Male Head Female Head

Locker Room

Conference Room

Three person office

Mechanical Room

CPO Office

Waiting Area

LHO Office

Kitchen Area

Carpentry Shop

C o r r i d o r

Electrical shop

Storage Area

Desk

Desk

Desk Desk

Desk

Desk

FILES

Entrance Shop Entrance

Deep Sink

Bench Bench

Secure Storage

Storage Entrance

Doors

Comp Room

Toilets

50’

100’

40’ 16’ 12’ 10’ 10’ 14’

42’

1” = 8’

Chair

Desk

Sink

Locker

Shower Shower

Computer

TV

Storage shelves

Windows

Carpentry 4 Male Heads 1 Female Head 1 Conference 3 LHO Office 1 Waiting area 1 Three person 4 Electrical 1

No Windows in storage area

Storage shelves

4’

Room sizes are approximate, scale rooms based on dimensions shown, increase as neccessary to provide a complete and functional facility

105A

MMcAll Text Box Shop entrance door and storage entrance door shall be min 10'-0" roll-up doors lockable from the inside and both motor and chain operated.

All other man doors shown will have door closers and kick plates on both sides.

MMcAll Text Box Doors

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Text Box Provide additional doors on exterior as needed for exiting requirements

MMcAll Text Box In addition to the outlets required in the RFP provide 8 recessed flush mounted duplex 20 amp 120 v floor outlets with covers in the carpentry shop area. Recessed outlet boxes must be traffic rated. Floor out lets must be on 4 separate circuits and disconnect with the 1 power off button for all outlets within this space.

MMcAll Text Box Provide 230v 60 amp breaker and outlet for welder and provide exhaust system.

MMcAll Line

MMcAll Text Box Double door

MMcAll Line

MMcAll Text Box provide a minimum of 1 exterior hydrant centered on each face of the building.

MMcAll Text Box provide expanded metal lockable cage full hieght wall and door

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Text Box

REVISED MAINTENANCE FLOOR PLAN DATED 3-21-16

MMcAll Text Box Provide flush mounted 2 duplex 20am 120 volt floor boxes in center of the Conference room in addition to other outlet requirements.

MMcAll Text Box Furnish and install overhead air distribution system and 2 retractable air hose systems with 50" of hose on each. Space reels 20 feet apart from the center of Carpenter shop. Provide piping to each of the compressed air points of connections shown.

MMcAll Oval

MMcAll Oval

MMcAll Oval

MMcAll Oval

MMcAll Oval

MMcAll Oval

MMcAll Oval

MMcAll Oval

MMcAll Text Box Compressed air point of connection

MMcAll Text Box

MMcAll Text Box

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Line

MMcAll Text Box Provide new two lane ac paved road to new maintenance building. Install road and provide lighting curbs gutters and sidewalks as required to meet State DOT and City of Astoria standards. Provide and stripping, wheel stops and parking spaces for 10 vehicles (9' x18' spaces min). Delivery truck can be assumed to back in for large loads. Provide K rail barrier at edge of road and parking area where necessary to keep vehicles from leaving paved area.

Insure access to existing office and garages remains usable during and after completion of new facility.

locate maintenance building in general area shown .adjust grades as necessary to provide parking and roads. demolish existing playground shown under new maintenance facility entirely. Provide bollards by all roll-up doors Provide a dumpster pad at least 8'x 12' Coordinate and pay for any utility connections directly with the utility provider and or City of Astoria.

MMcAll Text Box

REVISE MAINTENANCE BUILDING CONCEPT

SITE PLAN. Dated 3-21-16

Space Criteria Analysis Data Sheet

GREATER ASTORIA FAMILY HOUSING PHASE II / SECTOR COLUMBIA

RIVER

Housing Maintenance Shop/Storage Space Project SFRL 13-S04004

Sector Columbia River Family Housing

Minimum Housing Maintenance Building Space Requirements

SPACE NAME

SIZE

SPACE CODE

ENGLISH (sf)

Column1 Column2 Column3

CARPENTRY SHOP

Shop Assembly Area 100 219.002

Shop Equipment 219.003

Drill press 140 219.007

Table saw 265 219.017

Tool storage (10sf per DC/carpenter assigned) 50 219.018

Vertical saw (Panel Saw) 120 219.019

Work bench

(60sf per every two DC's/carpenters assigned) 120

CARPENTRY SHOP STORAGE 219.400

Secured Shop Storage (Table A sf) 150 219.401

Wood Storage Table (Table B sf) 400 219.402

Materials Storage (Table C sf) 300 219.403

219.030

219.430

219.031

219.431

ELECTRICAL MAINTENANCE 219.060

ELECTRICAL SHOP 219.061

Shop Circulation 150 219.062

Shop Equipment 219.063

Threader 60 219.066

(size per every two EM's/electricians assigned) 60 219.067

ELECTRICAL SHOP STORAGE 219.46

Secured Shop Storage (Table D sf) 120 219.461 Secured Materials/Lamp Storage (Table E sf) 100 219.462

GREATER ASTORIA FAMILY HOUSING PHASE II / SECTOR COLUMBIA

RIVER

Housing Maintenance Shop/Storage Space

SECURE STORAGE 219.080

Storage 120 219.081

219.480

ADMINISTRATIVE SPACES

Shared Office

DCC/E7 & DC1/E6 Office 150 Open Office Area (60sf per Workstation)

Work stations (1:3 Workstation to Mx Staff) 120 Shipping and receiving 200

Male/Female locker/toilet/showerss 300 Break Room/Coffee Mess 100

Conference room 250

Total min Net Square Feet Per Drawing

Mimimum TOTAL GROSS SQUARE FEET 5,000

Note: Maintenance building shall comply with ADA requirements increase spaces as required to provide accessable spaces.

GREATER ASTORIA FAMILY HOUSING PHASE II / SECTOR COLUMBIA RIVER

Housing Maintenance Shop/Storage Space Project SFRL 13-S04004

Room Number and Space Name: BUILDING SUPPORT SPACES, AS NEEDED: JANITOR’S

CLOSET, MECH / ELEC / COMM ROOMS

1. Space function / user activity:

Provide support spaces as needed. Provide a janitor’s closet for equipment, tools, and supplies

2. Number of occupants:

Not Applicable

3. Contractor Furnished and Contractor Installed (CFCI) Specialties, Equipment and Furnishings:

SU – Shelving Units – provide two (2) 18” deep,48” wide, and 87” high metal shelving units in Janitor’s closet

4. Government Furnished and Contractor Installed (GFCI) Specialties, Equipment and Furnishings:

None

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable) – requiring CFCI utility connections:

None

6. Finishes (function, durability and maintenance issues):

Floor: Sealed concrete Base: Resilient rubber Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent grade Walls in Janitor’s closet: Provide Fiberglass Reinforced Panels (FRP) over gypsum board Ceiling: Suspended acoustical ceiling tile system; minimum 9’ height or painted gypsum board.

Telecommunications closet: shall be a minimum of 100 sf, One wall will have a minimum of 32 sf 5/8” fire treated plywood painted white for telecommunications punch downs. Ceiling shall be sheetrock with surface mounted lighting in this space.

7. Doors: (note: verify any fire rating requirements):

Fire rating as required,

8. Windows:

None

9. Room Identification Signage: (install at latch side of door)

PER ADA requirements

10. Sound Attenuation Treatment including STC Rating requirements:

None

Housing Maintenance Shop/Storage Space Project SFRL 13-S04004

Room Number and Space Name: BUILDING SUPPORT SPACES, AS NEEDED: JANITOR’S

CLOSET, MECH / ELEC / COMM ROOMS

11. Physical Security (Classification, IDS, CCTV, etc):

Provide “Best” 7 pin, removable core, keyed locks on Communications room, Mechanical and electrical rooms. Provide passage set for janitor closet.

12. Mechanical (HVAC):

Standard ventilation, heating and cooling system per Section 01800-1.12.

13. Plumbing:

Plumbing for fixtures per Section 01800-1.11 Water Janitor’s mop sink

14. Electrical (power/lighting):

Provide lighting fixtures compatible with ceiling tile system per Specification Section 01800- 1.13.

Provide Receptacle Outlets per Specification Section 01800-1.13.

15. Communications:

Provide 1 tel/data outlet per Section 01800-1.14 (3 CAT 5 outlets).

16. Other:

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 101 - CARPENTRY SHOP

This space is used to repair, re-build or assemble miscellaneous general carpentry items for the housing units.

2. Number of occupants:

Normal Hours – 40-50 per week Maximum - Up to 10 personnel

3. Contractor Furnished and Contractor Installed (CFCI) Specialties, Equipment and

WH - Whiteboard, provide two (1) 4’ tall by 4’ wide porcelain steel surface with aluminum trim.

CB – Cork Board, provide one (1) 4’ tall by 4’ wide cork board with aluminum trim.

CH - Steel coat hooks. Provide four (4) grouped together and located at entry door.

FE - Fire Extinguisher, provide one (1) 15lb cabinet mounted WBL –Window Blinds, 1” horizontal, aluminum, provide one (1) at each window DUST COLLECTION SYSTEM - Per Section 01800-1.12.

None

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable) – requiring CFCI utility connections:

Table saw Drill Press Vertical Saw Work Benches (2) Tool Storage Shelving (3) Computers (2) Phones (2) Self contained Eyewash (1)

6. Finishes (function, durability and maintenance issues):

Floor: Sealed concrete, with non-slip/non-skid finish Base: Resilient rubber Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent grade Ceiling: Suspended acoustical ceiling tile system; minimum 12’ height

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 101 - CARPENTRY SHOP

Opening from Interior - Provide 3’ wide by 7’ tall wood door on steel frames and lockable lever handle. Provide “Best” 7 pin, removable core, keyed locks on all doors securing perimeter of Carpentry shop including interior doors.

8. Windows:

Vinyl, Double hung, with insulating glass ( provide 4 windows – min( 3’x 5’)) Provide solid surface sills, insect screens, and 1” horizontal blinds.

9. Room Identification Signage: (install at latch side of door)

PER ADA Requirements

10. Sound Attenuation Treatment including STC rating requirements:

Provide min 50 STC separation between Carpentry shop and office and conference spaces

11. Physical Security (Classification, IDS, CCTV, etc):

None

12. Mechanical (HVAC):

Standard heating and cooling system per Section 01800-1.12.

13. Plumbing:

None

14. Electrical (power/lighting):

Provide Lay-in Lighting fixtures compatible with ceiling tile system per Specification Section 01800-1.13.

Provide Receptacle Outlets per Specification Section 01800-1.13.

15. Communications:

Provide 2 tel/data outlets, at work bench area and 1 tel/data outlet every 20 feet along shop walls, per Section 01800-1.14 .

Keying – Provide Best brand locks with 7 pin removable cores to match existing at Coast Guard main office

Provide a shop area as shown on revised maintenance building floor plan dated 3-21-16.

Provide power kill buttons at all man doors entering the carpentry shop. This Power kill buttons shall disable all shop equipment and outlets within this carpentry shop space lights shall stay on. Provide protective cover and signage for all power “kill” buttons.

Provide Compressed air piping and outlets where shown on floor plan dated 3-21-16.

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 102 - CARPENTRY SHOP STORAGE

This space is used for bulk storage of miscellaneous general carpentry items, supporting the

Carpentry Shop. This space also supports shipping and receiving.

2. Number of occupants:

Storage System capable of 100lbs/sf of storage 3 shelves 12’ high 36” wide along walls and center of storage area as indicated on drawings

None

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable) – requiring CFCI utility connections:

Bulk material storage cabinets, bins, boxes, etc.

6. Finishes (function, durability and maintenance issues):

Floor: Sealed concrete, with non-slip/non-skid finish Base: Resilient rubber Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent

Ceiling: Suspended acoustical ceiling tile system; minimum 12’ height

Opening to Exterior, Provide 12’-0” wide by 10’-0” high insulated Overhead Sectional Door, lockable, automatic sectional door.

Opening from Interior – Provide 2- 3’ wide by 7’ tall wood doors on steel frames and lockable lever handle and 3’-0 high Kick plates both sides of doors.

8. Windows:

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 102 - CARPENTRY SHOP STORAGE

Per ADA requirements

10. Sound Attenuation Treatment including STC rating requirements:

11. Physical Security (Classification, IDS, CCTV, etc):

None

12. Mechanical (HVAC):

Standard heating system per Section 01800-1.12.

13. Plumbing:

Provide one exterior hose bib near the exterior doors

14. Electrical (power/lighting):

Provide Lay-in Lighting fixtures compatible with ceiling tile system per Specification Section 01800-1.13.

Provide Receptacle Outlets per Specification Section 01800-1.13.

15. Communications:

Provide 1 tel/data outlet, per Section 01800-1.14.

Keying – Provide Best brand locks, 5 button security rated lockset with removable 7 pin core.

Provide a minimum space required to make the storage area functional per the layout shown. Passage ways between storage shall be 4’-0” wide minimum.

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 103 – SECURESTORAGE STORAGE

This space is used as Secure storage space for higher value items

Maximum - Up to 3 personnel

WBL – Shelving provide shelving all 4 walls 5 shelves per wall, capacity 50 1bs/foot

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable – requiring CFCI utility connections:

Bulk material storage cabinets, bins, boxes, shelves, etc.

Base: Resilient rubber Walls: Painted gypsum board over 5/8” T&G Plywood on metal or wood studs (over concrete where walls abut adjacent grade Ceiling: Painted gypsum board over 5/8” T&G Plywood 9’ height min.

Opening from Interior - Provide 3’ wide by 7’ tall metal door on steel frames. Provide security rated 5 button combination lock and removable 7 pin core compatible with Best Access system.

none

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 103 – SECURESTORAGE STORAGE

12. Mechanical (HVAC):

Standard heating and cooling system per Section 01800-1.12.

13. Plumbing:

None

14. Electrical (power/lighting):

Provide lighting fixtures compatible with ceiling system per Specification Section 01800-1.13.

16. Other:

Keying – Provide Best brand locks

Size room per maintenance building layout dated 3-21-16 min 150 square feet.

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 104 – Conference Room

This space is used as conference and training room

Built in wall mounted desk/counter, min 28” wide solid surface material for training up to 4 people as shown.

WBL – Window Blinds, 1” horizontal, aluminum, provide one (1) at each window

4. Government Furnished and Contractor Installed (GFCI) Specialties, Equipment and Furnishings:

Conference table, wall mount TV

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable –

Bulk material storage cabinets, bins, boxes, shelves, etc. wall mounted TV

Base: Resilient rubber Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent

Ceiling: Suspended acoustical ceiling tile system; minimum 9’ height handle

Vinyl, Double Hung, with insulating glass ( min 2- 3’ X 5’ windows)

10. Sound Attenuation Treatment including STC Rating requirements:

50 STC all walls and ceiling

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 104 – Conference Room

12. Mechanical (HVAC):

Standard heating and cooling system per Section 01800-1.12.

13. Plumbing:

None

14. Electrical (power/lighting):

Provide Lay-in Lighting fixtures compatible with ceiling tile system per Specification Section 01800-1.13.

Provide duplex receptacle at each training area, Provide recessed quad outlet under conference room table (collocate with tele/data), Provide recessed wall outlet for TV. Receptacle Outlets per Specification Section 01800-1.13.

Provide (1) cable television outlet, per Section 01800-1.15 for TV 6’ above Finished floor.

15. Communications:

Provide 1 duplex tel/data outlet, per work station and every 6’ along walls. Provide recessed floor mounted quad tele data under conference room table. per Section 01800-1.14.

Keying – Provide lockable Handset with removable 7 pin core.

Provide a minimum of 250 net square feet

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 105 – ELECTRICAL MAINTENANCE

This space is used as an Electrical maintenance shop to support residential electrical equipment, fixtures, outlets, etc.

2. Number of occupants:

WBL – Window Blinds, 1” horizontal, aluminum, provide one (1) at each window (if windows are provided)

None

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable – requiring CFCI utility connections:

Threader

Floor: Sealed concrete, with non-slip/non-skid finish and static guard rubber flooring.

Base: Resilient rubber Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent grade Ceiling: Suspended acoustical ceiling tile system; minimum 9’ height or painted gypsum board.

Opening from Interior (2) 3’ wide by 7’ tall wood door on steel frames and lockable lever handle

8. Windows :

Vinyl, Double Hung, with insulating glass (Min 1 window 3’ x 5’)

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 105 – ELECTRICAL MAINTENANCE

12. Mechanical (HVAC):

Standard heating system per Section 01800-1.12.

13. Plumbing:

None

14. Electrical (power/lighting):

Provide 1 tel/data outlet, 1 per workstation, per Section 01800-1.14.

Keying – Provide Best brand locks to match existing at Coast Guard main office

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 105A – ELECTRICAL SHOP STORAGE

This space is used as secured storage in support of the Electrical maintenance shop.

None

4. Government Furnished and Contractor Installed (GFCI) Specialties, Equipment and Furnishings:

None

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable) – requiring CFCI utility connections:

Shelving and Storage cabinets

6. Finishes (function, durability and maintenance issues):

Floor: Sealed concrete, with non-slip/non-skid finish and static guard rubber flooring.

Base: Resilient rubber Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent grade 7 Gauge Expanded metal cage wall with sliding door full height Ceiling: Suspended acoustical ceiling tile system; minimum 9’ height or painted gypsum

Expanded metal Sliding door with removable 7 pin Core and handle.

9. Room Identification Signage: (install at latch side of door)

PER ADA Requirements

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 105A – ELECTRICAL SHOP STORAGE

Standard heating system per Section 01800-1.12.

13. Plumbing:

None

14. Electrical (power/lighting):

Keying – Provide Best brand locks with 7 pin removable core

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 106 – SHARED OFFICE

This space is used as a general office / work station area.

Maximum - Up to 5 personnel

WH - Whiteboard, provide one (1) 4’ tall by 4’ wide porcelain steel surface with aluminum trim.

WBL –Window Blinds, 1” horizontal, aluminum, provide one (1) at each window

4. Government Furnished and Contractor Installed (GFCI) Specialties, Equipment and Furnishings:

None

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable – requiring CFCI utility connections:

OSF - Office Systems Furniture, provide two (2) panel hung cubicle workstations.

DC – Desk chair, provide two (2) LF – Lateral file cabinet, provide two (2) 36” wide, 28” high, 18” deep, steel cabinet BK – Book shelf, provide one (1) FC – File cabinet, provide two (2) WH - Whiteboard, provide two (2) 4’ tall by 4’ wide porcelain steel surface with aluminum trim.

Computers (3) Phones (4)

Floor: Linoleum Base: Resilient rubber Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent grade Ceiling: Suspended acoustical ceiling tile system; minimum 9’ height or painted gypsum

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 106 – SHARED OFFICE handle

8. Windows:

Vinyl, Double Hung, with insulating glass (min 4- 3’ x 5’)

10. Sound Attenuation Treatment including STC Rating requirements:

None

11. Physical Security (Classification, IDS, CCTV, etc):

None

12. Mechanical (HVAC):

Standard heating and cooling system per Section 01800-1.12.

13. Plumbing:

None

14. Electrical (power/lighting):

Provide 1 tel/data outlet per workstation, per Section 01800-1.14.

16. Other:

Keying – Provide Best brand locks with 7 pin removable cores.

Provide a minimum of 150 net square feet

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 107 – LHO OFFICE COUNSELING AREA

This space is used as a housing manager office and tenant counseling.

Maximum - Up to 4 personnel

WH - Whiteboard, provide two (2) 4’ tall by 4’ wide porcelain steel surface with aluminum trim.

WBL –Window Blinds, 1” horizontal, aluminum, provide one (1) at each window

4. Government Furnished and Contractor Installed (GFCI) Specialties, Equipment and Furnishings:

None

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable – requiring CFCI utility connections:

OSF - Office Systems Furniture, provide two (2) panel hung cubicle workstations.

DC – Desk chair, provide two (2) LF – Lateral file cabinet, provide two (2) 36” wide, 28” high, 18” deep, steel cabinet BK – Book shelf, provide one (1) FC – File cabinet, provide two (2) Computers (1) Phones (1)

Floor: Linoleum Base: Resilient rubber Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent grade Ceiling: Suspended acoustical ceiling tile system; minimum 9’ height or painted gypsum board.

7. Doors: (note: verify any fire rating requirements):

handle.

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 107 – LHO OFFICE COUNSELING AREA

Vinyl, Double Hung, with insulating glass (Min 2- 3’x5’)

Per ADA Requirements

10. Sound Attenuation Treatment including STC Rating requirements:

50 STC walls and ceiling

11. Physical Security (Classification, IDS, CCTV, etc):

None

12. Mechanical (HVAC):

Standard heating and cooling system per Section 01800-1.12.

13. Plumbing:

None

14. Electrical (power/lighting):

Provide 1 quad tel/data outlet per workstation, per Section 01800-1.14.

16. Other:

Keying – Provide Best brand lockswith removable 7 pin core.

Provide a minimum of 150 net square feet

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 108 & 109 – MEN & WOMEN’S ROOM

This space provides toilet facilities for personnel.

N/A

3. Contractor Furnished and Contractor Installed (CFCI) Specialties, Equipment and Furnishings:

CH – Coat Hooks, provide four (4) per toilet room PAR – Partitions, at toilet stalls and urinals, HDPE construction MIR – Mirror, 36” high, full length of counter top, provide one (1) per toilet room PTD – Paper Towel Dispenser/Trash Receptacle, provide one (1) per toilet room SOD – Soap Dispenser, provide one (1) per sink TTD – Toilet Tissue Dispenser, double roll, provide one (1) per toilet stall SCD – Seat Cover Dispenser, provide one (1) per toilet stall FHD – Feminine Hygiene Disposal, provide one (1) per toilet stall. In Women’s

Toilet room only HDR – Hand Dryer, provide one (1) per toilet room (Electric Air dryer) WBL –Window Blinds, 1” horizontal, aluminum, provide one (1) at each window (if provided).

Shower Curtain/ shower stall

None

5. Government Furnished and Government Installed (GFGI) Equipment (fixed and movable) – requiring CFCI utility connections:

None

6. Finishes (function, durability and maintenance issues):

Floor: Ceramic tile Base: Ceramic tile cove base Walls: Painted moisture-resistant gypsum board over metal or wood studs (over concrete where walls abut adjacent grade), ceramic tile wainscot up to 4’-0” above finish floor Ceiling: Suspended acoustical ceiling tile system; minimum 9’ height or painted gypsum

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 111 CPO OFFICE

Opening from Interior - Provide 3’ wide by 7’ tall wood door on steel frames and push/pull hardware. Doors shall not be lockable.

8. Windows :

Vinyl, Casement , with insulating opaque glass

Per ADA Requirement

10. Sound Attenuation Treatment including STC Rating requirements:

Provide sound attenuation batt insulation in all surrounding stud wall cavities (STC 45 min). Provide sound attenuation batt insulation above ceiling tile.

12. Mechanical (HVAC):

Standard ventilation, heating and cooling system per Section 01800-1.12.

13. Plumbing:

Plumbing for fixtures per Section 01800-1.11 Water efficient lavatories, for all lavatories shown Water efficient urinal, provide per drawing of Men’s Toilet room

Provide a minimum of 120 net square feet each.

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 110 KITCHEN AREA

This space provides a break room / small conference area / all purpose space for personnel.

Maximum - Up to 4 personnel

RF – 25.0 cu ft Refrigerator Energy Star rated with ICE maker MW - 2.0 cubic foot countertop microwave oven, on shelf above countertop SSC - Solid Surface Countertop with backsplash.

CAB – Cabinets, under countertop and above counter continuous include shelf above for microwave

4. Government Furnished and Contractor Installed (GFCI) Specialties, Equipment and Furnishings:

None

5. ContractorFurnished and Contractor Installed (GFC) Equipment (fixed and movable) –

Floor: Vinyl tile Base: cove base Walls: Painted gypsum board over metal or wood studs (over concrete where walls abut adjacent grade), None.

9. Room Identification Signage: (install at latch side of door)

Per ADA Requirement

10. Sound Attenuation Treatment including STC Rating requirements:

None

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 110 KITCHEN AREA

Standard ventilation, heating and cooling system per Section 01800-1.12.

13. Plumbing:

Plumbing for fixtures per Section 01800-1.11 Water efficient kitchen sink Water supply with valves for Coffee maker separate from sink

Provide Receptacle Outlets per Specification Section 01800-1.13. Minimum of 4 duplex outlets above counter.

15. Communications:

None

16. Other:

Layout per drawing t.

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 112 LOCKER ROOM

This space provides a personnel clothing storage for staff

2. Number of occupants:

Maximum - Up to 12 personnel

Provide 12 24” X 18” X 6’ Metal lockers with lockable doors Lockers must be set on 4” high Concrete curb.e

None

5. ContractorFurnished and Contractor Installed (GFC) Equipment (fixed and movable) –

Base: cove base

None.

9. Room Identification Signage: (install at latch side of door)

Per ADA Requirement

10. Sound Attenuation Treatment including STC Rating requirements:

Standard ventilation, heating and cooling system per Section 01800-1.12.

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 112 LOCKER ROOM

13. Plumbing:

Plumbing for fixtures per Section 01800-1.11 Water efficient kitchen sink Separate Water supplies with valves for coffee maker separate from sink, and for Ice maker

14. Electrical (power/lighting):

Provide lighting fixtures compatible with ceiling system per Specification Section 01800-1.13.

Provide Receptacle Outlets per Specification Section 01800-1.13. Minimum of 4 duplex outlets above counter.

Layout per drawing

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 113 WAITING ROOM

This space provides a waiting area for tennats

2. Number of occupants:

Maximum - Up to 8 personnel

NONE

4. Government Furnished and Contractor Installed (GFCI) Specialties, Equipment and Furnishings:

None

5. ContractorFurnished and Contractor Installed (GFC) Equipment (fixed and movable) –

NONE

Base: cove base

Front door shall be fiberglass with 12”x 18” window light and have lockable Best hardware with removable 7 pin cores.

8. Windows:

Provide 1 vinyl window 3’x 5’ double hung with solid surface sill.

9. Room Identification Signage: (install at latch side of door)

Per ADA Requirement

10. Sound Attenuation Treatment including STC Rating requirements:

None

11. Physical Security (Classification, IDS, CCTV, etc):

None

12. Mechanical (HVAC):

Standard ventilation, heating and cooling system per Section 01800-1.12.

13. Plumbing:

Housing Maintenance Shop/Storage Space

Room Number and Space Name: RM 113 WAITING ROOM

Provide Receptacle Outlets per Specification Section 01800-1.13. Minimum of 2 duplex outlets

15. Communications:

Provide 1 data and telephone Jack

16. Other:

Provide Layout per drawing.

Provide walk off mat at entry

Housing Maintenance Shop/Storage Space

Room Number and Space Name: CORRIDOR

Room Number and Space Name: RM 114 Corridors

1. Walls Painted sheet rock

2. Provide stainless steel Corner Guards on all outside corners minimum 4’ high.

3. Provide lighting fixtures compatible with ceiling system per Specification Section 01800-1.13 Provide duplex outlet every 20 linear feet along corridor.

End of Section.