Appendix J - HC102812R0067.pdf
PDF 56 KB Posted
- Solicitation number
- HC102812R0067
- Issued by
-
Defense Information Systems Agency
About this file
Appendix J - Onmicable Cut Sheet
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARMORED CABLE
Aluminum Interlocked Armor 90°C - 600 Volt UL Type MC
Conductor:
- Stranded, bare copper in accordance with ASTM B3 and B8
Insulation:
- Cross-linked polyethylene type XHHW-2 per UL44
Ground Wire:
- Class B stranded bare copper in accordance with ASTM B3 and B8
Assembly:
- Conductors are cabled with suitable fillers and bare copper ground conductor
- Cable core is covered with binder tape
Armor:
- Aluminum interlocked armor
Jacket:
- Flame and sunlight resistant black PVC jacket
Standards:
- UL 1569, UL 44, UL 1581, UL Type MC-600 volts
- ICEA S-95-658/NEMA WC 70, ICEA T-29-520
- NEC Type XHHW-2 conductors
- IEEE 383, IEEE 1202
- Meets EPA 40 CFR part 261
- OSHA acceptable, NEC
Applications:
- Designed for use on power or control circuits
- Can be installed in cable tray, wire ways, racks, or buried directly
- Permitted for use in Class I, Division II and Class II, Division II per NEC
Part #
AWG
Size
No. of Cond.
Nom.
Insul.
Thick.
Ground Wire Size
Nom. O.D.
Lbs./M’ Ampacity*
40°C Ambient Recommend
Fitting Armor Overall
Y11203A 12... 3... .030”... 12... .54”... .65”... 215... – STE050
Y11003A 10... 3... .030”... 10... .61”... .73”... 300... – STE050
Y10803A 8... 3... .045”... 10... .75”... .85”... 410... 55... STE050
Y10603A 6... 3... .045”... 8... .83”... .93”... 551... 75... STE075
Y10403A 4... 3... .045”... 8... .101”... 1.01”... 735... 95... STE100
Y10203A 2... 3... .045”... 6... 1.05”... 1.15”... 1050... 130... STE125
Y10103A 1... 3... .055”... 6... 1.23”... 1.33”... 1283... 150... STE125
Y11/003A 1/0... 3... .055”... 6... 1.33”... 1.43”... 1553... 170... STE125
Y12/003A 2/0... 3... .055”... 6... 1.43”... 1.53”... 1859... 195... STE150
Y13/003A 3/0... 3... .055”... 4... 1.55”... 1.67”... 2314... 225... STE150
Y14/003A 4/0... 3... .055”... 4... 1.67”... 1.79”... 2781... 260... STE150
Y125003A 250... 3... .065”... 4... 1.81”... 1.93”... 3356... 290... STE200
Y135003A 350... 3... .065”... 3... 2.05”... 2.17”... 4485... 350... STE200
Y150003A 500... 3... .065”... 2... 2.33”... 2.48”... 6204... 430... STE250
Y160003A 600... 3... .080”... 2... 2.57”... 2.72”... 7321... 475... STE300
Y175003A 750... 3... .080”... 1... 2.85”... 3.00”... 9062... 535... STE300
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances.
*Ampacity per NEC Table 310-16
Color Code Chart 107 (Y11203A & Y11003A):
Cond. Num. Color Cond. Num. Color
1 Black 2 Red
3 Blue 4 Orange
5 Yellow 6 Brown
7 Red w/ Black Stripe 8 Blue w/ Black Stripe
9 Orange w/ Black Stripe 10 Yellow w/ Black Stripe
11 Brown w/ Black Stripe 12 Black w/ Red Stripe
Color Code Chart 108 (All Others):
Cond. Num. Cond. Marking Cond. Num. Cond. Marking
1 "1" One 2 "2" Two
3 "3" Three 4 "4" Four
July 29, 2011 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste050 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste050 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste050 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste075 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste100 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste125 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste125 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste125 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste150 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste150 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste150 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste200 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste200 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste250 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste300 http://www-public.tnb.com/ps/fulltilt/index.cgi?lang=en&co=US�=ste300
CHRIS
Rectangle
File details come from the government source that posted it. Updated .