ICT-ASR-HVAC 100 percent Design.pdf
PDF 5 MB Posted
- Solicitation number
- 6973GH-25-Q-00121
About this file
This document is a set of detailed engineering design drawings for an HVAC Replacement Project at the ASR (Airport Surveillance Radar) facility located at Dwight D. Eisenhower National Airport in Wichita, Kansas. The comprehensive set of drawings includes site plans, demolition plans, electrical diagrams, equipment schedules, and grounding specifications for a complete HVAC system replacement. Key technical details include installing new air conditioning units (ACU-1 and ACU-2), air handling units (AHU), electrical panel reconfigurations, and temporary HVAC systems to maintain continuous operations during the renovation. The project involves replacing existing HVAC equipment, rerouting ductwork, updating electrical infrastructure, and ensuring minimal disruption to the airport's technical operations, with specific attention to maintaining radar equipment functionality throughout the construction process.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/1
/2
:4
:5
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -g
.d w g
8 234567
H
G
F
E
D
C
A
B
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-G001
BT
DN
ASR
HVAC REPLACEMENT PROJECT
COVER SHEET, DRAWING INDEX, AND VICINITY MAP
ic t- -g
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1007172
KS
HVAC REPLACEMENT PROJECT
WICHITA, KS
ASR ICT (NASEB)
A
T OF TRANSPO
R T A T
IO
N
M
E R
IC
A
OF
STATES
U N
IT
E D
D E P A R
TM
EN
AVIA
T
IO
N
LA
R
E
D E
F
TRAT
IO
N
SI
NI
M
D A
NOT TO SCALE
VICINITY MAP
DRAWING NUMBER DRAWING TITLE
DRAWING INDEX
ICT-1007172-E002
ICT-1007172-E001
ICT-1007172-M003
ICT-1007172-M002
ICT-1007172-M001
ICT-1007172-D002
ICT-1007172-D001
ICT-1007172-C001
ICT-1007172-G003
ICT-1007172-G002
ICT-1007172-G001
PANELS AND FEEDER SCHEDULES
ONE LINE DIAGRAM, CONDUCTOR AND CONDUIT SCHEDULE
HVAC GROUNDING
HVAC WORK PLAN
HVAC SCHEDULE
ONE LINE DIAGRAM - DEMOLITION/TEMPORARY
HVAC DEMOLITION PLAN
SITE AND CONSTRUCTION STAGING PLAN
HAUL ROUTE
GENERAL AND MECHANICAL NOTES
COVER SHEET, DRAWING INDEX, AND VICINITY MAP
LONGITUDE: -97.43576
LATITUDE: 37.64333
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:0
:5
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -g
.d w g
8 234567
H
G
F
E
D
C
A
B
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-G002
ASR
HVAC REPLACEMENT PROJECT
GENERAL AND MECHANICAL NOTES
ic t- -g
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1007172
KS
GENERAL NOTES GENERAL NOTES CONTINUATION
TIGHT.
THE EXISTING HARDWARE (DOOR, ETC) SHALL BE REINSTALLED AND SEALED WATER/AIR
NEW SYSTEM FOR 72 HOURS, THE ENTIRE TEMPORARY SYSTEM SHALL BE REMOVED AND
COMPLETION OF INSTALLATION, TESTING, AND PROOF OF ACCEPTABLE OPERATION OF THE
OF 72 HOURS PRIOR TO THE EXISTING HVAC SYSTEM BEING DEMOLISHED. UPON WORK
WIRE MESH SCREEN. THE TEMPORARY SYSTEM MUST RUN AND BE TESTED FOR A MINIMUM
SHALL BE INSULATED AND BE OF WEATHERPROOF CONSTRUCTION AND WILL INCLUDE A
THE SPACE, AND WILL ENSURE ADEQUATE AIR DISTRIBUTION. THE RETURN AIR PLENUM
ATTACHED TO A TEMPORARY INSULATED FLEXIBLE DUCTWORK SYSTEM EXTENDING INTO
BE OF WEATHERPROOF CONSTRUCTION. THE INTERIOR PORTION OF THE PLENUM MAY BE
SUPPLY AND/OR RETURN AIR PLENUM. THE SUPPLY AIR PLENUM SHALL BE INSULATED AND
EXISTING DOOR SHOULD BE REMOVED AND TEMPORARILY SEALED OFF TO ACCEPT A
SHOULD BE SKID MOUNTED AND LOCATED ON THE BACK SIDE OF THE BUILDING. THE
CONDITIONS FOR ELECTRONIC EQUIPMENT. THE INSTALLATION OF THE TEMPORARY UNIT
OCCUR. TEMPORARY AIR CONDITIONING UNIT IS TO MAINTAIN CURRENT OPERATING
SHALL ENSURE THAT A BACK-UP UNIT IS READILY AVAILABLE SHOULD ANY PROBLEMS
LOADS FROM THE TEMPORARY AIR HANDLING UNIT SCHEDULE ON DRAWING D001 AND
CONTRACTOR SHALL PROVIDE A TEMPORARY AIR CONDITIONING UNIT MEETING THE 18.
WEATHER CONDITIONS UNTIL INSTALLATION.
MATERIALS. ALL EQUIPMENT SHALL BE STORED INSIDE AND NOT EXPOSED TO ANY
CONTRACTOR SHALL SUPPLY TEMPORARY HOUSING FOR ALL EQUIPMENT, DUCTWORK, AND 17.
CONTRACTOR SHALL USE A PROFESSIONAL RIGGER FOR RIGGING OF ALL EQUIPMENT.16.
AND FAA.
COORDINATE ANY REQUIRED EQUIPMENT SHUTDOWNS WITH THE RESIDENT ENGINEER
CONTRACTOR TO FIELD VERIFY ANY EXISTING CONDUITS AND REROUTE AS NEEDED. 15.
ALL CROSS HATCHING SHOWN ON DRAWING D001 IS DEMOLITION WORK ONLY.14.
NO MECHANICAL WORK IS TO BE DONE IN THE ENGINE GENERATOR ROOM.13.
INSTALLATION SHALL PROVIDE FOR READY ACCESS TO ALL CONTROL DEVICES.12.
WORK SITE.
CONTRACTOR SHALL PROPERLY REMOVE ALL DEMOLITION DEBRIS AND MATERIAL FROM 11.
WALL, THE PATCHES/SEALS MUST MATCH THE CURRENT FIRE RATED SPECS.
WALL SHALL BE REINFORCED AS REQUIRED. IF PENETRATIONS GO THROUGH A FIRE RATED
HOLES/OPENING/ PENETRATIONS IN EXISTING WALLS TO MATCH EXISTING MATERIALS.
WATER/AIR TIGHT. THE CONTRACTOR SHALL PROPERLY PATCH/SEAL AND PAINT ALL
ALL DUCT PENETRATIONS THROUGH WALLS SHALL BE SLEEVED, CAULKED, AND SEALED 10.
MAY PREVENT THE CORRECT INSTALLATION OF THE NEW MECHANICAL SYSTEM.
OBSERVATIONS OF EXISTING CONDITION WHICH ARE DISCOVERED IN THE FACILITY THAT
CONTRACTOR SHALL IMMEDIATELY REPORT TO THE RESIDENT ENGINEER (RE) ALL 9.
THE MANUFACTURER.
ALL POWER, INTERLOCKING WIRE, AND ALL CONTROL WIRING SHALL BE INSTALLED PER 8.
CONTROL AND MEASURING DEVICES.
CONTRACTOR SHALL INSTALL ALL APPROVED PIPE AND FITTINGS NECESSARY FOR THE 7.
HEIGHTS REQUIRED BY THE APPROVED APPLICABLE CODES AND REGULATIONS.
CONTRACTOR SHALL MOUNT ALL WALL MOUNTED CONTROLLING DEVICES AT THE MINIMUM 6.
OTHERWISE NOTED.
THE MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS, UNLESS
CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH 5.
APPROVED PURCHASED EQUIPMENT.
CONTRACTOR SHALL PROVIDE ALL NEW EQUIPMENT SUPPORTS AND SHALL BE FOR THE 4.
NOT BE SCALED TO DETERMINE THE EXACT LOCATIONS OF MECHANICAL WORK.
DIAGRAMMATIC AND ARE TO CONVEY SCOPE, GENERAL ARRANGEMENT ONLY, AND SHALL
REQUIRED DURING INSTALLATION TO BEST SUITE THE CONDITIONS. THE DRAWINGS ARE
CONTRACTORS AND EMPLOYEES WORKING AT THE FACILITY. SOME OFFSETS WILL BE
CONTRACTOR SHALL COORDINATE ALL WORK TO AVOID ANY AND ALL CONFLICTS WITH 3.
AS REQUIRED BY THE CODES.
MECHANICAL SYSTEMS OPERATES AS INDICATED IN THE DRAWINGS, SPECIFICATION, AND
COMPLETELY INSTALL THE NEW MECHANICAL SYSTEMS; AND SHALL MAKE SURE THE NEW
CONTRACTOR SHALL PROVIDE ALL MATERIALS, EQUIPMENT, AND LABOR REQUIRED TO 2.
THAT IS TO BE DEMOLISHED.
BEFORE THE START OF ALL WORK, CONTRACTORS SHALL VERIFY THEIR SCOPE OF WORK 1. 19. ALL DEMOLITION WORK AND NEW WORK IS TO COMPLY WITH FEDERAL, STATE, AND
LOCAL REGULATIONS.
20. ALL ELECTRICAL WORK SHALL COMPLY WITH SPECIFICATION FAA-C-1217H (INTERIOR
ELECTRICAL WORK) AND FAA-STD-019G (LIGHTING PROTECTION, GROUNDING, BONDING,
ETC.). CONTRACTOR SHALL VERIFY EXISTING POWER PANEL CAPACITY AND REPLACE
WIRING AND/OR CIRCUIT SIZE TO EXISTING POWER PANEL AS NECESSARY.
21. RADAR EQUIPMENT SHALL REMAIN OPERATIONAL THROUGHOUT THE PROJECT DURATION.
ALL FAA EQUIPMENT MUST BE PROTECTED FROM ALL CONSTRUCTION DEBRIS AT ALL
TIMES.
22. ALL EXTERIOR SUPPLY AND RETURN AIR DUCTWORK SHALL BE EXTERNALLY INSULATED
USING 2" THICK INSULATION. THAT IS NON-MICROBIAL TYPE AND EXTERIOR DUCTWORK
IS PROPERLY SEALED WEATHER TIGHT.
23. CONTRACTOR MUST PROVIDE SECURITY MEASURES ON ALL DUCTWORK PENETRATIONS
TO THIS FACILITY TO PREVENT ANY ACCESS THROUGH HOLES IF DUCTWORK IS REMOVED.
24. CONTRACTOR MUST SEAL ALL HOLES/OPENING IN EXTERIOR WALLS WATER/AIR TIGHT
DUE TO ALL DEMOLITION AND NEW WORK.
25. CONTRACTOR SHALL REBALANCE EXISTING AIR DEVICES
26. CONTRACTOR SHALL CLEAN AND SANITIZE ALL REMAINING EXISTING DUCTWORK AND AIR
DEVICES. CLEANING SHALL BE PERFORMED WITH A HEPA VACUUM CLEANER, BRUSHING
AND WIPING SURFACES. THE CONTRACTOR MUST BE A CERTIFIED MEMBER OF NATIONAL
AIR DUCT CLEANING ASSOCIATION (NADCA) AND HAVE A MINIMUM OF FIVE (5) YEARS
EXPERIENCE IN HVAC CLEANING.
27. ALL DIMENSIONS ARE FOR DESIGN PURPOSES. DIMENSIONS SHALL BE FIELD VERIFIED BY
THE CONTRACTOR DURING BIDDING
ABBREVIATIONS
AIR CONDITIONING
AIR CONDITIONING UNIT
AIR COOLED CONDENSER UNIT
ACCESS DOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AIRPORT SURVEILLANCE RADAR
BACKDRAFT DAMPER
BOTTOM OF DUCT/DIFFUSER
BTU PER HOUR
CONTROL DAMPER/CEILING DIFFUSER
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
CONNECTION
CONTRACTING OFFICER TECHNICAL REPRESENTATIVE
COMPUTER ROOM UNIT
CONTROL VALVE
EXHAUST AIR
ENTERING AIR TEMPERATURE
ELECTRIC DUCT HEATER
EXHAUST FAN
EXHAUST GRILLE
ENERGY MANAGEMENT AND CONTROL SYSTEM
EXTERNAL STATIC PRESSURE
EXISTING TO REMAIN
ELECTRIC UNIT HEATER
FILTER / CARBON FILTER
FRESH AIR
FAHRENHEIT DEGREES, DRY BULB
FAHRENHEIT DEGREES, WET BULB
HIGH LIMIT HUMIDIFIER SENSOR
HORSEPOWER
KILOWATT
LINEAR FEET
MINIMUM CIRCUIT AMPS
MOTORIZED DAMPER
NATIONAL PIPE THREAD
NOISE CRITERIA / NORMALLY CLOSED
NORMALLY OPEN
OPPOSED BLADE DAMPER
OUTSIDE AIR
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH GAUGE
REGISTER
RESIDENT ENGINEER
RETURN FAN
RETURN GRILLE
RETURN REGISTER
ROUND
SUPPLY AIR
SMOKE CONTROL PANEL
SUPPLY FAN
SUPPLY GRILLE
SUPPLY REGISTER
STRAINER
THERMOSTAT (T-STAT)
TRANSFER GRILLE
TRAP PRIMER
TEMPERATURE SENSOR
TYPICAL
VOLUME DAMPER
WATER COLUMN
WATER PRESSURE DROP
DOWN
EXISTING
ROOM DESIGNATION
WET BULBDRY BULB
ELEVATION
NONENONE65°
CLIMATIC ZONE SCHEDULE - INTERIOR DESIGN CONDITION
CLIMATIC ZONE SCHEDULE - EXTERIOR DESIGN CONDITION
95°F
75° 75°
TEMPERATURE °F
DESIGN
SUMMER INDOOR
DESIGN OPERATION TEMP
COOLING EQUIPMENT
SET POINT
CONTROL
COOLING
SET POINT
HUMIDIFICATION
SET POINT
DEHUMIDIFICATION
-8.4°F 91.5°F 75°F
NOTE: THESE DESIGN TEMPERATURES AND SET POINTS ARE TO BE ADJUSTABLE.
ASR-9 EQUIPMENT ROOM
PER ASHRAE 99.6%
WINTER DESIGN TEMP
AND SET POINT °F
DESIGN TEMPERATURE
WINTER INDOOR
745 FT
PER ASHRAE 0.4%
SUMMER DESIGN TEMP
T
AIR VENT
DROP IN PIPING
SUPPLY AIR REGISTER SIDEWALL
T
MANUAL VOLUME DAMPER
TEMPERATURE SENSOR
DESCRIPTIONGRAPHIC
FIRE DAMPER (MOTORIZED)
SMOKE DETECTOR
M
FLEXIBLE CONNECTION
RISE OR DROP IN DUCTWORK (SUPPLY)
TURNING VANES IN ELBOW
UNION
PLUG VALVE
TEST PORT
OUTSIDE AIR GRILLE
CD CONDENSATE DRAIN
RISE IN PIPING
FS
PIPE FLEXIBLE CONNECTION
AP OR AD ACCESS PANEL OR ACCESS DOOR
VD
RETURN AIR GRILLE SIDEWALL
FLEXIBLE DUCTWORK
HG
L
HOT GAS PIPING
LIQUID PIPING
SUPPLY DUCT
DEMOLITION WORK
RETURN/EXHAUST AIR DUCT
ELECTRIC UNIT HEATER
MOTORIZED CONTROL DAMPER (CD)
FIRE/SMOKE DAMPER (MOTORIZED)
HVAC LEGEND
(OUTSIDE AIR)
RISE OR DROP IN DUCTWORK
EXHAUST GRILLE
RETURN AIR REGISTER, GRILLE OR
FIGURES INDICATE NET INSIDE DIMENSION
DUCT SIZE, FIRST FIGURE IS SIDE SHOWN
(RETURN / EXHAUST)
RISE OR DROP IN DUCTWORK
R
OR DROP (D)
CHANGE OF ELEVATION RISE (R)
DIRECTIONAL ARROWS
CEILING DIFFUSER WITH AIR FLOW
12x20
SUPPLY DUCT (UNDER THE DUCT WORK)
AC
ACU
ACCU
AD
AFG
AHU
ASR
BDD
BOD
BTUH
CD
CFH
CFM
CONN
COR
CRU
CV
DN
EA
EAT
EDU
EF
EG
EMCS
ESP
ETR
EUH
EXIST. EA
F
FA
FDB
FWB
HL
HP
KW
LF
MCA
MD
NPT
NC
NO
OBD
OA
PRV
PSIG
R
RE
RF
RG
RR
RND
SA
SCP
SF
SG
SR
STR
T
TG
T PRIMER
TS
TYP
VD
WC
WPD
Site
GATE
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/1
/2
:4
:0
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -g
.d w g
8 234567
H
G
F
E
D
C
A
B
FLIGHT CREWS.
5. ALL LIGHTING WILL BE SHIELDED BY THE CONTRACTOR SO THAT IT DOES NOT AFFECT THE AIR TRAFFIC CONTROL TOWER OR
(TBD).
(RE), WHO WILL COORDINATE THE REQUEST WITH AIRPORT OPERATIONS. AIRPORT OPERATIONS CAN BE CONTACTED AT #
HOURS WRITTEN NOTICE (WEEKENDS EXCLUDED) OF REQUESTED CLOSING SHALL BE DIRECTED TO THE RESIDENT ENGINEER
ENABLE NECESSARY NOTICES TO AIRMEN (NOTAMS) OR ADVISORIES TO AIRPORT SERVIES OR TENANTS, A MINIMUM OF 72
4. NO RUNWAY, TAXIWAY, APRON OR AIRPORT ROADWAY SHALL BE CLOSED WITHOUT APPROVAL OF AIRPORT OPERATIONS. TO
TAXIWAYS, AND APRONS SHALL HAVE PRIORITY OVER THE CONTRACTOR'S TRAFFIC.
RADIO PROCEDURES AT THE AIRPORT. IT SHALL BE UNDERSTOOD BY THE CONTRACTOR THAT AIRPORT TRAFFIC ON RUNWAYS, INSTRUCTED BY AIRPORT OPERATIONS IN THE REGULATION GOVERNING OPERATIONS ON THE AIRCRAFT MOVEMENT AREA AND
CONTACT WITH THE ATCT. THE EMPLOYEE SHALL BE BADGED BY DFW AIRPORT OPERATION OFFICE, TRAINED AND
SAFETY AREAS, AND APPROACH CLEAR ZONES SHALL DO SO UNDER DIRECT CONTROL OF A BADGED EMPLOYEE IN RADIO
AIRPORT OPERATIONS AREA (AOA). ALL VEHICLES THAT ARE REQUIRED TO ACCESS OR CROSS ACTIVE RUNWAYS, TAXIWAYS,
3. THE CONTRACTOR SHALL MAINTAIN AND MONITOR COMMUNICATIONS WITH THE ATCT AT ALL TIMES WHILE INSIDE THE
USE AT ALL TIMES.
ADDITION, EACH VEHICLE AND PIECE OF EQUIPMENT SHALL HAVE A ROTATING YELLOW BEACON MOUNTED ON THE ROOF FOR
AND EQUIPMENT ITEM IN ALL WORK AREAS SHALL DISPLAY A FLAG WHICH SHALL BE MAINTAINED VERTICAL AT ALL TIMES. IN
VEHICLE AND EQUIPMENT USE, AND ONE FOOT SQUARE FOR PERSONAL USE. EACH SEPARATE GROUP OR INDIVIDUAL VEHICLE
2. THE CONTRACTOR SHALL FURNISH AIRCRAFT WARNING FLAGS, COLORED ORANGE AND WHITE, THREE FOOT SQUARE FOR
COMPLY WITH ALL FAA PART 139 TRAINING REQUIREMENTS AND REGULATIONS.
150/5370-2G AND AUGMENTED BY THESE PLANS AND SPECIFICATIONS, WILL APPLY TO THE WORK. THE CONTRACTOR SHALL
1. THE CONTRACTOR IS ADVISED THAT CERTAIN RULES AND RESTRICTIONS, AS CONTAINED IN FAA ADVISORY CIRCULAR
SAFETY PLAN:
PROTECTION TO THESE FACILITIES.
AIRPORT OPERATIONS. REQUIREMENTS OF THE CONTRACT SHALL NOT LIMIT ANY OBLIGATIONS TO MAINTAIN ADEQUATE
THE OPERATION OF AIR TRAFFIC CONTROL. THEIR FAILURE DUE TO CONSTRUCTION ACTIVITY MAY CAUSE DISRUPTION TO
10. CONTRACTOR OPERATIONS WILL OCCUR AROUND FAA FACILITIES AND EQUIPMENT. THESE FACILITIES ARE CRITICAL TO
IMMEDIATELY RESTORED TO ITS ORIGINAL CONDITION BY THE CONTRACTOR AT HIS OWN EXPENSE.
CONSTRUCTION VEHICLES BE KEPT CLEAR OF DEBRIS AT ALL TIMES. ANY AREA DAMAGED DURING CONSTRUCTION SHALL BE
9. THE CONTRACTOR SHALL MAKE SURE ALL TAXIWAYS, RUNWAYS, ROADS AND APRONS THAT ARE USED OR CROSSED BY
AUTHORITIES TO KEEP THE AIRPORT IN OPERATION.
BE LIMITED AND/OR REFUSED FOR LIMITED PERIODS OF TIME. THE CONTRACTOR MUST COOPERATE WITH AIRPORT
BADGED ESCORT. THE CONTRACTOR'S ATTENTION IS CALLED TO THE FACT THAT ACCESS TO CERTAIN CONTRACT AREAS MAY
8. THE CONTRACTOR CANNOT CROSS ANY ACTIVE RUNWAY OR TAXIWAY TO DELIVER MATERIAL OR WORKMEN WITHOUT A
IMPEDE THE PROGRESS OF THE WORK.
PROJECT, WILL BE ALLOWED DUE TO THE PHASING OF THE WORK OR DUE TO NORMAL WEATHER CONDITIONS WHICH MAY
7. NO ADDITIONAL COMPENSATION OR EXTENSION OF TIME OF COMPLETION FOR THE PROJECT, OR ANY PHASE OF THE
THE VARIOUS WORK SITES.
FOR THE CONSTRUCTION, REPAIR, AND/OR MAINTENANCE OF ALL HAUL ROADS TO AND FROM THE DESIGNATED ENTRANCE TO
DESIGNATED. NO PERSONAL VEHICLES WILL BE PERMITTED WITHIN THE AOA. THE CONTRACTOR SHALL BE RESPONSIBLE
PERSONNEL NECCESSARY TO DO THE WORK SHALL ENTER AND LEAVE THE CONTRACT SITE VIA THE GATES AND ROUTES
6. THE CONTRACTOR SHALL PLAN HIS CONSTRUCTION OPERATION SO THAT MATERIAL, EQUIPMENT, SUPPLIES, AND WORKING
WORK SITE.
5. WHEN SO ORDERED BY THE RE, THE CONTRACTOR SHALL REMOVE ALL EQUIPMENT, MACHINERY AND MATERIALS FROM THE
WITHOUT COORDINATION WITH AIRPORT OPERATIONS AND ATCT.
CONTRACTOR BE PERMITTED TO PARK VEHICLES/EQUIPMENT OR STORE MATERIALS OUTSIDE OF THE STAGING AREA SHOWN
CONTRACT SITE TO THE MUTUAL BENEFIT OF ALL IN COMPLETING THEIR RESPECTIVE WORK. IN NO CASE WILL THE
4. THE CONTRACTOR SHALL COOPERATE IN EVERY WAY WITH ANY OTHER CONTRACTOR DOING WORK ON OR NEAR THE
ACCESS THROUGH THE RE 48 HOURS PRIOR TO THE DESIRED ACCESS TIME.
3. ACCESS TO FAA FACILITIES MUST BE COORDINATED WITH THE LOCAL FAA SSC OFFICE. THE CONTRACTOR SHALL REQUEST
OPERATION OF THE AIRPORT.
SPECIFIED SO AS TO OFFER THE LEAST OBSTRUCTION AND/OR IMPEDIMENT TO AIRPORT TRAFFIC AND THE GENERAL
THE WORK IS AN ESSENTIAL FEATURE OF THIS CONTRACT AND WILL REQUIRE THE COMPLETION OF ALL WORK HEREIN
2. THE AIRPORT WILL BE IN OPERATION WHILE CONSTRUCTION UNDER THIS CONTRACT IS TAKING PLACE. COORDINATION OF
CHANGE IN THE REQUIREMENTS FOR ENTERING AND OPERATING WITHIN THE AOA.
RESTRICTED AREA. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO FAMILIARIZE CONSTRUCTION PERSONNEL WITH ANY
PERSONNEL SECURITY BADGES, AND SATISFY ALL SECURITY REQUIREMENTS PRIOR TO BEGINNING WORK WITHIN THE
1. ALL CONSTRUCTION WILL OCCUR WITHIN THE AOA. THE CONTRACTOR WILL BE REQUIRED TO OBTAIN ALL VEHICLE PASSES, AIPORT OPERATIONS:
THE PERIOD OF CONSTRUCTION.
5. THE CONTRACTOR MUST MAINTAIN DRAINAGE TO PREVENT PONDING OR FLOODING DURING
GRADE, AS APPROPRIATE AND IN ACCORDANCE WITH FAA ADVISORY CIRCULAR 150/5300-13.
SHALL BE RETURNED TO WITHIN 3 INCHES OR A MAXIMUM 5% SLOPE OF EXISTING OR FINISHED
BE BACKFILLED OR COVERED IAW AIRPORT OPERATIONS GUIDANCE. IN ADDITION, THE AREA
4. NO EXCAVATION SHALL REMAIN OPEN AFTER ANY WORK SHIFT. ALL OPEN EXCAVATIONS MUST
AND/OR DARKNESS. UNDER NO CIRCUMSTANCES ARE FLARE POTS PERMITTED.
(ACCEPTABLE TO AIRPORT OPERATIONS AND THE FAA) DURING HOURS OF RESTRICTED VISIBILITY
SHALL BE PROMINENTLY MARKED WITH BARRICADES AND LIGHTED WITH RED LIGHT UNITS
3. OPEN TRENCHES, EXCAVATIONS, AND STOCKPILED MATERIALS AT THE CONSTRUCTION SITE
COMPLETE CONSTRUCTION SCHEDULE.
THAN 30 DAYS PRIOR TO THE START OF CONSTRUCTION AND MUST BE ACCOMPANIED BY A
AIDS WHICH WILL BE AFFECTED BY THE CONSTRUCTION. THE REQUEST MUST BE MADE NO LESS
COORDINATE WITH THE FAA PROJECT ENGINEER FOR A SHUTDOWN OF THOSE NAVIGATIONAL
2. AFTER AWARD OF THIS CONTRACT AND PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL
SERVICE.
INFRASTRUCTURE SHALL BE INSTALLED PRIOR TO REMOVING THE EXISTING FACILITY FROM
1. THE CONTRACTOR SHALL PHASE THE CONSTRUCTION OF THE GLIDE SLOPE. ALL PRACTICABLE
CONSTRUCTION ACTIVITIES:
LEGEND:
- PATH
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-G003
BT
DN
ASR
HVAC REPLACEMENT PROJECT
HAUL ROUTE
ic t- -g
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1007172
KS
ASR
ENGINE
GENERATOR
ROOM
AHU
36" x 12" 28" x 12" 16" x 12"
(ABOVE CEILING)
EXISTING DUCT
EQUIPMENT
ROOM
(BELOW CEILING)
EXISTING DUCT
EACH DIFFUSER)
NEW SYSTEM 567CFM
(EXISTING BALANCE
20" DIA. NECK
6 CEILING DIFFUSERS
6 PLACES
12" X 9" (TYP.)
(BELOW CEILING)
EXISTING DUCT
4 CEILING DIFFUSERS
DIFFUSERS
2 CEILING
PANEL MDPE
PANEL MODES
PANEL MDP
AHU ECONOMIZER
EXISTING
DISCONNECT
ACU 1
DISCONNECT
ACU 2
CONDUIT
DISCONNECT
ACU 1
LINE
REFRIGERATION
ACU 1
LINE
REFRIGERATION
ACU 2
BOX
JUNCTION
BOX
JUNCTION
ACU
ACU
STAGING AREA
CONCRETE PAD
EXISTING
STORAGE
EXISTING BOLLARD (TYP)
CONDUIT
DISCONNECT
ACU 2
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:3
:0
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -c
.d w g
8 234567
H
G
F
E
D
C
A
B
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-C001
ASR
HVAC REPLACEMENT PROJECT
SITE AND CONSTRUCTION STAGING PLAN
ic t- -c
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1007172
KS
1. EXISTING CONCRETE PAD FOR THE EXISTING HVAC UNITS TO BE REUSED.
2. EXISTING BOLLARDS ARE TO BE REUSED
3. EXISTING DUCT WORK TO BE REUSED
4. DIMENSIONS TO BE VERIFIED ON SITE.
NOTES:
NOT TO SCALE
SITE AND CONSTRUCTION STAGING PLAN
EXISTING BOLLARD (TYP)
(ABOVE CEILING)
EXISTING DUCT
(BELOW CEILING)
EXISTING DUCT
567CFM EACH DIFFUSER
BALANCE NEW SYSTEM
20" DIA. NECK (EXISTING
6 CEILING DIFFUSERS
6 PLACES
12" X 9" (TYP.)
DISCONNECT
ACU 1
DISCONNECT
ACU 2 LEAD/LAG SWITCHES
ARE CONNECTED TO
2 THERMOSTATS
(4 THERMOSTATS)
ON AHU 1
1 THERMO-HYGRO
EXISTING CONCRETE PAD
DIFFUSERS
2 CEILING
4 CEILING DIFFUSERS
PANEL MDPE
PANEL MODES
PANEL MDP
AHU ECONOMIZER
EXISTING
CONDUIT
DISCONNECT
ACU 1
CONDUIT
DISCONNECT
ACU 2
LINE
REFRIGERATION
ACU 1
COMPLETION THE DOOR SHALL BE REINSTALLED
TEMPORARY SUPPLY AIR PLENUM. UPON
THIS OPENING SHALL BE USED FOR THE
DOOR SHALL BE REMOVED AND STORED.
OPPOSITE SIDE OF THE BUILDING TO COOL THE EQUIPMENT.
DUCTWORK WILL NEED TO BE ROUTED TO THE
TEMP HVAC ROUTING THROUGH THE DOOR.
BOX
JUNCTION
BOX
JUNCTION
10'
LINE
REFRIGERATION
ACU 2
1006032081200020
A/C UNIT
TEMPORARY
ROOM
EQUIPMENT
ASR
OUTSIDEAHU-T
MAX. CIRCUIT BREAKERHZPHV
ELECTRICAL
CFMNOMINAL COOLING CAPACITY (TONS)TYPESERVESLOCATIONMARK
TEMPORARY AIR CONDITIONING UNIT SCHEDULE
ROOM
GENERATOR
ENGINE
ACU
ACU
AHU
STORAGE
36" x 12" 28" x 12" 16" x 12"
EQUIPMENT ROOM
AHU
TEMP HVAC
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:3
:1
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -d
.d w g
8 234567
H
G
F
E
D
C
A
B
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-D001
ND
ASR
HVAC REPLACEMENT PROJECT
HVAC DEMOLITION PLAN
ic t- -d
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1007172
KS
WORK.
THIS PROJECT. REVIEW THESE PROCEDURES PRIOR TO EACH OUTAGE PHASE OF
LOCKOUT/TAGOUT PROCEDURES SHALL BE STRICTLY ENFORCED THROUGHOUT 14.
OUTAGE/CUTOVERS.
CONFIRM BRANCH CIRCUIT LAYOUT AND MOUNTING DETAILS PRIOR TO PLANNING
OUTAGE WORK. PERFORM FIELD INVESTIGATION ON EACH PANELBOARD AND
ACCOMPLISH AS MUCH NON-OUTAGE WORK AS POSSIBLE PRIOR TO START OF 13.
BEFORE START OF WORK.
AND DISCUSS OUTAGE PLAN WITH RE AND FAA TECHNICIAN EACH EVENING
PRIOR TO START OF BUSINESS EACH MORNING. REFER TO CRITICAL LOAD LIST
OCCUR DURING CLOSED HOURS OF OPERATION. POWER MUST BE RESTORED
CONTINUOUS POWER THROUGHOUT PROJECT. ALL FACILITY OUTAGES SHALL
IDENTIFY ALL CRITICAL BRANCH CIRCUITS WITHIN FACILITY TO HAVE 12.
AHU
DEMOLISH ALL ASSOCIATED ELECTRICAL EQUIPMENT AND ITEMS TO THE ACU & 11.
DEMOLISH EXISTING ECONOMIZER10.
DEMOLISH 2 JUNCTION BOXES NEAR PANEL MDP9.
DEMOLISH ACU 1 & ACU 2 DISCONNECT8.
DEMOLISH AHU 1 & AHU 27.
DEMOLISH ACU 1 & ACU 26.
BEFORE ANY DEMOLITION WORK CAN START
TEMPORARY UNIT MUST BE PROVEN BY RUNNING FOR A MINIMUM OF 72 HOURS 5.
SUBCONTRACTOR WILL REPLACE THE DOOR AT NO COST TO THE FAA
CONTRACTOR WILL SAFELY REMOVE AND STORE THE DOOR. IF DAMAGED, THE 4.
THERMOSTATS CONTROLLING THE TEMPORARY AIR CONDITIONING UNIT
CONTRACTOR WILL NEED TO PROVIDE FEEDERS AND CONTROL WIRING TO 3.
CONTRACTOR SHALL ENSURE PROPER FILTERS ARE INSTALLED AND MAINTAINED2.
WITH A NEW CIRCUIT BREAKER PROPERLY SIZED.
SCHEDULE ON THIS SHEET. PROVIDE ELECTRICAL SERVICE FROM PANEL MDPE
CONTROLS FOR APPROVAL PRIOR TO THE START OF AN WORK, REF AHU-T
SPECIFICATIONS FOR TEMPORARY CONDITIONING UNIT, DUCTWORK AND
CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF DUCTWORK LAYOUT AND 1.
DEMOLISH EQUIPMENT
DEMOLISH CONDUIT
LEGEND:
DEMOLITION NOTES:
NOT TO SCALE
HVAC DEMOLITION PLAN
TEMP HVACMDPE1 1/4" EMT
4 #2
#8G
TERMINATES ATFED FROMCONDUIT SIZECONDUCTOR SIZE#
CONDUCTOR AND CONDUIT SCHEDULE
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:0
:0
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -d
.d w g
8 234567
H
G
F
E
D
C
A
B
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-D002
ND
ASR
HVAC REPLACEMENT PROJECT
ONE LINE DIAGRAM - DEMOLITION/TEMPORARY
ic t- -d
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1007172
KS
M
NEW KCPL
SERVICE
PRIMARY
MIN
12.47KV, 480/277 VAC 2.0%Z
TRANSFORMER
WESTAR ENERGY UTILITY
400A
3P
350A
FUSES
DISCONNECT
ENTRANCE
SERVICE
SPD
RAYVOSS
PANELBOARD
SQUARE D QMB 364W
, 4W BUS, ?3
400A MLO, 480/277 VAC, MAIN DISTRIBUTION PANEL: MDP
225A
3P
, 4W BUS, ?3
600A MLO, 208Y/120 VAC,
225A
3P
100A
3P
DISTRIBUTION PANEL: MDPE
125A
3P
20A
3P
100A
3P
125A
3P
125A
3P
125A
3P
40A
3P
600A
3P
GEN
60A
3P
3?, 4W, NAT GAS
85KW, 277/480V,
175A
LOAD
BANK
M
REMOTE
RADIATOR
PANEL
MDPE-A
PANEL
ELPA
MDPE-B
(UPS)
SPARESPARE
200A
3P
175A
FUSES
200A
3P
175A
FUSES
200A
3P
175A
FUSES
ATS W/ BYPASS
800A
480/277 VAC
TEMP ACU. ENSURE YOU USE THE CORRECT WIRE SIZE.
PROVIDE (1) 100A CIRCUIT BREAKER IN DISTRIBUTION PANEL MDPE FOR USE TO
PROVIDE 100A HEAVY DUTY FUSED DISCONNECTS AT TEMPORARY ACU LOCATION. 4.
REVIEWED BY THE R.E. AND FAA FOR APPROVAL PRIOR TO INSTALLATION.
CONDUIT. CONDUCTOR ROUTING SHALL NOT FORM A TRIP HAZARD AND SHALL BE
SERVICE TEMPORARY ACU. TEMPORARY CIRCUIT SHALL BE INSTALLED IN
PROVIDE TEMPORARY FEEDERS, TEMPORARY CONDUIT, AND TERMINATIONS TO 3.
SSC APPROVAL TO MINIMIZE IMPACT ON OPERATIONS
BREAKER AND CONDUCTOR INSTALLATIONS. OUTAGES SHALL BE PERFORMED PER
MODES PANEL B. POWER OUTAGE FOR PANEL MDPE SHALL BE REQUIRED FOR
COORDINATE WITH FAA FOR WORK WITHIN DISTRIBUTION PANEL MDPE AND 2.
FOR WALL MOUNTED DEMOLISHED EQUIPMENT.
AND PROVIED WALL PATCHING AND PAINTING TO MATCH IF REQUIRED BY THE R.E
LEVEL. PLUG HOLES IN CABINETS AND PANELS LEFT BY DEMOLITION OF CONDUIT
EQUIPMENT SHALL ALSO BE DEMOLISHED. CAP "IN SLAB" CONDUITS AT SLAB
ALL CONDUIT, CONDUCTORS, DISCONNECTS, AND TERMINATIONS OF DEMOLISHED 1.
SW1
MIS
MBP
RAYVOSS
SPD
3P
175A
BATT.
CABINET
EATON 9390
UPS
MBP
3P
125A
PANEL
ALARM
REMOTE
LOAD BANK
TAP BOX /W
DISCO.
200A
3P
175A
FUSES
200A
3P
175A
FUSES
PANEL
MDPC
SW2
400A/3P
3P
175A
175A
3P
3P
100A
PORTABLE
LOAD BANK
100A
3P
100A
FUSES
RAYVOSS
SPD
%Z 5.1
, 3W?3
480/208V
112.5KVA
15A
3P
, 4W BUS,3
200A, 120/208 VAC,
15A
3P
30A
3P
MODES PANEL B
AHU 2
HANGING
UNIT
MSJB 1
ASR-9 STORAGE
BLD
30A
3P
40A
3P
FEI
A
DPS
A
15A
3P
W
RESPT.
15A
3P
FEI
A
OUTLET
DPS
A
OUTLET
30A
3P
FEI
B
15A
3P
30A
3P
CODEX #2 AHU 1
FLOOR
UNIT
15A
3P
SW
RESPT.
40A
3P
40A
3P
DPS
B
SPARE
15A
3P
15A
3P
FEI
B
OUTLET
DPS
B
OUTLET
15A
3P
15A
3P
CODEX #1 CODEX
RESPT.
1. UNLESS OTHERWISE NOTED, ALL CIRCUIT BREAKERS AND/OR SWITCHES ARE THREE POLE.
2. ALL ELECTRICAL EQUIPMENT AND WIRING SHOWN IN A LIGHT LINE, IS EXISTING TO
REMAIN.
3. ALL ELECTRICAL EQUIPMENT AND WIRING SHOWN IN A DARK LINE, IS TEMPORARY WORK
UNDER THIS CONTRACT.
4. ALL ELECTRICAL EQUIPMENT AND WIRING SHOWN IN A DARK DASHED LINE, IS TO BE
REMOVED UNDER THIS
CONTRACT.
TEMP
HVAC
GENERAL ONE-LINE DIAGRAM NOTES: DEMOLITION NOTES:
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:3
:3
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -m
.d w g
8 234567
H
G
F
E
D
C
A
B
AIR CONDITIONING UNIT SCHEDULE
MARK LOCATION SERVES TYPE
CAPACITY
COOLING
CFM ENTERING AIR (°F ) CONDENSER MOTOR EVAP FAN MOTOR REFRIGERANT COMPRESSOR ELECTRICAL DATA DRIVE TYPE FILTERS
NUMBER OR EQUAL
MANUFATURER AND MODEL
BASIS OF DESIGN
DB WB HP FLA QYT HP RPM FLA TYPE QTY STAGE VAC PH HZ MCA MOCP TYPE SIZE (INCH) QTY
ACU-1 OUTSIDE
ROOM
ASR EQUIPMENT
CONDENSER 240000 12000 0.25 1.50 4.00 R410A SCROLL 2 3 208 3 60 75 100 DIRECT 38AUDU25 OR EQUIVALENT
ACU-2 OUTSIDE
ROOM
ASR EQUIPMENT
CONDENSER 240000 12000 0.25 1.50 4.00 R410A SCROLL 2 3 208 3 60 75 100 DIRECT 38AUDU25 OR EQUIVALENT
AHU-1 INSIDE
ROOM
ASR EQUIPMENT
AIR HANDLER 240000 68.00 57.00 5.00 1760.00 18.00 R410A 208 3 60 23 40 MERV 8 4…16 X 20 X 2, 4…16 X 24 X2 8 CARRIER 40RUA25
AHU-2 INSIDE
ROOM
ASR EQUIPMENT
(HANGING)
AIR HANDLE
240000 68.00 57.00 5.00 1760.00 18.00 R410A 208 3 60 23 40 MERV 8 4…16 X 20 X 2, 4…16 X 24 X2 8 CARRIER 40RUA25
NOMINAL: 8000
AIRFLOW RANGE:
6000-10000
NOMINAL: 8000
AIRFLOW RANGE:
6000-10000
INCLUDE OVERHEAD SUSPENSION ACCESSORY FOR AHU TO BE HUNG FROM THE CEILING LIKE THE EXISTING.15.
CONDENSATE DRAIN SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS.14.
.38AUDU25 AND CARRIER 40RUA25UNITS MUST MEET OR EXCEED 13.
POWERED CONVENIENCE OUTLET.12.
FACTORY INSTALLED SUPPLY AIR SMOKE DETECTOR KIT.11.
FACTORY INSTALLED LOW AMBIENT KIT.10.
CONTRACTOR TO FURNISH AND INSTALL A ECONOMIZER THAT IS COMPATIBLE WITH AHU2 (HANGING UNIT).9.
REFRIGERANT CIRCUITS.
PROVIDE THERMOSTATIC EXPANSION VALVE, FILTER DRIER, AND SIGHT GLASS ON EACH OF THE8.
WITH AUTOMATIC/MANUAL SWITCH OVER AND START OF STANDBY/BACKUP DUTY UNIT SHALL FAIL.
PROVIDE TWO PROGRAMMABLE THERMOSTATS TO CONTROL EACH UNIT. THERMOSTATS SHALL BE PROVIDED7.
BEARINGS, AND NON SEIZE UP OPERATIONS.
CONDENSING FANS WITH WEATHERPROOF MOTORS, MEDIUM PRESSURE DRIVES, SELF LUBRICATING BALL6.
ELECTRO-COATING FOR CORROSION PREVENTION TO THE CONDENSING COILS AND EVAPORATING COILS.5.
VERIFY WITH MANUFACTURER FOR SHIPPING WEIGHTS.4.
COMPRESSOR ANTI-SHORT CYCLE CONTROL.3.
HINGED ACCESS DOORS FOR INDOOR FAN, COMPRESSOR, CONTROL BOX, AND FILTER.2.
FACTORY CONDENSER COIL PROTECTOR GRILLE/HAIL GUARD.1.
ACU-1 AND ACU-2 SEQUENCE OF OPERATIONS:
2 MINUTES. THE SYSTEM WILL CONTINUE TO OPERATE REGARDLESS OF THE STATUS OF THE FILTER SWITCH.
IS ENERGIZED WHEN THE SUPPLY FAN IS OPERATING AND THE CLOGGED FILTER SWITCH HAS BEEN CLOSED FOR AT LEAST
THE PRESSURE DIFFERENTIAL ACROSS THE FILTERS DECREASES TO APPROXIMATELY 0.4" WC THE LOGGED FILTER OUTPUT
PRESSURE DIFFERENTIAL ACROSS THE FILTERS IS AT LEAST 0.5" W.C. THE CONTACTS WILL AUTOMATICALLY OPEN WHEN
DIFFERENTIAL ACROSS THE RETURN AIR FILTERS. A DIAGNOSTIC SERVICE SIGNAL IS SENT TO THE REMOTE PANEL IF THE
DIRTY FILTER ALARM - UNITS WILL BE SUPPLIED WITH THE OPTIONAL CLOGGED FILTER SWITCH MONITORS THE PRESSURE5.
OF THE UNIT AND REQUIRES A MANUAL RESET.
DETECT SMOKE DUE TO FIRE IN THE AIR CONDITIONING OR VENTILATION DUCTS. IT PROVIDES HIGH LIMITS SHUTDOWN
SMOKE DETECTION SHUTDOWN - UNITS WILL BE SUPPLIED WITH SMOKE DETECTOR SENSOR. THE SENSOR IS USED TO4.
WILL OPERATE IN ECONOMIZER MODE WITH OA INTAKE.
IF THE OUTSIDE AIR TEMPERATURE IS LOWER THAN THE SET POINT (55 DEG F, ADJUST ABLE), THEN THE HANGING UNIT
EXCEEDING THE SET POINT, THE DUTY UNIT WILL STAGE THE COMPRESSORS TO SATISFY THE SET POINT TEMPERATURE.
COOLING: WHENEVER THE DUTY UNIT IS OPERATIONAL, AND THE SPACE THERMOSTAT SENSES THE TEMPERATURE3.
VENTILATION AIR SHALL BE PROVIDED AT ALL TIMES WHENEVER THE DUTY OR STANDBY/BACKUP UNIT IS OPERATIONAL.
VENTILATION (HANGING AHU ONLY): THE SHELTER REQUIRED AMOUNT (TO BE DETERMINED BY CONTRACTOR) OF2.
ANY SET BACK/SETUP TEMPERATURE CONTROL. THE CONTROL SYSTEM SHALL BE TWO (2) DIGIT AL THERMOSTATS.
ONLY TO THE ASR ELECTRONIC EQUIPMENT ROOM. THIS SYSTEM SHALL BE ACTIVE 24 HOURS, 7 DAYS A WEEK WITHOUT
GENERAL: THESE SPLIT SYSTEM AIR CONDITIONING UNITS SHALL BE CONSTANT VOLUME AND PROVIDING COOLING AIR1.
NOTES:
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-M001
QE
ND
ASR
HVAC REPLACEMENT PROJECT
HVAC SCHEDULE
ic t- -m
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
EXISTING BOLLARD (TYP)
DISCONNECT
ACU 1
NEW
DISCONNECT
NEW ACU 2
2 LEAD/LAG SWITCHES
CONNECTED TO
2 THERMOSTATS ARE
CONCRETE PAD
EXISTING
(ABOVE CEILING)
EXISTING DUCT
(BELOW CEILING)
EXISTING DUCT
BALANCE NEW SYSTEM
20" DIA. NECK (EXISTING
6 CEILING DIFFUSERS
6 PLACES
12" X 9" (TYP.)
(BELOW CEILING)
EXISTING DUCT
4 CEILING DIFFUSERS
DIFFUSERS
2 CEILING
PANEL MDPE
PANEL MODES
PANEL MDPC
PANEL HVAC
ECONOMIZER
AHU
GFCI
NEW
CONDUIT
DISCONNECT
ACU 1
REFRIGERATION LINE
ACU 1
CONDUIT
DISCONNECT
ACU 2
LINE
REFRIGERATION
ACU 2
3/4 CONDENSATE LINE
AHU 1
3/4 CONDENSATE LINE
AHU 2
120"
86 3/8"
/8
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:3
:4
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -m
.d w g
8 234567
H
G
F
E
D
C
A
B
STORAGE
36" x 12"
ENGINE
GENERATOR
ROOM
36" x 12" 28" x 12" 16" x 12"
EQUIPMENT ROOMNEW
ACU 1
NEW
ACU 2
NEW
AHU 1
NEW
AHU 2
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-M002
QE
ND
ASR
HVAC REPLACEMENT PROJECT
HVAC WORK PLAN
ic t- -m
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1007172
KS
REUSE THE EXISTING PENETRATION TO RUN NEW CONDENSATE PIPING.
CONTRACTOR WILL TIE IN THE EXISTING CONDENSATE PIPING TO THE NEW AHU IF POSSIBLE. IF NOT,7.
REFRIGERANT LINES CAN NOT BE BURIED.6.
EQUALLY DISTRIBUTE CFM ACROSS ALL DIFFUSERS AND TEST.5.
CLEAN AND VACUUM ALL EXISTING INTERIOR DUCTWORK.4.
AHUs TO BE CONNECTED TO THE EXISTING DUCTWORK.3.
ALL INTERIOR DUCTWORK TO REMAIN.4.
ACUs TO HAVE MINIMUM 1 FOOT CLEARANCE FROM EDGE OF THE CONCRETE PAD.3.
INSTALL AN ECONOMIZER THAT IS COMPATIBLE WITH AHU2.2.
ACU, AHU, DISCONNECTS, AND ASSOCIATED CABLING TO BE INSTALLED.1.
NOTES:
LEGEND
NEW EQUIPMENT
NEW CONDUIT
NOT SCALE
HVAC WORK PLAN
CONDUIT
DISCONNECT
ACU 1
REFRIGERATION LINE
ACU 1
CONDUIT
DISCONNECT
ACU 2
REFRIGERATION LINE
ACU 2
DISCONNECT
ACU 1
CONDUCTOR
4/0 GROUND
ACU 1
DISCONNECT
ACU 2
CONDUCTOR
4/0 GROUND
ACU 2
EXISTING EES
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:2
:5
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -m
.d w g
8 234567
H
G
F
E
D
C
A
B
ENGINE
GENERATOR
ROOM
ACU 1
ACU 2
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-M003
QE
ND
ASR
HVAC REPLACEMENT PROJECT
HVAC GROUNDING
ic t- -m
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1007172
KS
NOTES:
LEGEND
NEW WORK
FOR EACH GROUND CONDUCTOR.
CONTRACTOR TO PROVIDE AND INSTALL 1" SCHEDULE 80 PVC CONDUIT TO A MINIMUM 12" BELOW GRADE5.
MECHANICAL LUGS AND SHALL BE APPLIED ACROSS ALL EXTERIOR AND INTERIOR DUCTWORK SECTIONS.
PROVIDE 6 AWG JUMPER ACROSS HVAC DUCTWORK SECTIONS. JUMPER SHALL BE INSULATED 6AWG WITH4.
BOXES.
GROUNDS SHALL NOT BE PERMITTED. INCLUDE GROUNDING PIGTAILS IN ALL SWITCH AND RECEPTACLE
PROVIDE DEDICATED EQUIPMENT GROUNDS FOR EACH OVERCURRENT DEVICE. SHARED EQUIPMENT3.
DISCONNECTS, AND HANDHOLES.
GRS BELOW GRADE AND EXTERIOR CONDUITS SHALL INCLUDE GROUND BUSHINGS AT ALL J-BOXES,2.
ALL BELOW GRADE GROUNDING CONNECTIONS SHALL BE EXOTHERMICALLY WELDED - NO EXCEPTIONS.1.
NOT SCALE
HVAC GROUNDING
TVSSPANEL HVAC CKT #142" EMT
4 #3/0
1 #1/0G
AHU FLOOR UNITPANEL HVAC CKT #73/4" EMT4 #86
ACU 2PANEL HVAC CKT #81 1/4" EMT
4 #2
1 #8G
ACU 1PANEL HVAC CKT #21 1/4" EMT
4 #2
1 #8G
GFCI RECEPTACLEPANEL HVAC CKT #153/4" EMT3 #123
AHU HANGING UNITPANEL HVAC CKT #13/4" EMT4 #82
PANEL HVACPANEL MDPE2" EMT
4 #3/0
1 #6G
TERMINATES ATFED FROMCONDUIT SIZECONDUCTOR SIZE#
CONDUCTOR AND CONDUIT SCHEDULE
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:3
:1
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -e
.d w g
8 234567
H
G
F
E
D
C
A
B
M
NEW KCPL
SERVICE
PRIMARY
2.0%Z MIN
12.47KV, 480/277 VAC
TRANSFORMER
WESTAR ENERGY UTILITY
400A
3P
350A
FUSES
DISCONNECT
SERVICE ENTRANCE
SPD
RAYVOSS
SQUARE D QMB 364W PANELBOARD
, 4W BUS,3
400A MLO, 480/277 VAC,MAIN DISTRIBUTION PANEL: MDP
225A
3P
, 4W BUS, 3
600A MLO, 208Y/120 VAC,
225A
3P
100A
3P
DISTRIBUTION PANEL: MDPE
SPARE SPARE 100A
3P
200A
3P
SPARE 125A
3P
600A
3P
GEN
60A
3P
, 4W, NAT GAS3
85KW, 277/480V,
175A
LOAD
BANK
M
REMOTE
RADIATOR
PANEL
MDPE-A
PANEL
ELPA
MDPE-B
(UPS)
ACU
ACU
200A
3P
175A
FUSES
200A
3P
175A
FUSES
200A
3P
175A
FUSES
ATS W/ BYPASS
800A
480/277 VAC
SW1
MIS
MBP
R A
Y V
O S S
S P
D 3P
175A
BATT.
CABINET
EATON
9390 UPS
MBP
A /3
P
PANEL
ALARM
REMOTE
LOAD
BANK TAP
BOX /W
DISCO
200A
3P
175A
FUSES
200A
3P
175A
FUSES
PANEL
MDPC
SW2
400A/3P
3P
175A
175A
3P
3P
100A
PORTABLE
LOAD
BANK
100A
3P
100A
FUSES
R A
Y V
O S S
S P
D
%Z 5.1
, 3W3
480/208V
112.5KVA
15A
3P
200A, 120/208 VAC,
15A
3P
SPARE
MODES PANEL B
MSJB 1
ASR-9
STORAGE
BLDG.
30A
3P
40A
3P
FEI
A
DPS
A
15A
3P
W
RESPT.
15A
3P
FEI
A
OUTLET
DPS
A
OUTLET
30A
3P
FEI
B
15A
3P
SPARE
CODEX #2
15A
3P
SW
RESPT.
40A
3P
SPARE
DPS
B
15A
3P
15A
3P
FEI
B
OUTLET
DPS
B
OUTLET
15A
3P
15A
3P
CODEX #1 CODEX
RESPT.
AHU 2
HANGING
UNIT
AHU 1
FLOOR
UNIT
GFCI
RECEPTACLE
SPARE
, 4W BUS, 30 SPACES3
200A MLO, 208Y/120 VAC, DISTRIBUTION PANEL: HVAC
40A
3P
20A
1P
100A
3P
100A
3P
40A
3P 3P
100A SPARE SPARE
TVSS
DISCONNECTS
100A 3P
2 3 4 5 6 7
REMOVE ALL TEMPORARY POWER EQUIPMENT INSTALLED DURING CONSTRUCTION.7.
ADD GFCI TO PANEL HVAC ON A 20A BREAKER6.
MOVE ACU 1 AND ACU 2 FROM PANEL MDPE TO PANEL HVAC ON 100A BREAKERS 5.
MOVE A/C HANGING AND A/C FLOOR UNITS TO DISTRIBUTION PANEL HVAC ON 30 BREAKERS.4.
INSTALL A NEW 200A 3P 30 SPACE HVAC PANEL AFTER THE MDPE PANEL.3.
INSTALL 200A BREAKER INTO PANEL MDPE2.
ENCLOSURES, CONDUIT ETC. LEFT BEHIND BY DEMOLITION.
REMOVE TEMPORARY EQUIPMENT IN ITS ENTIRETY. CAP ALL SEAL ALL UNUSED/UNREMOVABLE1.
INSTALLATION NOTES:
LEGEND
NEW WORK
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-E001
QE
ND
ASR
HVAC REPLACEMENT PROJECT
ONE LINE DIAGRAM
ic t- -e
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
1RAYVOSS120-3Y-M3-4-06-ASPD
6BUSSMANN100A FUSESFUSES
2SQUARE D100A NEMA 3R. 2 POLE FUSEDHVAC DISCONNECT SWITCH
1NQ TYPE200A 3P 30 SPACE 120/208V 3P 4WHVAC PANEL
QYTMODELEQUIPMENT
RECOMMENDED EQUIPMENT LIST
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV DESCRIPTION JCN
DATE
REDLINE
APVD
SUBMITTED BY APPROVED BY
JCN
DRAWN
CHECKED
REV
ISSUED BY
H
G
F
E
D
C
B
A
8 1234567
DATE
DRAWING NO
DESIGNED
REVIEWED BY
/3
/2
:3
:2
A
M P lo tt e d b y S
R V
C -C
A E
G -E
D M
S -C
O O
R D
DATE
APPROVED
ic t- -e
.d w g
8 234567
H
G
F
E
D
C
A
B
MDPE-B (UPS)
-- 100 A 3
HVAC PANEL -- 200 A 3
23 24
21 3 40 A SPARE 22
PANELBOARD A 40 A 3
17 18
15 16
ASR-9 225 A 3 3 125 A STORAGE BID (SW#3)
11 12
9 10
ELPA 225 A 3 3 125 A COMPRESSOR #2
5 6
3 4
MDPE-A 100 A 3 3 125 A COMPRESSOR #1
NO.
CKT
DESCRIPTIONS CIRCUIT SIZE
AMPS
TRIP
POLES POLES
AMPS
TRIP
CIRCUIT SIZE DESCRIPTIONS
NO.
CKT
PANELBOARD:MDPE
31 A/C UNIT "FLOOR" -- 30 A 3
27 CODEX #2 -- -- 1 1 -- -- CODEX RESPT. 28
25 W RESPT. -- -- 1 1 -- -- CODEX #1 26
23 DPS A OUTLET -- -- 1 1 -- -- DPS B OUTLET 24
21 FEI A OUTLET -- 20 A 1 1 20 A -- FEI B OUTLET 22
19 1 20 A -- SW RESPT. 20
17 18
-- 15 A 3
3 30 A -- SPARE 16
A/C UNIT "CEILING" -- 30 A 3
11 12
9 DPS A 3 3 20 A -- DPS B 10
-- 40 A
5 6
3 4
FEI A -- 30 A 3 30 A
FEI B
NO.
CKT
DESCRIPTIONS CIRCUIT SIZE
AMPS
TRIP
POLES POLES
AMPS
TRIP
CIRCUIT SIZE DESCRIPTIONS
NO.
CKT
MSJB 1
23 24
21 3 SPARE 22
SPARE 3
17 18
15 16
GFCI RECEPTACLE 20 A 1 3 100 A TVSS
11 12
9 10
AHU FLOOR UNIT 40 A 3 3 100 A ACU #2
5 6
3 4
AHU HANGING UNIT 40 A 3 3 100 A ACU #1
NO.
CKT
DESCRIPTIONS CIRCUIT SIZE
AMPS
TRIP
POLES POLES
AMPS
TRIP
CIRCUIT SIZE DESCRIPTIONS
NO.
CKT
1SPACE
SPACE
(ESSENTIAL)
ENCLOSURE: NEMA 1
MOUNTING: SURFACE
SUPPLY FR.: SW1
LOCATION: EQUIPMENT ROOM
MCB FRAME / TRIP SIZE: 600 AF/400 AT
MAINS TYPE / LOCATION: TOP
VOLTAGE: 208Y/120V, 3P, 4W, 60HZ
NEUTRAL BUS RATING: 100%
MINIMUM BUS RATING: 600 A
INTERRUPTING RATING (KA SYMMETRICAL): 14 KA
(E) PANELBOARD:MODES
ENCLOSURE: NEMA 1
MOUNTING: SURFACE
SUPPLY FR.:
LOCATION: GENERATOR ROOM
MAINS TYPE / LOCATION: MLO / BOTTOM
VOLTAGE: 208Y/120V, 3P, 4W, 60HZ
NEUTRAL BUS RATING: 100%
MINIMUM BUS RATING: 200 A
INTERRUPTING RATING (KA SYMMETRICAL): 10 KA
NEW PANELBOARD:HVAC
ENCLOSURE: NEMA 1
MOUNTING: SURFACE
SUPPLY FR.: MDPE
LOCATION: EQUIPMENT ROOM
MCB FRAME / TRIP SIZE: 200AF/400AT
MAINS TYPE / LOCATION: TOP
VOLTAGE: 208Y/120V, 3P, 4W, 60HZ
NEUTRAL BUS RATING: 100%
MINIMUM BUS RATING: 200 A
INTERRUPTING RATING (KA SYMMETRICAL): TBD KA
NOTES:
LEGEND
NEW WORK
PANEL SCHEDULE.
CONTRACTOR TO PROVIDE ALL THE NECESSARY CIRCUIT BREAKERS FOR THE NEW LOADS PER THE6.
CONTRACTOR TO LEAVE THE BREAKERS IN THE PANEL AS SPARES.5.
CONTRACTOR TO SUPPLY FUSES AND 1 TO 1 EXTRA.4.
CONTRACTOR TO SUPPLY PROPER BREAKERS.3.
UPDATE PANEL SCHEDULES TO REFLECT THE CHANGES MADE.2.
MUST BE PERFORMED TO HAVE AN ACCURATE VALUE.
VA LOADS SHOWN ON THE PANELBOARD FOR EXISTING LOADS ARE ASSUMPTION ONLY. FIELD SURVEY1.
SPARE
REPLACE BREAKER WITH
IS
S
U E
D F
O R
E D
M
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
DO
NOT
SI
GN
08/07/2024
MGR: ENGINEERING - KANSAS CITY
WICHITA
ICT-1007172-E002
QE
ND
ASR
HVAC REPLACEMENT PROJECT
PANELS AND FEEDER SCHEDULES
ic t- -e
.d w g
INFRASTRUCTURE
ENGINEERING SERVICES
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
C O
N S
T R
U C
T
IO
N
DWIGHT D EISENHOWER NATIONAL AIRPORT
DRAWING PRODUCED ON ACE RO CAD SYSTEM
PROJECT ENGINEER
| ict-1007172-g001__Earl D-CTR Garcia |
| ict-1007172-g001 |
| ict-1007172-g002__Earl D-CTR Garcia |
| ict-1007172-g002 |
| ict-1007172-c001__Earl D-CTR Garcia |
| ict-1007172-c001 |
| ict-1007172-d001__Earl D-CTR Garcia |
| ict-1007172-d001 |
| ict-1007172-d002__Earl D-CTR Garcia |
| ict-1007172-d002 |
| ict-1007172-m001__Earl D-CTR Garcia |
| ict-1007172-m001 |
| ict-1007172-m002__Earl D-CTR Garcia |
| ict-1007172-m002 |
| ict-1007172-m003__Earl D-CTR Garcia |
| ict-1007172-m003 |
| ict-1007172-e001__Earl D-CTR Garcia |
| ict-1007172-e001 |
| ict-1007172-e002__Earl D-CTR Garcia |
| ict-1007172-e002 |
| ict-1007172-g001.pdf |
| ict-1007172-g001 |
| ict-1007172-g003.pdf |
| ict-1007172-g003 |
File details come from the government source that posted it. Updated .