Hult Center Improvements_Drawings.pdf
PDF 6 MB Posted
- Solicitation number
- S-KE0010-00016903
- Issued by
- Lane County, Oregon
About this file
This file contains construction drawings for the Hult Center Improvements project in Oregon, supporting Contract Opportunity COE 20262045 for seating, electrical, and mechanical upgrades. The base bid scope includes removal of seating platforms and light upgrades to the facility. Alternate 1 adds cooling system installation to the existing spot booth, requiring placement of a cooling unit in the booth with a corresponding rooftop unit. The work encompasses electrical extension through Silva Hall above the ceiling, gypsum plenum opening between roof structures, patching, core drilling, membrane roof modifications, and additional work as detailed in the provided drawings.
The drawings serve as the technical specifications and visual reference for bidders to understand the full extent of construction requirements, including material locations, installation points, structural modifications, and the integration of mechanical and electrical systems throughout the facility. These drawings are essential for contractors to prepare accurate bids and establish project costs, timelines, and resource allocation for both the base bid work and the cooling system alternate.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D R W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
O N
A-001
C O
V E R
S H
E E T
/7
JR
E
U G
E N
E C
E N
T E R
E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
HULT CENTER SEATING, ELECTRICAL &
MECHANICAL IMPROVEMENTS
BASE BID:
REMOVE SEATING PLATFORM & LIGHT UPGRADES.
ALTERNATE 1:
ADD COOLING TO EXISTING SPOT BOOTH. WORK REQUIRES INSTALLING COOLING UNIT IN
THE SPOT BOOTH AND ASSOCIATED ROOF TOP UNIT. EXTENDING ELECTRICAL THROUGH
SILVA HALL (ABOVE CEILING), OPENING GYPSUM PLENUM BETWEEN ROOF STRUCTURE AND
PATCHING, CORE DRILLING, MEMBRANE ROOF MODIFICATIONS, AND OTHER WORK AS
SHOWN ON DRAWINGS.
OWNER: CITY OF EUGENE, FACILITY MANAGEMENT
210 CHESHIRE AVE
EUGENE, OR 97401
CONTACT: JENNI ROGERS
541-682-5321
JLROGERS@EUGENE-OR.GOV
ARCHITECT: JENNI ROGERS, AIA
CITY OF EUGENE
FACILITIES DESIGN AND CONSTRUCTION
210 CHESHIRE AVE
EUGENE, OR 97401
STRUCTURAL
ENGINEER: HOHBACH-LEWIN, INC
199 EAST 5TH AVE, EUGENE, OR 97401
BRENT CRAWFORD
541-349-1701
BCRAWFORD@HOHBACH-LEWIN.COM
MECHANICAL
ENGINEER: SOLARC ENERGY GROUP LLC
PO BOX 1203, EUGENE, OR 97440
MIKE HATTEN
541-349-0966
MIKEH@SOLARCENERGYGROUP.COM
ELECTRICAL
ENGINEER: PARADIGM ENGINEERING
85193 APPLETREE DRIVE
EUGENE, OR 97405
JIM KRUMSICK
541-285-1680
JIM@PARADIGM-ENG.COM
PROJECT DESCRIPTION:
PROJECT TEAM:
VICINITY MAP: PROJECT LOCATION
A-001 COVER SHEET
A-002 CODE AND GENERAL
A-003 SITE PLAN
A-101 PLATFORM PLANS
A-102 HANDRAIL DETAILS
A-301 ROOF PLAN (ALT 1)
A-302 SECTION (ALT 1)
A-303 DETAILS (ALT 1)
S-301 STRUCTURAL DETAILS (ALT 1)
E-101 ELECTRICA PLAN VIEW
E-102 ELECTRICAL PLAN VIEW
E-201 HANDRIAL REPLACEMENT DETAILS
E-301 ELECTRICAL PLAN - CATWALK DETAILS (ALT 1)
E-302 ELECTRICAL ROOF PLAN ( ALT 1)
E-303 CONDUIT ROUTING (ALT 1)
E-304 CONDUIT ROUTING (ALT 1)
E-401 ELECTRICAL ONE LINE DIAGRAM (ALT 1)
M-001 MECHANICAL SCHEDULES (ALT 1)
M-301 MECHANICAL PARTIAL PLANS (ALT 1)
M-302 MECHANICAL DETAILS & SECTIONS (ALT 1)
SHEET INDEX:
DF
DF
109109.1
I-7
S-23 S-22
S-26
S-25
S-24
S-5
BELOW
STAGE
BELOW
S-9
D
U
U U
U
U
U U
S-20
D
S-19 D
114.2
S-16 U
S-17
D
DD
D
D
DD
D
S-18123
S-12
U
D
D D
D
S-35
BELOW
D
U
S-10
D D
S-35
D
S-45 S-46
DD
027 028
D
S-4
D
DNDNDN
VESTIBULE
S-32 D
FOLLOW SPOT
BOOTH
EQUIP.
ROOM
GRATING GRATING GRATING GRATING GRATING GRATING GRATING
OPEN
GRATING
GRATING
O P
E N
MAIN LOBBY
SILVA HALL
STAGE
ALTERNATE 1:
MECHANICAL COOLING
(SEE ROOF PLAN FOR
ROOF WORK)
CAT WALK ACCESS
CAT WALK STAGE
CROSSING BELOW
MER-3, 1 LEVEL
BELOW
D R W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
A-002
C O
D E A
N D
G E N
E R A L
/7
/2
JR
E
U G
E N
E C
E N
T E R
E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
1/64" = 1'-0"
MAIN LOBBY LEVEL - BASE BID WORK
1/64" = 1'-0"
GRID IRON PLAN - ALTERNATE 1
PLATFORM REMOVAL,
SEE ARCHITECTURAL
LIGHT UPGRADES SEE
ELECTRICAL FOR ALL
LOCATION
• MAP & TAX LOT: 1704252404001
• CONSTRUCTION TYPE: IA (NO CHANGE)
• TOTAL AREA: 135,026 SF (NO CHANGE)
• OCCUPANCY: A-1 (NO CHANGE)
• SPRINKLERS: YES (NO CHANGE)
• NO CHANGE TO EGRESS, OCCUPANCY, OR ADA COMPLIANCY
• FIRE RESISTANT RATING REQUIREMENTS
1. PRIMARY STRUCTURAL FRAME: 3 HOUR
2. BEARING WALLS: 3 HOUR
3. INTERIOR NONBEARING WALLS: 0
4. FLOOR CONSTRUCTION AND ASSOCIATED SECONDARY
STRUCTURAL MEMBERS: 2 HOUR
5. ROOF CONSTRUCTION AND ASSOCIATED SECONDARY
STRUCTURAL MEMBERS: 1.5 HOUR
6. STAIR TOWERS: 2 HOUR
CODE:
1. PROTECT BUILDING AND SITE FROM DAMAGE. REPAIR ANY
DAMAGE TO AREAS CAUSED BY WORK.
2. PROTECT AREAS BELOW FROM FALL HAZARDS.
3. VERIFY ALL DIMENSIONS. BUILDING DIMENSIONS AND AREAS
GIVEN ARE BASED ON EXISTING DRAWINGS.
4. LOCATIONS OF CONCRETE PENETRATIONS ARE APPROXIMATE.
VERIFY ALL LOCATIONS AND QUANTITIES.
5. IMMEDIATELY REPORT ALL UNFORESEEN CONDITIONS TO OWNER.
6. CONCRETE PENETRATIONS TO BE FIRESTOPPED PER FIRE
RESISTANT RATING REQUIREMENTS NOTED ABOVE.
7. SEE SITE PLAN FOR STAGING INFORMATION.
GENERAL NOTES:
PARKING GARAGE HULT CENTER
CONTRACTOR
PARKING (2) SPOTS
ADA SPOTS, DO NOT
BLOCK
NORTH LOADING
ENTRANCE
STORAGE AREA (BACK
OF SILVA HALL)
SECURITY ENTRANCE
POSSIBLE LOADING ENTRANCE -
COORDIANTE USE WITH OWNER
A L L E Y
N O
P A R
K
IN
G
7TH AVENUE (ONE WAY)
6TH AVENUE (ONE WAY)
D R W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
A-003
S
IT
E P
L A N
/7
/2
JR
E
U G
E N
E C
E N
T E R
E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
1/64" = 1'-0"
SITE PLAN
DEMO
(E) SEATS
DEMO (E)
PLATFORM
REMOVE ALL (E) PARTIAL
CARPET TILES, REPLACE
WITH FULL SIZED TILES (BOTH SIDES)
NEW FLOOR PLAN
DEMO
(E) SEATS
NO FIXED SEATING IN THIS AREA
PATCH CARPET WITH
(E) MATCHING STOCK FROM
HULT STORAGE (BOTH SIDES)
1/16"=1'-0"
DEMO PLAN
1/16"=1'-0"
NEW PLATFORM DETAIL
1/2"=1'-0"
(E) WOOD FRAME
STEPPED PLATFORM
REMOVE (E) SEATS -
DISMANTLE AND RELOCATE
PARTS TO ON SITE STORAGE
REMOVE UPPER PLATFORM,
PATCH CONCRETE AND PLYWOOD
AS NEEDED PER SPECIFICATION
PATCH IN OFCI
CARPET TILE
PLATFORM DEMO DETAIL
1/2"=1'-0"
(E) SLOPED STRUCTURAL
CONCRETE
B
A
A
B
ADD BLACK VINYL RUBBER
STAIR NOSING AT EDGE
TO LOBBY
DEMO
(E) PLATFORM
STAGING AREA
AREA OF WORK
DR
W
N:
DA
TE
GJ
N:
CH
KD
RE
V:
BL
DG
N O.
CI
TY
O F
EU
G
EN
E
FA
CI
LI
TY
M
AN
AG
EM
EN
T
CH
ES
HI
RE
A
VE
NU
E
EU
GE
NE
, O
RE
GO
N
PL
AT
FO
RM
P
LA
N
HU
LT
C
EN
TE
R
SE
AT
IN
G, E
LE
CT
RI
CA
L
EU
GE
NE
C
EN
TE
R, E
UG
EN
E, O
RE
GO
N
A-101
M
EC
HA
NI
CA
L
IM
PR
OV
EM
EN
TS
5/ 7/
KC
L
JR
NEW HANDRAIL SECTION DETAIL
1'-0"=1'-0" B
.31" W LED TAPE
200 LM/FT 2.9 W/FT
DIODE LED
24V-BLBSC2
DR
W
N:
DA
TE
GJ
N:
CH
KD
RE
V:
BL
DG
N O.
CI
TY
O F
EU
G
EN
E
FA
CI
LI
TY
M
AN
AG
EM
EN
T
CH
ES
HI
RE
A
VE
NU
E
EU
GE
NE
, O
RE
GO
N
HA
ND
RA
IL
D
ET
AI
L
HU
LT
C
EN
TE
R
SE
AT
IN
G, E
LE
CT
RI
CA
L
EU
GE
NE
C
EN
TE
R, E
UG
EN
E, O
RE
GO
N
A-102
M
EC
HA
NI
CA
L
IM
PR
OV
EM
EN
TS
5/ 7/
KC
L
LED TAPE INSTALLATION NOTES
1. REMOVE EXISTING T8 STRIP LIGHTS FROM EXISTING
HANDRAILS AND ALL ASSOCIATED BRANCH CIRCUIT WIRING
AND ABANDONED WIRING INSIDE HANDRAIL.
2. RECONNECT EXISTING 120 VOLT CIRCUIT SERVING HANDRAIL
TO NEW DRIVERS AND INSTALL LED TAPE INSIDE HANDRAIL PER
DETAILS.
3. LOCATE DRIVERS AT END OF HANDRAIL RUNS OR AT
HANDRAIL CORNER TRANSITIONS. PROVIDE 90 DEGREE
CONNECTORS AS REQUIRED FOR INDIVIDULA RUNS.
4. REPLACE EXISTING HANDRAIL LENS, FULL LENGTH OF
HANDRAIL. MATCH THICKNESS OF EXISTING LENS AND PROVIDE
MOUNTING CLIPS TO MATCH EXISTING.
5. EXISTING GROUND CONDUCTORS MAY BE REUSED. VERIFY
CONNECTIONS AT EACH EXISTING HANDRAIL GROUND SCREW.
6. RUN BRANCH CIRCUIT WIRING TO DRIVER LOCATION IN
EXISTING WIREWAY AT TOP OF HANDRAIL.
* SEE SHEETS E-102 AND E-201 FOR HANDRAIL LOCATIONS
EXISTING HANDRAIL
EXISTING FASTENER
EXISTING WIREWAY
PROVIDE NEW
ACRYLIC LENSES
AND SPRING CLIPS
HANDRAIL SUPPORT
(BEYOND)
EXISTING HANDRAIL SECTION DETAIL
1'-0"=1'-0" A
HANDRAIL EXAMPLE (TYP.)
1'-0"=1'-0"
DEMO ALL EXISTING
LIGHTING COMPONENETS
DEMO EXISTING
ACRYLIC LENSES
DEMO EXISTING
ACRYLIC LENSES
DEMO ALL EXISTING
LIGHTING COMPNENETS
(SEE NOTES)
JOINT AT WALL SUPPORT TYPICAL CORNER CONDITION ACRYLIC LENS AND CLIP
JR
UPPER ROOF
ACCESS ROOF
LOWER ROOF
DOOR ACCESS
LADDER TO
UPPER ROOF
NEW ROOFTOP
CURB AND UNIT
VIF
11' - 0" +/-
V
IF
A-301
AREA ROOF WORK
T Y P
T Y P
UNISTRUT FOR EQUIPMENT
MOUNTING
DOG HOUSE FOR UTILITY
PENETRATIONS
S L O
P E
A-303
STAINLESS STEEL CURB CAP
UNIT WHERE
OCCURS
D R W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
A-301
R O
O F P
L A N
A L T
/7
/2
JR
E
U G
E N
E C
E N
T E R E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
ALTERNATE 1
1/32" = 1'-0"
ROOF PLAN
3/4" = 1'-0"
ENLARGED CURB PLAN
EACH SIDE
2' - 6" +/-
INDOOR WALL UNIT AND LEDGER,
SEE MECHANICAL
ROUTE UTILITIES
THROUGH CEILING
PLATFORM. ACOUSTIC
SEALANT AROUND ALL
PENETRATIONS UTILITY SUPPORTS
MECH.
PLENUM
MECH.
PLENUM
REMOVE PORTION OF PLENUM ASSEMBLY AS
REQUIRED TO CORE THROUGH ROOF STRUCTURE.
PATCH AND REPAIR TO MATCH EXISTING.
BLOCKING AROUND PIPE PENETRATION
PATCH INSULATION TO
MATCH EXISTING
A-303
FIRE STOPING AT
PLENUM PENETRATION
FIRE STOPING AT ROOF
PENETRATION
PIPE & UTILITIES,
SEE MECHANICAL
D R W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
A-302
S E C T
IO
N
A L T
/7
/2
JR
E
U G
E N
E C
E N
T E R E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
1/2" = 1'-0"
SPOT BOOTH SECTION
ALTERNATE 1
SIMPSON HGAM10KTA IN THE MIDDLE
OF EA 2X (4 TOTAL). INSTALL W/ 1/4X3
1/4" TITAL TURBO SCREWS TO
CONCRETE (SEE S-301 NOTES FOR
GPR SCAN)
2X12 WOOD CURB, INSTALL W/
A35 EA. CORNER (4 TOTAL)
EXISTING MEMBRANE ROOF OVER 3"
INSULATION, OVER 2" TOPPING SLAB
AND PRECAST BULB TEES
4 1/8" DIAM PENETRATION,
SEE STRUCTURAL DETAIL
*NOTES
TYPICAL
EACH SIDE
FASTENER WITH NEOPRENE
WASHER
TYP
3' - 6"
1. AVOID ALL REBAR AND TENDONS. SEE SHEET S-301 FOR NOTES.
2. LOCATION OF CURB BASED ON FIELD VERIFICATION AND
LOCATION OF LINESET PENETRATION. CONTRACTOR TO VERIFY IN
FIELD AND CONFIRM LOCATION WITH OWNER, PRIOR TO CORE
DRILLING.
80 MILL TPO ROOFING SYSTEM
UP AND OVER CURB, HOT WELD
TO EXISTING ADJACENT
ROOFING
DOG HOUSE
UPTURN CAP FLASHING INTO
DOG HOUSE, SOLDIER ALL
SEAMS
1/2" SHIM FOR SLOPE, THIS SIDE
FASTENER AND PLATE
STAINLESS STEEL CAP
FLASHING
3/4" PLYWOOD
NEOPRENE SHIM UNDER RAIL TO
ACCOMMODATE SLOPE
3" LONG 4"X3"X1/4" ANGLE,
ANCHORED WITH (4) WOOD
STRUCTURAL SCREWS TO 2X12
(2) ROWS UNISTRUT BEYOND,
WITH THREADED ROD
CONNECTION TO HVAC UNIT AND
ANGLE
SLOPE
A-303
FILL WITH ROCKWOOL INSULATION
SILL FLASHING SHEET
0' - 6"
/4
0' - 6" 0' - 6 1/4"
/4
LINESETS, CONDUIT, &
DRAIN LINE SEE
MECHANICAL AND
ELECTRICAL
CUT OUT OPENINGS FOR
UTILITIES
FILL WITH FOAM
INSULATION
D R W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
A-303
D E T A
IL
S
A L T
/7
/2
JR
E
U G
E N
E C
E N
T E R
E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
1 1/2" = 1'-0"
TYPICAL DUCT PENETRATION1
1 1/2" = 1'-0"
DOG HOUSE HEAD
GENERAL NOTES:
ALTERNATE 1
W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
S-301
S T U
R C T U
R A L D
E T A
IL
S
A L T
/7
/2
E
U G
E N
E C
E N
T E R E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
ALTERNATE 1
18" MIN.
EXISTING 6'-0" WIDE
PRECAST BULB-TEE,
SEE NOTES 1 AND 2
EXISTING 2" MIN.
CONC. TOPPING SLAB
℄ EXISTING CONC. BULB-TEE
4" MAX DIAMETER HOLE, SEE
MECH DWGS FOR
LOCATION. SEE NOTE 1
10" MIN.
14" MAX
PENETRATION ZONE
NOTES:
1. GPR SCAN EXISTING CONCRETE TO LOCATE
EXISTING REINFORCING AND PRECAST
TENDONS. PENETRATIONS ARE TO BE A
MINIMUM OF 1 1/2" CLEAR OF REINFORCING.
2. DO NOT INSTALL EQUIPMENT ANCHORS INTO
PRECAST BULB-TEES WITHOUT LOCATING
EXISTING REINFORCING AND TENDONS.
ANCHORS ARE TO BE INSTALLED A MINIMUM OF
1 1/2" CLEAR OF REINFORCINGANDTENDONS.
HOHBACH-LEWIN,
S T R U C T U R A L E N G I N E E R S
B C
W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
/7
/2
C h e ck e r
E
U G
E N
E C
E N
T E R E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
PARADIGM ENGINEERING
85193 APPLETREE DRIVE
EUGENE, OR 97405
541-285 1680
Jkrumsick@outlook.com
EXP: 6-30-2027
E-101
E
LE
C
T R
IC
A
L P
LA
N
V
IE
W
O R
C H
E S
T R
A
LO
B
B Y
L E
V E
L
E-101
PLAN NOTES
1. RELAMP EXISITNG AISLE STEP LIGHTS AT RAMPED PLOOR LOCATIONS . TYPICAL 56 LIGHT FIXTURES
LEGEND
AISLE STEP LIGHT
PHOTO REFERENCE
NOTE REFERENCE
JUNCTION BOX
CONDUIT RUN EXPOSED
EXISTING CONDUIT
(E) EXISTING TO REMAIN
RECEPTACLE WITH WEATHERPROOF COVER
DISCONNECT SWITCH
BRANCH CIRCUIT PANEL
ILLUMINATED HANDRAIL
E303
J
(E)
WP
James Krumsick
W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
/7
/2
C h e ck e r
E
U G
E N
E C
E N
T E R E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
PARADIGM ENGINEERING
85193 APPLETREE DRIVE
EUGENE, OR 97405
541-285 1680
Jkrumsick@outlook.com
E-101
LE
C
T R
IC
A
L P
LA
N
V
IE
W
O R
C H
E S
T R
A
LO
B
B Y
L E
V E
L
.31"W x 40' LED TAPE 200 LM/Ft 2.9W/Ft
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER
DI-ODX-24V-120W-J
WITH 2 AMP IN LINE
DIMMER- #EI0715
.31"W x 32' LED TAPE 200 LM/Ft 2.9W/Ft
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER,
DI-ODX-24V-120W-J
E-102
.31"W x 40' LED TAPE 200 LM/Ft 2.9W/Ft
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER
DI-ODX-24V-120W-J
.31"W x 32' LED TAPE
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER,
DI-ODX-24V-120W-J
.31"W x 29' LED TAPE
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER,
DI-ODX-24V-120W-J
.31"W x 27' LED TAPE
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER,
DI-ODX-24V-120W-J
.31"W x 27' LED TAPE
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER,
DI-ODX-24V-120W-J
.31"W x 28' LED TAPE
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER,
DI-ODX-24V-120W-J
.31"W x 34' LED TAPE
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER,
DI-ODX-24V-120W-J
.31"W x 34' LED TAPE
DIODE LED
24V-BLBSC2
WITH 120 WATT,
24 VDC DRIVER,
DI-ODX-24V-120W-J
A
CONCOURSE LEVEL PLAN
R-1
R-2
S-12A
S-12
S-16
N.T.S.
CONCOURSE TO UPPER BALCONY STAIR PLAN
N.T.S.
LOBBY LEVEL PLAN
N.T.S.
A
S-15
S-14
S-13
C-1
*SEE SHEET A-102 FOR ADDITIONAL
HANDRAIL DETAILS
W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
/7
E
U G
E N
E C
E N
T E R E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
H A
N D
R A
IL
R
E P
LA
C
E M
E N
T P
LA
N
D E
T A
IL
S
PARADIGM ENGINEERING
85193 APPLETREE DRIVE
EUGENE, OR 97405
541-285 1680
Jkrumsick@outlook.com
EXP: 6-30-2027
E-201 ORIGINAL INSTALLATION DETAIL
NOTE: COLD CATHODE LIGHTING WAS ORIGINALLY INSTALLED IN THE HANDRAIL.
SUBSEQUENTLY THIS WAS REPLACED WITH T 8 FLUORESCENT LIGHTING
UNDER CURRENT PROJECT REPLACE T 8 LIGHITNG SYSTEM WITH LED LIGHT TAPE.
ARCYLIC LENS
WITH BRACKET
NEW INSTALLATION DETAIL
LED TAPE INSTALLATION NOTES
1. REMOVE EXISTING T8 STRIP LIGHTS FROM EXISTING HANDRAILS AND ALL ASSOCIATED BRANCH CIRCUIT WIRING AND ABANDONED WIRING INSIDE HANDRAIL.
2. RECONNECT EXISTING 120 VOLT CIRCUIT SERVING HAND RAIL TO NEW DRIVERS AND INSTALL LED TAPE LIGHT INSIDE HANDRAIL PER DETAILS.
3, LOCATE DRIVERS AT END OF HANDRAIL RUNS OR AT HANDRAIL CORNER TRANSITIONS. PROVIDE 90 DEGREE CONNECTORS AS REQUIRED FOR INDIVIDUAL RUNS.
4. REPLACE EXISTING HANDRAIL LENS, FULL LENGTH OF HANDRAIL. MATCH THICKNESS OF EXISTING LENS AND PROVIDE MOUNTING CLIPS TO MATCH EXISTING.
5. EXISTING GROUND CONDUCTORS MAY BE REUSED. VERIFY CONNECTIONS AT EACH EXISTING HANDRAIL GROUND SCREW,
6. RUN BRANCH CIRCUIT WIRING TO DRIVER LOCATION IN EXISTING WIREWAY AT TOP OF HANDRAIL.
ORIGINAL INSTALLATION DETAIL
ELEVATION STAIR 13
ELEVATION STAIR 14
ELEVATION STAIR 14
ELEVATION STAIR 15
ELEVATION MEZZANINE BALCONY
ELEVATION STAIR 16
ELEVATION WEST RAMP
ELEVATION EAST RAMP
HANDRAIL.
EXISTING FASTENER
EXISTING WIREWAY
REPLACE EXISTING ACRYLIC LENS
EXISTING LOUVER
HANDRAIL SUPPORT
.31"W LED TAPE
DIODE LED
24V-BLBSC2
TYPICAL FOR THREE STAIR RUNS
R-1
R-2
S-12A S-12 S-16
S-15
S-14
S-13
CONCOURSE LEVEL
C-1
CONCOURSE LEVEL
C-1
S-13
S-14
CONCOURSE TO PARKING RAMP
CONCOURSE TO PARKING RAMP
W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
/7
/2
C h e ck e r
E
U G
E N
E C
E N
T E R E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
PARADIGM ENGINEERING
85193 APPLETREE DRIVE
EUGENE, OR 97405
541-285 1680
Jkrumsick@outlook.com
EXP: 6-30-2027
E-301
ALTERNATE 1
JJ
J
J
(E)
PLAN NOTES
1, INSTALL NEW 25/2 CIRCUIT BREAKER IN EXISTNG PANEL
L-E1. USE TO FEED NEW ROOF TOP AIR CONDITIONING UNIT
2. RUN 1'C, 2# , #10 G EXPOSED THROUGH MECHANICAL ROOM
MER-3.
3. CORE DRILL WALL TO STAIRWAY AND CONNECT BRANCH
CIRCUIT CONDUIT TO PULL BOX HIGH ON WALL.
4, RUN CONDUIT EXPOSED IN STAIRWELL. TRANSITION TO
CAT WALK ACCESS AND CORE DRILL TO TRANSITION CONDUIT
TO CATWALK LEVEL.
5. CONNECT BRANCH CIRCUIT CONDUIT TO EXISTING EMPTY
JUNCTION BOX.
6, PULL BRANCH CIRCUIT WIRING THROUGH EXISTING EMPTY
CONDUIT MOUNTED ABOVE CATWALK RAILING.
7. INTERCEPT CONDUIT AND INSTALL NEW PULL BOX. RUN
NEW BRANCH CIRCUIT CONDUIT FROM THIS PULL BOX
THROUGH STAIRWELL WALL AND THROUGH STAIRWELL
TO NEW PULL BOX AT CATWALK ENTRY DOOR. FOLLOW
ROUTE OF EXISTING FIRE ALARM SYSTEM CONDUIT.
8. CORE DRILL STAIRWELL WALL AT CATWALK ACCESS
DOOR LOCATION AND RUN CONDUIT ABOVE EXISTING
CATWALK LIGHTING CONDUIT TO FOLLOW SPOT BOOTH.
9. PROVIDE ADDITIONAL BRANCH CIRCUIT PULL BOXES AS
REQUIRED.
10. PROVIDE JUNCTION BOX ADJACENT TO 4" SLEEVE PENETRATION
TO ROOF. SEE MECHANICAL DRAWINGS FOR DETAIL. RUN 1"
CONDUIT FROM THIS JUNCTION BOX THROUGH SLEEVE TO
ROOFTOP MECHANICAL UNIT AND SERVICE RECEPTACLE.
11. PROVIDE DISCONNECT SWITCH FOR NEW ROOFTOP MECHANICAL
UNIT AND CONNECT AS REQUIRED. INSTALL SERVICE RECEPTACLE
WITH WEATHERPROOF COVER ADJACENT TO DISCONNECT SWITCH
FEED SERVICE RECEPTACLE FROM EXISTING PANEL LST4 LOCATED
IN FOLLOW SPOT BOOTH. SEE DETAILS DRAWING E201.
12. USE SPARE 20/1 CIRCUIT BREAKER IN PANEL LST4 TO FEED NEW
SERVICE RECEPTACLE AT MECHANICAL UNIT. RUN 1/2" CONDUIT,
2#12, #12 GROUND FROM PANEL TO JUNCTION BOX REFERENCED
BY NOTE 10. CONTINUE CIRCUIT TO SERVICE RECEPTACLE IN
1" CONDUIT WITH MECHANICAL UNIT BRANCH CIRCUIT CONDUCTQORS
FOLLOW
SPOT BOOTH
ELECTRICAL SYSTEM PLAN VIEW
J
J
E304
E304
E304
5 4
3 2 E303E303
E303
E303
ABOVE DUCTWORK
James Krumsick
E
LE
C T
R
IC
A L
P
LA
N
C A
T W
A
LK
L E
V
L
SCALE: 1/2" = 1'-0"
PIPING ROOF PENETRATION / OUTDOOR UNIT MOUNTING
ELECTRICAL CONDUIT, INSULATED
REFRIGERANT LINES, AND
POWER/CONTROL CABLE. ROUTE
TO OUTDOOR UNIT POINT OF
CONNECTION..
STAINLESS STEEL RAIN SHROUD,
BEAM PENETRATION
ZONE
3-1/2" NOMINAL ALUMINUM CARRIER PIPE ROUTED THROUGH 4"
BEAM AND ROOF PENETRATION.
ROOF MEMBRANE OVER INSULATION, DECK, AND
CONCRETE TEE BEAMS.
STAINLESS STEEL CURB CAP OVER
INSULATED EQUIPMENT MOUNTING
CURB, WELDED CORNERS.
18" MIN. 10" MIN.
14" MAX
CROSS SECTION OF PIPING/CONDUIT BUNDLE TO BE ROUTED
INSIDE OF CARRIER PIPE.
MINI-SPLIT OUTDOOR UNIT.
EXISTING EXH. FAN
AC-1
CD, REFG. AND
ELECTRICAL THROUGH 4"
DIA. PENETRATION
SCALE: 1/8" = 1'-0"
ROOF PARTIAL PLAN
N
WC-1
FOLLOW SPOT
BOOTH
18/18
A B
O V
E
A
B O
V E
1-1/4" ELECTRICAL
CONDUIT. SEE ELECTRICAL
PLANS FOR ROUTING.
APPROX. LOCATION OF
EXHAUST DUCT ABOVE AND
RUNNING IN BEAM CAVITY.
RL, RG, ELEC, CD, AND
POWER/CONTROL CABLE TO BE
BUNDLED AND ROUTED ON TOP
OF THE BOOTH THROUGH THE
ROOF IN 4" O.D. CARRIER DUCT
SCALE: 1/8" = 1'-0"
FOLLOW SPOT BOOTH LEVEL PARTIAL PLAN
ELECTRICAL JUNCTION
BOX WITH SERVICE RECEPTACLE
WITH WEATHERPROOF COVER
AND 2 POLE SNAP SWITCH
DISCONNECT FOR OUTDOOR
UNIT. MOUNT ON TOP OF
CURB.
J
E-302
E
LE
C T
R
IC
A L
R O
O F
P
LA
W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
/7
E
U G
E N
E C
E N
T E R E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
ALTERNATE 1
208 VOLTS, 1 PHASE
23 MCA, 25 MOCP.
PARADIGM ENGINEERING
85193 APPLETREE DRIVE
EUGENE, OR 97405
541-285 1680
Jkrumsick@outlook.com
W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
E-303
C O
N D
U
IT
R O
U T
IN
G
A L T
/7
/2
C h e ck e r
E
U G
E N
E C
E N
T E R
E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
2 - FROM MER 3 UP ONE FLIGHT OF STAIRS
3 - FROM STAIRS TO STAGE CROSSING 4 - FROM STAIRS TO STAGE CROSSING CONTINUED
*PHOTOS ARE
SHOWN IN
SEQUENTIAL
ORDER FROM
MER3 TO
CATWALK TO
SPOT BOOTH*
UTILIZE THIS
CONDUIT TO
CROSS THE STAGE
CORE FOR 1" CONDUIT
THRU WALL AND
FIRESTOP, EXTACT
LOCATION TO BE
DETERMINED IN FIELD,
SEE PHOTO 7
CORE FOR 1"
CONDUIT THRU WALL
AND FIRESTOP
ALTERNATE 1
14" THICK CONCRETE WALL
12" THICK CONCRETE WALL
STAIR FROM MER 3
ON OPPOSITE SIDE
OF THIS WALL
CUT OUT SECTION OF MESH
FOR CONDUIT PENETRATION
TIE INTO EXISTING CONDUIT
CROSSING STAGE
EXISTING CONDUIT CROSSING
STAGE
MER 3 ON OPPOSITE SIDE
OF THIS WALL
1 - MER 3 TO STAIRS
CONDUIT PENETRATION FROM
STAIRWELL INTO MER 3 NEXT TO
DUCT OR ABOVE DUCT,
COORDIANTE IN FIELD
PARADIGM ENGINEERING
85193 APPLETREE DRIVE
EUGENE, OR 97405
541-285 1680
Jkrumsick@outlook.com
W
N
D A T E
G
JN
C H
K D
R E V
B L D
G N
O
C I T
Y O
F E
U G
E N
E
F A
C I L I T
Y M
A N
A G
E M
E N
T
C
H E S H
IR
E A
V E N
U E
E U
G E N
E O
R E G
E-304
C O
N D
U
IT
R O
U T
IN
G
A L T
/7
/2
C h e ck e r
E
U G
E N
E C
E N
T E R
E U
G E N
E O
R
H U
L T C
E N
T E R S
E A T
IN
G E L E C T R
IC
A L
M E C H
A N
IC
A L I
M P R
O V E M
E N
T S
6 - STAIRS TO SPOT BOOTH
7 - STAIRS TO SPOT BOOTH
STAGE CROSSOVER ON
OPPOSITE SIDE OF THIS
WALL
ALTERNATE 1
CORE AS NOTED IN
PHOTO 4
FOLLOW EXISTING
CONDUIT PATH
CORE FOR 1" CONDUIT THRU
WALL AND FIRESTOP (12" THICK
CONCRETE WALL)
CATWALK TO SPOT
BOOTH ON
OPPOSITE SIDE OF
THIS WALL
5 - OPPOSITE SIDE OF STAGE TO STAIRS TO SPOT BOOTH
MODIFY EXISTING CONDUIT AND
CONTINUE NEW PATHWAY
CORE FOR 1" CONDUIT THRU
WALL AND FIRESTOP (12" THICK
CONCRETE WALL)
STAIR TO
SPOT BOOTH
*PHOTOS ARE
SHOWN IN
SEQUENTIAL
ORDER FROM
MER3 TO
CATWALK TO
SPOT BOOTH*
PARADIGM ENGINEERING
85193 APPLETREE DRIVE
EUGENE, OR 97405
541-285 1680
Jkrumsick@outlook.com
1000A
EXISTING
DISTRIBUTION
PANEL "DL3"
1000 AMP BUS
120 / 208V, 3Ø, 4W
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text J
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text K
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text K
AutoCAD SHX Text
OREGON
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text P
AutoCAD SHX Text T
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXPIRES 6/30/2021
AutoCAD SHX Text
AutoCAD SHX Text E2
Jim Krumsick Rectangle
Jim Krumsick Line
Jim Krumsick Typewritten Text
Jim Krumsick Typewritten Text
(11) EXISTING FUSED SWITCHES
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Fuse
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Typewritten Text
ONE LINE DIAGRAM SWITCHBOARD DL3 - TRANSFORMER T3 208 VOLT SYSTEM
Jim Krumsick Typewritten Text
TRANSFORMER
T3 -300 KVA
208Y/120 VOLT
SECONDARY
Jim Krumsick
200A 200A 200A 40A 100A 70A 60A 100A 125A 50A 150A
200/3 200/3 200/3 60/3 100/3 100/3 100/3 100/3 200/3 100/3 200/3
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Typewritten Text
SORENG
COMPANY
SWITCH
Jim Krumsick Typewritten Text
SILVA
COMPANY
SWITCH
Jim Krumsick Typewritten Text
SILVA
COMPANY
SWITCH
Jim Krumsick Rectangle
Jim Krumsick Rectangle
Jim Krumsick Typewritten Text
SILVA
ASSISTED
LISTENING
Jim Krumsick Typewritten Text
SORENG
WORK LIGHT
SYSTEM
Jim Krumsick Typewritten Text
SORENG
CONTROL ROOM
NON-DIM
Jim Krumsick Typewritten Text
SILVA FOLLOW
SPOT BOOTH
PANEL LST4
Jim Krumsick Typewritten Text
SILVA
WORK LIGHT
SYSTEM
Jim Krumsick Typewritten Text
SILVA
STAGE
NON-DIM
Jim Krumsick Typewritten Text
SORENG
PANEL LST12
Jim Krumsick Typewritten Text
MER 3
PANEL L-E1
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line
Jim Krumsick Line jkrum Typewritten Text
ELECTRICAL ONE LINE DIAGRAM
jkrum Typewritten Text jkrum Ellipse jkrum Typewritten Text jkrum Ellipse jkrum Typewritten Text
PLAN NOTES
1. INSTALL 25/2 CIRCUIT BREAKER IN EXISTING PLANEL SPACE. USE TO FEED NEW AC/UNIT.
2. USE SPARE 20/1 BREKAER TO FEED NEW SERVICE RECEPTACLE
jkrum Image jkrum Image jkrum Rectangle jkrum Snapshot jkrum Rectangle jkrum Typewritten Text E-401 jkrum Rectangle jkrum Typewritten Text
ELECTRICAL ONE LINE DIAGRAM
jkrum
HU
LT
C
EN
TE
R
SE
AT
IN
G, E
LE
CT
RI
CA
L
SYMBOLS ABBREVATIONS
NOTES
DRAWINGS
M001 - SCHEDULES
M101 - PART PLANS
M201 - DETAILS
6 SECTION TAKEN AT
KEYED NOTE DESIGNATION
DETAIL OR DETAIL REFERENCE
AH-1 EQUIPMENT TAG
8/8
SUPPLY DIFFUSER: SIZE / CFM
THERMOSTAT
EXHAUST AIR UP
RETURN AIR UP
RETURN AIR DOWN
SUPPLY AIR UP
SUPPLY AIR DOWN
CD
CFM
EER
CONDENSATE DRAIN
CUBIC FEET PER MINUTE
ENERGY EFFICIENCY RATIO
ELEC ELECTRIC
LB POUNDS
MAX MAXIMUM
MCA
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MINIMUM CIRCUIT AMPACITY
MBH THOUSAND OF BRITISH THERMAL UNITS
PER HOUR
OD
REFG REFRIGERANT
RF REFRIGERANT, LIQUID
OUTER DIAMETER
RG REFRIGERANT, GAS
1. MECHANICAL SUBCONTRACTOR SHALL COORDINATE WITH
ALL DISCIPLINES, AND SHALL SCHEDULE WORK WITH
OWNER.
2. WORK AREA LOCATIONS ARE INSIDE OF THE SPOT FOLLOW
BOOTH, ON TOP OF THE SPOT FOLLOW BOOTH, AND ON THE
ROOF. WORK ON TOP OF THE SPOT FOLLOW BOOTH AND
ON THE ROOF SHALL COMPLY WITH ALL APPLICABLE
SAFETY REQUIREMENTS.
DR
W
N:
DA
TE
GJ
N:
CH
KD
RE
V:
BL
DG
N O.
CI
TY
O F
EU
G
EN
E
FA
CI
LI
TY
M
AN
AG
EM
EN
T
CH
ES
HI
RE
A
VE
NU
E
EU
GE
NE
, O
RE
GO
N
M-001
M
EC
HA
NI
CA
L
SC
HE
DU
LE
S 5/
7/
M
JH
EU
GE
NE
C
EN
TE
R, E
UG
EN
E, O R
M
EC
HA
NI
CA
L
IM
PR
OV
EM
EN
TS
ALTERNATE 1
M
JH
LOAD CALCULATIONS
1. CALCULATIONS USE RADIANT TIME SERIES
APPROACH AS EMBODIED IN DOE2.3.
2. SENSIBLE LOAD = 24,329 BTU/HR.
3. TOTAL LOAD = 25,129 BTU/HR.
WC-1
T
FOLLOW SPOT
BOOTH
18/18
/1
AB
O
VE
/1
A
BO
VE
1-1/4" ELECTRICAL
CONDUIT. SEE ELECTRICAL
PLANS FOR ROUTING.
APPROX. LOCATION OF
EXHAUST DUCT ABOVE AND
RUNNING IN BEAM CAVITY.
CAVITY BETWEEN
BEAM WEBS
2/2 FRAMED OFFSET SECTION FOR
WALL CASSETTE MOUNTING.
APPROX. LOCATION OF EXHAUST DUCT
BELOW BEAMS AND SHEET ROCK
CONDENSATE LIFT PUMP
BELOW WALL CASSETTE.
RL, RG, ELEC, CD, AND
POWER/CONTROL CABLE TO BE
BUNDLED AND ROUTED ON TOP
OF THE BOOTH THROUGH THE
ROOF IN 4" O.D. CARRIER DUCT
(4" 30 GA. MIN GALV. DUCT).
WC-1 T
FOLLOW SPOT
BOOTH
18/18
/1
A
BO
VE
/1
A
BO
VE
AC-1
EXISTING EXH. FAN
CD, REFG. & ELECTRICAL
THROUGH ROOF
EXISTING EXH. FAN
AC-1
CD, REFG. AND
ELECTRICAL THROUGH 4"
DIA. PENETRATION
KEYED SHEET NOTES
CIRCULAR PENETRATION THROUGH CONCRETE TEE BEAM FLANGE, ROOF DECK,
INSULATION, AND MEMBRANE. FINAL LOCATION AND SIZE PER STRUCTURAL
DRAWINGS.
2X LEDGER ATTACHED TO EXISTING WALL STUDS. MOUNT WALL CASSETTE TO
LEDGER WITH MANUFACTURER SUPPLIED BRACKET.
GENERAL SHEET NOTES
1. FIELD VERIFY EXACT LOCATION OF EXISTING ELEMENTS. COORDINATE
FINAL EQUIPMENT LOCATION WITH OTHER UTILITIES AND ARCHITECTURAL
AND STRUCTURAL ELEMENTS.
HU
LT
C
EN
TE
R
SE
AT
IN
G, E
LE
CT
RI
CA
L
SCALE: 1/8" = 1'-0"1 FOLLOW SPOT BOOTH LEVEL PARTIAL PLAN
N
KEY PLAN
SCALE: 1/8" = 1'-0"2 ROOF PARTIAL PLAN
N
KEY PLAN
DR
W
N:
DA
TE
GJ
N:
CH
KD
RE
V:
BL
DG
N O.
CI
TY
O F
EU
G
EN
E
FA
CI
LI
TY
M
AN
AG
EM
EN
T
CH
ES
HI
RE
A
VE
NU
E
EU
GE
NE
, O
RE
GO
N
M-301
M
EC
HA
NI
CA
L
PA
RT
IA
L
PL
AN
S 5/
7/
M
JH
EU
GE
NE
C
EN
TE
R, E
UG
EN
E, O R
M
EC
HA
NI
CA
L
IM
PR
OV
EM
EN
TS
ALTERNATE 1
M
JH
HU
LT
C
EN
TE
R
SE
AT
IN
G, E
LE
CT
RI
CA
L
SCALE: 1/2" = 1'-0"1 PIPING ROOF PENETRATION / OUTDOOR UNIT MOUNTING
SCALE: 1/8" = 1'-0"2 WALL CASSETTE INSTALLATION SECTION
ELECTRICAL CONDUIT, INSULATED
REFRIGERANT LINES, AND
POWER/CONTROL CABLE. ROUTE
TO OUTDOOR UNIT POINT OF
CONNECTION.. ROOF PENETRATION SHROUD TO ACCOMODATE 1"
POWER CONDUIT, REFG LINESETS, DRAIN, AND
POWER/CONTROL CABLE. DETAIL 1/M201 AND
ARCHITECTURAL DETAIL 2/A302.
WC-1
CONDENSATE PUMP BELOW
WC-1. WIRE FROM TERMINAL
STRIP IN WC-1.
5/8" CD, INSULATED RG AND RL, 1" ELEC, AND
POWER/CONTROL CABLE. ROUTE ON TOP OF BOOTH
AND SUPPORT FROM BELOW. BUNDLE PER
MANUFACTURER'S RECOMMENDATION TO FIT INTO 4"
O.D. ALUM. CARRIER PIPE TO MAKE PENETRATIONS
THROUGH ROOF. FINAL PENETRATION LOCATION PER
STRUCTURAL DRAWINGS.
FOLLOWSPOT
BOOTH.
NEW 2/ LEDGER FOR MOUNTING. FINAL LOCATION TO
ALIGN WITH EXISTING WALL STUDS AND UPPER
BUMP-OUT SECTION. MAINTAIN 5" MIN. CLEARANCE
ABOVE WC-1 AND PROVIDE FOR PIPING PENETRATIONS
THROUGH CEILING STRUCTURE. COVER PIPING WITH
SOFFIT COVER AS SPECIFIED.
STAINLESS STEEL DOG HOUSE. SEAL
WATER TIGHT AT CONNECTION TO
CURB CAP AND AT END PENETRATION
FOR PIPING. SEE ARCHITECTURAL
DETAILS ON A302 FOR CONSTRUCTION
DETAILING AND DIMENSIONS.
BEAM PENETRATION
ZONE
3-1/2" NOMINAL ALUMINUM CARRIER PIPE ROUTED THROUGH 4"
BEAM AND ROOF PENETRATION. SUPPORT WITH VERTICAL RISER
CLAMP AT DECK AND WITH UNISTRUT BRACKET AND CLAMP AT
LOWER PENTRATON THROUGH PLENUM SHEET ROCK.
ROOF MEMBRANE OVER INSULATION, DECK, AND
CONCRETE TEE BEAMS.
ROOF MEMBRANE OVER
INSULATION, DECK, AND
CONCRETE TEE BEAMS.
STAINLESS STEEL CURB CAP OVER
EQUIPMENT MOUNTING CURB. SEE
ARCHITECTURAL DETAILS ON A302
FOR CONSTRUCTION DETAILING AND
DIMENSIONS.
18" MIN. 10" MIN.
14" MAX
CREATE TEMPORARY WORKING OPENING IN SHEETROCK BOTTOM
OF RETURN AIR PLENUM. PATCH, REPAIR, AND SEAL AROUND
CARRIER PIPE WHEN WORK IS COMPLETE.
CROSS SECTION OF PIPING/CONDUIT BUNDLE TO BE ROUTED
INSIDE OF CARRIER PIPE. CONTRACTOR TO FINALIZE PIPING
ARRANGEMENT TO ACCOMODATE ROOF ROUTING.
MINI-SPLIT OUTDOOR UNIT. MAINTAIN
MANUFACTURER REQUIRED LEARANCE FOR AIR
FLOW.
UNI-STRUT BRACKET AND CLAMP.
ATTACH TO BEAM PER ARCHITECT.
DR
W
N:
DA
TE
GJ
N:
CH
KD
RE
V:
BL
DG
N O.
CI
TY
O F
EU
G
EN
E
FA
CI
LI
TY
M
AN
AG
EM
EN
T
CH
ES
HI
RE
A
VE
NU
E
EU
GE
NE
, O
RE
GO
N
M-302
M
EC
HA
NI
CA
L
DE
TA
IL
S
AN
D
SE
CT
IO
NS
5/ 7/
M
JH
EU
GE
NE
C
EN
TE
R, E
UG
EN
E, O R
M
EC
HA
NI
CA
L
IM
PR
OV
EM
EN
TS
ALTERNATE 1
M
JH
| Sheets |
| A-001 - COVER SHEET |
| A-002 - CODE AND GENERAL |
| A-003 - SITE PLAN |
| A-101-PLATFORM PLAN |
| A-102-HANDRAIL DETAIL |
| A-301 - ROOF PLAN (ALT 1) |
| A-302 - SECTION |
| A-303 - DETAILS (ALT 1) |
| S-301-STRUCTURAL DETAILS |
| E-101-ELECTRICAL PLAN VIEW |
| E-102-ELECTRICAL PLAN VIEW |
| E-201-HANDRAIL REPLACEMENT PLAN DETAILS |
| E-301-ELECTRICAL PLAN - CATWALK LEVEL |
| E-302-ELECTRICAL ROOF PLAN |
| E-303-CONDUIT ROUTING |
| E-304-CONDUIT ROUTING |
| M001-SCHEDULES |
| M301-PART PLANS |
| M302-DETAILS |
| Permit Drawings - Electrical_Update 8 |
File details come from the government source that posted it. Updated .