This is an Interface Control Document (ICD) for the NBOC MLV (Mobile Launch Vehicle) Power and Control system, defining electrical interfaces between major subsystems including the Power Panel (PP1), Control Panel (CP1), Hydraulic Power Unit (HPU), generator set, and remote control systems.
The document specifies a 30kW, 120-240VAC, 60Hz onboard generator supplying power through a NEMA 4X 90A distribution panel. PP1 is a 200A, 120-240VAC three-phase panel with bonded neutral and surge suppression, providing power to the HPU (20HP motor, 33GPM pump, 1000psi MAWP), Launch Deck Lift (1HP motor), area lighting (3500W LED circuits), and three GFCI-equipped auxiliary receptacle circuits rated for 120VAC service. CP1 receives 120VAC power and connects a RC27-18/40 BODAS controller managing system operations through multiple sensor inputs including boom elevation/extension encoders, lockout pin limit switches, hydraulic pressure and temperature transducers, and hydraulic oil level switches. The control system interfaces with a Hetronic RC Belly Pack remote control unit via CAN bus communications and includes three emergency stop buttons located on the RC unit, CP1, and HPU starter. The system employs 24VDC control power distributed through terminal blocks, proportional solenoid outputs for hydraulic actuation, and discrete inputs for operational status monitoring. Reference schematics (08-20018-SCH-01 and 08-20018-SCH-02) provide detailed wiring diagrams and cabling specifications for all power distribution and control signal routing throughout the vehicle.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CUI (Controlled Unclassified Information) DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 1 OF 28
DOCUMENT NUMBER 08-20018-DOC-01 EFFECTIVE DATE:
3/31/2025
1 of 28 10015-15-01 Rev
Revision: B Effective Date: 3/31/2025 Supersedes: A
Reviewed by: Released by:
X Electrical Engineer
Approved by:
X Configuration Management
Approved by:
X GNC/EE Engineering Manager Signed by: Scott Sterling
X Safety and QA Manager Signed by: Dean, Christopher L
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 2 OF 28
DOCUMENT NUMBER 08-20018-DOC-01 EFFECTIVE DATE:
3/31/2025
2 of 28 10015-15-01 Rev C
Table of Contents
1 Purpose & Scope
2 Description
3 Genset Interfaces
3.1 Power Panel (PP1)
3.2 Control Panel (CP1)
4 Power Panel (PP1) Interfaces
4.1 Control Panel (CP1)
4.2 Hydraulic Power Unit (HPU)
4.3 Launch Deck Lift (LDL)
4.4 MLV Auxiliary Receptacles
5 Control Panel (CP1) Interfaces
5.1 MLV Sensors
5.2 HPU
5.3 Genset
5.4 MLV Lighting
6 Controls
6.1 BODAS Controller
6.2 Software
6.3 RC Unit
6.4 Emergency Stop Control
6.5 Pilot Devices
A1 Appendix A - Change Log
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 3 OF 28
DOCUMENT NUMBER 08-20018-DOC-01 EFFECTIVE DATE:
3 of 28 10015-15-01 Rev C
Table of Figures
Figure 1: MLV Top Level Block Diagram Figure 2: MLV PP1 Schedule Diagram Figure 3: MLV Auxiliary Receptacle Placement Figure 4: MLV Lighting Placement Figure 5: Remote Box Control Block Diagram Figure 6: MLV Auxiliary Block Diagram Figure 7: RF Unit Components Figure 8: ESTOP Chain
List of Tables
Table 1: MLV Electrical Interfaces Table 2: J1/P1 Interface Table 3: MLV Power Cable and Conduits Table 4: System Power Requirements *Total allowable for all circuits Table 5: MLV and HPU Sensor List Table 6:MLV Control Cables and Conduit Table 7: Sensor Interface (Part 1) Table 8: Sensor Interface (Part 2) Table 9: Hydraulic Control Interface Table 10: Genset Interface Table 11: BODAS Controller (RC27-18/40) K Interface Table 12: BODAS Controller (RC27-18/40) A Interface Table 13: Hetronic Transceiver (RX ES-CAN-HL) Table 14: MLV Emergency Stop Devices Table 15: MLV Pilot Devices
Reference Schematics
08-20018-SCH-01
08-20018-SCH-02
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 4 OF 28
4 of 28 10015-15-01 Rev C
Abbreviations and Acronyms
MLV Mobile Launch Vehicle RF Radio Frequency OCP Over-Current Protection Device LOTO Lockout Tag-out LDL Launch Deck Lift RC Remote Control CP Control Panel PP Power Panel ICD Interface Control Document GSE Ground Support Equipment GUI Graphical User Interface UMBI Umbilical ESTOP Emergency Stop EX Extension EL Elevation ENC Encoder C/D Control/Data LIM Limit LSW Limit Switch SW Switch DN Down HPU Hydraulic Power Unit REC Receptacle LHT Light MCC Motor Control Circuit Comms Communication FLA Full Load Amperes MAWP Maximum Allowable Working
Pressure GPM Gallons Per Minute HP Horsepower psi Pounds Per Square Inch in Inches 3ph Three Phase 1ph Single Phase
AWG American Wire Gauge VAC Alternating Current Voltage VDC Direct Current Voltage TX Transmit RX Receive C Conductors A Amperes W Watts DI Discrete Input AI Analog Input DO Discrete Output AO Analog Output AOV Analog Output (Setpoint mV) MULTI Multi-Conductor AIV Analog Input Voltage AID Analog Input (Discrete) AIC Analog Input Current RI Resistance Input FI Frequency Input SENT SAE J2716 Input PO Proportional Output POD Proportional Output (Digital) POC Prop. Out (Current Controlled) XMTR Transmitter/Transceiver SOL Solenoid CMD Command N/O Normally Open N/C Normally Closed COM Common NC Not Connected
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 5 OF 28
5 of 28 10015-15-01 Rev C
1 Purpose & Scope The purpose of this Interface Control Document (ICD) is to define the electrical interfaces between the MLV Power and Control system.
2 Description The MLV Power and Control system is primarily comprised of a Power Panel (PP1), Control Panel
(CP1), an RF connection to a Remote Control (RC1), and the hydraulic system. For the purposes of this document the mechanical structure/chassis along with will be referred to as the “MLV” and the drives and instrumentation will be referred to as being part of the hydraulic system. The interface connections between all these systems are illustrated in the top-level block diagram below in Figure 1 and further enumerated in Table 1.
Figure 1: MLV Top Level Block Diagram
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 6 OF 28
6 of 28 10015-15-01 Rev C
Table 1: MLV Electrical Interfaces
Connection Type
Genset PP1 Power CP1 Control/Data
PP1
CP1 Power HPU Power LDL Power
MLV Auxiliary Receptacles Power
CP1
MLV Sensors Control/Data HPU Control/Data
Genset Control/Data MLV Lighting Power
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 7 OF 28
7 of 28 10015-15-01 Rev C
3 Genset Interfaces The electrical power to the MLV is supplied by an onboard 30kW, 120-240VAC, 60Hz generator located at the on the removable power plant section of the chassis.
3.1 Power Panel (PP1)
MLV auxiliary power from the genset is distributed through a NEMA 4X 90A, 120-240VAC, four-wire, 60Hz power distribution panel. This panel contains the OCPs for the various 240V and 120V circuits and is the main point for LOTO. PP1 is also connectorized using five (5) contact twist lock sleeve connectors so that the genset can be removed for maintenance independently of the rest of the electrical system (see Table 2). A basic panel schedule for the MLV is illustrated in Figure 2 with the cable and conduit requirements defined in Table 3.
Table 2: J1/P1 Interface
Pin Allocation
1 240VAC, 3ɸ, Phase A 2 240VAC, 3ɸ, Phase B 3 240VAC, 3ɸ, Phase C 4 Neutral 5 Ground
3.2 Control Panel (CP1)
The Genset provides statuses and receives commands from the control panel via CAN Bus communication. The CAN Bus communication from the genset provides oil pressure and temperature
Figure 2: MLV PP1 Schedule Diagram
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 8 OF 28
8 of 28 10015-15-01 Rev C information to the Control Panel which relays the genset data to Remote Control (RC1) over Zigbee radio. These connections are illustrated in Figure 3 and further defined in Table 3.
4 Power Panel (PP1) Interfaces The MLV’s electrical power for the hydraulic and control system is distributed through PP1. This is a 200A 120-240VAC, three phase, panel with a bonded 100% rated neutral and installed surge suppression. PP1 provides power to the hydraulic power unit (HPU), control panel, area lighting, and auxiliary receptacles for tooling. It is capable of providing 240VAC 3ph, 120VAC 1ph, and 208VAC 1ph power. See Figure 2, Table 2 and Table 4 for further electrical details.
Table 3: MLV Power Cable and Conduits
Cable To From Signal Type Min.
Conduit
PP1 PP1 Genset 240VAC, 3ɸ, 60HZ 5C, 3/0
AWG 1”
HPU1 PP1 P2 240VAC, 3ɸ, 60HZ 5C, 3AWG 1”
HPU2 J2 Starter 240VAC, 3ɸ, 60HZ 5C, 3AWG 1”
HPU3 Starter Hyd. Power Unit 240VAC, 3ɸ, 60HZ 5C, 4AWG 1”
LDL1 LDL PP1 240VAC, 3ɸ, 60HZ 5C, 12AWG 1”
REC1 Receptacle Circuit #1 PP1 120VAC, 1ɸ, 60Hz 3C, 12AWG 1”
REC2 Receptacle Circuit #2 PP1 120VAC, 1ɸ, 60Hz 3C, 12AWG 1”
REC3 Receptacle Circuit #3 PP1 120VAC, 1ɸ, 60Hz 3C, 12AWG 1”
LHT1 Lighting Circuit #1 CP1 24VDC 2C, 16AWG ½”
LHT2 Lighting Circuit #2 CP1 24VDC 2C, 16AWG ½”
CP1 CP1 PP1 120VAC, 1ɸ, 60Hz 3C, 12AWG 1”
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 9 OF 28
9 of 28 10015-15-01 Rev C
System Name Voltage Freq. Phase Connection Load
Power Panel 1 240VAC 60Hz 3ɸ 4 Wire N/A Control Panel 1 120VAC 60Hz 1 ɸ 3 Wire 5FLA
Hydraulic Power Unit 240VAC 60Hz 3ɸ 3 Wire 48FLA Launch Deck Lift 240VAC 60Hz 3ɸ 3 Wire 4FLA
Receptacles* 120VAC 60Hz 1 ɸ 3 Wire 20A Lighting* 24VDC N/A DC 2 Wire 10A
Jump Seat 120VAC 60Hz 1 ɸ 3 Wire 3A Table 4: System Power Requirements
*Total allowable for all circuits
4.1 Control Panel (CP1)
PP1 provides 120VAC to CP1. CP1 has a separate 15A circuit for isolating the panel during installation and maintenance.
4.2 Hydraulic Power Unit (HPU)
The HPU is the primary mover for the MLV and is responsible for boom movement, operating the outriggers, and actuating the various lockout pins; this includes the Deadman (EL) lockout pins. It consists of a Hydraulic Pump, Electric Motor and an MCC. The hydraulic system is primed and pressurized using a pump with a 33GPM, 1000psi MAWP and an 20HP electric motor.
4.3 Launch Deck Lift (LDL)
This section of the MLV consists of a self-contained hydraulic scissor lift platform that is used by the Launch Team to interface with the payload while it is hoisted by the boom. The lift has a 1HP motor that requires 240VAC, 3ph power and is controlled by an onboard control pendant.
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 10 OF 28
10 of 28 10015-15-01 Rev C
4.4 MLV Auxiliary Receptacles
PP1 feeds three GFCI equipped convenience receptacle circuits with in-use rated covers for all-weather use by the Launch Team for additional powered tooling. There is one set of single gang duplexes outlets along with a double gang set on the chassis deck. There is one final double gang outlet on the very front of the chassis. The single gang sets are placed on the forward and aft sections of the chassis: one set near the LDL and the other place aft by the boom pedestals. The chassis deck circuits are on a single 15A breaker with an expected load of 5A each. The double gangs are on separate 15A breakers with a load not to exceed 12A each, for higher load equipment.
Figure 3: MLV Auxiliary Receptacle Placement
Single Gang
Double Gang
CP1
PP1
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 11 OF 28
11 of 28 10015-15-01 Rev C
5 Control Panel (CP1) Interfaces CP1 is the base station for the remote control (RC) system that operates the MLV hydraulics. Sensors on the genset, MLV chassis, and the HPU provide data to the controller for processing.
5.1 MLV Sensors
The MLV has limit switches for the lockout pins as well as two analog position sensors for boom travel.
The lockout pin switches provide a set/reset status to the controller to prevent the boom from moving in a direction where the pins are set. The two position sensors provide angle and linear measurement the controller so height of the launch head above grade can be determined. See Table 5 for sensor details and Table 6 for cabling.
Sensor Description Type Signal Location Ref.
Des.
EL PIN 1 SW Boom EL Lockout Pin 1 Switch DI 24VDC Boom P106 EL PIN 2 SW Boom EL Lockout Pin 2 Switch DI 24VDC Boom P107 EX PIN 1 SW Boom EXT Lockout Pin 1 Switch DI 24VDC Boom P108 EX PIN 2 SW Boom EXT Lockout Pin 2 Switch DI 24VDC Boom P109
EL ENC Boom EL Analog Angle Encoder DI 4-20mA Boom P104
EX ENC Boom EXT Analog Linear Position Encoder DI 4-20mA Boom P101
HPU PT Hydraulic System Pressure Transducer AI 4-20mA HPU P102
HPU TEMP Hydraulic System Temperature Transducer AI 4-20mA HPU P103
HPU LLSW Hydraulic Oil Low-Level Switch DI 24VDC HPU P105
Table 5: MLV and HPU Sensor List
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 12 OF 28
12 of 28 10015-15-01 Rev C
5.2 HPU
The HPU has three sensors for providing a general status of the hydraulics to the controller. There is a hydraulic pressure sensor on the outlet of the HPU, a temperature sensor and low-level switch sensor for the hydraulic oil reservoir. See Table 7/8 for sensor details and Table 6 for cabling. CP1 actuates the hydraulics in the HPU via electrical connections on the Control Block. The Control Block is a set of electrohydraulic valves that actuate the cylinders for the various components of the hydraulic system.
See Table 9 for details and Table 6 cabling.
Cable To From Signal Type Min.
Cond uit
ELENC EL Encoder CP1 4-20mA 6C, 20AWG, TW, SH ¾” EXENC EX Encoder CP1 4-20mA 6C, 20AWG, TW, SH ¾” EXPIN1 Boom EX Lockout Pin SW 1 CP1 24VDC 4C, 20AWG, TW, SH ¾” EXPIN2 Boom EX Lockout Pin SW 1 CP1 24VDC 4C, 20AWG, TW, SH ¾” ELPIN1 Boom EL Lockout Pin SW 1 CP1 24VDC 4C, 20AWG, TW, SH ¾” ELPIN2 Boom EL Lockout Pin SW 2 CP1 24VDC 4C, 20AWG, TW, SH ¾”
GENC CP1 GENSET CAN 4C, 20AWG, TW, SH ¾”
HPUMTR Hyd. Motor & Starter Hyd.
Motor 24VDC 8C, 20AWG, TW, SH ¾”
HPULLSW Hyd. Level Transmitter CP1 4-20mA 6C, 20AWG, TW, SH ¾” HPUPT Hyd. Pres. Transducer CP1 4-20mA 2C, 20AWG, TW, SH ¾”
HPUTMP Hyd. Temp. Sensor CP1 4-20mA 2C, 20AWG, TW, SH ¾” HPUCTRL Hyd. Control Block CP1 24VDC 16C, 20AWG, TW, SH 1”
Table 6:MLV Control Cables and Conduit
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 13 OF 28
13 of 28 10015-15-01 Rev C
Device Pin Description Ref.
Des.
Mating Connector Wire Type Cable Signal
EL
P
IN
S W
1 PIN SET (N/C)
J106 DT06-4S 20 SH, MULTI ELPIN1 24 VDC
2 COMMON (+24VDC)
3 PIN RESET (N/O)
4 COMMON (NC) (+24VDC)
EL
P
IN
S W
1 PIN SET (N/C)
J107 DT06-4S 20 SH, MULTI ELPIN2 24 VDC
2 COMMON (+24VDC)
3 PIN RESET (N/O)
4 COMMON (NC) (+24VDC)
EX
P
IN
S W
1 PIN SET (N/C)
J108 DT06-4S 20 SH, MULTI EXPIN1 24 VDC
2 COMMON (+24VDC)
3 PIN RESET (N/O)
4 COMMON (NC) (+24VDC)
EX
P
IN
S W
1 PIN SET (N/C)
J109 DT06-4S 20 SH, MULTI EXPIN2 24 VDC
2 COMMON (+24VDC)
3 PIN RESET (N/O)
4 COMMON (NC) (+24VDC)
2 COMMON (+24VDC)
3 PIN RESET (N/O)
4 COMMON (NC) (+24VDC)
Table 7: Sensor Interface (Part 1)
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 14 OF 28
14 of 28 10015-15-01 Rev C
Device Pin Description Ref.
Des. Connector Wire Type Cable Signal
EL
E
NC
1 +UB
M12, 4P Male 22 SH, MULTI ELENC 4-20mA
2 NOT CONNECTED
3 0V J104
4 SIGNAL
5 NOT CONNECTED
EX
1 +V
RK 4.4T-2 22 SH, MULTI EXENC 4-20mA
2 NOT CONNECTED
3 SIGNAL J101
4 NOT CONNECTED
HP
U
PT
1 SIGNAL +
J102 M12, 5P Male 22 SH, MULTI HPUPT 4-20mA
2 NOT CONNECTED
3 SIGNAL -
4 NOT CONNECTED
HP
U
LL
SW
1 +24VDC
M12, 5P Male 22 SH, MULTI HPULLSW 4-20mA
2 SIGNAL 1
3 GND (0V) J105
4 SIGNAL 2
5 GND
HP
U
TE
M
P 1 SIGNAL +
DT06-3S 20 SH, MULTI HPUTMP 4-20mA2 SIGNAL - J103
3 NOT CONNECTED
Table 8: Sensor Interface (Part 2)
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 15 OF 28
15 of 28 10015-15-01 Rev C
5.3 Genset
Status information from the Genset is passed to CP1 through an interface module which can provide remote operation and monitoring. The Genset can be interfaced with using common J1939 CAN Bus protocol through the MFG provided interface connector (mating connector HDP26-24-31PT). The only connections that will be used from this interface are the CAN Bus connections. See Table 10 below for details.
Pin Description Ref.
Des. Wire Type Cable Signal
6 +5VDC J301 16 MULTI GENSET SENSOR SUPPLY
1 +BATT VOLTS J301 16 MULTI GENSET +BATT VOLTS (5A)
Device Pin Description Ref.
Des.
Mating Connector Wire Type Cable Signal
BM
R
ET
SO
L 1 +24VDC
J114 DT06-2S 20 SH, MULTI HPUCTRL 24 VDC
2 RETURN
BM
XT
SO
L 1 +24VDC
J115 DT06-2S 20 SH, MULTI HPUCTRL 24 VDC
2 RETURN
BM
E
L
DN
S O
L 1 +24VDC
J116 DT06-2S 20 SH, MULTI HPUCTRL 24 VDC
2 RETURN
BM
E
L
UP
S O
L 1 +24VDC
J117 DT06-2S 20 SH, MULTI HPUCTRL 24 VDC
2 RETURN
HP
U
W
AR
M
UP
1 +24VDC
J118 DT06-2S 20 SH, MULTI HPUCTRL 24 VDC
2 RETURN
BM
E
X
PI
N
SO
L 1 +24VDC
J119 DT06-2S 20 SH, MULTI HPUCTRL 24 VDC
2 RETURN
BM
E
L
PI
N
SO
L 1 +24VDC
J120 DT06-2S 20 SH, MULTI HPUCTRL 24 VDC
2 RETURN
Table 9: Hydraulic Control Interface
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 16 OF 28
16 of 28 10015-15-01 Rev C
Pin Description Ref.
Des. Wire Type Cable Signal
10 GROUND J301 16 SH, MULTI GENSET GROUND
24 +CAN J301 16 SH, MULTI GENSET CAN BUS
29 -CAN J301 16 SH, MULTI GENSET CAN BUS
25 +RS485 (B) J301 16 MULTI GENSET MODBUS
23 -RS485 (A) J301 16 MULTI GENSET MODBUS
22 RS485 COMMON J301 16 MULTI GENSET MODBUS
27 SENSOR INPUT 10 J301 16 MULTI GENSET 4-20mA, 0-5V DC, 0-750Ω 11 SENSOR INPUT 1 J301 16 MULTI GENSET 4-20mA, 0-5V DC, 0-7500Ω 30 SENSOR INPUT 2 J301 16 MULTI GENSET 4-20mA, 0-5V DC, 0-7500Ω 5 SENSOR INPUT 3 J301 16 MULTI GENSET 4-20mA, 0-5V DC, 0-750Ω
13 SENSOR INPUT 4 J301 16 MULTI GENSET 4-20mA, 0-5V DC, 0-750Ω 26 SENSOR INPUT 5 J301 16 MULTI GENSET 4-20mA, 0-5V DC, 0-7500Ω 18 SENSOR INPUT 9 J301 16 MULTI GENSET 4-20mA, 0-5V DC, 0-750Ω
2 SWITCH OUTPUT 6 J301 16 MULTI GENSET +BATT VOLTS (1A)
28 SWITCHED INPUT 1 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
16 SWITCHED INPUT 10 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
17 SWITCHED INPUT 11 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
20 SWITCHED INPUT 12 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
31 SWITCHED INPUT 3 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
3 SWITCHED INPUT 4 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
21 SWITCHED INPUT 5 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
14 SWITCHED INPUT 7 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
15 SWITCHED INPUT 9 J301 16 MULTI GENSET +BATT VOLTS, GROUND, OPEN
12 SWITCHED OUTPUT 10 J301 16 MULTI GENSET +BATT VOLTS (500mA)
7 SWITCHED OUTPUT 4 J301 16 MULTI GENSET +BATT VOLTS (1A)
19 SWITCHED OUTPUT 5 J301 16 MULTI GENSET +BATT VOLTS (1A)
4 SWITCHED OUTPUT 7 J301 16 MULTI GENSET +BATT VOLTS (1A)
8 SWITCHED OUTPUT 8 J301 16 MULTI GENSET +BATT VOLTS (1A)
9 SWITCHED OUTPUT 9 J301 16 MULTI GENSET +BATT VOLTS (500mA)
Table 10: Genset Interface
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 17 OF 28
17 of 28 10015-15-01 Rev C
5.4 MLV Lighting
PP1 feeds several convenience receptacle circuits for launch operations and two (2) 24VDC LED lighting circuits via CP1. Both of the two switch-controlled LED lighting circuits are located on the boom. The first, is a circuit of eight (8) lights along the boom’s underside to illuminate the chassis walkways and work areas. Then the second, is a circuit of two (2) lights facing down and aft to illuminate where the MLV mates with the CAT966M loader. These lighting circuits contain 3500W all-weather LEDs that are rated for adverse outdoor environments. MLV Lighting Placement
6 Controls The MLV is with the RC Unit allows for wireless remote control of the boom travel and the boom extension and Deadman lockout pins. The controller is comprised of a BODAS controller, Hetronic transceiver, and a Hetronic RC Belly Pack. The system works with the onboard sensors and has various ESTOP devices and pilot controls for operating the hydraulic system of the MLV.
6.1 BODAS Controller
The MLV sensors, HPU and Pilot Devices will interface with a RC27-18/40 BODAS controller through two
(2) mating connectors wired to terminal blocks located in CP1. The interface on the BODAS controller is a 154-way (154P-V EMS) connector that is separated into two sections: A (60-way) and K (94-way). See Tables 11 and Table 12 for details.
Area Lighting
Figure 4: MLV Lighting Placement
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 18 OF 28
18 of 28 10015-15-01 Rev C
Table 11: BODAS Controller (RC27-18/40) K Interface
Pin Description Ref.
Des. Wire Type Assignment Signal
K01 +24VDC PLC-K 20 MULTI POWER SUPPLY 24VDC
K03 +24VDC PLC-K 20 MULTI POWER SUPPLY 24VDC
K05 +24VDC PLC-K 20 MULTI POWER SUPPLY 24VDC
K24 RESET/ON PLC-K 20 MULTI RESET/ON
SWITCH 24VDC
K02 -24VDC PLC-K 20 MULTI POWER SUPPLY 24VDC
K04 -24VDC PLC-K 20 MULTI POWER SUPPLY 24VDC
K06 -24VDC PLC-K 20 MULTI POWER SUPPLY 24VDC
K22 INHIBIT INPUT 1 PLC-K 20 MULTI ESTOP CHAIN 24VDC
K21 INHIBIT INPUT 2 PLC-K 20 MULTI ESTOP CHAIN 24VDC
K71 VSS1 150mA @ 5V PLC-K 20 MULTI K72 VSS1 150mA @ 5V PLC-K 20 MULTI K93 VSS2 150mA @ 5V PLC-K 20 MULTI
K94 VSS2 150mA @ 5V PLC-K 20 MULTI
K70 VSS3 300mA @ 5V PLC-K 20 MULTI SENSOR POWER 24VDC
K20 VSS4 500mA @ 10V PLC-K 20 MULTI SENSOR POWER 24VDC
K43 INPUT DEVICE 1: DI, AIV, RI PLC-K 20 MULTI
K38 INPUT DEVICE 1: DI, AIV, AIC, RI PLC-K 20 MULTI
K39 INPUT DEVICE 1: DI, AIV, AIC, RI PLC-K 20 MULTI
K40 INPUT DEVICE 1: DI, AIV, AIC, RI PLC-K 20 MULTI
K41 INPUT DEVICE 1: DI, AIV, AIC, RI PLC-K 20 MULTI
K42 INPUT DEVICE 1: DI, AIV, AIC, RI PLC-K 20 MULTI
K52 INPUT DEVICE 1: DI, AIV, AIC, SENT, FI, RI PLC-K 20 MULTI
K53 INPUT DEVICE 1: DI, AIV, AIC, SENT, FI, RI PLC-K 20 MULTI
K59 INPUT DEVICE 1: DI, AIV, AIC, SENT, FI, RI PLC-K 20 MULTI
K60 INPUT DEVICE 1: DI, AIV, AIC, SENT, FI, RI PLC-K 20 MULTI
K54 INPUT DEVICE 1: DI, AIV, AIC, FI, DSM1/DST1 PLC-K 20 MULTI
K55 INPUT DEVICE 1: DI, AIV, AIC, FI, DSM1/DST1 PLC-K 20 MULTI
K62 INPUT DEVICE 2: DI, AIV, AOV PLC-K 20 MULTI
K44 INPUT DEVICE 2: DI, AIV, AIC, RI PLC-K 20 MULTI EL ENC 4-
20mA
K45 INPUT DEVICE 2: DI, AIV, AIC, RI PLC-K 20 MULTI EX ENC 4-
20mA
K63 INPUT DEVICE 2: DI, AIV, AIC, RI PLC-K 20 MULTI HPU PT 4-
20mA
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 19 OF 28
19 of 28 10015-15-01 Rev C
Des. Wire Type Assignment Signal
K64 INPUT DEVICE 2: DI, AIV, AIC, RI PLC-K 20 MULTI HPU TEMP 4-
20mA
K65 INPUT DEVICE 2: DI, AIV, AIC, RI PLC-K 20 MULTI
K36 INPUT DEVICE 2: DI, AIV, AIC, SENT, FI, RI PLC-K 20 MULTI
K56 INPUT DEVICE 2: DI, AIV, AIC, SENT, FI, RI PLC-K 20 MULTI
K57 INPUT DEVICE 2: DI, AIV, AIC, SENT, FI, RI PLC-K 20 MULTI
K58 INPUT DEVICE 2: DI, AIV, AIC, SENT, FI, RI PLC-K 20 MULTI
K37 INPUT DEVICE 2: DI, AIV, AIC, FI, DSM1/DST1 PLC-K 20 MULTI
K61 INPUT DEVICE 2: DI, AIV, AIC, FI, DSM1/DST1 PLC-K 20 MULTI
K32 INPUT DEVICE 3: DI, AIV, RI PLC-K 20 MULTI
K33 INPUT DEVICE 3: DI, AIV, RI PLC-K 20 MULTI
K30 INPUT DEVICE 3: DI, AIV, AIC, FI, DSM1/DST1 PLC-K 20 MULTI
K10 IO GROUP 4: AI, AID, AIV PLC-K 20 MULTI EL PIN 1 SW SET 24VDC
K31 IO GROUP 4: AI, AID, AIV PLC-K 20 MULTI EL PIN 1 SW RET 24VDC
K34 IO GROUP 4: AI, AID, AIV PLC-K 20 MULTI EL PIN 2 SW SET 24VDC
K74 IO GROUP 4: AI, AID, AIV PLC-K 20 MULTI EL PIN 2 SW RET 24VDC
K75 IO GROUP 4: AI, AID, AIV PLC-K 20 MULTI EX PIN 1 SW SET 24VDC
K76 IO GROUP 4: AI, AID, AIV PLC-K 20 MULTI EX PIN 1 SW RET 24VDC
K77 IO GROUP 4: AI, AID, AIV PLC-K 20 MULTI EX PIN 2 SW SET 24VDC
K78 IO GROUP 4: AI, AID, AIV PLC-K 20 MULTI EX PIN 2 SW RET 24VDC
K11 IO GROUP 6: AI, AID, AIV PLC-K 20 MULTI
K35 IO GROUP 6: AI, AID, AIV PLC-K 20 MULTI
K18 SIGNAL GROUND PLC-K 20 MULTI
K19 SIGNAL GROUND PLC-K 20 MULTI
K23 SIGNAL GROUND PLC-K 20 MULTI
K46 SIGNAL GROUND PLC-K 20 MULTI
K47 SIGNAL GROUND PLC-K 20 MULTI
K79 SIGNAL GROUND PLC-K 20 MULTI
K07 OUTPUT CLUSTER 1: Hi-SIDE 4A PO, POC, POD PLC-K 20 MULTI BM EXT SOL PWM K08 OUTPUT CLUSTER 1: Hi-SIDE 4A PO, POC, POD PLC-K 20 MULTI BM RET SOL PWM K09 OUTPUT CLUSTER 1: Hi-SIDE 4A PO, POC, POD PLC-K 20 MULTI K29 OUTPUT CLUSTER 1: Hi-SIDE 4A PO, POC, POD PLC-K 20 MULTI K73 OUTPUT CLUSTER 1: Hi-SIDE 4A PO, POC, POD PLC-K 20 MULTI K17 OUTPUT CLUSTER 1: Hi-SIDE 3A PO, POC, POD PLC-K 20 MULTI K14 OUTPUT CLUSTER 1: Lo-SIDE 4A PO, POC, POD PLC-K 20 MULTI K15 OUTPUT CLUSTER 1: Lo-SIDE 4A PO, POC, POD PLC-K 20 MULTI
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 20 OF 28
20 of 28 10015-15-01 Rev C
Des. Wire Type Assignment Signal
K16 OUTPUT CLUSTER 1: Lo-SIDE 4A PO, POC, POD PLC-K 20 MULTI
K12 OUTPUT CLUSTER 1: PWM, PO, POD PLC-K 20 MULTI BM EXT SOL RTN PWM
K51 OUTPUT CLUSTER 1: PWM, PO, POD PLC-K 20 MULTI BM RET SOL RTN PWM
K13 OUTPUT CLUSTER 1: Lo-SIDE 4A DO PLC-K 20 MULTI K80 Lo-SIDE PO, POD, PWM PLC-K 20 MULTI K81 Lo-SIDE PO, POD, PWM PLC-K 20 MULTI K82 Lo-SIDE PO, POD, PWM PLC-K 20 MULTI K83 Lo-SIDE PO, POD, PWM PLC-K 20 MULTI K84 Lo-SIDE DO PLC-K 20 MULTI K85 Lo-SIDE DO PLC-K 20 MULTI K86 Lo-SIDE DO PLC-K 20 MULTI K87 Lo-SIDE DO PLC-K 20 MULTI
K25 PWM ANALOG, AOV PLC-K 20 MULTI
K92 LIN INTERFACE PLC-K 20 MULTI
K88 CAN1 HIGH, (NON-SELECTIVE) PLC-K 20 MULTI HETRONIC XMTR CAN
K66 CAN1 LOW (NON-SELECTIVE) PLC-K 20 MULTI HETRONIC XMTR CAN
K89 CAN2 HIGH (PROGRAMMING) PLC-K 20 MULTI PROGRAMMING CAN
K67 CAN2 LOW (PROGRAMMING) PLC-K 20 MULTI PROGRAMMING CAN
K90 CAN3 HIGH (ISOBUS) PLC-K 20 MULTI
K68 CAN3 LOW (ISOBUS) PLC-K 20 MULTI
K91 CAN4 HIGH (SELECTIVE) PLC-K 20 MULTI GENSET J1939
K69 CAN4 HIGH (SELECTIVE) PLC-K 20 MULTI GENSET J1939
K27 ETHERNET+ PLC-K 20 MULTI
K28 ETHERNET- PLC-K 20 MULTI
K26 NOT CONNECTED PLC-K 20 MULTI
K48 NOT CONNECTED PLC-K 20 MULTI
K49 NOT CONNECTED PLC-K 20 MULTI
K50 NOT CONNECTED PLC-K 20 MULTI
Table 12: BODAS Controller (RC27-18/40) A Interface
Pin Description Ref.
Des. Wire Type Assignment Signal
A45 +24VDC PLC-A 20 MULTI POWER SUPPLY 24VDC
A60 +24VDC PLC-A 20 MULTI POWER SUPPLY 24VDC
A15 -24VDC PLC-A 20 MULTI POWER SUPPLY 24VDC
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 21 OF 28
21 of 28 10015-15-01 Rev C
Des. Wire Type Assignment Signal
A30 -24VDC PLC-A 20 MULTI POWER SUPPLY 24VDC
A13 IO GROUP 5: AI, AID, AIV PLC-A 20 MULTI
A25 IO GROUP 5: AI, AID, AIV PLC-A 20 MULTI
A26 IO GROUP 5: AI, AID, AIV PLC-A 20 MULTI
A27 IO GROUP 5: AI, AID, AIV PLC-A 20 MULTI
A40 IO GROUP 5: AI, AID, AIV PLC-A 20 MULTI HPU MOTOR ON 24VDC
A41 IO GROUP 5: AI, AID, AIV PLC-A 20 MULTI STARTER FAULT 24VDC
A42 IO GROUP 5: AI, AID, AIV PLC-A 20 MULTI
A14 IO GROUP 6: AI, AID, AIV PLC-A 20 MULTI ESTOP RESET 24VDC
A28 IO GROUP 6: AI, AID, AIV PLC-A 20 MULTI HPU LLSW 24VDC
A29 IO GROUP 6: AI, AID, AIV PLC-A 20 MULTI HETRONIC RELAY K3 24VDC
A57 IO GROUP 6: AI, AID, AIV PLC-A 20 MULTI HETRONIC RELAY K4 24VDC
A58 OUTPUT CLUSTER 1: Hi-SIDE 5A DO PLC-A 20 MULTI
A11 OUTPUT CLUSTER 1: Lo-SIDE 3A DO PLC-A 20 MULTI A56 OUTPUT CLUSTER 1: Lo-SIDE 3A DO PLC-A 20 MULTI A31 OUTPUT CLUSTER 2: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI HPU WARM-UP SOL 24VDC A32 OUTPUT CLUSTER 2: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI HPU RUN CMD 24VDC A33 OUTPUT CLUSTER 2: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI EX PIN SOL 24VDC A46 OUTPUT CLUSTER 2: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI EL PIN SOL 24VDC A47 OUTPUT CLUSTER 2: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI A48 OUTPUT CLUSTER 2: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI A49 OUTPUT CLUSTER 2: Hi-SIDE 5A DO PLC-A 20 MULTI A05 OUTPUT CLUSTER 2: Lo-SIDE 4A PO, POC, POD PLC-A 20 MULTI EX PIN SOL RTN 24VDC A19 OUTPUT CLUSTER 2: Lo-SIDE 4A PO, POC, POD PLC-A 20 MULTI EL PIN SOL RTN 24VDC A20 OUTPUT CLUSTER 2: Lo-SIDE 4A PO, POC, POD PLC-A 20 MULTI HPU CMD RTN 24VDC
A03 OUTPUT CLUSTER 2: PWM, PO, POD PLC-A 20 MULTI HPU WARM-UP SOL
RTN 24VDC
A18 OUTPUT CLUSTER 2: PWM, PO, POD PLC-A 20 MULTI HPU FAULT RESET 24VDC
A04 OUTPUT CLUSTER 2: Lo-SIDE 3A DO PLC-A 20 MULTI A01 OUTPUT CLUSTER 2: Lo-SIDE 3A DO PLC-A 20 MULTI A55 OUTPUT CLUSTER 2: Lo-SIDE 3A DO PLC-A 20 MULTI A34 OUTPUT CLUSTER 3: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI BM UP SOL PWM A35 OUTPUT CLUSTER 3: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI BM DN SOL PWM A51 OUTPUT CLUSTER 3: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI A52 OUTPUT CLUSTER 3: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI A53 OUTPUT CLUSTER 3: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 22 OF 28
22 of 28 10015-15-01 Rev C
Des. Wire Type Assignment Signal
A54 OUTPUT CLUSTER 3: Hi-SIDE 3A PO, POC, POD PLC-A 20 MULTI A50 OUTPUT CLUSTER 3: Hi-SIDE 5A DO PLC-A 20 MULTI A02 OUTPUT CLUSTER 2: Lo-SIDE 4A PO, POC, POD PLC-A 20 MULTI A09 OUTPUT CLUSTER 2: Lo-SIDE 4A PO, POC, POD PLC-A 20 MULTI A17 OUTPUT CLUSTER 2: Lo-SIDE 4A PO, POC, POD PLC-A 20 MULTI
A07 OUTPUT CLUSTER 2: PWM, PO, POD PLC-A 20 MULTI BM UP SOL RTN PWM
A08 OUTPUT CLUSTER 2: PWM, PO, POD PLC-A 20 MULTI BM DN SOL RTN PWM
A10 OUTPUT CLUSTER 2: Lo-SIDE 3A DO PLC-A 20 MULTI A06 OUTPUT CLUSTER 2: Lo-SIDE 3A DO PLC-A 20 MULTI A16 OUTPUT CLUSTER 2: Lo-SIDE 3A DO PLC-A 20 MULTI
A36 INPUT DEVICE 3: DI, AI, AID, AIV PLC-A 20 MULTI
A37 INPUT DEVICE 3: DI, AI, AID, AIV PLC-A 20 MULTI
A38 INPUT DEVICE 3: DI, AI, AID, AIV PLC-A 20 MULTI
A39 INPUT DEVICE 3: DI, AI, AID, AIV PLC-A 20 MULTI
A21 INPUT DEVICE 3: DI, AID, AIV, FI PLC-A 20 MULTI
A22 INPUT DEVICE 3: DI, AID, AIV, FI PLC-A 20 MULTI
A23 INPUT DEVICE 3: DI, AID, AIV, FI PLC-A 20 MULTI
A24 INPUT DEVICE 3: DI, AID, AIV, FI PLC-A 20 MULTI
A43 INPUT DEVICE 3: DI, AIV, AIC, FI, DSM1/DST1 PLC-A 20 MULTI
A44 INPUT DEVICE 3: FI (INDUCTIVE) PLC-A 20 MULTI
A59 INPUT DEVICE 3: FI (INDUCTIVE) PLC-A 20 MULTI
A12 PWM ANALOG, AOV PLC-A 20 MULTI
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 23 OF 28
23 of 28 10015-15-01 Rev C
6.2 Software
Protocols in the controller firmware use this data to prevent the hydraulic power unit from operating in an unsafe condition while disseminating it to the RC Unit using Hetronic transceivers for display. The user can view the status of the entire system while operating it remotely. See Figure 5 and Figure 6 for details.
Figure 5: Remote Box Control Block Diagram
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 24 OF 28
24 of 28 10015-15-01 Rev C
UP Limit Indicator
DOWN Limit Indicator
IN Limit Indicator
OUT Limit Indicator
UP Limit DN Limit IN Limit OUT Limit
Elevation Display
Extension ELength Display
STOP
Yes
Yes Yes Yes
Elevation Encoder
Extension Encoder/
Pot
ADC
REMOTE
Hydraulic Temp.
Hydraulic Pressure.
Hydraulic Temp.
Display
ADC ADC
Hydraulic Pressure Display
STOP
Temp. HI
Temp. LO
Press. HI
Press. LO
Yes
Yes
Yes
Yes
OPERATING
CONDITIONSHydraulic
Fluid Level
Level LO Yes
Boom Height Above- Grade
Trig.
Hyd.
Warm-Up
Cycle
Hyd.
Warm-Up
Cycle
Gen.
Oil Temp.
Display
Gen.
Oil Press.
Display
Gen.
Bat. Chg.
Display
Genset
REMOTE
Hydraulic Motor
Hyd. ON Switch
Boom Rotation
Pin 1
Boom Rotation
Pin 2
Boom Extension
Pin 1
Boom Extension
Pin 2
Yes
Yes Yes Yes
Boom Rot.
Pin 1
Indicator
Boom Rot.
Pin 2
Indicator
Boom Ext.
Pin 1
Indicator
Boom Ext.
Pin 2
Indicator
MLV Chassis
ALARM
WARM UP
INHIBIT
Warm Up Cycle On
Figure 6: MLV Auxiliary Block Diagram
6.3 RC Unit
The MLV controller comes with a yellow Hetronic RC Belly Pack that can control various parts of the hydraulic system remotely through an RF link to CP1’s transceiver (RX ES-CAN-HL). See Table 13 for details.
Figure 7: RF Unit Components
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 25 OF 28
25 of 28 10015-15-01 Rev C
Table 13: Hetronic Transceiver (RX ES-CAN-HL)
Pin Description Ref. Des. Wire Type Assignment Signal
1 XMTR 20 MULTI
2 XMTR 20 MULTI
3 XMTR 20 MULTI
4 XMTR 20 MULTI
5 XMTR 20 MULTI
6 XMTR 20 MULTI
7 XMTR 20 MULTI
8 XMTR 20 MULTI
9 XMTR 20 MULTI
10 XMTR 20 MULTI
11 CAN- XMTR 20 MULTI PLC COMM CAN
12 CAN GND XMTR 20 MULTI PLC COMM CAN
13 CAN+ XMTR 20 MULTI PLC COMM CAN
14 XMTR 20 MULTI
15 K3 - RELAY 1 IN XMTR 20 MULTI XMTR STATUS 24VDC
16 K4 - RELAY 2 IN XMTR 20 MULTI XMTR STATUS 24VDC
17 XMTR 20 MULTI
18 XMTR 20 MULTI
19 MC2 IN XMTR 20 MULTI XMTR FAULT 24VDC
20 MC2 OUT XMTR 20 MULTI XMTR FAULT 24VDC
21 +24VDC XMTR 20 MULTI POWER SUPPLY 24VDC
22 -24VDC XMTR 20 MULTI POWER SUPPLY 24VDC
23 XMTR 20 MULTI
24 K3 - RELAY 1 N/O XMTR 20 MULTI
25 K3 - RELAY 1 N/C XMTR 20 MULTI
26 K4 - RELAY 2 N/C XMTR 20 MULTI
27 K4 - RELAY 2 N/O XMTR 20 MULTI
28 XMTR 20 MULTI
29 MC1 IN XMTR 20 MULTI XMTR FAULT 24VDC
30 MC1 OUT XMTR 20 MULTI XMTR FAULT 24VDC
6.4 Emergency Stop Control
There are three (3) emergency stop buttons on the MLV control system. Further detail on their action and location is below in Table 14. The ESTOP chain consists of fault contacts on the transceiver, DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 26 OF 28
26 of 28 10015-15-01 Rev C programmed overtravel limits in the software and ultimately the emergency stop buttons. See Figure 8 for details.
Type Action Location
Red, Mushroom Pull-To-Reset RC Unit Red, Mushroom Twist-To-Reset CP1 Red, Mushroom Twist-To-Reset HPU Starter
K1
K2
ESTOP
ESTOP 1
HETRONIC
XMTR
FAULT
RELAYS
EMERGENC
STOP
LOCATED ON
CP1
CONTROLLER
FAULT
SOFTWARE
LIMITS
+24VDC
SOFT START
FAULT
RC1: ESTOP 3
PUSHBUTTON
ESTOP 2
EMERGENC
STOP
LOCATED ON
HPU STARTER
+24VDC
Figure 8: ESTOP Chain
6.5 Pilot Devices
There are various pilot devices that control or provide indication for certain functionalities across the control system such as ETOP, motion joysticks and device switches. See Table 15 for pilot device details.
Table 14: MLV Emergency Stop Devices
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 27 OF 28
DOCUMENT NUMBER 08-20018-DOC-01 EFFECTIVE DATE:
3/31/2025
27 of 28 10015-15-01 Rev C
Device Type Label Function Location
Red, Mushroom
Button Control ESTOP 1 Emergency Stop CP1
Black, Button Control RESET/ON Emergency Stop Reset CP1 Red, Mushroom Button
Control ESTOP 3 Remote Emergency Stop RC1
Elevation Joystick Control EL Boom Elevation Up, Down RC1
Extension Joystick Control EXT Boom Extension, In, Out RC1
Warm-Up Switch Control WARM-UP Warm-Up Circuit Start RC1
Elevation Pins Switch Control EL PINS Reset/Set Elevation Lockout Pins RC1
Extension Pins Switch Control EXT PINS Reset/Set Extension Lockout
Pins RC1
Black, Button Control RESET Soft Start Fault Reset HPU Starter Black, Selector Control HOA HPU In-Hand, Off, Auto Selector HPU Starter
Red, Mushroom
Button Control ESTOP 2 Emergency Stop HPU Starter
Rotary, Lever Power HPU ON/OFF Mechanical Disconnect Switch, Rotary, Starter HPU Starter
Table 15: MLV Pilot Devices
DOCUMENT TITLE NBOC MLV Power and Control ICD REV. B PAGE: 28 OF 28
DOCUMENT NUMBER 08-20018-DOC-01 EFFECTIVE DATE:
3/31/2025
28 of 28 10015-15-01 Rev C
A1 Appendix A - Change Log
Date Ver. Change (All changes must be made in accordance with ADM-001) By Whom 09/19/2024 - Establish Baseline AA 02/19/2025 A Per CR 2816: Updated sections 4, 5, and 6 to start with subsection 1. KWS 3/31/2025 B Updated header to show document number throughout entire document CLT
D D
C C
B B
A A
SIGNATURE PANEL
Page #Description
AUX. POWER THREELINE
20018
DWG #
RECEPTACLE CIRCUITS 3
08-20018-SCH-01
08-20018-SCH-01
THIS DRAWING IS THE PROPERTY OF THE NASA BALLOON PROGRAM AND MAY NOT BE USED, COPIED, OR DISTRIBUTED (OUTSIDE OF AUTHORIZED CONTRACTORS) FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED WITHOUT THE EXPRESS WRITTEN AUTHORITY OF THE NASA BALLON PROGRAM.
EAR ECCN: EAR99
- EXPORT ADMINISTRATION REGULATIONS (EAR) NOTICE -
THIS DOCUMENT CONTAINS INFORMATION WITHIN THE PURVIEW OF THE EXPORT ADMINISTRATION REGULATIONS (EAR), 15 CFR §73 -774, AND IS EXPORT-CONTROLLED. IT IS PROHIBITED FOR SALE, EXPORT, RE-EXPORT OR TRANSFER TO ORGANIZATIONS AND NATIONALS OF EMBARGOED
COUNTRIES: CUBA, SUDAN, NORTH KOREA, IRAN, SYRIA AND CRIMEA A REGION OF UKRAINE, UNLESS AN EXPORT LICENSE OBTAINED FROM THE BUREAU OF INDUSTRY AND SECURITY, UNITED STATES
DEPARTMENT OF COMMERCE. VIOLATIONS OF THESE REGULATIONS ARE PUNISHABLE BY FINE,
IMPRISONMENT, OR BOTH
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
01. NBOC II MLV - AUX. POWER SYSTEM - TITLE AND SIGNATURE PANEL
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-01 BA 1 3
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
01. NBOC II MLV - AUX. POWER SYSTEM - TITLE AND SIGNATURE PANEL
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-01 BA 1 3
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
01. NBOC II MLV - AUX. POWER SYSTEM - TITLE AND SIGNATURE PANEL
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-01 BA 1 3
D D
C C
B B
A A
PHASE A
PHASE B (HI-LEG)
PHASE C
NUET.
GND
100A 15A 15A 15A 15A
120V, 60Hz 10A
CONTROLLER
15A
120V, 60Hz 12A
REC. CIRC. #1 REC. CIRC. #2
120V, 60Hz
5A
15A
120V, 60Hz 5A
REC. CIRC. #3
15A 15A
CP1
12AWG
2C w/GND
3/4" COND
REC1
12AWG
2C w/GND
3/4" COND
REC2
12AWG
2C w/GND
3/4" COND
REC3
12AWG
2C w/GND
3/4" COND
PP1, 200A, 120-240VAC, 3PH, 4W, 60Hz, 100% NEUT.
LDL1
12AWG
3C w/GND
3/4" COND
200A
MFG. JUMPER
DATE REV DESCRIPTION ENG
AA- INITIAL RELEASE9/13/2024
PENTALIFT UNIT
Ref. Des.
CB1
CB2 thru CB9
GEN1
J2
P2
PP1
S1
SPD1
SS1
MB1
RESET SW
HOA SW
ESTOP
CP1,
REC1 Thru REC3
PP1
HPU1, HPU2
HPU3
LDL1
Description
Circuit Breaker, QO, 100A, 3 Pole, 120/240VAC, 22kA, plug-in mount
GFI Circuit Breaker, QO, 15A, 1 Pole, 120VAC, 10kA, plug-in mount
38kW, 3Ph, 240VAC, 60Hz Genset
100A, Weather Proof, Sleeve Connector Recpt.
100A, Weather Proof, Sleeve Connector Plug
200A, 30 Space, 208Y/120/240V AC, 25kA
100A, 230VAC 3Ph, 100kAIC Starter, Disconnect Capable w/ Handle Operating Mechanism
AC Surge Protector, 120/208/240 Vac 3-Phase Delta (Hi Leg)
72A, 230VAC, 50-60Hz, 20kW Soft Starter
Circuit Breaker, QO, 200A, 3 Pole, 120/240VAC, 22kA, plug-in mount
Momentary Pushbutton, 250VAC, 50VDC, 5A
3POS, Selector Switch, 1NO, 250VAC 5A
ESTOP Pushbutton, Twist to Reset
12AWG, 2C W/ GND, 600V TRAY CABLE
3/0AWG, 4C W/ GND, 600V TRAY CABLE
3AWG, 3C W/ GND, 600V TRAY CABLE
4AWG, 3C W/ GND, 600V TRAY CABLE
12AWG, 3C W/ GND, 600V TRAY CABLE
Qty.
SEE NOTE 4
SEE NOTE 4
SEE NOTE 4
SEE NOTE 4
SEE NOTE 4
350'
50'
50'
50'
THIS DRAWING IS THE PROPERTY OF THE NASA BALLOON PROGRAM AND MAY NOT BE USED, COPIED, OR DISTRIBUTED (OUTSIDE OF AUTHORIZED CONTRACTORS) FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED WITHOUT THE EXPRESS WRITTEN AUTHORITY OF THE NASA BALLON PROGRAM.
EAR ECCN: EAR99
- EXPORT ADMINISTRATION REGULATIONS (EAR) NOTICE -
THIS DOCUMENT CONTAINS INFORMATION WITHIN THE PURVIEW OF THE EXPORT ADMINISTRATION REGULATIONS (EAR), 15 CFR §73 -774, AND IS EXPORT-CONTROLLED. IT IS PROHIBITED FOR SALE, EXPORT, RE-EXPORT OR TRANSFER TO ORGANIZATIONS AND NATIONALS OF EMBARGOED
COUNTRIES: CUBA, SUDAN, NORTH KOREA, IRAN, SYRIA AND CRIMEA A REGION OF UKRAINE, UNLESS AN EXPORT LICENSE OBTAINED FROM THE BUREAU OF INDUSTRY AND SECURITY, UNITED STATES
DEPARTMENT OF COMMERCE. VIOLATIONS OF THESE REGULATIONS ARE PUNISHABLE BY FINE,
IMPRISONMENT, OR BOTH
REFERENCE MECHANICAL DRAWING 08-20001 THRU 08-
20003 FOR ALL LENGTHS, ROUTING, AND LOCATIONS
PHASES TO BE LABLED WITH COLORED
ELECTRICAL TAPE AT LUGS
TO BE INSTALLED IN ACCORDANCE WITH THE NEC
AND BEST STANDARDS AND PRACTICES
NOTES
HPU STARTER
HPU3
4AWG
3C w/GND
3/4" COND
HPU1
3AWG
3C w/GND
3/4" COND
3AWG
3C w/GND
3/4" COND
HPU2
3AWG
3C w/GND
3/4" COND
ON
OFF
RESET
ESTOP
UP
ON
OFF
DOWN
HAND
OFF
AUTO
PP1
3/0 4C w/GND
1" COND
PART OF ENCLOSED COMBINATION SOFT STARTER
EATON P/N: ECS95V2CAG-C34P7S3 OR EQUIVALENT4
A3/10/2025 MBCR 2826
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
02. NBOC II MLV - AUXILIARY POWER SYSTEM - THREELINE POWER
Tuesday, August 06, 2024 Sunday, November 26, 2023 Monday, March 10, 2025
08-20018-SCH-01 CustomA 2 3
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
02. NBOC II MLV - AUXILIARY POWER SYSTEM - THREELINE POWER
Tuesday, August 06, 2024 Sunday, November 26, 2023 Monday, March 10, 2025
08-20018-SCH-01 CustomA 2 3
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
02. NBOC II MLV - AUXILIARY POWER SYSTEM - THREELINE POWER
Tuesday, August 06, 2024 Sunday, November 26, 2023 Monday, March 10, 2025
08-20018-SCH-01 CustomA 2 3
OL
S1
NON-REVERSING
SIZE 3
60 OVL
100 FLA
TM
J2
CB2
CB4
CB6
LAUNCH DECK LIFT
1HP
4.2FLA
3ph240VAC 60Hz
L1 L2 L3 G N
D
OL OL
CB1
MB1
CB9
SS1
SOFT START
70FLA
L1 L2 L3
T1 T2 T3
HYD. PUMP MOTOR
20HP
48.2FLA
3ph240VAC 60Hz
L1 L2 L3 G N
D
CB8
SPD1
A0T-701-314 1phBK (Hi) 2phOR
3phBK2
NEUT.WH
GNDGR
CB7
CB3
TM
CB5
OL
P2
TM
GEN1
38kW, 3Ph, 240VAC, 60Hz
2 3
5 67 8
OL OL
D D
C C
B B
A A
FROM PP1
REC. CIRCUIT
#1
FROM PP1
REC. CIRCUIT
#3
MLV LAUNCHER CHASSIS - PP1
MLV LAUNCHER CHASSIS
REC1
12AWG
2C w/GND
1" COND
REC3
12AWG
2C w/GND
1" COND
REC2
12AWG
2C w/GND
1" COND
FROM PP1
REC. CIRCUIT
#2
ENG
9/13/2024
REV
AAINITIAL RELEASE
DESCRIPTIONDATE
NOTES
TO BE ENCASED IN AN "IN-USE" WEATHERPROOF
GANGBOX WITH SEALS AND GLANDS
Description
125VAC, US Outlet
Qty.
Ref. Des.
O1 Thru O8
TO BE LABELED "GFCI EQUIPED"
3 REFERENCE MECHANICAL DRAWING 08-20001 THRU
08-20003 FOR LENGTHS, ROUTING, AND LOCATIONS
THIS DRAWING IS THE PROPERTY OF THE NASA BALLOON PROGRAM AND MAY NOT BE USED, COPIED, OR DISTRIBUTED (OUTSIDE OF AUTHORIZED CONTRACTORS) FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED WITHOUT THE EXPRESS WRITTEN AUTHORITY OF THE NASA BALLON PROGRAM.
EAR ECCN: EAR99
- EXPORT ADMINISTRATION REGULATIONS (EAR) NOTICE -
THIS DOCUMENT CONTAINS INFORMATION WITHIN THE PURVIEW OF THE EXPORT ADMINISTRATION REGULATIONS (EAR), 15 CFR §73 -774, AND IS EXPORT-CONTROLLED. IT IS PROHIBITED FOR SALE, EXPORT, RE-EXPORT OR TRANSFER TO ORGANIZATIONS AND NATIONALS OF EMBARGOED
COUNTRIES: CUBA, SUDAN, NORTH KOREA, IRAN, SYRIA AND CRIMEA A REGION OF UKRAINE, UNLESS AN EXPORT LICENSE OBTAINED FROM THE BUREAU OF INDUSTRY AND SECURITY, UNITED STATES
DEPARTMENT OF COMMERCE. VIOLATIONS OF THESE REGULATIONS ARE PUNISHABLE BY FINE,
IMPRISONMENT, OR BOTH
CR 2826A MB3/10/2025
H N G H N GH N G
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
03. NBOC II MLV - AUXILIARY POWER SYSTEM - RECEPTACLE CIRCUITS
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-01 CustomA 3 3
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
03. NBOC II MLV - AUXILIARY POWER SYSTEM - RECEPTACLE CIRCUITS
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-01 CustomA 3 3
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
03. NBOC II MLV - AUXILIARY POWER SYSTEM - RECEPTACLE CIRCUITS
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-01 CustomA 3 3
D1B
DUAL GANG OUTLET
H1N1
G1
N2
G2
H2
O2
AC WALL OUTLET
H1 N1
G1
N2
G2
H2
O3
AC WALL OUTLET
H1 N1
G1
N2
G2
H2
O1
AC WALL OUTLET
H1 N1
G1
N2
G2
H2
D1A
DUAL GANG OUTLET
H1 N1
G1
N2
G2
H2
D D
C C
B B
A A
SIGNATURE PANEL
Page
Description
SENSOR WIRING DIAGRAMS
20018
2, 3
DWG #
08-20018-SCH-02
THIS DRAWING IS THE PROPERTY OF THE NASA BALLOON PROGRAM AND MAY NOT BE USED, COPIED, OR DISTRIBUTED (OUTSIDE OF AUTHORIZED CONTRACTORS) FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIED WITHOUT THE EXPRESS WRITTEN AUTHORITY OF THE NASA BALLON PROGRAM.
EAR ECCN: EAR99
- EXPORT ADMINISTRATION REGULATIONS (EAR) NOTICE -
THIS DOCUMENT CONTAINS INFORMATION WITHIN THE PURVIEW OF THE EXPORT ADMINISTRATION REGULATIONS (EAR), 15 CFR §73 -774, AND IS EXPORT-CONTROLLED. IT IS PROHIBITED FOR SALE, EXPORT, RE-EXPORT OR TRANSFER TO ORGANIZATIONS AND NATIONALS OF EMBARGOED
COUNTRIES: CUBA, SUDAN, NORTH KOREA, IRAN, SYRIA AND CRIMEA A REGION OF UKRAINE, UNLESS AN EXPORT LICENSE OBTAINED FROM THE BUREAU OF INDUSTRY AND SECURITY, UNITED STATES
DEPARTMENT OF COMMERCE. VIOLATIONS OF THESE REGULATIONS ARE PUNISHABLE BY FINE,
IMPRISONMENT, OR BOTH
HPU CONTROL WIRING 408-20018-SCH-02
08-20018-SCH-02 CONTROLLER WIRING 5 Thru 9
10XMTR & GENSET WIRING08-20018-SCH-02
11HPU SOFT START WIRING08-20018-SCH-02
08-20018-SCH-02 12CONTROL POWER WIRING
CP1 PANEL LAYOUT08-20018-SCH-02 13
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
01. NBOC II MLV - CONTROL SYSTEM - TITLE/SIGNATURE PANEL
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-02 BA 1 13
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
01. NBOC II MLV - CONTROL SYSTEM - TITLE/SIGNATURE PANEL
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-02 BA 1 13
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
01. NBOC II MLV - CONTROL SYSTEM - TITLE/SIGNATURE PANEL
Tuesday, August 06, 2024 Tuesday, March 19, 2024 Monday, March 10, 2025
08-20018-SCH-02 BA 1 13
D D
C C
B B
A A
ENG
9/16/2024
REV
AAINITIAL RELEASE
DESCRIPTIONDATE
B/S: 1011-231-0305
SEAL: 114017
ALT: 1095839
SEE MECHANICAL DWG 08-20001 THRU 08-20003
FOR APPROX. LENGTHS , ROUTING, AND
LOCATIONS ON MLV ASSEMBLY
UNTERMINATED WIRES SHALL BE COILED AND
STOWED
SPLICES TO BE A MINIMUM OF 6IN FROM
CONDUIT ENTRY AT THE SENSOR
NOTES
Ref. Des.
J101
J102
J103
J103
J103
J104
J105
J101 thru J105
Qty.
300'
Description
M12 CONNECTOR PIG TAIL FROM MFG.
M12 4P, CONNECTOR, FEMALE
DT06-3S CON w/16-20AWG CONTACTS
DEUTSCH RCPT. 3POS BACKSHELL
SEAL PLUG
MFG. CONNECTOR PIG TAIL
M12 5P, CONNECTOR, FEMALE
4PR TWISTED SHIELDED, 300V TRAY CABLE
EXENC
20AWG
TW/SH/PR
HPUPT
20AWG
TW/SH/PR
HPUTMP
20AWG
TW/SH/PR
ELENC
20AWG
TW/SH/PR
HPULLSW
20AWG
TW/SH/PR
4 UTILIZE TERMINAL BLOCKS INSTALLED IN CP1
WHERE FEASIBLE
DW8000-135-116-7ASALWL-H1151
8466-A-2000-000
EX ENC
HPU PT
828K-A-012-011
HPU TEMP
EL ENC
1236-C01-360L-P01-V106-M01-S2PD-000
HPU LLSW
LLE G 0024U A110 1 A 70
Sensor Reference Table Ref. Des.
P106
P107
P108
P109
P110
P111
P112
P113
P104
P101
P102
P103
P105
Qty.
P/N
TR 330-11Y-1903
TR 330-11Y-1903
TR 330-11Y-1903
TR 330-11Y-1903
TR 330-11Y-1903
TR 330-11Y-1903
TR 330-11Y-1903
TR 330-11Y-1903
1236-C01-360L-P01-
V106-M01-S2PD-000
DW8000-135-116-
7ASALWL-H1151
8466-A-2000-000
828K-A-012-011
LLE G 0024U A110
1 A 70
Description
Boom EL Lockout Pin 1 Switch
Boom EL Lockout Pin 2 Switch
Boom EXT Lockout Pin 1 Switch
Boom EXT Lockout Pin 2 Switch
Boom UP EL Overtravel Limit Switch
Boom DN EL Overtravel Limit Switch
Boom EXT IN Overtravel Limit Switch
Boom EXT OUT Overtravel Limit Switch
Boom EL Analog Angle Encoder
Boom EXT Analog Linear Position Encoder
Hydraulic System Pressure Transducer
Hydraulic System Temperature Transducer
Hydraulic Oil Low-Level Switch
Bill Of Materials
Name
EL PIN 1 SW
EL PIN 2 SW
EX PIN 1 SW
EX PIN 2 SW
EL UP LSW
EL DN LSW
EX IN LSW
EX OUT LSW
EL ENC
EX ENC
HPU PT
HPU TEMP
HPU LLSW
APPROX. 45' ± 5'
THIS DRAWING IS THE PROPERTY OF THE NASA
BALLOON PROGRAM AND MAY NOT BE USED, COPIED,
OR DISTRIBUTED (OUTSIDE OF AUTHORIZED
CONTRACTORS) FOR ANY PURPOSE OTHER THAN THAT
FOR
WHICH IT IS SUPPLIED WITHOUT THE EXPRESS
WRITTEN AUTHORITY OF THE NASA BALLON PROGRAM.
EAR ECCN: EAR99
- EXPORT ADMINISTRATION REGULATIONS (EAR)
NOTICE -
THIS DOCUMENT CONTAINS INFORMATION WITHIN THE
PURVIEW OF THE EXPORT ADMINISTRATION
REGULATIONS (EAR), 15 CFR §73 -774, AND IS
EXPORT-CONTROLLED. IT IS PROHIBITED FOR SALE,
EXPORT, RE-EXPORT OR TRANSFER TO ORGANIZATIONS
AND NATIONALS OF EMBARGOED
COUNTRIES: CUBA, SUDAN, NORTH KOREA, IRAN,
SYRIA AND CRIMEA A REGION OF UKRAINE, UNLESS
AN EXPORT LICENSE OBTAINED FROM THE BUREAU OF
INDUSTRY AND SECURITY, UNITED STATES
DEPARTMENT OF COMMERCE. VIOLATIONS OF THESE
REGULATIONS ARE PUNISHABLE BY FINE,
IMPRISONMENT, OR BOTH
Reference CR# 28243/10/2025 EKA
TS1(16A) (PAGE 5)
NOT-CONNECTED
TS1(16B) (PAGE 5)
TS1(34A) (PAGE 7)
TS1(17A) (PAGE 5)
TS1(34B) (PAGE 7)
TS1(17B) (PAGE 5)
TS1(24B) (PAGE 6)
TS1(95B) (PAGE 12)
TS1(50A) (PAGE 7)
TS1(65B) (PAGE 8)
TS1(96A) (PAGE 12)
TS1(25A) (PAGE 6)
NOT-CONNECTED
NOT-CONNECTED
NOT-CONNECTED
NOT-CONNECTED
NOT-CONNECTED
NOT-CONNECTED
NOT-CONNECTED
NOT-CONNECTED
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
02. NBOC II MLV - CONTROL SYSTEM - SENSOR WIRING - PAGE 1
Tuesday, August 06, 2024 Sunday, November 26, 2023 Monday, March 10, 2025
08-20018-SCH-02 BA 2 13
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
02. NBOC II MLV - CONTROL SYSTEM - SENSOR WIRING - PAGE 1
Tuesday, August 06, 2024 Sunday, November 26, 2023 Monday, March 10, 2025
08-20018-SCH-02 BA 2 13
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
02. NBOC II MLV - CONTROL SYSTEM - SENSOR WIRING - PAGE 1
Tuesday, August 06, 2024 Sunday, November 26, 2023 Monday, March 10, 2025
08-20018-SCH-02 BA 2 13
J101
RK 4.4T-2
V+3
SIG2
N/C4 N/C
J105
M12 5P, FEMALE
+24VDC2
SIG13
GND (0V)4
SIG25
GND
J102
M12 4P, FEMALE
SIG+3
SIG-2
NC4
NC
J103
DT06-3S w/ 16-20AWG CONTACTS
SIG+2
SIG-3
NC
J104
HAT 6006792
+Ub2
NC3
0V4
SIG5
D D
C C
B B
A A
ENG
9/16/2024
REV
AAINITIAL RELEASE
DESCRIPTIONDATE
SEE MECHANICAL DWG 08-20001 THRU 08-20003
FOR APPROX. LENGTHS , ROUTING, AND
LOCATIONS MLV ON ASSEMBLY
2 UNTERMINATED WIRES SHALL BE COILED AND
STOWED
NOTES
B/S: 1011-235-0405
SEAL: 114017 SEAL: 114017
B/S: 1011-237-0405
B/S: 1011-237-0405
SEAL: 114017SEAL: 114017
B/S: 1011-235-0405
B/S: 1011-237-0405
SEAL: 114017SEAL: 114017
B/S: 1011-235-0405
SEAL: 114017 SEAL: 114017
B/S: 1011-235-0405 B/S: 1011-237-0405
BOOM ASSEMBLYELPIN1
20AWG
TW/SH/PR
ELPIN2
20AWG
TW/SH/PR
EXPIN1
20AWG
TW/SH/PR
EXPIN2
20AWG
TW/SH/PR
20AWG
TW/SH/PR
20AWG
TW/SH/PR
20AWG
TW/SH/PR
20AWG
TW/SH/PR
3 NO-CONNECT TO BE WIRED, CAPPED AND STOWED
IN DEVICE AS SPARE CONDUCTOR
6"
4 UTILIZE TERMINAL BLOCKS INSTALLED IN CP1
WHERE FEASIBLE
APPROX. 45' ± 5'
THIS DRAWING IS THE PROPERTY OF THE NASA BALLOON PROGRAM
AND MAY NOT BE USED, COPIED,
OR DISTRIBUTED (OUTSIDE OF AUTHORIZED CONTRACTORS) FOR
ANY PURPOSE OTHER THAN THAT FOR
WHICH IT IS SUPPLIED WITHOUT THE EXPRESS WRITTEN
AUTHORITY OF THE NASA BALLON PROGRAM.
EAR ECCN: EAR99
- EXPORT ADMINISTRATION REGULATIONS (EAR) NOTICE -
THIS DOCUMENT CONTAINS INFORMATION WITHIN THE PURVIEW OF
THE EXPORT ADMINISTRATION
REGULATIONS (EAR), 15 CFR §73 -774, AND IS
EXPORT-CONTROLLED. IT IS PROHIBITED FOR SALE,
EXPORT, RE-EXPORT OR TRANSFER TO ORGANIZATIONS AND
NATIONALS OF EMBARGOED
COUNTRIES: CUBA, SUDAN, NORTH KOREA, IRAN, SYRIA AND
CRIMEA A REGION OF UKRAINE, UNLESS
AN EXPORT LICENSE OBTAINED FROM THE BUREAU OF INDUSTRY
AND SECURITY, UNITED STATES
DEPARTMENT OF COMMERCE. VIOLATIONS OF THESE REGULATIONS
ARE PUNISHABLE BY FINE,
IMPRISONMENT, OR BOTH
Qty.
250'
Bill Of Materials Ref. Des.
J106 THRU J113
J106 THRU J113
P106 THRU P113
P106 THRU P113
ALL CONNECTORS
Description
DT06-4S w/ 16-20AWG CONTACTS
DEUTSCH 4POS RCPT BACKSHELL
DT04-4P w/ 16-20AWG CONTACTS
DEUTSCH 4POS PLUG BACKSHELL
SEAL PLUG
20AWG, 4PR, TW/SH, 300V TRAY CABLE
Reference CR# 28243/10/2025 EKA
TS1(5B) (PAGE 5)
TS1(87B) (PAGE 12)
TS1(18A) (PAGE 6)
NOT-CONNECTED
TS1(19B) (PAGE 6)
TS1(88A) (PAGE 12)
TS1(39B) (PAGE 7)
NOT-CONNECTED
TS1(40A) (PAGE 7)
TS1(88B) (PAGE 12)
TS1(40B) (PAGE 7)
NOT-CONNECTED
TS1(41A) (PAGE 7)
TS1(89A) (PAGE 12)
TS1(41B) (PAGE 7)
NOT-CONNECTED
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
03. NBOC II MLV - CONTROL SYSTEM - SENSOR WIRING - PAGE 2
Tuesday, August 06, 2024 Monday, August 12, 2024 Monday, March 10, 2025
08-20018-SCH-02 BA 3 13
Engineered By:
Reviewed By:
CM Approver:
QA Approver:
Originating Facility: QA Stamp:
Page Description:
Sch Created:
Page Created:
Page Modified:
Document Number: Rev: Drawing Size: Sheet:
of
03. NBOC II MLV - CONTROL SYSTEM - SENSOR WIRING - PAGE 2
Tuesday, August 06, 2024 Monday, August 12, 2024 Monday, March 10, 2025
08-20018-SCH-02 BA 3 13
Engineered By:
Reviewed By:
CM…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .