE PROTECTION DEVICESPD

PUSH BUTTON

PHOTOVOLTAIC INVERTER

UPS AND BATTERIES

AUTOMATIC TRANSFER SWITCH. NUMBERS INDICATE

CURRENT RATING, VOLTAGE, AND POLES. SEE

SPECIFICATIONS FOR TYPE.

GROUND CONNECTION.

C

PB

POWER PLAN SYMBOLS

SURFACE METAL RACEWAY WITH RECEPTACLES

AND/OR TELEDATA OUTLETS. SEE DRAWINGS AND

SPECIFICATIONS FOR TYPE AND MOUNTING HEIGHT.

SIMPLEX RECEPTACLE IN 4"x4" BOX WITH PLASTER

RING. NUMBERS INDICATE BRANCH CIRCUIT.

DUPLEX RECEPTACLE, NEMA 5-20R UON, IN 4"x4" BOX

WITH PLASTER RING. NUMBER INDICATES BRANCH

CIRCUIT. "GFCI" INDICATES GROUND FAULT CIRCUIT

INTERRUPTER.

CLOCK MOUNTING RECEPTACLE. NEMA 5-15R UON

IN 2"x4" FLUSH BOX. NUMBER INDICATES BRANCH

CIRCUIT.

ENCLOSED CIRCUIT BREAKER. NUMBERS INDICATE

AMPS/POLES.

DRY-TYPE TRANSFORMER, FLOOR MOUNTED. SEE

SINGLE-LINE DIAGRAM FOR SIZE.

PAD-MOUNTED UTILITY TRANSFORMER. SEE

SINGLE-LINE DIAGRAM FOR SIZE.

PANELBOARD, FLUSH MOUNTED. SEE SINGLE-LINE

DIAGRAM AND PANEL SCHEDULES FOR VOLTAGE,

SIZE, AND POLES.

PANELBOARD, SURFACE MOUNTED. SEE SINGLE-LINE

DIAGRAM AND PANEL SCHEDULES FOR VOLTAGE,

SIZE, AND POLES.

CONTROL PUSHBUTTONS. SEE DRAWINGS FOR TYPES.

LIGHTING OR MOTOR CONTROL CONTACTOR.

NUMBERS INDICATE AMPS/POLES.

HEAVY DUTY NON-FUSED SAFETY SWITCH. NUMBER

INDICATES AMPS/POLES.

HEAVY DUTY FUSED SAFETY SWITCH. NUMBER

INDICATES AMPS/POLES.

AUTOMATIC MOTOR STARTER. NUMBERS INDICATE

POLES AND STARTER SIZE.

COMBINATION SWITCH AND STARTER. NUMBERS

INDICATE AMPS/POLES; STARTER SIZE. CONTROL

VOLTAGE AS REQUIRED.

VARIABLE FREQUENCY DRIVE (VFD). SEE

SPECIFICATIONS FOR TYPE.

AUTOMATIC TRANSFER SWITCH. NUMBERS INDICATE

CURRENT RATING, VOLTAGE, AND POLES. SEE

SPECIFICATIONS FOR TYPE.

PULLBOX, SEE DRAWINGS FOR LOCATION, SIZE, AND

SPECIFICATIONS.

MOTOR

SR

T

AA

AA

CB

POLE MOUNTED UTILITY TRANSFORMER

COMBINATION FUSED SWITCH AND STARTER.

NUMBERS INDICATE AMPS/POLES; STARTER SIZE.

CONTROL VOLTAGE AS REQUIRED.

SPECIAL RECEPTACLE - CEILING MOUNTED

METER

EMERGENCY POWER OFF

PAD-MOUNTED SWITCH

PROJECT GENERAL NOTES

A. FIELD LIGHTING MANUFACTURER WILL PROVIDE EXACT

LOCATIONS OF THE NEW FIELD LIGHTING POLES.

B. ELECTRICAL CONTRACTOR SHALL PROVIDE A CONTINUOUS PULL

WHERE EVER POSSIBLE FOR ALL UNDERGROUND CONDUIT. THE

ALLOWED PULLBOXES ARE SHOWN ON THE PLANS. ADDITIONAL

PULLBOXES ARE TO BE APPROVED BY THE OWNER AND

ENGINEER PRIOR TO INSTALLATION.

C. DAMAGE TO EXISTING UNDERGROUND UTILITIES (INCLUDING

IRRIGATION) WHETHER SHOWN ON THE PLANS OR MARKED AT

THE SITE SHALL BE REPAIRED BY THE CONTRACTOR AT NO

ADDITIONAL COST TO THE OWNER.

D. THIS PLAN SHALL BE USED FOR APPROXIMATE DISTANCES AND

ROUTING. CONTRACTOR SHALL FIELD VERIFY EXACT ROUTING

AND DISTANCES.

E. ALL WORK TO COMPLY WITH NEC 2017 REQUIREMENTS.

CONTRACTOR FOR LIGHTING FIXTURES TO PROVIDE CALCULATIONS

TO CITY OF TUCSON'S PERMITTING DEPARTMENT (OR APPROPRIATE

AUTHORITY) AS A DEFERRED SUBMITTAL PACKAGE. FINAL FIXTURE

CALCULATIONS SHALL BE AT THE DISCRETION OF AND PER CITY OF

TUCSON (OR APPROPRIATE AUTHORITY)

NOTICE OF DEFERRED SUBMITTAL

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

ELECTRICAL SYMBOLS

AND ABBREVIATIONS

E-001

'CA-2'-2

S10

'CA-1'-1,3,5

S11

'CA'-1'-7,9,11

S13

'CA'-1'-2,4,6

S12 'CA'-1'-19,21,23

S15

'CA'-1'-20,22,24

S14

'CA-1'-14,16,18

S19 'CA'-1'-19,21,23

S18 'CA'-1'-13,15,17 S17

'CA'-1'-7,9,11

S16'CA'-1'-1,3,5

'CA-2'-2'CA-2'-2

'CA-2'-2

'CA-2'-2

'CA-2'-2

'CA-2'-4

'CA-2'-4

'CA-2'-4

'CA-2'-4

SA2

'CA-2'-6

'CA'-1'-13,15,17

'CA'-1'-25,27,29

EXISTING

400A SES

EXISTING FIELD I EXISTING FIELD H

EXISTING FIELD G

ADD ALTERNATE 1

ADD ALTERNATE 2

X

X

T

T

KEY MAP

N.

F

AI

RV

IE

W

A

VE

SCALE: 01 1" = 40'-0"

ELECTRICAL OVERALL CODE COMPLIANCE SITE PLAN

20 40 80

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

R

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

ELECTRICAL OVERALL CODE

COMPLIANCE SITE PLAN

E-002

GENERAL NOTES

A. REFER TO E-001 SHEET FOR SYMBOLS, ABBREVIATIONS, AND

PROJECT GENERAL NOTES.

B. REFER TO E-003 FOR LIGHT FIXTURE SCHEDULE, AND OUTDOOR

LIGHTING CALCULATION.

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

ELECTRICAL COMPLIANCE

CODE LIGHTING CALC

E-003

GENERAL NOTES

A. REFER TO E-001 SHEET FOR SYMBOLS, ABBREVIATIONS, AND

PROJECT GENERAL NOTES.

B. REFER TO E-002 FOR ELECTRICAL OVERALL CODE COMPLIANCE

SITE PLAN.

C. CONTRACTOR SHALL SUPPLY THE LIGHTING REPRESENTATIVE A

COMPLETE COPY OF THE CONSTRUCTION DOCUMENTS.

D. CONTRACTOR SHALL PROVIDE POINT BY POINT CALCULATIONS,

CONTROLS DIAGRAMS, AND CONTROLS LAYOUTS AS PART OF

THE LIGHTING AND CONTROLS SUBMITTAL.

EXISTING FIELD I EXISTING FIELD H

1 1 1

1 1 1

70' LIGHT POLE WITH

5' WALKWAY ON TOP

70' LIGHT POLE WITH

5' WALKWAY ON TOP

ADD ALTERNATE 2

SCALE: 01 1" = 40'-0"

ELECTRICAL SITE PLAN DEMOLITION - AREA 1

20 40 80

1. LIGHTING AND WALKWAY TO BE CAREFULLY REMOVED AT TOP

OF POLE. EXISTING POLE TO REMAIN. HANDHOLD PEGS AND

OPENINGS LONG POLE TO BE REMOVED AND SEALED CLOSED.

2. DEMOLISH LIGHTING CABINET. ALL CIRCUITRY REMOVED BACK

TO SOURCE.

KEYNOTES

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

R

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

X

X

T

T

KEY MAP

N.

F

AI

RV

IE

W

A

VE

MATCHLINE - SEE SHEET ES102

AREA

GENERAL NOTES

A. REFER TO E-001 SHEET FOR SYMBOLS, ABBREVIATIONS AND

PROJECT GENERAL NOTES.

ELECTRICAL SITE PLAN

DEMOLITION AREA 1

ES101

EXISTING

400A SES

EXISTING FIELD G

1 1

70' LIGHT POLE

70' LIGHT POLE70' LIGHT POLE

70' LIGHT POLE

ADD ALTERNATE 1

X

X

T

T

KEY MAP

N.

F

AI

RV

IE

W

A

VE

.SCALE: 01 1" = 40'-0"

ELECTRICAL SITE PLAN DEMOLITION - AREA 2

20 40 80

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

R

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

MATCHLINE - SEE SHEET ES101

AREA

GENERAL NOTES

A. REFER TO E-001 SHEET FOR SYMBOLS, ABBREVIATIONS AND

PROJECT GENERAL NOTES.

ELECTRICAL SITE PLAN

DEMOLITION AREA 2

ES102

1. LIGHTING AND WALKWAY TO BE CAREFULLY REMOVED AT TOP

OF POLE. EXISTING POLE TO REMAIN. HANDHOLD PEGS AND

OPENINGS LONG POLE TO BE REMOVED AND SEALED CLOSED.

2. REMOVE 'M' PANEL. CITY OF TUCSON SHALL FIRST SALVAGE

RIGHTS TO REMOVED EQUIPMENT. ELECTRICAL CONTRACTOR TO

DISPOSE OF UNWANTED PORTION(S)OF SALVAGED PANEL 'M'.

3. REPLACE (6) EXISTING LIGHTS IN RESTROOMS WITH NEW LED

FIXTURE. PER FIXTURE SCHEDULE.

KEYNOTES

'CA-2'-2

S10

'CA-1'-1,3,5

S11

'CA'-1'-7,9,11

S13

'CA'-1'-2,4,6

S12 'CA'-1'-19,21,23

S15

'CA'-1'-20,22,24

S14

'CA-1'-14,16,18

PB

PB

PB PB PB

PB

'CA-2'-2'CA-2'-2

'CA-2'-2

'CA-2'-2

'CA-2'-2

PB

'CA'-1'-13,15,17

'CA'-1'-25,27,29

EXISTING FIELD 1 EXISTING FIELD 2

1 1

2Y

10Y

2Y

10Y

(2) SETS

10Y

10Y

10Y

10Y

(2) SETS

2Y

2Y 2Y

SECURITY LIGHT (2)#10,

1#10G,1"C FROM SOURCE

TYP.

10Y

(2) SETS(2) SETS10Y

(4) SETS

ADD ALTERNATE 2

SCALE: 01 1" = 40'-0"

ELECTRICAL SITE PLAN - AREA 1

20 40 80

1. PROVIDE NEW SPORT LED LAMPS AT TOP OF POLES. PROVIDE

BRANCH CIRCUIT AND CONDUIT TO TO NEW LIGHTING CONTROL

CABINET. REFER TO PANEL SCHEDULES FOR CIRCUIT NUMBERS.

KEYNOTES

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

R

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

X

X

T

T

KEY MAP

N.

F

AI

RV

IE

W

A

VE

MATCHLINE - SEE SHEET ES202

AREA

GENERAL NOTES

A. REFER TO E-001 SHEET FOR SYMBOLS, ABBREVIATIONS AND

PROJECT GENERAL NOTES.

ELECTRICAL SITE PLAN

AREA 1

ES201

ID

S19 'CA'-1'-19,21,23

S18 'CA'-1'-13,15,17 S17

'CA'-1'-7,9,11

S16'CA'-1'-1,3,5

PB

PBPB

PB

PB

'CA-2'-4

'CA-2'-4

'CA-2'-4

'CA-2'-4

PB

SA2

'CA-2'-6

EXISTING

400A SES

EXISTING FIELD 3

RENOVATED PLAYGROUND

2E

2Y

2Y

2Y

SECURITY LIGHT (2)#10,

1#10G,1"C FROM SOURCE

TYP.

10Y

7Y

10Y

(2) SETS

10Y

(2) SETS10Y

(4) SETS

2Y

ADD ALTERNATE 1

X

X

T

T

KEY MAP

N.

F

AI

RV

IE

W

A

VE

SCALE: 01 1" = 40'-0"

ELECTRICAL SITE PLAN - AREA 2

20 40 80

1. PROVIDE NEW SPORT LED LAMPS AT TOP OF POLES. PROVIDE

BRANCH CIRCUIT AND CONDUIT TO TO NEW LIGHTING CONTROL

CABINET.

2. PROVIDE NEW GEAR AND LIGHTING CONTROL CABINET. REFER

TO SHEET E-601 FOR ADDITIONAL INFORMATION.

3. PROVIDE NEW GUTTER FOR IRRIGATION WIRE TO RUN THROUGH

AT DEMOLISHED PANEL 'M' LOCATION. FIELD VERIFY EXACT

LOCATION.

KEYNOTES

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

R

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

MATCHLINE - SEE SHEET ES201

AREA

GENERAL NOTES

A. REFER TO E-001 SHEET FOR SYMBOLS, ABBREVIATIONS AND

PROJECT GENERAL NOTES.

B. REFER TO PANEL SCHEDULES FOR CIRCUIT NUMBERS.

ELECTRICAL SITE PLAN

AREA 2

ES202

ID

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

ELECTRICAL DETAILS

E-501

CLEAN BACKFILL MATERIAL

COMPACTED A MINIMUM OF

95% DENSITY AS PER ASTM D698.

CONDUIT. SEE SITE PLAN FOR ROUTING

AND SINGLE LINE DIAGRAM FOR SIZE

3" WIDE RED WARNING TAPE WITH

LARGE BLACK LETTERS READING:

"WARNING - BURIED ELECTRICAL".

PROVIDE TAPE WITH INTEGRAL WIRE FOIL

BACKING OR OTHER MEANS FOR METAL

DETECTION.

" M

IN

. B

EL

O

W

EX

IS

TIN

G G

RA

D

E

SAND BACKFILL

C O

N D

UI

T

12" MAX

A

BO

V E

3"

3/16" X 1" FLAT IRON

WELDED FRAME. PRIME

& PAINT TO MATCH

CABINET (TYP. 3 SIDES)

BEE-PROOF SCREEN.

SUBMIT SAMPLE FOR

OWNER APPROVAL.

1/4"x1-1/2" TAMPER-

RESISTANT BOLT, NUT &

WASHER (TYP. OF 4)

GRIND CORNERS ON

TOP FLANGE TO ROUND

TYP 2 SIDES OF CABINET

CONCRETE PAD.

REFER TO SITE PLAN.

SECTION "A"

CABINET. REFER TO ELECTRICAL

EQUIPMENT ENCLOSURE CABINET

ELEVATION.

A

A

1"

TY

P

SI

D

ES

3" x7

O

PE

N

IN

G

OUTSIDE INSIDE

CABINET FRONT EDGE.

MAX

PROVIDE 3/4" STEEL BAR ACROSS FRONT

OF SWITCHBOARD 4" LONGER THAN

CABINET WIDTH. DRILL HOLE FOR

PADLOCK IN ONE END AND A WELD A

METAL SQUARE PAD AT OTHER END. CITY

OF TUCSON TO PROVIDE LOCKS.

MAXIMUM LENGTH OF ANY ONE BAR IS

THREE SWITCHBOARD SECTIONS. PROVIDE

ADDITIONAL BARS AND HARDWARE AS

NEEDED.

DRILL HOLE FOR 3/4"

ROUND STEEL BAR TO

PASS THROUGH.

WELD PIECE OF 1/8' FLAT BAR TO

EACH SIDE OF EACH CABINET.

WELD ALONG ALL 3 SIDES OF

PLATE. PRIME & PAINT TO MATCH

CABINET (TYP BOTH SIDES)

1/4"

FINISHED GRADE

GROUND BAR AND

EQUIPMENT GROUNDING

CONDUCTOR

PANELBOARD AND BRANCH CIRCUIT

BREAKERS. REFER TO PANELBOARD

SCHEDULES.

MAIN CIRCUIT BREAKER

NEUTRAL BAR AND CONDUCTOR

PHASE CONDUCTORS. REFER TO SINGLE LINE

DIAGRAM FOR ADDITIONAL INFORMATION.

UFER GROUND OR

(2) 3/4" X 8'

COPPER CLAD

STEEL RODS AS

SHOWN.

COPPER GROUNDING

ELECTRODE CONDUCTOR PER

NEC 250. REFER TO SINGLE

LINE DIAGRAM.

6'-0" MIN

UNDERGROUND FEEDER. REFER TO PLANS

FOR SIZE.

G

N

NOTES:

1. FOR UNITIZED ELECTRICAL EQUIPMENT,

PROVIDE BEE-PROOF SCREENS AT EACH

SET OF VENTILATION OPENINGS.

SCALE:1 NOT TO SCALE

CABINET VENTING DETAIL

SCALE:2 NOT TO SCALE

LOCKING BAR DETAIL

SCALE:3 NOT TO SCALE

REMOTE PANELBOARD INSTALLATION DETAIL

SCALE:4 NOT TO SCALE

CONDUIT TRENCH DETAIL

(E)TEP TRANSFORMER

EXISTING TEP PRIMARY

CONDUIT, CONDUCTORS

AND EASEMENT TO

REMAIN.

F1

(E)'SES' 225A, 277/480V, 3PH, 4W,

(35k AIC) SERVICE ENTRANCE RATED EQUIPMENT

35KAIC BRACED

0A

B

US

(E)MCB

225/3

LSG

F2

(E)(4)600 KCMIL

M

N G

(N)CABINET #1

MUSCO

CONTROL

CONTACTOR

CABINET

(N)'CA' 225A, 277/480V, 3PH, 4W

F3

REFER TO PANEL

SCHEDULE

100/3

100/3

PANEL

CA-1

PANEL

CA-2

F3

DECEMBER 20, 2024

CI

TY

O F

TU

CS

ON

OC

HO

A

PA

RK

IM

PR

OV

EM

EN

TS

N

. F

AI

RV

IE

W S

TR

EE

T, T

UC

SO

N

AZ

Parks & Recreation Capital Planning & Development Unit

03.03.23 30% CD

07.10.23 75% CD

418 NORTH TOOLE AVENUE

TUCSON, AZ 85701

P 520.622.9565

12.15.23 100% CD

TD-DEV-1223-00487

100% CD02.23.24

100% CD03.07.24

IFC SET12.20.24

ELECTRICAL SINGLE

LINE DIAGRAM

E-601

SCALE:1 NTS

SINGLE LINE DIAGRAM

03.03.23 30% CD

Sheets and Views
12.01 (Date) E-001 - ELECTRICAL ABBREVIATIONS AND SYMBOLS (Submission)-36x24
P2_12.02 (2024 12 17) E-002 - ELECTRICAL OVERALL CODE COMPLIANCE SITE PLAN (CDS)
12.02 (Date) E-002 - ELECTRICAL OVERALL CODE COMPLIANCE SITE PLAN (Submission)-E-002
P2_12.03 (2024 12 17) E-003 - ELECTRICAL COMPLIANCE CODE LIGHTING CALC (CDS)
12.03 (Date) E-003 - ELECTRICAL COMPLIANCE CODE LIGHTING CALC (Submission)-36x24
P2_12.04 (2024 12 17) ES101 - ELECTRICAL DEMOLITION SITE PLAN - AREA 1 (CDS)
12.04 (Date) ES101 - ELECTRICAL DEMOLITION SITE PLAN - AREA 1-2 (Submission)-ES101
P2_12.05 (2024 12 17) ES102 - ELECTRICAL DEMOLITION SITE PLAN - AREA 2 (CDS)
12.04 (Date) ES101 - ELECTRICAL DEMOLITION SITE PLAN - AREA 1-2 (Submission)-ES102
P2_12.06 (2024 12 17) ES201 - ELECTRICAL SITE PLAN - AREA 1 (CDS)
12.06 (Date) ES201 - ELECTRICAL SITE PLAN - AREA 1-2 (Submission)-ES201
P2_12.07 (2024 12 17) ES202 - ELECTRICAL SITE PLAN - AREA 2 (CDS)
12.06 (Date) ES201 - ELECTRICAL SITE PLAN - AREA 1-2 (Submission)-ES202
P2_12.08 (2024 12 17) E-501 - ELECTRICAL DETAILS (CDS)
12.08 (Date) E-501 - ELECTRICAL DETAILS (Submission)-36x24
P2_12.09 (2024 12 17) E-601 - ELECTRICAL SINGLE LINE DIAGRAM (CDS)
12.09 (Date) E-601 - ELECTRICAL SINGLE LINE DIAGRAM (Submission)-36x24

File details come from the government source that posted it. Updated .