Hult Center Improvements_Drawings.pdf

PDF 6 MB Posted

Attached to
COE 20262045 Hult Center Seating, Electrical and Mechanical Improvements
Solicitation number
S-KE0010-00016903
Issued by
Lane County, Oregon

About this file

This file contains construction drawings for the Hult Center Improvements project in Oregon, supporting Contract Opportunity COE 20262045 for seating, electrical, and mechanical upgrades. The base bid scope includes removal of seating platforms and light upgrades to the facility. Alternate 1 adds cooling system installation to the existing spot booth, requiring placement of a cooling unit in the booth with a corresponding rooftop unit. The work encompasses electrical extension through Silva Hall above the ceiling, gypsum plenum opening between roof structures, patching, core drilling, membrane roof modifications, and additional work as detailed in the provided drawings.

The drawings serve as the technical specifications and visual reference for bidders to understand the full extent of construction requirements, including material locations, installation points, structural modifications, and the integration of mechanical and electrical systems throughout the facility. These drawings are essential for contractors to prepare accurate bids and establish project costs, timelines, and resource allocation for both the base bid work and the cooling system alternate.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D R W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

O N

A-001

C O

V E R

S H

E E T

/7

JR

E

U G

E N

E C

E N

T E R

E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

HULT CENTER SEATING, ELECTRICAL &

MECHANICAL IMPROVEMENTS

BASE BID:

REMOVE SEATING PLATFORM & LIGHT UPGRADES.

ALTERNATE 1:

ADD COOLING TO EXISTING SPOT BOOTH. WORK REQUIRES INSTALLING COOLING UNIT IN

THE SPOT BOOTH AND ASSOCIATED ROOF TOP UNIT. EXTENDING ELECTRICAL THROUGH

SILVA HALL (ABOVE CEILING), OPENING GYPSUM PLENUM BETWEEN ROOF STRUCTURE AND

PATCHING, CORE DRILLING, MEMBRANE ROOF MODIFICATIONS, AND OTHER WORK AS

SHOWN ON DRAWINGS.

OWNER: CITY OF EUGENE, FACILITY MANAGEMENT

210 CHESHIRE AVE

EUGENE, OR 97401

CONTACT: JENNI ROGERS

541-682-5321

JLROGERS@EUGENE-OR.GOV

ARCHITECT: JENNI ROGERS, AIA

CITY OF EUGENE

FACILITIES DESIGN AND CONSTRUCTION

210 CHESHIRE AVE

EUGENE, OR 97401

STRUCTURAL

ENGINEER: HOHBACH-LEWIN, INC

199 EAST 5TH AVE, EUGENE, OR 97401

BRENT CRAWFORD

541-349-1701

BCRAWFORD@HOHBACH-LEWIN.COM

MECHANICAL

ENGINEER: SOLARC ENERGY GROUP LLC

PO BOX 1203, EUGENE, OR 97440

MIKE HATTEN

541-349-0966

MIKEH@SOLARCENERGYGROUP.COM

ELECTRICAL

ENGINEER: PARADIGM ENGINEERING

85193 APPLETREE DRIVE

EUGENE, OR 97405

JIM KRUMSICK

541-285-1680

JIM@PARADIGM-ENG.COM

PROJECT DESCRIPTION:

PROJECT TEAM:

VICINITY MAP: PROJECT LOCATION

A-001 COVER SHEET

A-002 CODE AND GENERAL

A-003 SITE PLAN

A-101 PLATFORM PLANS

A-102 HANDRAIL DETAILS

A-301 ROOF PLAN (ALT 1)

A-302 SECTION (ALT 1)

A-303 DETAILS (ALT 1)

S-301 STRUCTURAL DETAILS (ALT 1)

E-101 ELECTRICA PLAN VIEW

E-102 ELECTRICAL PLAN VIEW

E-201 HANDRIAL REPLACEMENT DETAILS

E-301 ELECTRICAL PLAN - CATWALK DETAILS (ALT 1)

E-302 ELECTRICAL ROOF PLAN ( ALT 1)

E-303 CONDUIT ROUTING (ALT 1)

E-304 CONDUIT ROUTING (ALT 1)

E-401 ELECTRICAL ONE LINE DIAGRAM (ALT 1)

M-001 MECHANICAL SCHEDULES (ALT 1)

M-301 MECHANICAL PARTIAL PLANS (ALT 1)

M-302 MECHANICAL DETAILS & SECTIONS (ALT 1)

SHEET INDEX:

DF

DF

109109.1

I-7

S-23 S-22

S-26

S-25

S-24

S-5

BELOW

STAGE

BELOW

S-9

D

U

U U

U

U

U U

S-20

D

S-19 D

114.2

S-16 U

S-17

D

DD

D

D

DD

D

S-18123

S-12

U

D

D D

D

S-35

BELOW

D

U

S-10

D D

S-35

D

S-45 S-46

DD

027 028

D

S-4

D

DNDNDN

VESTIBULE

S-32 D

FOLLOW SPOT

BOOTH

EQUIP.

ROOM

GRATING GRATING GRATING GRATING GRATING GRATING GRATING

OPEN

GRATING

GRATING

O P

E N

MAIN LOBBY

SILVA HALL

STAGE

ALTERNATE 1:

MECHANICAL COOLING

(SEE ROOF PLAN FOR

ROOF WORK)

CAT WALK ACCESS

CAT WALK STAGE

CROSSING BELOW

MER-3, 1 LEVEL

BELOW

D R W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

A-002

C O

D E A

N D

G E N

E R A L

/7

/2

JR

E

U G

E N

E C

E N

T E R

E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

1/64" = 1'-0"

MAIN LOBBY LEVEL - BASE BID WORK

1/64" = 1'-0"

GRID IRON PLAN - ALTERNATE 1

PLATFORM REMOVAL,

SEE ARCHITECTURAL

LIGHT UPGRADES SEE

ELECTRICAL FOR ALL

LOCATION

• MAP & TAX LOT: 1704252404001

• CONSTRUCTION TYPE: IA (NO CHANGE)

• TOTAL AREA: 135,026 SF (NO CHANGE)

• OCCUPANCY: A-1 (NO CHANGE)

• SPRINKLERS: YES (NO CHANGE)

• NO CHANGE TO EGRESS, OCCUPANCY, OR ADA COMPLIANCY

• FIRE RESISTANT RATING REQUIREMENTS

1. PRIMARY STRUCTURAL FRAME: 3 HOUR

2. BEARING WALLS: 3 HOUR

3. INTERIOR NONBEARING WALLS: 0

4. FLOOR CONSTRUCTION AND ASSOCIATED SECONDARY

STRUCTURAL MEMBERS: 2 HOUR

5. ROOF CONSTRUCTION AND ASSOCIATED SECONDARY

STRUCTURAL MEMBERS: 1.5 HOUR

6. STAIR TOWERS: 2 HOUR

CODE:

1. PROTECT BUILDING AND SITE FROM DAMAGE. REPAIR ANY

DAMAGE TO AREAS CAUSED BY WORK.

2. PROTECT AREAS BELOW FROM FALL HAZARDS.

3. VERIFY ALL DIMENSIONS. BUILDING DIMENSIONS AND AREAS

GIVEN ARE BASED ON EXISTING DRAWINGS.

4. LOCATIONS OF CONCRETE PENETRATIONS ARE APPROXIMATE.

VERIFY ALL LOCATIONS AND QUANTITIES.

5. IMMEDIATELY REPORT ALL UNFORESEEN CONDITIONS TO OWNER.

6. CONCRETE PENETRATIONS TO BE FIRESTOPPED PER FIRE

RESISTANT RATING REQUIREMENTS NOTED ABOVE.

7. SEE SITE PLAN FOR STAGING INFORMATION.

GENERAL NOTES:

PARKING GARAGE HULT CENTER

CONTRACTOR

PARKING (2) SPOTS

ADA SPOTS, DO NOT

BLOCK

NORTH LOADING

ENTRANCE

STORAGE AREA (BACK

OF SILVA HALL)

SECURITY ENTRANCE

POSSIBLE LOADING ENTRANCE -

COORDIANTE USE WITH OWNER

A L L E Y

N O

P A R

K

IN

G

7TH AVENUE (ONE WAY)

6TH AVENUE (ONE WAY)

D R W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

A-003

S

IT

E P

L A N

/7

/2

JR

E

U G

E N

E C

E N

T E R

E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

1/64" = 1'-0"

SITE PLAN

DEMO

(E) SEATS

DEMO (E)

PLATFORM

REMOVE ALL (E) PARTIAL

CARPET TILES, REPLACE

WITH FULL SIZED TILES (BOTH SIDES)

NEW FLOOR PLAN

DEMO

(E) SEATS

NO FIXED SEATING IN THIS AREA

PATCH CARPET WITH

(E) MATCHING STOCK FROM

HULT STORAGE (BOTH SIDES)

1/16"=1'-0"

DEMO PLAN

1/16"=1'-0"

NEW PLATFORM DETAIL

1/2"=1'-0"

(E) WOOD FRAME

STEPPED PLATFORM

REMOVE (E) SEATS -

DISMANTLE AND RELOCATE

PARTS TO ON SITE STORAGE

REMOVE UPPER PLATFORM,

PATCH CONCRETE AND PLYWOOD

AS NEEDED PER SPECIFICATION

PATCH IN OFCI

CARPET TILE

PLATFORM DEMO DETAIL

1/2"=1'-0"

(E) SLOPED STRUCTURAL

CONCRETE

B

A

A

B

ADD BLACK VINYL RUBBER

STAIR NOSING AT EDGE

TO LOBBY

DEMO

(E) PLATFORM

STAGING AREA

AREA OF WORK

DR

W

N:

DA

TE

GJ

N:

CH

KD

RE

V:

BL

DG

N O.

CI

TY

O F

EU

G

EN

E

FA

CI

LI

TY

M

AN

AG

EM

EN

T

CH

ES

HI

RE

A

VE

NU

E

EU

GE

NE

, O

RE

GO

N

PL

AT

FO

RM

P

LA

N

HU

LT

C

EN

TE

R

SE

AT

IN

G, E

LE

CT

RI

CA

L

EU

GE

NE

C

EN

TE

R, E

UG

EN

E, O

RE

GO

N

A-101

M

EC

HA

NI

CA

L

IM

PR

OV

EM

EN

TS

5/ 7/

KC

L

JR

NEW HANDRAIL SECTION DETAIL

1'-0"=1'-0" B

.31" W LED TAPE

200 LM/FT 2.9 W/FT

DIODE LED

24V-BLBSC2

DR

W

N:

DA

TE

GJ

N:

CH

KD

RE

V:

BL

DG

N O.

CI

TY

O F

EU

G

EN

E

FA

CI

LI

TY

M

AN

AG

EM

EN

T

CH

ES

HI

RE

A

VE

NU

E

EU

GE

NE

, O

RE

GO

N

HA

ND

RA

IL

D

ET

AI

L

HU

LT

C

EN

TE

R

SE

AT

IN

G, E

LE

CT

RI

CA

L

EU

GE

NE

C

EN

TE

R, E

UG

EN

E, O

RE

GO

N

A-102

M

EC

HA

NI

CA

L

IM

PR

OV

EM

EN

TS

5/ 7/

KC

L

LED TAPE INSTALLATION NOTES

1. REMOVE EXISTING T8 STRIP LIGHTS FROM EXISTING

HANDRAILS AND ALL ASSOCIATED BRANCH CIRCUIT WIRING

AND ABANDONED WIRING INSIDE HANDRAIL.

2. RECONNECT EXISTING 120 VOLT CIRCUIT SERVING HANDRAIL

TO NEW DRIVERS AND INSTALL LED TAPE INSIDE HANDRAIL PER

DETAILS.

3. LOCATE DRIVERS AT END OF HANDRAIL RUNS OR AT

HANDRAIL CORNER TRANSITIONS. PROVIDE 90 DEGREE

CONNECTORS AS REQUIRED FOR INDIVIDULA RUNS.

4. REPLACE EXISTING HANDRAIL LENS, FULL LENGTH OF

HANDRAIL. MATCH THICKNESS OF EXISTING LENS AND PROVIDE

MOUNTING CLIPS TO MATCH EXISTING.

5. EXISTING GROUND CONDUCTORS MAY BE REUSED. VERIFY

CONNECTIONS AT EACH EXISTING HANDRAIL GROUND SCREW.

6. RUN BRANCH CIRCUIT WIRING TO DRIVER LOCATION IN

EXISTING WIREWAY AT TOP OF HANDRAIL.

* SEE SHEETS E-102 AND E-201 FOR HANDRAIL LOCATIONS

EXISTING HANDRAIL

EXISTING FASTENER

EXISTING WIREWAY

PROVIDE NEW

ACRYLIC LENSES

AND SPRING CLIPS

HANDRAIL SUPPORT

(BEYOND)

EXISTING HANDRAIL SECTION DETAIL

1'-0"=1'-0" A

HANDRAIL EXAMPLE (TYP.)

1'-0"=1'-0"

DEMO ALL EXISTING

LIGHTING COMPONENETS

DEMO EXISTING

ACRYLIC LENSES

DEMO EXISTING

ACRYLIC LENSES

DEMO ALL EXISTING

LIGHTING COMPNENETS

(SEE NOTES)

JOINT AT WALL SUPPORT TYPICAL CORNER CONDITION ACRYLIC LENS AND CLIP

JR

UPPER ROOF

ACCESS ROOF

LOWER ROOF

DOOR ACCESS

LADDER TO

UPPER ROOF

NEW ROOFTOP

CURB AND UNIT

VIF

11' - 0" +/-

V

IF

A-301

AREA ROOF WORK

T Y P

T Y P

UNISTRUT FOR EQUIPMENT

MOUNTING

DOG HOUSE FOR UTILITY

PENETRATIONS

S L O

P E

A-303

STAINLESS STEEL CURB CAP

UNIT WHERE

OCCURS

D R W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

A-301

R O

O F P

L A N

A L T

/7

/2

JR

E

U G

E N

E C

E N

T E R E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

ALTERNATE 1

1/32" = 1'-0"

ROOF PLAN

3/4" = 1'-0"

ENLARGED CURB PLAN

EACH SIDE

2' - 6" +/-

INDOOR WALL UNIT AND LEDGER,

SEE MECHANICAL

ROUTE UTILITIES

THROUGH CEILING

PLATFORM. ACOUSTIC

SEALANT AROUND ALL

PENETRATIONS UTILITY SUPPORTS

MECH.

PLENUM

MECH.

PLENUM

REMOVE PORTION OF PLENUM ASSEMBLY AS

REQUIRED TO CORE THROUGH ROOF STRUCTURE.

PATCH AND REPAIR TO MATCH EXISTING.

BLOCKING AROUND PIPE PENETRATION

PATCH INSULATION TO

MATCH EXISTING

A-303

FIRE STOPING AT

PLENUM PENETRATION

FIRE STOPING AT ROOF

PENETRATION

PIPE & UTILITIES,

SEE MECHANICAL

D R W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

A-302

S E C T

IO

N

A L T

/7

/2

JR

E

U G

E N

E C

E N

T E R E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

1/2" = 1'-0"

SPOT BOOTH SECTION

ALTERNATE 1

SIMPSON HGAM10KTA IN THE MIDDLE

OF EA 2X (4 TOTAL). INSTALL W/ 1/4X3

1/4" TITAL TURBO SCREWS TO

CONCRETE (SEE S-301 NOTES FOR

GPR SCAN)

2X12 WOOD CURB, INSTALL W/

A35 EA. CORNER (4 TOTAL)

EXISTING MEMBRANE ROOF OVER 3"

INSULATION, OVER 2" TOPPING SLAB

AND PRECAST BULB TEES

4 1/8" DIAM PENETRATION,

SEE STRUCTURAL DETAIL

*NOTES

TYPICAL

EACH SIDE

FASTENER WITH NEOPRENE

WASHER

TYP

3' - 6"

1. AVOID ALL REBAR AND TENDONS. SEE SHEET S-301 FOR NOTES.

2. LOCATION OF CURB BASED ON FIELD VERIFICATION AND

LOCATION OF LINESET PENETRATION. CONTRACTOR TO VERIFY IN

FIELD AND CONFIRM LOCATION WITH OWNER, PRIOR TO CORE

DRILLING.

80 MILL TPO ROOFING SYSTEM

UP AND OVER CURB, HOT WELD

TO EXISTING ADJACENT

ROOFING

DOG HOUSE

UPTURN CAP FLASHING INTO

DOG HOUSE, SOLDIER ALL

SEAMS

1/2" SHIM FOR SLOPE, THIS SIDE

FASTENER AND PLATE

STAINLESS STEEL CAP

FLASHING

3/4" PLYWOOD

NEOPRENE SHIM UNDER RAIL TO

ACCOMMODATE SLOPE

3" LONG 4"X3"X1/4" ANGLE,

ANCHORED WITH (4) WOOD

STRUCTURAL SCREWS TO 2X12

(2) ROWS UNISTRUT BEYOND,

WITH THREADED ROD

CONNECTION TO HVAC UNIT AND

ANGLE

SLOPE

A-303

FILL WITH ROCKWOOL INSULATION

SILL FLASHING SHEET

0' - 6"

/4

0' - 6" 0' - 6 1/4"

/4

LINESETS, CONDUIT, &

DRAIN LINE SEE

MECHANICAL AND

ELECTRICAL

CUT OUT OPENINGS FOR

UTILITIES

FILL WITH FOAM

INSULATION

D R W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

A-303

D E T A

IL

S

A L T

/7

/2

JR

E

U G

E N

E C

E N

T E R

E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

1 1/2" = 1'-0"

TYPICAL DUCT PENETRATION1

1 1/2" = 1'-0"

DOG HOUSE HEAD

GENERAL NOTES:

ALTERNATE 1

W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

S-301

S T U

R C T U

R A L D

E T A

IL

S

A L T

/7

/2

E

U G

E N

E C

E N

T E R E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

ALTERNATE 1

18" MIN.

EXISTING 6'-0" WIDE

PRECAST BULB-TEE,

SEE NOTES 1 AND 2

EXISTING 2" MIN.

CONC. TOPPING SLAB

℄ EXISTING CONC. BULB-TEE

4" MAX DIAMETER HOLE, SEE

MECH DWGS FOR

LOCATION. SEE NOTE 1

10" MIN.

14" MAX

PENETRATION ZONE

NOTES:

1. GPR SCAN EXISTING CONCRETE TO LOCATE

EXISTING REINFORCING AND PRECAST

TENDONS. PENETRATIONS ARE TO BE A

MINIMUM OF 1 1/2" CLEAR OF REINFORCING.

2. DO NOT INSTALL EQUIPMENT ANCHORS INTO

PRECAST BULB-TEES WITHOUT LOCATING

EXISTING REINFORCING AND TENDONS.

ANCHORS ARE TO BE INSTALLED A MINIMUM OF

1 1/2" CLEAR OF REINFORCINGANDTENDONS.

HOHBACH-LEWIN,

S T R U C T U R A L E N G I N E E R S

B C

W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

/7

/2

C h e ck e r

E

U G

E N

E C

E N

T E R E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

PARADIGM ENGINEERING

85193 APPLETREE DRIVE

EUGENE, OR 97405

541-285 1680

Jkrumsick@outlook.com

EXP: 6-30-2027

E-101

E

LE

C

T R

IC

A

L P

LA

N

V

IE

W

O R

C H

E S

T R

A

LO

B

B Y

L E

V E

L

E-101

PLAN NOTES

1. RELAMP EXISITNG AISLE STEP LIGHTS AT RAMPED PLOOR LOCATIONS . TYPICAL 56 LIGHT FIXTURES

LEGEND

AISLE STEP LIGHT

PHOTO REFERENCE

NOTE REFERENCE

JUNCTION BOX

CONDUIT RUN EXPOSED

EXISTING CONDUIT

(E) EXISTING TO REMAIN

RECEPTACLE WITH WEATHERPROOF COVER

DISCONNECT SWITCH

BRANCH CIRCUIT PANEL

ILLUMINATED HANDRAIL

E303

J

(E)

WP

James Krumsick

W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

/7

/2

C h e ck e r

E

U G

E N

E C

E N

T E R E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

PARADIGM ENGINEERING

85193 APPLETREE DRIVE

EUGENE, OR 97405

541-285 1680

Jkrumsick@outlook.com

E-101

LE

C

T R

IC

A

L P

LA

N

V

IE

W

O R

C H

E S

T R

A

LO

B

B Y

L E

V E

L

.31"W x 40' LED TAPE 200 LM/Ft 2.9W/Ft

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER

DI-ODX-24V-120W-J

WITH 2 AMP IN LINE

DIMMER- #EI0715

.31"W x 32' LED TAPE 200 LM/Ft 2.9W/Ft

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER,

DI-ODX-24V-120W-J

E-102

.31"W x 40' LED TAPE 200 LM/Ft 2.9W/Ft

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER

DI-ODX-24V-120W-J

.31"W x 32' LED TAPE

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER,

DI-ODX-24V-120W-J

.31"W x 29' LED TAPE

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER,

DI-ODX-24V-120W-J

.31"W x 27' LED TAPE

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER,

DI-ODX-24V-120W-J

.31"W x 27' LED TAPE

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER,

DI-ODX-24V-120W-J

.31"W x 28' LED TAPE

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER,

DI-ODX-24V-120W-J

.31"W x 34' LED TAPE

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER,

DI-ODX-24V-120W-J

.31"W x 34' LED TAPE

DIODE LED

24V-BLBSC2

WITH 120 WATT,

24 VDC DRIVER,

DI-ODX-24V-120W-J

A

CONCOURSE LEVEL PLAN

R-1

R-2

S-12A

S-12

S-16

N.T.S.

CONCOURSE TO UPPER BALCONY STAIR PLAN

N.T.S.

LOBBY LEVEL PLAN

N.T.S.

A

S-15

S-14

S-13

C-1

*SEE SHEET A-102 FOR ADDITIONAL

HANDRAIL DETAILS

W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

/7

E

U G

E N

E C

E N

T E R E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

H A

N D

R A

IL

R

E P

LA

C

E M

E N

T P

LA

N

D E

T A

IL

S

PARADIGM ENGINEERING

85193 APPLETREE DRIVE

EUGENE, OR 97405

541-285 1680

Jkrumsick@outlook.com

EXP: 6-30-2027

E-201 ORIGINAL INSTALLATION DETAIL

NOTE: COLD CATHODE LIGHTING WAS ORIGINALLY INSTALLED IN THE HANDRAIL.

SUBSEQUENTLY THIS WAS REPLACED WITH T 8 FLUORESCENT LIGHTING

UNDER CURRENT PROJECT REPLACE T 8 LIGHITNG SYSTEM WITH LED LIGHT TAPE.

ARCYLIC LENS

WITH BRACKET

NEW INSTALLATION DETAIL

LED TAPE INSTALLATION NOTES

1. REMOVE EXISTING T8 STRIP LIGHTS FROM EXISTING HANDRAILS AND ALL ASSOCIATED BRANCH CIRCUIT WIRING AND ABANDONED WIRING INSIDE HANDRAIL.

2. RECONNECT EXISTING 120 VOLT CIRCUIT SERVING HAND RAIL TO NEW DRIVERS AND INSTALL LED TAPE LIGHT INSIDE HANDRAIL PER DETAILS.

3, LOCATE DRIVERS AT END OF HANDRAIL RUNS OR AT HANDRAIL CORNER TRANSITIONS. PROVIDE 90 DEGREE CONNECTORS AS REQUIRED FOR INDIVIDUAL RUNS.

4. REPLACE EXISTING HANDRAIL LENS, FULL LENGTH OF HANDRAIL. MATCH THICKNESS OF EXISTING LENS AND PROVIDE MOUNTING CLIPS TO MATCH EXISTING.

5. EXISTING GROUND CONDUCTORS MAY BE REUSED. VERIFY CONNECTIONS AT EACH EXISTING HANDRAIL GROUND SCREW,

6. RUN BRANCH CIRCUIT WIRING TO DRIVER LOCATION IN EXISTING WIREWAY AT TOP OF HANDRAIL.

ORIGINAL INSTALLATION DETAIL

ELEVATION STAIR 13

ELEVATION STAIR 14

ELEVATION STAIR 14

ELEVATION STAIR 15

ELEVATION MEZZANINE BALCONY

ELEVATION STAIR 16

ELEVATION WEST RAMP

ELEVATION EAST RAMP

HANDRAIL.

EXISTING FASTENER

EXISTING WIREWAY

REPLACE EXISTING ACRYLIC LENS

EXISTING LOUVER

HANDRAIL SUPPORT

.31"W LED TAPE

DIODE LED

24V-BLBSC2

TYPICAL FOR THREE STAIR RUNS

R-1

R-2

S-12A S-12 S-16

S-15

S-14

S-13

CONCOURSE LEVEL

C-1

CONCOURSE LEVEL

C-1

S-13

S-14

CONCOURSE TO PARKING RAMP

CONCOURSE TO PARKING RAMP

W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

/7

/2

C h e ck e r

E

U G

E N

E C

E N

T E R E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

PARADIGM ENGINEERING

85193 APPLETREE DRIVE

EUGENE, OR 97405

541-285 1680

Jkrumsick@outlook.com

EXP: 6-30-2027

E-301

ALTERNATE 1

JJ

J

J

(E)

PLAN NOTES

1, INSTALL NEW 25/2 CIRCUIT BREAKER IN EXISTNG PANEL

L-E1. USE TO FEED NEW ROOF TOP AIR CONDITIONING UNIT

2. RUN 1'C, 2# , #10 G EXPOSED THROUGH MECHANICAL ROOM

MER-3.

3. CORE DRILL WALL TO STAIRWAY AND CONNECT BRANCH

CIRCUIT CONDUIT TO PULL BOX HIGH ON WALL.

4, RUN CONDUIT EXPOSED IN STAIRWELL. TRANSITION TO

CAT WALK ACCESS AND CORE DRILL TO TRANSITION CONDUIT

TO CATWALK LEVEL.

5. CONNECT BRANCH CIRCUIT CONDUIT TO EXISTING EMPTY

JUNCTION BOX.

6, PULL BRANCH CIRCUIT WIRING THROUGH EXISTING EMPTY

CONDUIT MOUNTED ABOVE CATWALK RAILING.

7. INTERCEPT CONDUIT AND INSTALL NEW PULL BOX. RUN

NEW BRANCH CIRCUIT CONDUIT FROM THIS PULL BOX

THROUGH STAIRWELL WALL AND THROUGH STAIRWELL

TO NEW PULL BOX AT CATWALK ENTRY DOOR. FOLLOW

ROUTE OF EXISTING FIRE ALARM SYSTEM CONDUIT.

8. CORE DRILL STAIRWELL WALL AT CATWALK ACCESS

DOOR LOCATION AND RUN CONDUIT ABOVE EXISTING

CATWALK LIGHTING CONDUIT TO FOLLOW SPOT BOOTH.

9. PROVIDE ADDITIONAL BRANCH CIRCUIT PULL BOXES AS

REQUIRED.

10. PROVIDE JUNCTION BOX ADJACENT TO 4" SLEEVE PENETRATION

TO ROOF. SEE MECHANICAL DRAWINGS FOR DETAIL. RUN 1"

CONDUIT FROM THIS JUNCTION BOX THROUGH SLEEVE TO

ROOFTOP MECHANICAL UNIT AND SERVICE RECEPTACLE.

11. PROVIDE DISCONNECT SWITCH FOR NEW ROOFTOP MECHANICAL

UNIT AND CONNECT AS REQUIRED. INSTALL SERVICE RECEPTACLE

WITH WEATHERPROOF COVER ADJACENT TO DISCONNECT SWITCH

FEED SERVICE RECEPTACLE FROM EXISTING PANEL LST4 LOCATED

IN FOLLOW SPOT BOOTH. SEE DETAILS DRAWING E201.

12. USE SPARE 20/1 CIRCUIT BREAKER IN PANEL LST4 TO FEED NEW

SERVICE RECEPTACLE AT MECHANICAL UNIT. RUN 1/2" CONDUIT,

2#12, #12 GROUND FROM PANEL TO JUNCTION BOX REFERENCED

BY NOTE 10. CONTINUE CIRCUIT TO SERVICE RECEPTACLE IN

1" CONDUIT WITH MECHANICAL UNIT BRANCH CIRCUIT CONDUCTQORS

FOLLOW

SPOT BOOTH

ELECTRICAL SYSTEM PLAN VIEW

J

J

E304

E304

E304

5 4

3 2 E303E303

E303

E303

ABOVE DUCTWORK

James Krumsick

E

LE

C T

R

IC

A L

P

LA

N

C A

T W

A

LK

L E

V

L

SCALE: 1/2" = 1'-0"

PIPING ROOF PENETRATION / OUTDOOR UNIT MOUNTING

ELECTRICAL CONDUIT, INSULATED

REFRIGERANT LINES, AND

POWER/CONTROL CABLE. ROUTE

TO OUTDOOR UNIT POINT OF

CONNECTION..

STAINLESS STEEL RAIN SHROUD,

BEAM PENETRATION

ZONE

3-1/2" NOMINAL ALUMINUM CARRIER PIPE ROUTED THROUGH 4"

BEAM AND ROOF PENETRATION.

ROOF MEMBRANE OVER INSULATION, DECK, AND

CONCRETE TEE BEAMS.

STAINLESS STEEL CURB CAP OVER

INSULATED EQUIPMENT MOUNTING

CURB, WELDED CORNERS.

18" MIN. 10" MIN.

14" MAX

CROSS SECTION OF PIPING/CONDUIT BUNDLE TO BE ROUTED

INSIDE OF CARRIER PIPE.

MINI-SPLIT OUTDOOR UNIT.

EXISTING EXH. FAN

AC-1

CD, REFG. AND

ELECTRICAL THROUGH 4"

DIA. PENETRATION

SCALE: 1/8" = 1'-0"

ROOF PARTIAL PLAN

N

WC-1

FOLLOW SPOT

BOOTH

18/18

A B

O V

E

A

B O

V E

1-1/4" ELECTRICAL

CONDUIT. SEE ELECTRICAL

PLANS FOR ROUTING.

APPROX. LOCATION OF

EXHAUST DUCT ABOVE AND

RUNNING IN BEAM CAVITY.

RL, RG, ELEC, CD, AND

POWER/CONTROL CABLE TO BE

BUNDLED AND ROUTED ON TOP

OF THE BOOTH THROUGH THE

ROOF IN 4" O.D. CARRIER DUCT

SCALE: 1/8" = 1'-0"

FOLLOW SPOT BOOTH LEVEL PARTIAL PLAN

ELECTRICAL JUNCTION

BOX WITH SERVICE RECEPTACLE

WITH WEATHERPROOF COVER

AND 2 POLE SNAP SWITCH

DISCONNECT FOR OUTDOOR

UNIT. MOUNT ON TOP OF

CURB.

J

E-302

E

LE

C T

R

IC

A L

R O

O F

P

LA

W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

/7

E

U G

E N

E C

E N

T E R E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

ALTERNATE 1

208 VOLTS, 1 PHASE

23 MCA, 25 MOCP.

PARADIGM ENGINEERING

85193 APPLETREE DRIVE

EUGENE, OR 97405

541-285 1680

Jkrumsick@outlook.com

W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

E-303

C O

N D

U

IT

R O

U T

IN

G

A L T

/7

/2

C h e ck e r

E

U G

E N

E C

E N

T E R

E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

2 - FROM MER 3 UP ONE FLIGHT OF STAIRS

3 - FROM STAIRS TO STAGE CROSSING 4 - FROM STAIRS TO STAGE CROSSING CONTINUED

*PHOTOS ARE

SHOWN IN

SEQUENTIAL

ORDER FROM

MER3 TO

CATWALK TO

SPOT BOOTH*

UTILIZE THIS

CONDUIT TO

CROSS THE STAGE

CORE FOR 1" CONDUIT

THRU WALL AND

FIRESTOP, EXTACT

LOCATION TO BE

DETERMINED IN FIELD,

SEE PHOTO 7

CORE FOR 1"

CONDUIT THRU WALL

AND FIRESTOP

ALTERNATE 1

14" THICK CONCRETE WALL

12" THICK CONCRETE WALL

STAIR FROM MER 3

ON OPPOSITE SIDE

OF THIS WALL

CUT OUT SECTION OF MESH

FOR CONDUIT PENETRATION

TIE INTO EXISTING CONDUIT

CROSSING STAGE

EXISTING CONDUIT CROSSING

STAGE

MER 3 ON OPPOSITE SIDE

OF THIS WALL

1 - MER 3 TO STAIRS

CONDUIT PENETRATION FROM

STAIRWELL INTO MER 3 NEXT TO

DUCT OR ABOVE DUCT,

COORDIANTE IN FIELD

PARADIGM ENGINEERING

85193 APPLETREE DRIVE

EUGENE, OR 97405

541-285 1680

Jkrumsick@outlook.com

W

N

D A T E

G

JN

C H

K D

R E V

B L D

G N

O

C I T

Y O

F E

U G

E N

E

F A

C I L I T

Y M

A N

A G

E M

E N

T

C

H E S H

IR

E A

V E N

U E

E U

G E N

E O

R E G

E-304

C O

N D

U

IT

R O

U T

IN

G

A L T

/7

/2

C h e ck e r

E

U G

E N

E C

E N

T E R

E U

G E N

E O

R

H U

L T C

E N

T E R S

E A T

IN

G E L E C T R

IC

A L

M E C H

A N

IC

A L I

M P R

O V E M

E N

T S

6 - STAIRS TO SPOT BOOTH

7 - STAIRS TO SPOT BOOTH

STAGE CROSSOVER ON

OPPOSITE SIDE OF THIS

WALL

ALTERNATE 1

CORE AS NOTED IN

PHOTO 4

FOLLOW EXISTING

CONDUIT PATH

CORE FOR 1" CONDUIT THRU

WALL AND FIRESTOP (12" THICK

CONCRETE WALL)

CATWALK TO SPOT

BOOTH ON

OPPOSITE SIDE OF

THIS WALL

5 - OPPOSITE SIDE OF STAGE TO STAIRS TO SPOT BOOTH

MODIFY EXISTING CONDUIT AND

CONTINUE NEW PATHWAY

CORE FOR 1" CONDUIT THRU

WALL AND FIRESTOP (12" THICK

CONCRETE WALL)

STAIR TO

SPOT BOOTH

*PHOTOS ARE

SHOWN IN

SEQUENTIAL

ORDER FROM

MER3 TO

CATWALK TO

SPOT BOOTH*

PARADIGM ENGINEERING

85193 APPLETREE DRIVE

EUGENE, OR 97405

541-285 1680

Jkrumsick@outlook.com

1000A

EXISTING

DISTRIBUTION

PANEL "DL3"

1000 AMP BUS

120 / 208V, 3Ø, 4W

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text J

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text K

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text K

AutoCAD SHX Text

OREGON

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text T

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXPIRES 6/30/2021

AutoCAD SHX Text

AutoCAD SHX Text E2

Jim Krumsick Rectangle

Jim Krumsick Line

Jim Krumsick Typewritten Text

Jim Krumsick Typewritten Text

(11) EXISTING FUSED SWITCHES

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Fuse

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Typewritten Text

ONE LINE DIAGRAM SWITCHBOARD DL3 - TRANSFORMER T3 208 VOLT SYSTEM

Jim Krumsick Typewritten Text

TRANSFORMER

T3 -300 KVA

208Y/120 VOLT

SECONDARY

Jim Krumsick

200A 200A 200A 40A 100A 70A 60A 100A 125A 50A 150A

200/3 200/3 200/3 60/3 100/3 100/3 100/3 100/3 200/3 100/3 200/3

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Typewritten Text

SORENG

COMPANY

SWITCH

Jim Krumsick Typewritten Text

SILVA

COMPANY

SWITCH

Jim Krumsick Typewritten Text

SILVA

COMPANY

SWITCH

Jim Krumsick Rectangle

Jim Krumsick Rectangle

Jim Krumsick Typewritten Text

SILVA

ASSISTED

LISTENING

Jim Krumsick Typewritten Text

SORENG

WORK LIGHT

SYSTEM

Jim Krumsick Typewritten Text

SORENG

CONTROL ROOM

NON-DIM

Jim Krumsick Typewritten Text

SILVA FOLLOW

SPOT BOOTH

PANEL LST4

Jim Krumsick Typewritten Text

SILVA

WORK LIGHT

SYSTEM

Jim Krumsick Typewritten Text

SILVA

STAGE

NON-DIM

Jim Krumsick Typewritten Text

SORENG

PANEL LST12

Jim Krumsick Typewritten Text

MER 3

PANEL L-E1

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line

Jim Krumsick Line jkrum Typewritten Text

ELECTRICAL ONE LINE DIAGRAM

jkrum Typewritten Text jkrum Ellipse jkrum Typewritten Text jkrum Ellipse jkrum Typewritten Text

PLAN NOTES

1. INSTALL 25/2 CIRCUIT BREAKER IN EXISTING PLANEL SPACE. USE TO FEED NEW AC/UNIT.

2. USE SPARE 20/1 BREKAER TO FEED NEW SERVICE RECEPTACLE

jkrum Image jkrum Image jkrum Rectangle jkrum Snapshot jkrum Rectangle jkrum Typewritten Text E-401 jkrum Rectangle jkrum Typewritten Text

ELECTRICAL ONE LINE DIAGRAM

jkrum

HU

LT

C

EN

TE

R

SE

AT

IN

G, E

LE

CT

RI

CA

L

SYMBOLS ABBREVATIONS

NOTES

DRAWINGS

M001 - SCHEDULES

M101 - PART PLANS

M201 - DETAILS

6 SECTION TAKEN AT

KEYED NOTE DESIGNATION

DETAIL OR DETAIL REFERENCE

AH-1 EQUIPMENT TAG

8/8

SUPPLY DIFFUSER: SIZE / CFM

THERMOSTAT

EXHAUST AIR UP

RETURN AIR UP

RETURN AIR DOWN

SUPPLY AIR UP

SUPPLY AIR DOWN

CD

CFM

EER

CONDENSATE DRAIN

CUBIC FEET PER MINUTE

ENERGY EFFICIENCY RATIO

ELEC ELECTRIC

LB POUNDS

MAX MAXIMUM

MCA

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MINIMUM CIRCUIT AMPACITY

MBH THOUSAND OF BRITISH THERMAL UNITS

PER HOUR

OD

REFG REFRIGERANT

RF REFRIGERANT, LIQUID

OUTER DIAMETER

RG REFRIGERANT, GAS

1. MECHANICAL SUBCONTRACTOR SHALL COORDINATE WITH

ALL DISCIPLINES, AND SHALL SCHEDULE WORK WITH

OWNER.

2. WORK AREA LOCATIONS ARE INSIDE OF THE SPOT FOLLOW

BOOTH, ON TOP OF THE SPOT FOLLOW BOOTH, AND ON THE

ROOF. WORK ON TOP OF THE SPOT FOLLOW BOOTH AND

ON THE ROOF SHALL COMPLY WITH ALL APPLICABLE

SAFETY REQUIREMENTS.

DR

W

N:

DA

TE

GJ

N:

CH

KD

RE

V:

BL

DG

N O.

CI

TY

O F

EU

G

EN

E

FA

CI

LI

TY

M

AN

AG

EM

EN

T

CH

ES

HI

RE

A

VE

NU

E

EU

GE

NE

, O

RE

GO

N

M-001

M

EC

HA

NI

CA

L

SC

HE

DU

LE

S 5/

7/

M

JH

EU

GE

NE

C

EN

TE

R, E

UG

EN

E, O R

M

EC

HA

NI

CA

L

IM

PR

OV

EM

EN

TS

ALTERNATE 1

M

JH

LOAD CALCULATIONS

1. CALCULATIONS USE RADIANT TIME SERIES

APPROACH AS EMBODIED IN DOE2.3.

2. SENSIBLE LOAD = 24,329 BTU/HR.

3. TOTAL LOAD = 25,129 BTU/HR.

WC-1

T

FOLLOW SPOT

BOOTH

18/18

/1

AB

O

VE

/1

A

BO

VE

1-1/4" ELECTRICAL

CONDUIT. SEE ELECTRICAL

PLANS FOR ROUTING.

APPROX. LOCATION OF

EXHAUST DUCT ABOVE AND

RUNNING IN BEAM CAVITY.

CAVITY BETWEEN

BEAM WEBS

2/2 FRAMED OFFSET SECTION FOR

WALL CASSETTE MOUNTING.

APPROX. LOCATION OF EXHAUST DUCT

BELOW BEAMS AND SHEET ROCK

CONDENSATE LIFT PUMP

BELOW WALL CASSETTE.

RL, RG, ELEC, CD, AND

POWER/CONTROL CABLE TO BE

BUNDLED AND ROUTED ON TOP

OF THE BOOTH THROUGH THE

ROOF IN 4" O.D. CARRIER DUCT

(4" 30 GA. MIN GALV. DUCT).

WC-1 T

FOLLOW SPOT

BOOTH

18/18

/1

A

BO

VE

/1

A

BO

VE

AC-1

EXISTING EXH. FAN

CD, REFG. & ELECTRICAL

THROUGH ROOF

EXISTING EXH. FAN

AC-1

CD, REFG. AND

ELECTRICAL THROUGH 4"

DIA. PENETRATION

KEYED SHEET NOTES

CIRCULAR PENETRATION THROUGH CONCRETE TEE BEAM FLANGE, ROOF DECK,

INSULATION, AND MEMBRANE. FINAL LOCATION AND SIZE PER STRUCTURAL

DRAWINGS.

2X LEDGER ATTACHED TO EXISTING WALL STUDS. MOUNT WALL CASSETTE TO

LEDGER WITH MANUFACTURER SUPPLIED BRACKET.

GENERAL SHEET NOTES

1. FIELD VERIFY EXACT LOCATION OF EXISTING ELEMENTS. COORDINATE

FINAL EQUIPMENT LOCATION WITH OTHER UTILITIES AND ARCHITECTURAL

AND STRUCTURAL ELEMENTS.

HU

LT

C

EN

TE

R

SE

AT

IN

G, E

LE

CT

RI

CA

L

SCALE: 1/8" = 1'-0"1 FOLLOW SPOT BOOTH LEVEL PARTIAL PLAN

N

KEY PLAN

SCALE: 1/8" = 1'-0"2 ROOF PARTIAL PLAN

N

KEY PLAN

DR

W

N:

DA

TE

GJ

N:

CH

KD

RE

V:

BL

DG

N O.

CI

TY

O F

EU

G

EN

E

FA

CI

LI

TY

M

AN

AG

EM

EN

T

CH

ES

HI

RE

A

VE

NU

E

EU

GE

NE

, O

RE

GO

N

M-301

M

EC

HA

NI

CA

L

PA

RT

IA

L

PL

AN

S 5/

7/

M

JH

EU

GE

NE

C

EN

TE

R, E

UG

EN

E, O R

M

EC

HA

NI

CA

L

IM

PR

OV

EM

EN

TS

ALTERNATE 1

M

JH

HU

LT

C

EN

TE

R

SE

AT

IN

G, E

LE

CT

RI

CA

L

SCALE: 1/2" = 1'-0"1 PIPING ROOF PENETRATION / OUTDOOR UNIT MOUNTING

SCALE: 1/8" = 1'-0"2 WALL CASSETTE INSTALLATION SECTION

ELECTRICAL CONDUIT, INSULATED

REFRIGERANT LINES, AND

POWER/CONTROL CABLE. ROUTE

TO OUTDOOR UNIT POINT OF

CONNECTION.. ROOF PENETRATION SHROUD TO ACCOMODATE 1"

POWER CONDUIT, REFG LINESETS, DRAIN, AND

POWER/CONTROL CABLE. DETAIL 1/M201 AND

ARCHITECTURAL DETAIL 2/A302.

WC-1

CONDENSATE PUMP BELOW

WC-1. WIRE FROM TERMINAL

STRIP IN WC-1.

5/8" CD, INSULATED RG AND RL, 1" ELEC, AND

POWER/CONTROL CABLE. ROUTE ON TOP OF BOOTH

AND SUPPORT FROM BELOW. BUNDLE PER

MANUFACTURER'S RECOMMENDATION TO FIT INTO 4"

O.D. ALUM. CARRIER PIPE TO MAKE PENETRATIONS

THROUGH ROOF. FINAL PENETRATION LOCATION PER

STRUCTURAL DRAWINGS.

FOLLOWSPOT

BOOTH.

NEW 2/ LEDGER FOR MOUNTING. FINAL LOCATION TO

ALIGN WITH EXISTING WALL STUDS AND UPPER

BUMP-OUT SECTION. MAINTAIN 5" MIN. CLEARANCE

ABOVE WC-1 AND PROVIDE FOR PIPING PENETRATIONS

THROUGH CEILING STRUCTURE. COVER PIPING WITH

SOFFIT COVER AS SPECIFIED.

STAINLESS STEEL DOG HOUSE. SEAL

WATER TIGHT AT CONNECTION TO

CURB CAP AND AT END PENETRATION

FOR PIPING. SEE ARCHITECTURAL

DETAILS ON A302 FOR CONSTRUCTION

DETAILING AND DIMENSIONS.

BEAM PENETRATION

ZONE

3-1/2" NOMINAL ALUMINUM CARRIER PIPE ROUTED THROUGH 4"

BEAM AND ROOF PENETRATION. SUPPORT WITH VERTICAL RISER

CLAMP AT DECK AND WITH UNISTRUT BRACKET AND CLAMP AT

LOWER PENTRATON THROUGH PLENUM SHEET ROCK.

ROOF MEMBRANE OVER INSULATION, DECK, AND

CONCRETE TEE BEAMS.

ROOF MEMBRANE OVER

INSULATION, DECK, AND

CONCRETE TEE BEAMS.

STAINLESS STEEL CURB CAP OVER

EQUIPMENT MOUNTING CURB. SEE

ARCHITECTURAL DETAILS ON A302

FOR CONSTRUCTION DETAILING AND

DIMENSIONS.

18" MIN. 10" MIN.

14" MAX

CREATE TEMPORARY WORKING OPENING IN SHEETROCK BOTTOM

OF RETURN AIR PLENUM. PATCH, REPAIR, AND SEAL AROUND

CARRIER PIPE WHEN WORK IS COMPLETE.

CROSS SECTION OF PIPING/CONDUIT BUNDLE TO BE ROUTED

INSIDE OF CARRIER PIPE. CONTRACTOR TO FINALIZE PIPING

ARRANGEMENT TO ACCOMODATE ROOF ROUTING.

MINI-SPLIT OUTDOOR UNIT. MAINTAIN

MANUFACTURER REQUIRED LEARANCE FOR AIR

FLOW.

UNI-STRUT BRACKET AND CLAMP.

ATTACH TO BEAM PER ARCHITECT.

DR

W

N:

DA

TE

GJ

N:

CH

KD

RE

V:

BL

DG

N O.

CI

TY

O F

EU

G

EN

E

FA

CI

LI

TY

M

AN

AG

EM

EN

T

CH

ES

HI

RE

A

VE

NU

E

EU

GE

NE

, O

RE

GO

N

M-302

M

EC

HA

NI

CA

L

DE

TA

IL

S

AN

D

SE

CT

IO

NS

5/ 7/

M

JH

EU

GE

NE

C

EN

TE

R, E

UG

EN

E, O R

M

EC

HA

NI

CA

L

IM

PR

OV

EM

EN

TS

ALTERNATE 1

M

JH

Sheets
A-001 - COVER SHEET
A-002 - CODE AND GENERAL
A-003 - SITE PLAN
A-101-PLATFORM PLAN
A-102-HANDRAIL DETAIL
A-301 - ROOF PLAN (ALT 1)
A-302 - SECTION
A-303 - DETAILS (ALT 1)
S-301-STRUCTURAL DETAILS
E-101-ELECTRICAL PLAN VIEW
E-102-ELECTRICAL PLAN VIEW
E-201-HANDRAIL REPLACEMENT PLAN DETAILS
E-301-ELECTRICAL PLAN - CATWALK LEVEL
E-302-ELECTRICAL ROOF PLAN
E-303-CONDUIT ROUTING
E-304-CONDUIT ROUTING
M001-SCHEDULES
M301-PART PLANS
M302-DETAILS
Permit Drawings - Electrical_Update 8