This document is a detailed design and site map for a Transformer Upgrade project at Joint Base Lewis-McChord, dated Friday, May 24, 2024, Revision A. The primary electrical and civil work includes installing new electrical infrastructure: (1) a new 2-cell fiberglass conduit riser with 100A cutout switches, (2) a 5'x4' pullbox vault, and (3) a 1,500kVA, 30-pad mount transformer on a 6"x6"x6" concrete pad with ground rod terminations. The project involves pulling 600 CLF (1,800 SCLF) of 2 AWG CU tape shield conductor and approximately 1,500 SCLF of 2 AWG CU tape shield conductor for transformer installation.
The map shows the detailed site layout at Joint Base Lewis-McChord, with design layers including power lines, underground duct banks, overhead switches, pad services, transformers, handholes, and conduits. The document is marked as Proprietary & Confidential For Official Use Only (FOUO) and Controlled Unclassified Information (CUI) in the Critical Energy Infrastructure Information (CEII) category. The point of contact is Ryan Atchison from City Light & Power (CLP) Engineering, with the contact email rna@clpinc.com.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
This map is for reference only. Although every effort has been made to ensure the accuracy of information, errors and conditions originating from physical sources used to develop the database may be reflected on this map. GIS Office shall not be liable for any errors, omissions, or damages that result from inappropriate use of this document.
Joint Base Lewis-McChord J00567 Transformer Upgrade
Friday, May 24, 2024
Rev A
Power Lines- All
UG - Duct Bank
Design Layers OH Switches
Pad Service Transformers
Handholes
Conduit
Demolition Hatch Area
Existing Layers
OH Service Transformers
OH Switches
Light Fixtures
Poles
Pad Service Transformers
OH Bare
UG Duct Bank
UG Conduit
Conduit
Buildings
Reference Layers
Wastewater Utility Lines
Thermal Utility Lines
J00566
J00572
J00564
J00565
J00567
T567-225-3
T566-300-3
T565-225-3
14P86
14P88
14P89
14P90
14P9114P9214P93
14P100
14P87
14P99
14-SL-TAW3
14-SL-TAE3
14-SL-TAW4
14-SL-TAW2
14-SL-TAW1
14-SL-TAE1
14-SL-TAE2
0 80 16040 US Feet 1 inch equals 56 feet Proprietary & Confidential For Official Use Only (FOUO)
CUI
CUI
Controlled by: City Light & Power Controlled by: CLP Engineering
CUI Category - CEII Limited Dissemination Control: N/A
POC – Ryan Atchison rna@clpinc.com rna Text Box Primary Civil Work:
Note #1: All open trench construction duct banks for primary electric shall be installed 36" below grade and 3000-psi controlled density filled. See provided CLP Construction Standards.
1-2) Directional bore 85 LF of 2x4" HDPE. Core bore into new vault.
2-3) Trench and install 402 LF of 2x4" PVC 40 concrete encased duct bank, Core bore into new vault.
rna Text Box Primary Electric and Civil Location Scope:
1) Reframe pole 14P90 with a 2x4"PVC 40 conduit riser. Install (1) new cutout 10' fiberglass crossarm and (3) 100A cutout switches. Terminate with (3) 1-phase 100A disconnect switches with skirted terminations.
2) Install (1) 5'x5'x4' (504LA) pullbox vault.
3) Install (1) 500kVA, 3Ø, pad mount 13.8KVd-208Y/120V transformer on a 6' x 6' x 6" precast transformer pad with a ground ring.
Terminate with (3) 200A LB elbows and (3) 15KV 12.7 MCOV elbow arrestors rna Text Box Primary Wire Pulls:
1-3) Pull 600 CLF (1800 SCLF) of #2 AWG CU tape shield conductor and 600 SCLF of #6 THHN CU str conductor.
rna Text Box Demo:
Note #1: Preserve existing pole 14P90.
(1) 225kVA, 3Ø, pad mount 13.8KVd-208Y/120V transformer (T567-225-3) Approx. 1500 SCLF of #2 AWG CU Tape shield conductor
(3) 100A Cutout Switches rna Text Box Definitions:
LF: Linear Feet CLF: Circuit linear feet SCLF: Single conductor linear feet
File details come from the government source that posted it. Updated .