p57783 Text Box SH-1=SH-3 missing but were previously approved. Please put them in the Final As-builts.
Door swing needs to be corrected in all affected sheets
See updated grounding page.
Line p57783
Door Swing should be reversed on all sheets
Door is ok here p57783 Line p57783
Make upper case
Comment Q/A indicated should be 4" p57783 Line p57783
6' max
FCC tower id sign needs to be included
Door Swing p57783 Line p57783 Line p57783 Line p57783 Line p57783 Line p65349 Text Box Possible to remove the tower ground ring in this area and connect to compound ground ring.
p57783 Line p57783 Line p65349 Callout Bond Fence post to compound ground ring- 3 sides.
p57783 Rectangle p57783 Rectangle p57783 Rectangle p57783 Line p57783 Rectangle p57783 Rectangle p57783 Rectangle p57783 Line p57783 Line p57783 Line p57783 Oval p57783 Oval p57783 Text Box Bond compound ground ring and tower ground ring on three sides p57783 Line p57783 Rectangle p57783 Rectangle p57783 Rectangle p57783 Line p57783 Oval p57783 Line p57783 Rectangle p57783 Rectangle p57783 Line p57783 Text Box Bond fence post to compound ground ring p57783 Line p57783 Text Box Deterrent wires grounded at each corner post p57783 Line p57783 Rectangle p57783 Oval p57783 Line p57783 Text Box Bond fence post to ground ring.