REVISIONS TO BID DOCUMENTS – August 13, 2014
New Commissary Facility, NASJAX, Jacksonville, Florida
Solicitation Issue - May 2014
TABLE OF CONTENTS
00 01 10-1
New Commissary Facility, NASJAX, Jacksonville, Florida
TABLE OF CONTENTS
(Edited from DeCA June 2013 Design Criteria)
DIVISION 00 – PROCUREMENT AND CONTRACTING REQUIREMENTS
00 01 00 Table of Contents Bid Schedule 00 31 00 Available Project Information Geotechnical Report
DIVISION 01 GENERAL REQUIREMENTS
01 11 00 Summary of Work – Revision to Bid Documents – 30 June 2014 01 13 00 Notice to Proceed Form 1413 Statement and Acknowledgement 01 14 00 Work Restrictions 01 26 00 Contract Modification Procedures 01 30 00 Administration Requirements ENG Form 4025-R Submittal Register 01 31 13.13 Mechanical, Refrigeration, Food Service Equipment, and Electrical Coordination 01 31 23 Project Website 01 32 16 Construction Progress Documentation 01 33 29 Sustainable Design Reporting (LEED) LEED Checklist LEED Narrative 01 35 26 Government Safety Requirements 01 35 40 Environmental Management 01 35 43.19 Environmental Procedures for Refrigeration 01 35 46 Indoor Air Quality Procedures 01 42 00 References 01 45 00 Quality Control Statement of Special Inspections Statement of SI Requirements for Wind Resistance Schedule of Special Inspections Final Report of Special Inspections Contractor Statement of Responsibility Fabricator Certificate of Compliance Special Inspection Daily Report Special Inspection Discrepancy Notice
01 50 00 Temporary Facilities and Controls 01 56 39 Temporary Tree and Plant Protection 01 64 00 Government Furnished Products 01 73 29 Cutting and Patching 01 77 00 Closeout Procedures
Solicitation: HDEC03-14-R-0003 NAS Jacksonville Amend 02 - Addendum 04 - Intrusion Dection Revision Aug 13, 2014 peterssh Line
TABLE OF CONTENTS
00 01 10-2
Form dd1354 Transfer Form 01 79 00 Demonstration and Training 01 91 13 General Commissioning Requirements
DIVISION 02 EXISTING CONDITIONS
02 41 00 Demolition – Existing Conditions
DIVISION 03 CONCRETE
03 30 00 Cast-In-Place Concrete 03 30 50 Insulated Freezer Floors 03 35 43 Polished Concrete Finishing 03 45 00 Precast Architectural Concrete 03 47 13 Tilt-Up Concrete
DIVISION 04 MASONRY
04 20 00 Unit Masonry – Revision to Bid Documents – 30 June 2014 04 43 01 Stone Masonry Veneer
DIVISION 05 METALS
05 12 00 Structural Steel Framing 05 21 00 Steel Joist Framing 05 30 00 Steel Decking 05 40 00 Cold-Formed Metal Framing 05 44 00 Cold-Formed Metal Trusses 05 50 13 Metal Fabrications 05 51 00 Metal Stairs 05 52 00 Pipe Railings
DIVISION 06 WOOD, PLASTICS, AND COMPOSITES
06 10 00 Rough Carpentry 06 16 00 Sheathing 06 40 23 Interior Architectural Woodwork 06 83 16 Fiberglass Reinforced Paneling
DIVISION 07 THERMAL AND MOISTURE PROTECTION
07 21 00 Thermal Insulation 07 24 00 Direct Applied Exterior Finish Systems 07 25 00 Building Air Barrier System 07 40 00 Metal Panels – Revision to Bid Documents – 30 June 2014 07 53 23 Ethylene Propylene Diene Monomer Roofing (White) 07 60 00 Sheet Metal Flashing and Trim 07 71 00 Roof Specialties
Solicitation: HDEC03-14-R-0003 NAS Jacksonville Amend 02 - Addendum 04 - Intrusion Dection Revision Aug 13, 2014
TABLE OF CONTENTS
00 01 10-3
07 81 50 Sprayed-on Fireproofing 07 84 00 Firestopping 07 92 00 Joint Sealants
DIVISION 08 OPENINGS
08 08 00 Commissioning of Openings 08 11 13 Hollow Metal Doors and Frames 08 14 16 Flush Wood Doors 08 31 13 Access Doors and Frames 08 33 23 Overhead Coiling Doors 08 38 00 Traffic Doors 08 41 13 Aluminum-Framed Entrances and Storefronts 08 42 29.23 Sliding Automatic Entrances 08 42 29.43 Sliding Automatic Entrances Impact Rated 08 62 00 Daylighting 08 71 00 Door Hardware 08 79 13 Key Storage Equipment 08 81 00 Glazing 08 83 00 Mirrors
DIVISION 09 FINISHES
09 05 61 Common Work Results for Flooring Preparation 09 22 36.23 Metal Lath 09 29 00 Gypsum Board 09 30 00 Tiling 09 51 00 Acoustical Ceilings 09 65 19 Resilient Tile Flooring 09 67 23 Resinous Flooring 09 90 00 Painting and Coatings 09 96 00 High Performance Coatings
DIVISION 10 SPECIALTIES
10 08 00 Commissioning of Specialties 10 10 00 Visual Display Surfaces 10 14 00 Signage 10 15 00 Interior Decor Specialties 10 21 13 Toilet Compartments 10 22 13 Wire Mesh Partitions 10 26 00 Wall and Equipment Protection 10 28 13 Toilet Accessories 10 44 00 Fire-Protection Specialties 10 51 13 Metal Lockers 10 56 23 Rotating Modular System
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
TABLE OF CONTENTS
00 01 10-4
10 56 29 Storage Racks
DIVISION 11 EQUIPMENT
11 08 00 Commissioning of Equipment 11 13 00 Loading Dock Equipment 11 17 00 Teller and Service Equipment 11 40 00.13 Bakery Equipment 11 40 00.16 Deli Equipment 11 40 00.19 Grocery Equipment 11 40 00.24 Miscellaneous Equipment 11 40 00.26 Produce Equipment 11 82 36 Facility Waste Balers
DIVISION 12 FURNISHINGS
12 21 13 Horizontal Louver Blinds 12 48 13.16 Recessed Floor Mats and Frames 12 59 00 Systems Furniture 12 93 00 Site Furnishings
DIVISION 13 SPECIAL CONSTRUCTION
13 08 00 Commissioning of Special Construction 13 10 00 Lightning Protection 13 21 26 Cold Storage Rooms
DIVISION 14 CONVEYING SYSTEMS
14 21 23 Machine Room-Less Elevators
DIVISION 21 FIRE SUPPRESSION
21 08 00 Commissioning of Fire Suppression 21 13 00 Fire Suppression Sprinkler Systems 21 30 00 Fire Pumps
DIVISION 22 PLUMBING
22 05 00 Common Work Results for Plumbing 22 05 19 Plumbing Specialties 22 05 29 Hangers and Supports for Plumbing Piping and Equipment 22 05 53 Identification for Plumbing Piping and Equipment 22 07 19 Plumbing Piping Insulation 22 08 00 Commissioning of Plumbing 22 10 00 Plumbing Piping 22 30 00 Plumbing Equipment 22 40 00 Plumbing Fixtures
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
TABLE OF CONTENTS
00 01 10-5
DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING (HVAC)
23 01 00 Maintenance and Repair for HVAC and Refrigeration 23 05 00 Common Work Results for HVAC 23 05 13 Common Motor Requirements for HVAC Equipment 23 05 29 Hangers and Supports for HVAC Piping And Equipment 23 05 53 Identification for HVAC Piping and Equipment 23 05 93 Testing Adjusting and Balancing for HVAC 23 07 13 Duct Insulation 23 07 19 HVAC Piping Insulation 23 08 00 Commissioning of HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 16 Refrigeration Monitoring and Control Systems (RMCS) 23 23 00 Refrigerant Piping for HVAC 23 31 13 Metal Ducts and Air Accessories 23 34 23 HVAC Power Ventilators 23 37 13 Diffusers Registers and Grilles 23 38 13 Commercial Kitchen Hoods 23 51 00 Breechings, Chimneys and Stacks 23 54 16 Fuel-Fired Heaters 23 74 13 Packaged Rooftop HVAC Units 23 81 26 Ductless Split-System Air Conditioners 23 82 16 Air Coils 23 84 16 Mechanical Dehumidification Units 23 90 00 Product Refrigeration Systems – Revision to Bid Documents – 30 June 2014
DIVISION 26 ELECTRICAL
26 05 00 Common Work Results for Electrical 26 05 13 Medium-Voltage Cables 26 05 19 Low-Voltage Electrical Power Conductors and Cables 26 05 26 Grounding and Bonding for Electrical Systems 26 05 33 Raceways and Boxes for Electrical Systems 26 05 36 Cable Trays for Electrical Systems 26 05 48 Vibration and Seismic Controls for Electrical Systems 26 05 53 Identification for Electrical Systems 26 05 60 Arc Flash Hazard Analysis 26 08 00 Commissioning of Electrical Systems 26 09 23 Lighting Control Devices 26 12 19 Medium-Voltage Transformers 26 22 00 Low-Voltage Transformers 26 23 00 Switchboards 26 24 16 Panelboards 26 25 00 Enclosed Bus Assemblies 26 27 26 Wiring Devices 26 27 73 Processing Area Signaling (Doorbell) System 26 28 01 Coordinated Power System Protection
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
TABLE OF CONTENTS
00 01 10-6
26 28 13 Fuses 26 28 16 Enclosed Switches and Circuit Breakers 26 32 14 Diesel-Engine Driven Generator Sets 26 34 20 Air Interrupter Switches 26 36 00 Transfer Switches 26 42 13 Passive Cathodic Protection for Underground and Submerged Piping 26 43 00 Transient Voltage Suppression 26 51 00 Interior Lighting 26 56 00 Exterior Lighting 26 57 00 Dimming Controls
DIVISION 27 COMMUNICATIONS
27 08 00 Commissioning of Communications Systems 27 15 00 Communications Horizontal Cabling 27 51 16 Public Address and Music Systems
DIVISION 28 ELECTRONIC SAFETY
28 08 00 Commissioning of Electronic Safety and Security Systems 28 16 00 Intrusion Detection – Revision to Bid Documents – 13 August 2014 28 31 00 Fire Detection and Alarm– Revision to Bid Documents – 13 August 2014 28 39 00 Mass Notification Systems
DIVISION 31 EARTHWORK
31 00 00 Earthwork – Revision to Bid Documents – 30 June 2014 31 10 00 Site Clearing 31 31 16 Termite Control
DIVISION 32 EXTERIOR IMPROVEMENTS
32 08 00 Commissioning of Exterior Improvements 32 12 17 Hot-Mix Bituminous Pavement 32 13 13 Concrete Paving 32 13 73 Concrete Paving Joint Sealants 32 31 13 Chain Link Fences and Gates 32 90 00 Planting
DIVISION 33 SITE UTILITIES
33 08 00 Commissioning of Utilities 33 11 00 Water Distribution 33 30 00 Sanitary Sewers 33 40 00 Storm Drainage Utilities 33 71 02 Underground Electrical Distribution
END TABLE OF CONTENTS
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
May 2014
INTRUSION DETECTION
28 16 00 - 1
SECTION 28 16 00
INTRUSION DETECTION
(Edited from DeCA June 2012 Design Criteria)
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Intrusion detection with multiplexed, modular, microprocessor-based controls, intrusion sensors and detection devices, and hard-wired premise communication links to perform monitoring, alarm, and control functions.
B. Related Sections:
1. Division 27 Section COMMUNICATIONS HORIZONTAL CABLING for cabling between central-station control units and field-mounted devices and controllers.
1.2 DEFINITIONS
A. LCD: Liquid-crystal display.
B. LED: Light-emitting diode.
C. PIR: Passive infrared.
D. RFI: Radio-frequency interference.
E. UPS: Uninterruptible power supply.
F. Protected or Protection Zone: A space or area for which an intrusion must be detected and uniquely identified, the sensor or group of sensors assigned to perform the detection, and any interface equipment between sensors and communication link to central-station control unit.
G. Standard Intruder: A person who weighs 100 lbor less and whose height is 60 inchesor less;
dressed in a long-sleeved shirt, slacks, and shoes.
H. Standard-Intruder Movement: Any movement, such as walking, running, crawling, rolling, or jumping, of a "standard intruder" in a protected zone.
1.3 SUBMITTALS
A. Product Data: Components for sensing, detecting, and control, including dimensions and data on features, performance, electrical characteristics, ratings, and finishes.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 2
1. Site and Floor Plans: Indicate final outlet and device locations, routing of raceways, and cables inside and outside the building.
2. Device Address List: Coordinate with final system programming.
3. System Wiring Diagrams: Include system diagrams unique to Project. Show connections for all devices, components, and auxiliary equipment. Include diagrams for equipment and for system with all terminals and interconnections identified.
4. Details of surge-protection devices and their installation.
5. Sensor detection patterns and adjustment ranges.
B. Equipment and System Operation Description: Include method of operation and supervision of each component and each type of circuit. Show sequence of operations for manually and automatically initiated system or equipment inputs. Description must cover this specific Project;
manufacturer's standard descriptions for generic systems are not acceptable.
C. Qualification Data: For Installer, testing agency.
D. Field quality-control test reports.
E. Operation and Maintenance Data: For intrusion detection system to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 01 Section Administrative Requirements, include the following:
1. Data for each type of product, including features and operating sequences, both automatic and manual.
2. Central-station control-unit hardware and software data.
F. Warranty: Special warranty specified in this Section.
G. Other Information Submittals:
1. Test Plan and Schedule: Test plan defining all tests required to ensure that system meets technical, operational, and performance specifications within 60 days of date of Contract award.
2. Examination reports documenting inspections of substrates, areas, and conditions.
3. Anchor inspection reports documenting inspections of built-in and cast-in anchors.
1.4 QUALITY ASSURANCE
A. Installer Qualifications:
1. An employer of workers, at least one of whom is a technician certified by the National Burglar & Fire Alarm Association.
2. Manufacturer's authorized representative who is trained and approved for installation of units required for this Project.
B. Intrusion Detection Systems Integrator Qualifications: An experienced intrusion detection equipment supplier and Installer who has completed systems integration work for installations similar in material, design, and extent to that indicated for this Project, whose work has resulted in construction with a record of successful in-service performance.
C. Testing Agency Qualifications: An independent testing agency, with the experience and capability to conduct the testing indicated, that is a member company of the National Burglar &
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 3
Fire Alarm Association or is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7.
1. Testing Agency's Field Supervisor: Person currently certified as an advanced alarm technician by the National Burglar & Fire Alarm Association to supervise on-site testing specified in Part 3.
D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
E. FMG Compliance: FMG-approved and -labeled intrusion detection devices and equipment.
F. Comply with NFPA 70.
1.5 PROJECT CONDITIONS
A. Environmental Conditions: Capable of withstanding the following environmental conditions without mechanical or electrical damage or degradation of operating capability:
1. Altitude: Sea level to 4000 feet.
2. Central-Station Control Unit: Rated for continuous operation in an ambient of 60 to 85 deg F and a relative humidity of 20 to 80 percent, noncondensing.
3. Interior, Controlled Environment: System components, except central-station control unit, installed in temperature-controlled interior environments shall be rated for continuous operation in ambients of 36 to 122 deg F dry bulb and 20 to 90 percent relative humidity, noncondensing.
4. Interior, Uncontrolled Environment: System components installed in non-temperature-controlled interior environments shall be rated for continuous operation in ambients of 0 to 122 deg F dry bulb and 20 to 90 percent relative humidity, noncondensing.
1.6 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer and Installer agree to repair or replace components of intrusion detection devices and equipment that fail in materials or workmanship within specified warranty period.
1. Warranty Period: One year from date of Substantial Completion.
1.7 EXTRA MATERIALS
A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Intrusion Detection Devices: Furnish quantity equal to five percent of the number of units of each type installed, but no fewer than one of each type.
2. Fuses: Three of each kind and size.
3. Tool Kit: Provide six sets of tools for use with security fasteners, each packaged in a compartmented kit configured for easy handling and storage.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 4
4. Security Fasteners: Furnish no fewer than 1 box for every 50 boxes or fraction thereof, of each type and size of security fastener installed.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Basis-of-Design Products: To establish the significant qualities related to type, function, dimension, in-service performance, physical properties, appearance, and other characteristics for purposes of evaluating comparable products of other manufacturers, a specific manufacturer's product is named and accompanied by the words "basis of design," including make or model number or other designation. Subject to compliance with requirements, provide either the named products or equal products.
B.A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.
2.2 FUNCTIONAL DESCRIPTION OF SYSTEM
A. Supervision: System components shall be continuously monitored for normal, alarm, supervisory, and trouble conditions. Indicate deviations from normal conditions at any location in system. Indication includes identification of device or circuit in which deviation has occurred and whether deviation is an alarm or malfunction.
1. Alarm Signal: Display at central-station control unit and actuate audible and visual alarm devices.
2. Trouble Condition Signal: Distinct from other signals, indicating that system is not fully functional. Trouble signal shall indicate system problems such as battery failure, open or shorted transmission line conductors, or controller failure.
3. Supervisory Condition Signal: Distinct from other signals, indicating an abnormal condition as specified for the particular device or controller.
B. System Control: Central-station control unit shall directly monitor intrusion detection devices and connecting wiring in a multiplexed distributed control system or as part of a network.
C. System shall automatically reboot program without error or loss of status or alarm data after any system disturbance.
D. Operator Commands:
1. Help with System Operation: Display all commands available to operator. Help command, followed by a specific command, shall produce a short explanation of the purpose, use, and system reaction to that command.
2. Acknowledge Alarm: To indicate that alarm message has been observed by operator.
3. Place Protected Zone in Access: Disable all intrusion-alarm circuits of a specific protected zone. Tamper circuits may not be disabled by operator.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 5
4. Place Protected Zone in Secure: Activate all intrusion-alarm circuits of a protected zone.
5. Protected Zone Test: Initiate operational test of a specific protected zone.
6. System Test: Initiate system-wide operational test.
7. Print Reports.
E. Printed Record of Events: Print a record of alarm, supervisory, and trouble events on system printer. Sort and report by protected zone, device, and function. When central-station control unit receives a signal, print a report of alarm, supervisory, or trouble condition. Report type of signal (alarm, supervisory, or trouble), protected zone description, date, and time of occurrence.
Differentiate alarm signals from other indications. When system is reset, report reset event with the same information concerning device, location, date, and time. Commands shall initiate the reporting of a list of current alarm, supervisory, and trouble conditions in system or a log of past events.
F. Response Time: Thirty seconds maximum between actuation of any alarm and its indication at central-station control unit.
G. Circuit Supervision: Supervise all signal and data transmission lines, links with other systems, and sensors from central-station control unit. Indicate circuit and detection device faults with both protected zone and trouble signals, sound a distinctive audible tone, and illuminate an LED. Maximum permissible elapsed time between occurrence of a trouble condition and indication at central-station control unit is 20 seconds. Initiate an alarm in response to opening, closing, shorting, or grounding of a signal or data transmission line.
H. Manual Secure-Access Control: Coded entries at manual stations shall change status of associated protected zone between secure and access conditions.
I. Alarm Transmission to Remote Monitoring Station: Transmit all alarm indications to a designated remote monitoring station via telephone lines. Transmissions must be compatible with monitoring station equipment used. (AMAG 2100 Alarm Boards). Coordinate with local authority having jurisdiction.
2.3 SYSTEM COMPONENT REQUIREMENTS
A. Surge Protection: Protect components from voltage surges originating external to equipment housing and entering through power, communication, signal, control, or sensing leads. Include surge protection for external wiring of each conductor entry connection to components.
1. Minimum Protection for Power Lines 120 V and More: Auxiliary panel suppressors complying with requirements in Division 26 Section Transient Voltage Suppression.
2. Minimum Protection for Communication, Signal, Control, and Low-Voltage Power Lines:
Comply with requirements in Division 26 Section Transient Voltage Suppression as recommended by manufacturer for type of line being protected.
B. Interference Protection: Components shall be unaffected by radiated RFI and electrical induction of 15 V/m over a frequency range of 10 to 10,000 MHz and conducted interference signals up to 0.25-V RMS injected into power supply lines at 10 to 10,000 MHz.
C. Tamper Protection: Tamper switches on detection devices, controllers, annunciators, pull boxes, junction boxes, cabinets, and other system components shall initiate a tamper-alarm signal when unit is opened or partially disassembled and when entering conductors are cut or
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 6 disconnected. Central-station control-unit alarm display shall identify tamper alarms and indicate locations.
D. Addressable Devices: Transmitter and receivers shall communicate unique device identification and status reports to central-station control unit.
2.4 ENCLOSURES
A. Interior Sensors: Enclosures that protect against dust, falling dirt, and dripping noncorrosive liquids.
B. Interior Electronics: NEMA 250, Type 12.
C. Screw Covers: Where enclosures are accessible to unauthorized persons, secure with security fasteners of type appropriate for enclosure.
2.5 SECURE AND ACCESS DEVICES
A. Available Manufacturers:
1. AMAG Technology, Inc.
1.2. ADEMCO Group; Pittway Corporation.
2.3. ADT
3.4. Continental Instruments.
4.5. Corby Industries Inc.
5.6. Crow Electronic Engineering, Inc.
6.7. George Risk Industries.
7.8. Honeywell International Inc.
8.9. International Electronics Inc.
9.10. NAPCO Security Systems, Inc.
10.11. Optex.
11.12. Richardson Electronics, Ltd.
12.13. Visonic Inc.
B. Keypad and Display Module: Arranged for entering and executing commands for system-status changes and for displaying system-status and command-related data.
2.6 DOOR AND WINDOW SWITCHES
A. Available Manufacturers:
1. AMAG Technology, Inc.
1.2. ADEMCO Group; Pittway Corporation.
2.3. ADT
3.4. Aleph International Corporation.
4.5. Amseco; Division of Kobishi America, Inc.
5.6. FBII; Pittway Corporation.
6.7. GE Interlogix; General Electric Company.
7.8. George Risk Industries.
8.9. Honeywell International Inc.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 7
9.10. Optex.
10.11. Ultrak, Inc.; a division of Ademco Video Systems.
B. Description: Balanced-magnetic switch, complying with UL 634, installed on frame with integral overcurrent device to limit current to 80 percent of switch capacity. Bias magnet and minimum of two encapsulated reed switches shall resist compromise from introduction of foreign magnetic fields.
C. Flush-Mounted Switches: Unobtrusive and flush with surface of door and window frame.
D. Overhead Door Switch: Balanced-magnetic type, listed for outdoor locations, and having door-mounting magnet and floor- or frame-mounting switch unit.
2.7 PIR SENSORS
A. Available Manufacturers:
1. AMAG Technology, Inc.
1.2. ADEMCO Group; Pittway Corporation.
2.3. ADT.
3.4. Aleph International Corporation.
4.5. Crow Electronic Engineering, Inc.
5.6. Digital Security Controls, Ltd.
6.7. FBII; Pittway Corporation.
7.8. Honeywell International Inc.
8.9. NAPCO Security Systems, Inc.
9.10. Optex.
10.11. Richardson Electronics, Ltd.
11.12. Visonic Inc.
B. Description: Sensors detect intrusion by monitoring infrared wavelengths emitted from a human body within their protected zone and by being insensitive to general thermal variations.
1. Wall-Mounting Unit Maximum Detection Range: 125 percent of indicated distance for individual units and not less than 50 feet.
2. Ceiling-Mounting Unit Spot-Detection Pattern: Full 360-degree conical.
3. Ceiling-Mounting Unit Pattern Size: 84-inchdiameter at floor level for units mounted 96 inches above floor; 18-foot diameter at floor level for units mounted 25 feet above floor.
C. Device Performance:
1. Sensitivity: Adjustable pattern coverage to detect a change in temperature of 2 deg For less, and standard-intruder movement within sensor's detection patterns at any speed between 0.3 to 7.5 fps across 2 adjacent segments of detector's field of view.
2. Test Indicator: LED test indicator that is not visible during normal operation. When visible, indicator shall light when sensor detects an intruder. Locate test enabling switch under sensor housing cover.
2.8 DURESS-ALARM SWITCHES
A. Available Manufacturers:
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 8
1. AMAG Technology, Inc.
1.2. ADEMCO Group; Pittway Corporation.
2.3. ADT.
3.4. GE Interlogix; General Electric Company.
4.5. NAPCO Security Systems, Inc.
5.6. Visonic Inc.
B. Description: A switch with a shroud over the activating lever that allows an individual to covertly send a duress signal to central-station control unit over supervised wiring, with no visible or audible indication when activated. Switch shall lock in activated position until reset with a key.
1. Minimum Switch Rating: 50,000 operations.
2. Push Button: Finger activated, suitable for mounting on horizontal or vertical surface.
2.9 VIBRATION SENSORS
A. Available Manufacturers:
1. AMAG Technology, Inc.
1.2. ADEMCO Group; Pittway Corporation.
2.3. Potter Electric Signal.
3.4. PULNiX America, Inc.
B. Description: A sensor controller and piezoelectric crystal sensor elements that are designed to be rigidly mounted to structure being protected.
C. Device Performance: Detects high-frequency vibrations generated by use of such tools as oxyacetylene torches, oxygen lances, high-speed drills and saws, and explosives that penetrate a structure while not responding to any other mechanical vibration.
1. Circular detection pattern, with at least a 72-inch radius on protected structure.
2. Hookup Cable: Factory installed, not less than 72 inches.
3. Controller: Integral with sensor housing or in a separate assembly, locally adjustable by control under housing cover.
2.10 CENTRAL-STATION CONTROL UNITS
A. Available Acceptable Manufacturers:
1. AMAG Enterprise, HSE Version 7, utilizing AMAG 2100 and 2150 multi-node controllers with encrypted NIC modules, as manufactured by AMAG Technology, Inc.
2. No substitution.
1. ADEMCO Group; Pittway Corporation.
2. ADT.
3. Amseco; Division of Kobishi America, Inc.
4. DAQ Electronics, Inc.
5. Diebold, Incorporated.
6. FBII; Pittway Corporation.
7. GE Interlogix; General Electric Company.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 9
8. Honeywell International Inc.
9. Magal Security Systems Ltd.
10. NAPCO Security Systems, Inc.
11. Perimeter Products, Inc.
12. Richardson Electronics, Ltd.
13. Visonic Inc.
B. Description: Panel shall provide supervision of sensors and detection subsystems and their connecting communication links, status control (secure or access) of sensors and detector subsystems, activation of alarms and supervisory and trouble signals, and other indicated functions. The above manufacturers are only approved if compatible with the Host installation.
C. Construction: Modular, with separate and independent alarm and supervisory system modules.
Alarm-initiating protected zone boards shall be plug-in cards. Arrangements that require removal of field wiring for module replacement are not acceptable.
D. Comply with UL 1076.
1. Alarm Indication: Audible signal sounds and a plain-language identification of protected zone originating the alarm appears on LED, LCD, or cathode-ray-tube display at central-station control unit. Annunciator panel alarm light and audible tone identify protected zone signaling an alarm.
E. Operator Controls: Manual switches and push-to-test buttons that do not require a key to operate. Include the following:
1. Acknowledge alarm.
2. Silence alarm.
3. System reset.
4. LED test.
F. Resetting Controls: Prevent resetting of alarm, supervisory, or trouble signals while alarm or trouble condition persists.
G. Alphanumeric Display and System Controls: Arranged for interface between operator and addressable system components, including annunciation and supervision. Display alarm, supervisory, component status messages, and programming and control menu.
1. Display: LCD, 80 characters, minimum.
2. Keypad: Arranged to permit entry and execution of programming, display, and control commands.
H. Protected Zones: Quantity of alarm and supervisory zones as indicated, with capacity for expanding number of protected zones by a minimum of 25 percent.
I. Power Supply Circuits: Central-station control units shall provide power for remote power-consuming detection devices. Circuit capacity shall be adequate for at least a 25 percent increase in load.
J. Emergency Power Supply: Provide standby rechargeable batteries complete with built-in charger for direct power supply to the system.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 10
K. Cabinet: Lockable, steel enclosure arranged so operations required for testing, normal operation, and maintenance are performed from front of enclosure. If more than a single cabinet is required to form a complete control unit, provide exactly matching modular enclosures. Accommodate all components and allow ample gutter space for field wiring.
Identify each enclosure by an engraved, laminated, phenolic-resin nameplate. Lettering on enclosure nameplate shall not be less than 1 inch high. Identify, with permanent labels, individual components and modules within cabinets.
2.11 SECURITY FASTENERS
A. Operable only by tools produced for use on specific type of fastener by fastener manufacturer or other licensed fabricator. Drive system type, head style, material, and protective coating as required for assembly, installation, and strength.
B. Available Manufacturers:
1. Camcar Textron Inc.
2. Holo-Krome; a Danaher Corporation.
3. Safety Socket Screw Corporation.
4. Tamper-Pruf Screws, Inc.
5. Pinned Torx, or pinned hex (Allen).
C. Socket Flat Countersunk Head Fasteners:
1. Heat-treated alloy steel, ASTM F 835.
2. Stainless steel, ASTM F 879, Group 1 CW.
D. Socket Button Head Fasteners:
1. Heat-treated alloy steel, ASTM F 835.
2. Stainless steel, ASTM F 879, Group 1 CW.
E. Socket Head Cap Fasteners:
1. Heat-treated alloy steel, ASTM A 574.
2. Stainless steel, ASTM F 837, Group 1 CW.
F. Protective Coatings for Heat-Treated Alloy Steel:
1. Zinc chromate, ASTM F 1135, Grade 3 or 4; for exterior applications and interior applications where indicated.
2. Zinc phosphate with oil, ASTM F 1137, Grade I, or black oxide, unless otherwise indicated.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 11
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of intrusion detection.
1. Examine roughing-in for embedded and built-in anchors to verify actual locations of intrusion detection connections before intrusion detection installation.
2. For the record, prepare written report, endorsed by Installer, listing conditions detrimental to performance of intrusion detection.
B. Inspect built-in and cast-in anchor installations, before installing intrusion detection, to verify that anchor installations comply with requirements. Prepare inspection reports.
1. Remove and replace anchors where inspections indicate that they do not comply with requirements. Reinspect after repairs or replacements are made.
2. Perform additional inspections to determine compliance of replaced or additional anchor installations. Prepare inspection reports.
C. For material whose orientation is critical for its performance as a ballistic barrier, verify installation orientation.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 SYSTEM INSTALLATION
A. Comply with UL 681.
B. Security Fasteners: Where accessible to unauthorized persons, install intrusion detection components using security fasteners with head style appropriate for fabrication requirements, strength, and finish of adjacent materials except that a maximum of two different sets of tools shall be required to operate security fasteners for Project. Provide stainless-steel security fasteners in stainless-steel materials.
3.3 WIRING INSTALLATION
A. Wiring Method: Install wiring in metal raceways according to Division 26 Section Raceways and Boxes for Electrical Systems. Conceal raceway except in unfinished spaces and as indicated.
Minimum conduit size shall be 1/2 inch. Control and data transmission wiring shall not share conduit with other building wiring systems.
B. Wiring Method: Cable in metal raceways, concealed in accessible ceilings, walls, and floors when possible.
C. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points. Use lacing bars and distribution spools. Separate power-limited and non-power-limited conductors as recommended in writing by manufacturer. Install conductors parallel with or at right angles to sides and back of enclosure. Connect conductors that are terminated, spliced, or interrupted in
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 12 any enclosure associated with intrusion system to terminal blocks. Mark each terminal according to system's wiring diagrams. Make all connections with approved crimp-on terminal spade lugs, pressure-type terminal blocks, or plug connectors.
D. Wires and Cables:
1. Conductors: Size as recommended in writing by system manufacturer, unless otherwise indicated.
2. 120-V Power Wiring: Install according to Division 26 Section Low-Voltage Electrical Power Conductors and Cables, unless otherwise indicated.
3. Control and Signal Transmission Conductors: Install unshielded, twisted-pair cable, unless otherwise indicated or if manufacturer recommends shielded cable, according to Division 27 Section Communications Horizontal Cabling.
4. Computer and Data-Processing Cables: Install according to Division 27 Section Communications Horizontal Cabling.
E. Splices, Taps, and Terminations: Make connections only on numbered terminal strips in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures.
F. Install power supplies and other auxiliary components for detection devices at controllers, unless otherwise indicated or required by manufacturer. Do not install such items near devices they serve.
G. Identify components with engraved, laminated-plastic or metal nameplate for central-station control unit and each terminal cabinet, mounted with corrosion-resistant screws. Nameplates and label products are specified in Division 26 Section Identification for Electrical Systems.
H. All cable shall be clearly identified on the outside jacket as being RoHS compliant.
3.4 GROUNDING
A. Ground system components and conductor and cable shields to eliminate shock hazard and to minimize ground loops, common-mode returns, noise pickup, cross talk, and other impairments.
B. Signal Ground Terminal: Locate at main equipment rack or cabinet. Isolate from power system and equipment grounding. Provide 5-ohm ground. Measure, record, and report ground resistance.
C. Install grounding electrodes of type, size, location, and quantity indicated. Comply with installation requirements in Division 26 Section Grounding and Bonding for Electrical Systems.
3.5 FIELD QUALITY CONTROL
A. Pretesting: After installation, align, adjust, and balance system and perform complete pretesting to determine compliance of system with requirements in the Contract Documents. Correct deficiencies observed in pretesting. Replace malfunctioning or damaged items with new ones and retest until satisfactory performance and conditions are achieved. Prepare forms for systematic recording of acceptance test results.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 13
1. Report of Pretesting: After pretesting is complete, provide a letter certifying that installation is complete and fully operable; include names and titles of witnesses to preliminary tests.
B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust field-assembled components and equipment installation, including connections, and to assist in field testing. Report results in writing.
C. Perform the following field tests and inspections and prepare reports:
1. Inspection: Verify that units and controls are properly labeled and interconnecting wires and terminals are identified.
2. Operational Tests: Schedule tests after pretesting has been successfully completed.
Test all modes of system operation and intrusion detection at each detection device.
Test for detection of intrusion and for false alarms in each protected zone. Test for false alarms by simulating activities outside indicated detection patterns.
3. Electrical Tests: Comply with NFPA 72, Section A-7. Minimum required tests are as follows:
a. Verify the absence of unwanted voltages between circuit conductors and ground.
b. Test all conductors for short circuits using an insulation-testing device.
c. With each circuit pair, short circuit at the far end of circuit and measure circuit resistance with an ohmmeter. Record circuit resistance of each circuit on Record Drawings.
d. Verify that each controller is in normal condition as detailed in manufacturer's operation and maintenance manual.
e. Test signal and data transmission circuits complying with requirements in Division 27 Section Communications Horizontal Cabling for proper signal transmission under open-circuit conditions. One connection each should be opened at not less than 10 percent of initiating and indicating devices. Observe proper signal transmission according to class of wiring used.
f. Verify that transient surge-protection devices are installed according to manufacturer's written instructions.
g. Test each initiating and indicating device for alarm operation and proper response at central-station control unit.
h. Test both primary and secondary power. Verify, by test, that UPS is capable of operating the system for period and in manner specified.
D. Report of Tests and Inspections: Prepare a written record of tests, inspections, and detailed test results in the form of a test log.
E. Tag all equipment, stations, and other components for which tests have been satisfactorily completed.
3.6 DEMONSTRATION
A. Engage a factory-authorized service representative to train Government's maintenance personnel to adjust, operate, and maintain intrusion detection. Refer to Division 01 Section Demonstration and Training.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
INTRUSION DETECTION
28 16 00 - 14
3.7 ADJUSTING
A. Occupancy Adjustments: When requested within 12 months of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to three visits to Project during other than normal occupancy hours for this purpose. Visits for this purpose shall be in addition to any required by warranty.
END OF SECTION
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
FIRE DETECTION AND ALARM
28 31 00 - 1
SECTION 28 31 00
FIRE DETECTION AND ALARM
(Edited from DeCA June 2013 Design Criteria)
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Fire alarm systems.
B. Related Sections:
1. Division 08 Section Door Hardware for door closers and holders with associated smoke detectors, electric door locks, and release devices that interface with the fire alarm system.
2. Division 28 Section Mass Notification Systems (if provided).
1.2 DEFINITIONS
A. FMCP: Fire Alarm / Mass Notification Control Panel.
B. LED: Light-emitting diode.
C. NICET: National Institute for Certification in Engineering Technologies.
D. Definitions in NFPA 72 apply to fire alarm terms used in this Section.
E. AHJ: Authority Having Jurisdiction is an individual responsible for review, inspection, and/or approval of a system and shall include the building official, fire marshal, engineer, Contracting Officer, or Government's insurance representative. For this project, the AHJ shall be NAS JAX COR and Base Fire Department.
1.3 REFERENCES
A. All references shall be of the latest edition.
B. Factory Mutual (FM):
1. FM AG Approval Guide.
C. National Fire Protection Association (NFPA):
1. NFPA 13 Standard For The Installation of Sprinkler Systems.
2. NFPA 70 National Electrical Code.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
FIRE DETECTION AND ALARM
28 31 00 - 2
3. NFPA 72 National Fire Alarm Code.
4. NFPA 90A Standard For The Installation of Air Conditioning And Ventilating Systems.
5. NFPA 101 Life Safety Code.
D. Underwriters' Laboratories, Inc. (UL): Appropriate UL equipment standards:
1. UL 864 Control Panels.
2. UL 268 Smoke Detectors.
3. UL 268A Smoke Detectors (HVAC).
4. UL 38 Manually Actuated Signaling Boxes.
5. UL 346 Water flow Indicators for Fire Protection Signaling.
6. UL 1971, Standard for Visual Signaling Appliances.
E. Building Codes:
1. International Building Code.
2. International Fire Code.
F. ADA, and/or State and local equivalency standards as adopted by The Authority Having Jurisdiction.
G. Military Unified Facilities Criteria:
1. UFC 3-600-1.
2. UFC 3-600-02.
3. UFC 4-021-01.
1.4 SYSTEM DESCRIPTION
A. Noncoded, analog-addressable system; automatic sensitivity control of certain smoke detectors;
and multiplexed signal transmission. Signal communication within the premises shall be by hard-wired circuits.
B. All equipment furnished shall be new and the latest state of the art products of a single manufacturer, engaged in the manufacturing and sale of analog fire detection devices for over ten years.
C. The system as specified shall be reviewed, fully tested and approved by each of the Authorities Having Jurisdiction, and turned over to the Government in an operational condition.
D. In the interest of job coordination and responsibilities the installing contractor shall contract with a single supplier for fire alarm equipment, engineering, programming, inspection and testing.
E. The contractor shall provide a representative as requested for project meetings such as to assist in coordination of crafts.
1.5 PERFORMANCE REQUIREMENTS
A. Comply with NFPA 72.
B. Fire alarm signal initiation shall be by one or more of the following devices:
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
FIRE DETECTION AND ALARM
28 31 00 - 3
1. Manual stations.
2. Smoke detectors.
3. Automatic sprinkler system water flow.
4. Fire extinguishing system operation.
C. Fire alarm signal shall initiate the following actions:
1. Sound an audible alarm and display a custom screen/message defining the building/zone/room in alarm and the specific alarm point initiating the alarm.
2. Log to the system history archives all activity pertaining to the alarm condition.
3. Sound the ANSI 117-1 signal with synchronized audible alarm and visual strobe signals throughout the facility.
4. Audible signals shall be silenced from the fire alarm control panel by an alarm silence switch. Visual signals shall be programmable to flash until system reset or additional alarm silencing, as required.
5. A signal dedicated to sprinkler system water flow alarm shall not be silenced while the sprinkler system is flowing at a rate of flow equal to a single head.
6. Activation of any smoke detector in a single elevator lobby, or elevator equipment room when installed shall cause the recall of that bank of elevators to the first floor and control lockout. In the event of recall initiation by a detector in the first floor lobby, the recall shall be to the alternate floor as determined by the AHJ.
a. Where specifically required by the local AHJ and provided in writing, other alarm devices such as general alarms may initiate elevator recall. This is in violation of ANSI A17.1 "Elevator Code" and shall only be initiated when required by written and adopted Code of the local jurisdiction. Coordinate this feature with the Government’s Designated Representative through the Contracting Officer.
7. HVAC shut down shall be accomplished by system operated duct detectors as per local requirements. Unless specifically required by the AHJ, HVAC and duct detectors shall initiate a supervisory signal and not a building evacuation.
8. Door hold-open devices shall release upon alarm signal received by the FMCP.
9. Electric door locking devices shall release upon alarm signal received by the FMCP.
10. Provide for an alarm condition at an approved off-site monitoring station or as indicated on Drawings.
D. Supervisory signal initiation shall be by one or more of the following devices or actions:
1. FMCP and Loc LOC Remote Panel.
2. Display the origin of the supervisory condition report at the local panel.
3. Activate supervisory audible and dedicated visual signal.
4. Provide a means for silencing a supervisory signal shall be permitted only if it is key-operated, located in a locked enclosure, or arranged to provide equivalent protection against unauthorized use. Such a means shall be permitted only if it transfers the supervisory indication to a lamp or other visible indicator and subsequent supervisory signals in other zones cause the supervisory notification appliance(s) to re-sound.
5. Record within system history the initiating device and time of occurrence of the event.
6. Transmit the signal to the monitoring station.
E. System trouble signal initiation shall be by one or more of the following devices or actions:
1. Display at the local FMCP and loc remote panel the origin of the trouble condition report.
2. Activate trouble audible and visual signals at the control panel and as indicated on the drawings.
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
FIRE DETECTION AND ALARM
28 31 00 - 4
3. Silence audible signals from the fire alarm control panel via a trouble acknowledge switch.
4. Trouble reports for primary system power failure to the master control shall be optionally delayed for a period of time not greater than 200 seconds. Trouble conditions that have been restored to normal shall be automatically removed from the trouble display queue and not require operator intervention. This feature shall be software selectable and shall not preclude the logging of trouble events to the historical file.
5. Record within system history, the occurrence of the event, the time of occurrence and the device initiating the event.
6. Transmit the signal to the monitoring station.
F. System Trouble and Supervisory Signal Actions: Ring trouble alarm and annunciate at the FMCP and remote annunciators.
G. Power and Voltage Limitations:
1. Battery capacity calculations. Battery size shall be a minimum of 125 percent of the calculated requirement.
2. Power supplies shall be sized to furnish the total connected load in a worst-case condition plus 25 percent spare capacity. (i.e. 4A supply x .25 spare = 1A reserve.)
3. Voltage drop calculations for wiring runs demonstrating worst-case condition. Unless otherwise approved by the engineer, voltage drop calculations shall be performed using the Lump-Sum approach using device nominal rating voltage. Calculations must include and clearly indicate wire length out and back to panel. Calculations shall be provided for speaker, strobe, and text appliance circuits. Use of notification power booster panels shall be limited.
4. Device current values for voltage calculations shall be based on the lowest nameplate voltage. (i.e. current values at a voltage of 20 volts shall be used when available rather than current values for 24 volts.)
5. Notification Appliance Circuit (NAC) design shall incorporate a 25 percent spare capacity for future expansion.
6. End-of-line voltage reading will be required for each circuit and must have a 25 percent spare capacity. (i.e. 24V circuit - 21V nameplate = 3 volt drop x 0.25 spare = 0.75 volt safety factor required.)
7. In no case shall horn/strobe circuits be designed or measured to have an end-of-line voltage below 20 volts or the manufactures nameplate voltage, whichever is higher.
1.6 SUBMITTALS
A. Product Data: For each type of product indicated.
B. Shop Drawings: Five copies of all submittals shall be submitted to the Contracting Officer for review. The contractor shall include the following information in submittals.
1. Shop Drawings shall be prepared and signed by persons with the following qualifications:
a. Trained and certified by manufacturer in fire alarm system design.
b. Fire alarm certified by NICET, minimum Level III.
2. System Operation Description: Detailed description for this Project, including method of operation and supervision of each type of circuit and sequence of operations for manually
Solicitation: HDEC03-14-R-0003 NAS Jacksonville
FIRE DETECTION AND ALARM
28 31 00 - 5 and automatically initiated system inputs and outputs. Manufacturer's standard descriptions for generic systems are not acceptable.
3. Device Address List: Coordinate with final system programming.
4. Control input/output Matrix.
5. System riser diagram with device addresses, conduit sizes, and cable…