ADDENDUM # 005
Date: 30 September 2016
Project #: 2009121.11
Project: Building 25 - EPA Lab
U.S. General Services Administration
Bid Documents Issued: 30 August 2016
The Drawings, Specifications, and Contract Documents on the project are modified, corrected, supplemented, and/or superseded as hereinafter described. It will be construed that each bidder’s proposal is submitted with full knowledge of all modifications and supplemental data specified herewith. This addendum may affect pricing. Failure to acknowledge this addendum may be cause for rejection of bid.
DRAWINGS:
ARCHITECTURAL
A-101A Remove Work Note 173 for 6” concrete curb and associated dimension strings from 1A-250, R8 CLLE Lab
ADDENDUM # 005
30 September 2016
LABORATORY FURNISHINGS
LF-304 Concrete curb removed from Enlarged Lab Plan 1 & 2 Detail reference removed form Enlarged Lab Plan 1 & 2 Concrete curb removed from Elevation 3 & 6
LF-801 Detail 1 removed from sheet
Attachments:
Sections as indicated above.
End of Addendum
CENTRIFUGAL HVAC FANS 23 34 16-1
(Addendum 05, 9/30/16) (Addendum 01, 5/27/16)
SECTION 23 34 16 - CENTRIFUGAL HVAC FANS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Dryer Exhaust Duct Power Ventilator
1.02 RELATED REQUIREMENTS
A. Section 23 05 13 - Common Motor Requirements for HVAC Equipment.
B. Section 23 05 48 - Vibration Controls for HVAC Piping and Equipment.
C. Section 23 07 13 - Duct Insulation.
D. Section 23 33 00 - Air Duct Accessories: Backdraft dampers.
E. Section 01 91 13: Commissioning requirements that apply to all types of work.
F. Section 23 08 00 - Commissioning of HVAC.
1.03 REFERENCE STANDARDS
A. ABMA STD 9 - Load Ratings and Fatigue Life for Ball Bearings; American Bearing
Manufacturers Association, Inc.; 1990 (Reapproved 2008).
B. ABMA STD 11 - Load Ratings and Fatigue Life for Roller Bearings; American Bearing
Manufacturers Association, Inc.; 2014.
C. AMCA 99 - Standards Handbook; Air Movement and Control Association International, Inc.;
2010.
D. AMCA 210 - Laboratory Methods of Testing Fans for Aerodynamic Performance Rating; Air
Movement and Control Association International, Inc.; 2007 (ANSI/AMCA 210, same as
ANSI/ASHRAE 51).
E. AMCA (DIR) - [Directory of] Products Licensed Under AMCA International Certified Ratings Program; Air Movement and Control Association International, Inc.;
http://www.amca.org/certified/search/company.aspx.
F. AMCA 300 - Reverberant Room Method for Sound Testing of Fans; Air Movement and Control Association International, Inc.; 2008.
G. AMCA 301 - Methods for Calculating Fan Sound Ratings from Laboratory Test Data; Air Movement and Control Association International, Inc.; 2007.
H. SMACNA (DCS) - HVAC Duct Construction Standards; 2005.
I. UL DEDPV Supplement to UL705
1.04 PERFORMANCE REQUIREMENTS
A. Performance Ratings: Determined in accordance with AMCA 210 and bearing the AMCA
Certified Rating Seal.
B. Sound Ratings: AMCA 301, tested to AMCA 300, and bear AMCA Certified Sound Rating
Seal.
C. Fabrication: Conform to AMCA 99.
D. Performance Base: 5500 foot elevation conditions.
E. Static and Dynamic Balance: Eliminate vibration or noise transmission to occupied areas.
1.05 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
SENSITIVE BUT UNCLASSIFIED (SBU)
CENTRIFUGAL HVAC FANS 23 34 16-2
B. Product Data: Provide data on centrifugal fans and accessories, fan curves, sound power levels for both fan inlet and outlet at rated capacity, and electrical characteristics and connection requirements.
C. Shop Drawings: Indicate assembly of centrifugal fans and accessories including fan curves with specified operating point clearly plotted, sound power levels for both fan inlet and outlet at rated capacity, and electrical characteristics and connection requirements.
D. Manufacturer's Instructions: Include complete installation instructions.
E. Maintenance Data: Include instructions for lubrication, motor and drive replacement, spare parts list, and wiring diagrams.
1.06 QUALITY ASSURANCE
A. Manufacturer Qualifications: Company specializing in manufacturing the type of products specified in this section, with minimum three years of documented experience.
B. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories Inc. as suitable for the purpose specified and indicated.
1.07 DELIVERY, STORAGE, AND HANDLING
A. Protect motors, shafts, and bearings from weather and construction dust.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Fantech B. Substitutions: See Section 01 60 00 - Product Requirements.
A. Greenheck (AD 01) B. Loren-Cook (AD 01) C. Acme (AD 01) D. PennBarry (AD 01) E. Twin City Fans (AD 05)
2.02 DRYER EXHAUST DUCT POWER VENTILATOR
A. MANUFACTURERS (AD 01)
1. Fantech (AD 01)
2. Substitutions: See Section 01 60 00 - Product Requirements. (AD 01)
B. Dryer Exhaust Duct power ventilator shall be furnished with all accessories for installation including fan, pressure switch, LED indicator panel and duct clamps for smooth duct installation.
2.03 CENTRIFUGAL INLINE FAN
A. Drives: Variable pitch V-belt drives or direct driven as scheduled.
B. Housings: Hinged, heavy gauge aluminum enclosing motor outside airstream.
C. Motor: Ball bearing type, designed for heavy duty vertical mounting. Isolate motors and fans from base with rubber isolators. Select motor such that motor BHP does not exceed nameplate at rated conditions.
D. Fans: Centrifugal type, statically and dynamically balanced.
E. Provide:
1. Lubricated lifetime sealed ball bearings.
2. Disconnect switch on 3-phase units furnished under Division 26, unless noted as a fan accessory on fan schedule.
3. Bird screen on fan intake.
4. Provide with rubber-n-shear isolation hangers
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
CENTRIFUGAL HVAC FANS 23 34 16-3
PART 3 EXECUTION
3.01 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Install a minimum of 5 feet from the dryer outlet.
C. Install LED indicator panel on wall adjacent to the dryer location.
D. Pressure switch shall be connected to automatically turn fan on when dryer is in use and turn off after dryer stops. Fan shall continue to run for short period of time after dryer shuts down to reduce temperature of duct and dryer.
E. Fan shall shutdown if dryer exhaust rises above 165 degrees F.
END OF SECTION
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
VENTURI AIR VALVES 23 36 05-1
(Addendum 02, 8/5/16)
SECTION 23 36 05 - VENTURI AIR VALVES
PART 1 - GENERAL
1.01 VENTURI VALVES
1.02 SECTION INCLUDES
A. Venturi Valves - Electronic Variable Air Volume Supply B. Venturi Valves - Constant Volume
C. RELATED SECTIONS
1. Section 23 07 16 - HVAC Equipment Insulation (AD 02)
2. Section 23 31 00 – HVAC Ducts and Casings.
3. Section 23 09 13 - Instrumentation and Control Devices for HVAC
4. Section 23 09 23 – Direct-Digital Control System for HVAC
5. Section 01 91 13 - Commissioning requirements that apply to all types of work.
6. Section 23 08 00 - Commissioning of HVAC.
D. REFERENCES
1. NFPA 90A - Standard for the Installation of Air Conditioning and Ventilation Systems;
National Fire Protection Association.
2. UL 181 - Standard for Factory-Made Air Ducts and Air Connectors; Underwriters
Laboratories Inc.
E. SUBMITTALS
1. See Section 013300 - Submittal Procedures.
2. Product Data: Provide data indicating configuration, general assembly, and materials used in fabrication. Include catalog performance ratings which indicate air flow, static pressure, and NC designation. Include electrical characteristics and connection requirements.
3. Shop Drawings: Indicate configuration, general assembly, and materials used in fabrication, and electrical characteristics and connection requirements.
4. Manufacturer's Installation Instructions: Indicate support and hanging details, and service clearances required.
5. Project Record Documents: Record actual locations of units.
6. Operation and Maintenance Data: Include manufacturer's descriptive literature, operating instructions, maintenance and repair data, and parts lists. Include directions for resetting constant volume regulators.
7. Warranty: Submit manufacturer warranty and ensure forms have been completed in Owner's name and registered with manufacturer.
F. QUALITY ASSURANCE
1. Manufacturer Qualifications: Company specializing in manufacturing the type of products specified in this section, with minimum three years of documented experience.
2. Products Requiring Electrical Connection: Listed and classified by Underwriters
Laboratories Inc. as suitable for the purpose specified and indicated.
G. WARRANTY
1. See Section 017700 - Closeout Procedures, for additional warranty requirements.
2. Provide three (3) year manufacturer warranty for venturi valves.
H. ATTIC STOCK
1. Provide two of each size actuator and two of each type of controller used in the scope of work for attic stock. Provide to owner before substantial completion of project. (AD02)
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
VENTURI AIR VALVES 23 36 05-2
PART 2 - PRODUCTS
2.01 MANUFACTURERS
A. Products shall be provided by one of the following manufacturers:
1. Phoenix Controls; Product Medium Pressure Venturi Valves: Constant or Variable Volume
(refer to drawings), and Base Upgradable.
2. CRC (Critical Room Control) – www.criticalroom.com
3. TSI Incorporated
4. Triatek, LLC
5. Siemens Building Technologies, Inc.
6. Engineer-approved equal. Each lab shall have a single manufacturer for air valves.
Labs may not have a mix of manufacturers to ensure that full functionality and compatibility is maintained for fast acting control to maintain required room airflow offsets. (AD05)
a. All existing Phoenix Air Valves to have retrofit from pneumatic to electric actuators shall be Phoenix controllers. No other brand allowed, except for if alternate method in item d below is used.
b. All labs that have existing Phoenix supply air valves with added exhaust air valves, the new valves shall be Phoenix to allow for full compatibility and function. No other brand allowed, except for if alternate method in item d below is used.
c. Any labs with new supply and exhaust air valves, the valves may be of the brands listed above.
d. Alternately, at contractor option, for any spaces with existing or retrofitted Phoenix valves, the existing valve(s) may be replaced in its entirety with one of the manufacturers listed above to provide a single. Replacement will include all modifications to ductwork to accommodate new valve and all connections to electrical and control system.
B. MANUFACTURED UNITS
1. Identify each valve with clearly marked identification label and air flow indicator. Include unit nominal air flow, maximum factory set airflow, minimum factory set air flow, and coil type.
C. ELECTRONIC VARIABLE VOLUME VALVE
1. The airflow control device shall be a variable volume venturi valve.
2. The valve assembly manufacturer's Quality Management System shall be registered to
ISO 9001:2000.
3. The airflow control device shall be pressure independent over its specified differential static pressure operating range (0.6" to 3.0" W.C. pressure drop across the valve). An integral pressure independent assembly shall respond and maintain specific airflow within one second of a change in duct static pressure irrespective of the magnitude of pressure and/or flow change or quantity of airflow controllers on a manifold system.
4. The airflow control device shall maintain a factory calibrated flow set point based on a digital signal. Devices requiring feedback shall generate a 0 to 10 volt or 4 to 20 mA feedback signal that is linearly proportional to its airflow. Full interoperability with the BACnet BCS is required. Technology for peer-to-peer communication between room controllers shall be included.
5. Device shall track airflow supplied and exhausted from room served to ensure negative laboratory pressure.
6. Device shall send alarm on low airflow.
7. Device shall fail in mode that ensures negative laboratory pressure.
8. Actuators shall be high speed electronic. (AD 02)
9. All supply air valves shall be supplied with factory applied external insulation. (AD 02)
D. ELECTRONIC CONSTANT VOLUME VALVE
1. The airflow control device shall be a venturi valve.
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
VENTURI AIR VALVES 23 36 05-3
2. The valve assembly manufacturer's Quality Management System shall be registered to
ISO 9001:2000.
3. The airflow control device shall be pressure independent over its specified differential static pressure operating range (0.6" to 3.0" W.C. pressure drop across the valve). An integral pressure independent assembly shall respond and maintain specific airflow within one second of a change in duct static pressure irrespective of the magnitude of pressure and/or flow change or quantity of airflow controllers on a manifold system.
4. The airflow control device shall maintain a factory calibrated flow set point based on a locked pivot arm. The pivot arm position shall be field adjustable to maintain constant flow corresponding to the locked arm position. Full interoperability with the BACnet BCS is required. Technology for peer-to-peer communication between room controllers shall be included.
5. Device shall track airflow supplied and exhausted from room served to ensure negative laboratory pressure.
6. Device shall send alarm on low airflow.
7. Device shall fail in mode that ensures negative laboratory pressure.
8. Actuators shall be high speed electronic. (AD 02)
E. SASH POSITION SENSOR
1. Refer to section 23 09 13 Instrumentation and Control Devices for HVAC.
F. ZONE OCCUPANCY SENSOR
1. Occupancy sensor shall be provided and installed by division 26. Coordinate with division
26 from proper placement for control of air valves and lighting systems.
2. Follow manufacturer installation instructions to fully install and integrate zone occupancy sensor into venturi valve room controller.
G. VENTURI VALVE ROOM CONTROLLER
1. Refer to section 23 09 13 Instrumentation and Control Devices for HVAC.
H. CERTIFICATION
1. Each airflow control device shall be factory calibrated to the job specific airflows as detailed on the plans and specifications using NIST traceable air stations and instrumentation have a combined accuracy of no more than ± 1% of signal over the entire range of measurement. Electronic airflow control devices shall be further calibrated and their accuracy verified to ± 5% of signal at a minimum of eight different airflows across the full operating range of the device.
2. All airflow control devices shall be individually marked with device specific and factory characterization data. As a minimum, include: tag number, serial number, model number, characterization information (for electronic devices), and quality control inspection numbers. All information shall be stored by the manufacturer. Job related information, such as tag number, serial number and model number, shall be stored by the manufacturer for use with as-built documentation.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Install in accordance with manufacturer's instructions, paying special attention to airflow direction and mounting position requirements.
B. Support venturi valves individually from structure. Do not support from adjacent ductwork.
Orient as required by manufacturer. Coordinate all units that are not installed horizontal prior to ordering.
C. Connect all airflow control valve linkages.
D. Provide and install insulation in accordance with Section 230700.
E. Connect to ductwork in accordance with Section 233113.
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
VENTURI AIR VALVES 23 36 05-4
F. Provide and install electronic controls to actuators, and provide and install all sash position sensors, occupancy sensors, room controllers and interconnecting wiring to form a fully-functional lab supply/exhaust system that communicates with the building BCS.
END OF SECTION
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
CABINET, DUCT AND UNIT
HEATERS (AD 01)
23 81 01-1
(Addendum 05, 9/30/16) (Addendum 01, 5/27/16)
SECTION 23 81 01 – CABINET, DUCT AND UNIT HEATERS (AD 01)
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Unit Ceiling mounted heaters. (AD 01) B. Cabinet unit heaters.
C. Electric Duct Heater (AD 01)
1.02 RELATED REQUIREMENTS
A. Section 23 05 13 - Common Motor Requirements for HVAC Equipment.
B. Section 26 27 17 - Equipment Wiring: Electrical characteristics and wiring connections.
Installation of room thermostats. Electrical supply to units.
1.03 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide typical catalog of information including arrangements.
C. Shop Drawings:
1. Indicate cross sections of cabinets, grilles, bracing and reinforcing, and typical elevations.
2. Submit schedules of equipment and enclosures typically indicating length and number of pieces of element and enclosure, corner pieces, end caps, cap strips, access doors, pilaster covers, and comparison of specified heat required to actual heat output provided.
3. Indicate mechanical and electrical service locations and requirements., D. Manufacturer's Instructions: Indicate installation instructions and recommendations.
E. Operation and Maintenance Data: Include manufacturers descriptive literature, operating instructions, installation instructions, maintenance and repair data, and parts listings.
F. Warranty: Submit manufacturer's warranty and ensure forms have been completed in Owner's name and registered with manufacturer.
G. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.
1. See Section 01 60 00 - Product Requirements, for additional provisions.
2. Extra Filters: One set of each type and size.
1.04 QUALITY ASSURANCE
A. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories
Inc. as suitable for the purpose specified and indicated.
1.05 WARRANTY
A. See Section 01 78 00 - Closeout Submittals, for additional warranty requirements.
B. Provide five year manufacturers warranty for unit heater motors.
PART 2 PRODUCTS
2.01 UNIT CEILING MOUNTED HEATERS
A. Manufacturers:
1. Trane Inc: www.trane.com.
2. Marley-QMark; Model CDF.
3. Modine (AD 05)
43. Substitutions: See Section 01 60 00 - Product Requirements.
B. Casing: 20 gauge recessed steel chasis, 7" deep.
C. Face: 20 gauge steel with adjustable louvers. Provide with ceiling mounting ring.
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
CABINET, DUCT AND 23 81 01-2
UNIT HEATERS (AD 01)
D. Fan: Direct drive propeller type, statically and dynamically balanced, with fan guard; horizontal models with permanently lubricated sleeve bearings; vertical models with grease lubricated ball bearings.
E. Air Outlet: Adjustable pattern diffuser on projection models and two way louvers on horizontal throw models.
F. The heating elements shall be guaranteed for five years and shall be of non-glowing design consisting of 80/20 NiCh resistance wire, enclosed in a steel sheath, to which steel plate fins are brazed. The elements shall cover the entire air intake area to ensure uniform heating of all discharged air.
2.02 CABINET UNIT HEATERS
A. Manufacturers:
1. Trane Inc; Model ______: www.trane.com. (AD 01)
2. Zehnder Rittling; Model FW-270.
3. Substitutions: See Section 01 60 00 - Product Requirements.
B. Coils: Evenly spaced aluminum fins mechanically bonded to copper tubes, 1/2" nominal 0.016"thick copper tubes tested to 300 psig. with manual air vents.
C. Casing: 14 gauge steel cabinet and panel with 1/2" foil faced insulation.
D. Finish: Factory applied baked enamel of white color as selected on visible surfaces of enclosure or cabinet.
E. Fans: Centrifugal forward-curved double-width wheels, statically and dynamically balanced, direct driven.
F. Motor: ECM, resiliently mounted.
2.03 ELECTRIC DUCT HEATERS (AD 01)
A. Electric heating coils shall be provided of the capacity shown on the drawings.
B. Units with heaters shall be U.L. or ETL listed for zero clearance and shall bear the proper listing mark and label. Each heater shall meet all requirements of the National Electrical Code.
C. Each heater terminal box and frame shall be constructed of minimum 20 gauge corrosion resistant metal. Heating elements shall be constructed of high grade nickel/chromium wire and shall not glow when operating at the rated quantities.
D. Heaters shall be provided with factory supplied and prewired branch circuit fusing as required by NEC and U.L. including control fusing on primary voltage hot line, and heater fusing on all sizes.
E. Main power connections to be supplied integral with each unit by the heater manufacturer to break all ungrounded conductors. All units shall have door interlocked fused disconnect switch and a control disconnect.
F. Provide 24 VAC transformer for controls. Factory mount transformer in control enclosure.
G. Electric heating coil shall be removable without disturbing the duct system.
H. Each heater shall be complete with:
a. Primary automatic thermal cutoff and a manual reset thermal secondary safety device to de-energize the heater in case of overheating.
b. Proportional electronic airflow sensor which shall be totally independent of the duct static pressure and shall adjust the heater capacity according to the available airflow. The heaters shall deliver maximum heating when needed with normal minimum airflow, reduce heating with lower than minimum airflow and stop heating with no airflow.
I. Heaters shall be equipped with full proportional SCR controller to modulate the heater load according to the temperature control signal. The electronic controller shall be compatible with the following input signals:- Variable voltage signal 0-10 VDC, Pulse width modulation AC or
DC
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed http://www.trane.com/
CABINET, DUCT AND 23 81 01-3
UNIT HEATERS (AD 01)
PART 3 EXECUTION
3.01 INSTALLATION
A. Install in accordance with manufacturer's instructions.
B. Install equipment exposed to finished areas after walls and ceiling are finished and painted. Do not damage equipment or finishes.
C. Protection: Provide finished cabinet units with protective covers during balance of construction.
D. Unit Heaters: Hang from building structure, with pipe hangers anchored to building, not from piping. Mount as high as possible to maintain greatest headroom unless otherwise indicated.
E. Cabinet Unit Heaters: Install as indicated. Coordinate to assure correct recess size for recessed units.
F. Install electric heating equipment including devices furnished by manufacturer but not factory-mounted. Furnish copy of manufacturer's wiring diagram submittal. Install electrical wiring in accordance with manufacturer's submittals and Section 26 27 17.
END OF SECTION
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
AIR COILS 23 82 16-1
SECTION 23 82 16 - AIR COILS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Water heating coils.
1.02 RELATED REQUIREMENTS
A. Section 23 07 19 - HVAC Piping Insulation.
B. Section 23 21 14 - Hydronic Specialties.
C. Section 23 31 00 - HVAC Ducts and Casings: Installation of duct coils.
D. Section 01 91 13: Commissioning requirements that apply to all types of work.
E. Section 23 08 00 - Commissioning of HVAC.
1.03 REFERENCE STANDARDS
A. AHRI 410 - Standard for Forced-Circulation Air-Cooling and Air-Heating Coils; Air-Conditioning, Heating, and Refrigeration Institute; 2001 (R2011).
B. SMACNA (DCS) - HVAC Duct Construction Standards; Sheet Metal and Air Conditioning
Contractors' National Association; 2005.
1.04 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide coil and frame configurations, dimensions, materials, rows, connections, and rough-in dimensions.
C. Shop Drawings: Indicate coil and frame configurations, dimensions, materials, rows, connections, and rough-in dimensions.
D. Warranty: Submit manufacturer's warranty and ensure forms have been completed in Owner's name and registered with manufacturer.
1.05 DELIVERY, STORAGE, AND HANDLING
A. Protect coil fins from crushing and bending by leaving in shipping cases until installation, and by storing indoors.
B. Protect coils from entry of dirt and debris with pipe caps or plugs.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Aerofin Corporation: www.aerofin.com.
B. Luvata: www.luvata.com.
C. Trane Inc: www.trane.com.
D. Titus (AD 05) D. Substitutions: See Section 01 60 00 - Product Requirements.
2.02 WATER HEATING COILS
A. Tubes: 5/8 inch (16 mm) OD seamless copper or brass arranged in parallel or staggered pattern, expanded into fins, silver brazed joints.
B. Fins: Aluminum or copper continuous plate type with full fin collars.
C. Casing: Die formed channel frame of 16 gage, 0.0598 inch (1.52 mm) galvanized steel with mounting holes on 3 inch (75 mm) centers. Provide tube supports for coils longer than 36 inches (900 mm).
D. Headers: Cast iron with tubes expanded into header.
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed http://www.trane.com/
AIR COILS 23 82 16-2
E. Testing: Air test under water to 200 psi (1380 kPa) for working pressure of 200 psi (1380 kPa) and 220 degrees F (104 degrees C).
F. Configuration: Drainable, with threaded plugs for drain and vent.
G. Fin Spacing: 8 fins per inch (3.1 mm on center).
PART 3 EXECUTION
3.01 INSTALLATION
A. Install in accordance with manufacturers written instructions.
B. Install in ducts and casings in accordance with SMACNA (DCS).
1. Support coil sections independent of piping on steel channel or double angle frames and secure to casings.
2. Arrange supports to avoid piercing drain pans.
3. Provide airtight seal between coil and duct or casing.
C. Protect coils to prevent damage to fins and flanges. Comb out bent fins.
D. Install coils level. Install cleanable tube coils with 1:50 pitch.
E. Make connections to coils with unions and flanges.
F. Hydronic Coils:
1. Hydronic Coils: Connect water supply to leaving air side of coil (counterflow arrangement).
2. Provide shut-off valve on supply line and lockshield balancing valve with memory stop on return line.
3. Locate water supply at bottom of supply header and return water connection at top.
4. Provide manual air vents at high points complete with stop valve.
5. Ensure water coils are drainable and provide drain connection at low points.
G. Insulate headers located outside air flow as specified for piping. Refer to Section 22 07 19.
END OF SECTION
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
FAN COIL UNITS 23 82 19-1
SECTION 23 82 19 - FAN COIL UNITS
PART 1 - GENERAL
1.01 WORK INCLUDED
A. Provide fan coil units and air curtains in sizes and capacities shown on mechanical drawings and in locations shown on drawings. Characteristics of equipment shall be as shown herein.
1.02 RELATED WORK
A. Section 23 09 13: Instrumentation and Control Devices for HVAC B. Section 23 21 13: Hydronic Piping C. Section 23 21 14: Hydronic Specialties D. Section 01 91 13: Commissioning requirements that apply to all types of work.
E. Section 23 08 00 - Commissioning of HVAC.
1.03 SUBMITTALS
A. Submit product data for review.
PART 2 - PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
A. Trane B. Carrier C. McQuay/Daiken D. York/JCI E. Air Therm F. International Environmental G. MultiAqua (for chiller cabinets in 1C-150, 160, 520) Model type: MHCFC4W Cassette H. Mars - air curtain for 1C-180
2.02 FAN COIL EQUIPMENT REQUIREMENTS
A. Units to be complete with fan, ECM motor, outside casing, filter track and 2" MERV 8 filter, double wall insulated panels(except chiller cabinet units), insulated drain pan, and separate copper tube aluminum finned cooling and heating coils, all arranged for mounting as called for on schedule. Insulate units internally to prevent external sweating and heat loss. Cabinets to have removable front panels for access.
B. Fan Motors: ECM type. Motor watt draw not to exceed maximum scheduled on drawings.
(Chiller cabinet is PSC type, direct drive, direct drive.) ECM motor shall be supplied for all sizes available in manufacturers catalog listings. If ECM motor is not available in manufacturer’s standard line, or in some larger unit sizes scheduled on plans, manufacturer may provide a variable frequency drive(VFD) in lieu of ECM motor. VFD shall be per section 23 05 14, except the enclosure can be NEMA 1 instead of NEMA 3R.
Contractor shall provide all required connections to the building controls system and required programming to allow for modulation of the fan coil unit airflow. Contractor shall coordinate required additional wiring with the electrical contractor. No additional costs shall be allowed to the contract for substitution of VFDs. (AD 05)
C. Manual air vent to be located at highest point of supply or return lines.
D. Auxiliary insulated drain pans to be sufficient to collect condensation from coil connections and shutoff valves.
E. Unit hanger suspension and accessories.
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
FAN COIL UNITS 23 82 19-2
F. Provide new and unused filters at time building is turned over to Owner. Do not operate units without filters. Position filter rack access door to allow for accessible filter replacement from side or bottom of unit as allowed by field installation requirements.
G. Units to have sufficient space for maintaining heating and cooling control package consisting of:
H. Automatic cooling coil valve: 2-way (by Control Contractor) I. Valve shutoff package: (By unit manufacturer) J. Control Package: Valves and room type thermostat for ceiling mounted units, valves and unit mounted thermostats for floor mounted units.
K. Provide condensate pump package, connected to unit electrical service with no separate wiring requirements, as required by field conditions to allow for proper condensate drainage.
2.03 AIR CURTAIN EQUIPMENT REQUIREMENTS
A. Wall mounted unit with dynamically balanced fan, ECM motor, variable speed controller, low profile design, wall mounting brackets, white powder coat finish.
B. Maximum sound discharge of 49dBA at 10'.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Install fan coil units at locations designated on drawings in accordance with manufacturer's published instructions.
B. Provide piping connections per diagram on drawings.
C. Insure proper condensate drainage.
D. Chiller cabinet units shall be piped to have both primary and secondary coils in parallel on the chilled water piping per manufacturer's instructions. Provide supplemental steel supports up from chiller support structure to support fan coil unit at the top of the chiller cabinet. Trim edge of the face plate to allow for installation of unit in cabinet to allow for closing of door. Provide thermostat in cabinet to allow for modulation of fan coil unit.
3.02 START-UP AND TEST
A. Start-up unit, check for satisfactory performance as required by plans and specifications.
B. Test units for fan operation and coil performance.
C. Insure that system piping is thoroughly vented, cleaned and all debris is removed from control valves to insure specified water flow.
D. Demonstrate operation to Owner's maintenance personnel and instruct them in system operation.
END OF SECTION
Bid Set 30 August, 2016
EPA Building 25 Co-Location Project
2009121.11 PROPERTY OF THE UNITED STATES GOVERNMENT - FOR OFFICIAL USE ONLY. Do not remove this notice. Properly destroy document when no longer needed
I
2928272625
J
K
L
M
(E) SECURITY
1A-080
(E) OFFICE
1A-090
(E) OPEN
OFFICE
1A-005
(E) OFFICE
1A-015
(E) OFFICE
1A-025
(E) OFFICE
1A-035
(E) OFFICE
1A-045
(E) OFFICE
1A-055
(E) OFFICE
1A-085
(E) OFFICE
1A-075
(E) OFFICE
1A-110
R8 FIELD PREP
1A-110
ESAT
INSTRUMENTS
1A-235
ESAT
TOXICOLOGY &
GENERAL BIO
1A-245
R8
MACROBIOLOGY
1A-260
SHARED
METAL PREP
1A-265
R8 ORGANIC
PREP
1A-270
ESAT
ASBESTOS
1A-255A
ESAT
ASBESTOS
PLM
1A-255
R8 CLLE
1A-250
(E) ELEC
1B-025
(E) RESTROOM
1A-115
(E) NEIC FIELD
SUPPORT
1A-135
(E) NEIC FIELD
SHOP
1A-145
LAB CORRIDOR
C1A2
SERVICE
CORRIDOR
C1A1
SERVICE
CORRIDOR
C1A4
C
A
1A-245
1A-260 1A-255
1A-270 1A-265
1A-235
C
A
A-4212 1
ACID LIFT
1A-120
RE: 1 / A-101D
RE: 1 / A-101C
RE: 1 / A-101B
GAS CLOSET
1A-231
1A-231
1A-120
R E
A
-1 B
R E
A
-1 D
LAB CORRIDOR
C1A5
CORRIDOR
C1A0
STAIR
ST-02
A-421
101101101
RE: 1 / A-101B
C6
C
129129
G
G
C
C
C
C
C
F2
1A-110
129129
F
129129129
129129 129129
G
FE(E)
FE(E)
FE-1
S T
-0
.1
R8 SUPPLIES
1A-220
(E) TELE ROOM
1B-030
MECHANICAL
1B-035
1A-220
(E) OFFICE
1A-095
C
GAS CLOSET
1A-246
GAS CLOSET
1A-254
1A-255A
C1A5
F2
F2
F2
7' - 0"
7' - 7" 7' - 3"
129129
129129
TYP
3' - 0"
3' - 0"
/4
129129
129129
129129
/4
/4
129129
CLR
5' - 0"
1A-250
/2
C
C
C
B
12' - 5"
/2
1A-246
1A-254
169169 100 101101
/4
" SERVICE
CORRIDOR
C1A1
FE-1
FE-1
CL
CL
B
B6
B6
CCC
C6
GAS CLOSET
1A-256
1A-256.1
1A-256.2
F2
129129
B6
4' - 6"
TYP
3' - 0"
TYP
3' - 0"
3' - 4" 1' - 6"
10' - 0"
13' - 1 1/4"
A-621
10' - 0"
16' - 0"
CL
CL
FE-1
FE-1
A-621
1' - 11" 34' - 7"
WORK NOTES GENERAL NOTES
7. REPAIR ALL EXISTING SURFACES WHERE EXISTING MOUNTED ITEMS HAVE BEEN
REMOVED, MATCH EXISTING ADJACENT SURFACE FINISH.
8. PROVIDE BLOCKING IN WALLS FOR ALL MOUNTED ITEMS.
9. AT LOCATIONS WHERE EXISTING WALLS ARE REMOVED, REPAIR REMAINING
WALLS ADJACENT TO THE DEMO AREA, MATCH ADJACENT SURFACE FINISH.
10. COORDINATE CONSTRUCTION ACTIVITIES WITH CONTINUOUS BUILDING
OCCUPANCY. MAINTAIN REQUIRED EXIT AND LIFE SAFETY SYSTEMS. MAINTAIN
OPERATIONAL RESTROOM FACILITIES. PROVIDE TEMPORARY PARTITIONS TO
SEPARATE CONSTRUCTION ACTIVITIES FROM OCCUPIED AREAS AND EGRESS. ALLOW
FOR DELIVERIES AND EMERGENCY ACCESS.
11. PROVIDE 48" TALL POWDER-COATED STAINLESS STEEL CORNER GUARDS AT ALL
OUTSIDE GB WALL CORNERS IN THE LAB CORRIDORS.
12. INTERIOR DIMENSIONS ARE TO FINISHED FACE OF PARTITION, U.O.N.
13. ALL CHANGES IN FLOOR MATERIAL AT DOORS OCCUR AT INSIDE CORNER OF
THE STOP AT THE DOOR SIDE
1. FIELD VERIFY ALL EXISTING CONDITIONS. NOTIFY ARCHITECT PRIOR TO
START OF WORK IF ANY EXISTING CONDITIONS AFFECT ANY NEW WORK
SHOWN. THIS ALSO APPLIES TO WORK SHOWN ON STRUCTURAL,
LABORATORY, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION
DRAWINGS.
2. ALL PARTITIONS, NEW INFILL AND EXTENSIONS AT EXISTING WALLS SHALL BE
PARTITION TYPE 'B', UON., MATCH THICKNESS OF EXISTING PARTITION AT INFILL
AND EXTENSIONS. EXTEND PARTITIONS FULL HEIGHT TO BOTTOM OF DECK
ABOVE, UON.
3. REFERENCE CODE PLANS FOR LOCATIONS OF FIRE RATED WALLS.
4. REFERENCE LABORATORY PLANS FOR LAB INFORMATION.
5. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS AND NOTIFY ARCHITECT
OF ANY DISCREPANCIES BETWEEN ACTUAL FIELD CONDITIONS AND INFORMATION
SHOWN IN THESE DOCUMENTS PRIOR TO START OF ANY WORK.
6. AT LOCATIONS WHERE EXISTING FLOORS, WALLS, OR CEILINGS ARE OPENED
FOR NEW WORK, REPAIR TO MATCH ADJACENT CONSTRUCTION AND FINISH.
LEGEND
EXISTING WALLS
NEW DOORS
MATCHLINE
NEW PARTITIONS, COLUMN
WRAPS, AND FUR OUTS
EXISTING DOORS
PROJECT BOUNDARY
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
GENERAL SERVICES ADMINISTRATION
ROCKY MOUNTAIN REGION
MOUNTAIN PLAINS SERVICE CENTER (8PSMP)
P.O. BOX 25546
BUILDING 41
DENVER FEDERAL CENTER
DENVER, CO 80225
303-236-2854
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211
Telephone: 303-294-9448
FAX: 303-294-0762
Architect
Iron Horse Architects
475 17th Street, Suite 720
Denver, CO, 80202
Telephone: 720-855-7572
Laboratory Planning
Martin Martin
12499 West Colfax Avenue
Lakewood, CO, 80215
Telephone: 303-431-6100
Structural Engineering
Farnsworth Group
4755 Forge Road, Suite 150
Colorado Springs, CO, 80907
Telephone: 303-692-8838
Mechanical Engineering
MEP Engineering
6402 South Troy Circle, Suite 100
Centennial, CO, 80111-6439
Telephone: 303-936-1633
Electrical Engineering
Jensen Hughes, Inc
520 Courtney Way, Suite A
Lafayette, CO, 80026
Telephone: 303-439-0485
Fire Protection
Advanced Consulting Engineers, Inc
3900 S. Wadsworth Blvd., Suite 595
Lakewood, CO, 80235
Telephone: 720-981-4150
Code Consultant
1A
1B
1C
1D
PLAN KEY
Parametrix, Inc
7186 South Highland Drive
Salt Lake City, UT, 84121
Telephone: 801-733-5900
Cost Estimator
GSA PROJECT NO. N10565510
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
Seal
Do not remove this notice.
Properly destroy or return document when no longer needed.
/2
/2
:1 :5
P
M
A-101A
LEVEL 1 FLOOR PLAN - AREA 1A
2009121.11
JF
CO
DP
EPA BUILDING 25
CO-LOCATION PROJECT
DENVER FEDERAL CENTER
BUILDING 25, LAKEWOOD, CO
15 APRIL 2016100% Construction Documents
4' 16'2' 8' A-101A 1/8" = 1'-0"
1LEVEL 1 FLOOR PLAN - AREA 1A
160 CONFRIM CLOSET DIMENSIONS WITH
NEW CHILLER UNIT, OFCI
169 FIRE SEALANT AT BASE OF EXISTING
WALL, BS, FOR 1 HR RATED PARTITION,
RE: CODE PLANS; INSTALL NEW WALL
BASE AS SCHEDULED
178 SAW CUT SLAB AT DASHED LINES FOR
VIBRATION SEPARATION, RE: STRUC
101 NO ARCHITECTURAL WORK AT THIS
SPACE EXCEPT REQUIRED REPAIRS
RESULTING FROM OTHER WORK THAT
MAY BE REQUIRED AND UON
(MECHANICAL, ELECTRICAL, FIRE
PROTECTION, ETC.)
121 NEW 6" CONCRETE HOUSEKEEPING PAD
AT HATCHED AREA, RE: MECH/STRUC
129 ALIGN
130 NEW PARTITION INFILL SIMILAR TO
PARTITION TO TYPE B - MATCH EXISTING
ADJACENT WALL THICKNESS, PAINT AND
FINISH OF ADJACENT WALL SURFACE AT
BOTH SIDES
142 CENTER DOORS BETWEEN SIDE WALLS
151 PATCH AND FILL EXISTING SLOPED
FLOOR, AREA TO BE FLUSH WITH TOP OF
ADJACENT SLAB, TYP., RE: STRUC
156 PATCH AND FILL EXISTING VAULT, AREA
TO BE FLUSH WITH TOP OF ADJACENT
SLAB, RE: STRUC
TRUE NORTH
Addendum 05 30 SEPT 2016
KK
LF-304
LF-304
LF-3047
CW CW CW CW CW
CW CW CW CW CW
TYP
R8 CLLE
1A-250
LAB CORRIDOR
C1A2
E Q
E Q
5'-0"
S-04
1' - 6"
ESEW-1
1' - 9" 6" 4' - 6" 6" 4' - 6" 6" 4' - 6" 6" 4' - 6" 6"
1' - 9" 6" 4' - 6" 6" 4' - 6" 6" 4' - 6" 6" 4' - 6" 6"
TYP.
E Q
E Q
1' - 4"
TYP
Level 1 100' - 2"
CW CW CW CW CWCWCWCWCWCW
LB6-36 LB6-36 LB6-36 LB2-36 LB6-36 LB2-36 LB6-36 LB2-36VN2-48
ALIGN
Level 1 100' - 2"
CW CW CW CW CWCW CW CW CWCW
LB2-36 LB6-36 LB2-36 LB6-36 LB2-36 LB6-36 LB2-36 LB6-36
ALIGN
WR-1
Level 1 100' - 2"
LB2-36 LB6-36 LB2-36 LB6-36 LB2-36LB2-36
Level 1
100' - 2"LB2-36 LB6-36 LB2-36 LB6-36 LB6-36 LB6-36
Level 1
100' - 2"LS1-36 LB2-36
KK
RC-04 CH-01
CH-02
SR-01
R8 CLLE
1A-250
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
GENERAL SERVICES ADMINISTRATION
ROCKY MOUNTAIN REGION
MOUNTAIN PLAINS SERVICE CENTER (8PSMP)
P.O. BOX 25546
BUILDING 41
DENVER FEDERAL CENTER
DENVER, CO 80225
303-236-2854
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211 Telephone: 303-294-9448
FAX: 303-294-0762
Architect
Iron Horse Architects 475 17th Street, Suite 720
Denver, CO, 80202 Telephone: 720-855-7572
Laboratory Planning
Martin Martin 12499 West Colfax Avenue
Lakewood, CO, 80215 Telephone: 303-431-6100
Structural Engineering
Farnsworth Group 4755 Forge Road, Suite 150
Colorado Springs, CO, 80907 Telephone: 303-692-8838
Mechanical Engineering
MEP Engineering 6402 South Troy Circle, Suite 100
Centennial, CO, 80111-6439 Telephone: 303-936-1633
Electrical Engineering
Jensen Hughes Associates, Inc 520 Courtney Way, Suite A
Lafayette, CO, 80026 Telephone: 303-439-0485
Fire Protection
Advanced Consulting Engineers, Inc 3900 S. Wadsworth Blvd., Suite 595
Lakewood, CO, 80235 Telephone: 720-981-4150
Code Consultant
1A
1B
1C
1D
PLAN KEY
Parametrix, Inc 7186 South Highland Drive
Salt Lake City, UT, 84121 Telephone: 801-733-5900
Cost Estimator
GSA PROJECT NO. N10565510
Seal
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
Do not remove this notice.
Properly destroy or return document when no longer needed.
100% Construction Documents 15 APRIL 2016
No.
/2
/2
:5 :0
P
M
LF-304
ENLARGED LAB PLAN - 1A-250
201505.000
RG
VD
VD
EPA BUILDING 25
CO-LOCATION PROJECT
DENVER FEDERAL CENTER
BUILDING 25, LAKEWOOD, CO
1' 2'0' 8'
TRUE NORTH
4'4'
1/4" = 1'-0"LF-304
ENLARGED LAB PLAN - 1A-250 - R8 CLLE1
1' 2'0' 8'4'4'
1/4" = 1'-0"LF-304
INTERIOR ELEVATION - 1A-250 - EAST6
1' 2'0' 8'4'4'
1/4" = 1'-0"LF-304
INTERIOR ELEVATION - 1A-250 - WEST3
1' 2'0' 8'4'4'
1/4" = 1'-0"LF-304
INTERIOR ELEVATION - 1A-250 - EAST 24
1' 2'0' 8'4'4'
1/4" = 1'-0"LF-304
INTERIOR ELEVATION - 1A-250 - WEST 25
LAB KEYNOTES
1 NEW LABORATORY CASEWORK, RE: ELEVATION FOR
TYPE
2 NEW FLOOR DRAIN, RE: PLUMB
3 NEW FLAMMABLE STORAGE CABINET,RE: SPECS
4 NEW VENTED STORAGE CABINET, RE: ELEVATION FOR
TYPE
5 NEW ADJUSTABLE HEIGHT TABLE FRAME
6 EXTENTS OF LABORATORY PLANNING SCOPE TO
INCLUDE FUME HOOD RETROFIT ONLY - AS NOTED IN
PLANS
7 REQUIRED ADA CLEARANCE
8 PROVIDE GAS CYLINDER MANIFOLD AT WALL, RE: SPECS
9 NEW CANOPY HOOD EXHAUST - 18GA 316 STAINLESS
STEEL. GRIND AND POLISH ALL WELDS. SUPPORT FROM
STRUCTURE AS REQUIRED. PROVIDE GUTTERS WITH
HEMMED EDGES. RE: MECH FOR DUCT SIZE AND
CONNECTION.
10 NEW OVERHEAD SERVICE CARRIER @ 7'-0" AFF, RE:
SPECS
11 VENTED CABINET - OFCI
12 PROVIDE NEW WALL MOUNTED GAS CYLINDER
RESTRAINT, RE: SPECS
13 EXISTING TO REMAIN
14 REPLACE/ADD (AS REQUIRED) SELF CLOSING
MECHANISM, PER MANUFACTURERS DETAILS TO
COMPLY WITH 2015 IFC 5704.3.2.1.3, RE: SPECIFICATIONS
15 EXTENTS OF LABORATORY PLANNING SCOPE TO
INCLUDE FUME HOOD RETROFIT AND EYE WASH SAFETY
SHOWER COMBINATION UNIT ONLY - AS NOTED IN PLANS
16 TIE INTO EXISTING VENTING ABOVE, RE: MECH
17 NEW TALL CABINET, RE: ELEVATION FOR SIZE AND TYPE
18 NO LABORATORY PLANNING SCOPE WITHIN THIS ROOM
19 EXTENTS OF LABORATORY PLANNING SCOPE TO
INCLUDE REPLACEMENT OF EYE WASH & SAFETY
SHOWER COMBINATION UNIT ONLY - AS NOTED IN PLANS
20 NEW STORAGE SHELVING - SECURE AS REQUIRED, RE:
SPECS
22 NEW CHAIN LINK ENCLOSURE - RE: ARCH
25 NEW SHOWER & EYE WASH - HAWS 8309WC OR SIM
26 NEW FLEXIBLE SNORKEL ARM (ABOVE), RE: SPECS - RE:
MECH FOR CONTINUATION
27 PROVIDE ACID WASTE, RE: PLUMB
29 STORAGE RACK - OFOI
30 GAS CYLINDER, OFOI
32 TABLE FRAME - OFOI, TYP, UNO
36 BALANCE TABLE - OFOI
37 UNDER COUNTER TASK LIGHTING, TYP, RE: ELEC
38 NEW WATER PURIFICATION UNIT AT SINK
39 PRO UNIT AT SINK - OFOI
40 NEW CORROSIVE STORAGE CABINET, VENT AS
REQUIRED (RE: MECH.)
41 FLAMMABLE STORAGE CABINET - OFCI
42 SALVAGE & REUSE CASEWORK
44 SALVAGE & REUSE CURRENT QUANTITIES OF
CASEWORK
46 EXISTING OVERHEAD EXHAUST TO REMAIN
47 NEW PVC AIR DELIVERY SYSTEM (ABOVE), RE:
ELEVATION FOR HEIGHT & SPIGOT LOCATIONS
48 MOBILE LAB CART - OFOI
49 EXISTING BIOSAFETY CABINET, RELOCATED
50 EXISTING EXHAUST TO BE REPLACED
52 PROVIDE NEW FLEXIBLE EXHAUST, RE: MECH
53 PROVIDE NEW RIGID VENT PIPE, RE: MECH
56 NEW 4" PVC AIR EXHAUST SYSTEM (ABOVE) - OFOI
57 EXISTING SAFETY SHOWER AND EYE WASH TO BE
REPLACED, RE: SPECS
58 VENTED CABINET RELOCATED FROM GAS CLOSET
1C-415
59 SPECIALTY GAS TURRENT, RE: MECH PLANS FOR
SOURCE LOCATION
60 WATER SPIGOT , RE: PLUMBING
61 COOLER CONDENSING UNITS STACK MOUNTED TO THIS
WALL. COOLER MANUFACTURER TO PROVIDE RACK -
COORDINATE WALL BLOCKING
62 REFER TO PLUMBING DRAWINGS FOR PIPE CONNECTION
AND VAVLE TYPE
*** NOTE: NOT ALL KEYNOTES ARE USED ON EVERY SHEET
1' 2'0' 8'4'4'
1/4" = 1'-0"LF-304
INTERIOR ELEVATION - 1A-250 - SOUTH7
1A-250 - EQUIPMENT SCHEDULE
EQUIPMENT DESCRIPTION DIMENSIONS ELECTRICAL
Cupsink Data Comments System
Grouping Equip Mark Property # Furn/Inst Equip Name Model MFR Room Origin Width Depth Height
Normal Power
Standby Power UPS Light
CH-01 R8 Chiller 3' - 11" 2' - 4 3/4" 4' - 3 5/8" Yes No No
CH-02 R8 Chiller HX-500 NESLAB 3' - 10" 2' - 4 3/4" 4' - 3 5/8" Yes No No
RC-04 E10263 R8 Refrigerated Circulator CFT-33 Neslab 1' - 2 3/4" 1' - 10" 2' - 0 1/2" Yes No No
SR-01 E10264 R8 Solvent Recycler M490 B/R Instruments D128 3' - 2" 2' - 0" 7' - 0" Yes No No
1' 2'0' 8'
TRUE NORTH
4'4'
1/4" = 1'-0"LF-304
ENLARGED LAB PLAN - 1A-250 - R8 CLLE EQUIPMENT2
3 Addendum 02 05 AUG 2016
4 Addendum 03 30 SEPT 2016
Addendum 05 30 SEPT 2016Addendum 05
PHENOLIC RESIN
COUNTERTOP, TYP
FACE OF BASE CABINET
3/16" RADIUS DRIP
GROOVE, TYP
1"
1/2"
/4
CHAMFER EDGE, TYP
SECTION @ BRACKET (AS REQUIRED) SECTION @ AIR SPIGOT (2'-0" O.C.)
2" DIA. PVC PIPE, RE: ENALRGED LAB
PLAN AND ELEVATIONS FOR EXTENTS
WALL MOUNTED PIPE
BRACKET - SPACING AS
REQUIRED
PVC REDUCING TEE
AXONOMETRIC (N.T.S.)
PVC REDUCING TEE
2" PVC PIPE
WALL MOUNTED PIPE
BRACKET - SPACING AS
REQUIRED. PROVIDE
CONCEALED BLOCKING.
AIR SPIGOT, RE: SPECS
EXTEND FLOOR FINISH, PROVIDED UNDER DIV.
9,WALL TO WALL UNDER CASEWORK
BASE, PROVIDED UNDER DIV. 9, AT CABINETS
AND KNEE SPACES
BASE CABINET WHERE INDICATED ON
LABORATORY CASEWORK PLANS AND
ELEVATIONS
3/4" PHENOLIC RESIN BENCHTOP
LAB TURRET, BEYOND - SEE LABORATORY
PLANS & ELEVATIONS FOR LOCATION AND
TYPE
WIREMOLD, SEE LABORATORY ELEVATIONS
FOR EXTENT
SHELF RETAINING CLIP STRIP, TYP
ADJUSTABLE METAL SHELF UNIT WITH
3-PRONG CONNECTION TO VERTICAL FRAME,
REFER TO ELEVATIONS FOR WIDTH OF EACH UNIT.
CORE FRAME SYSTEM, BY MFR.
UNDERSHELF LIGHT, RE: ELECTRICAL
DRAWINGS
2' - 5" 1' - 0" 2' - 5"
STRUCTURAL FRAMING/BRACING, AS
REQUIRED
DUCTWORK - COORDINATE LOCATION,
SIZE, CONNECTIONS, ETC.
SECTION
7'-0" A.F.F
TYP, MATCH
EXISTING WHERE
APPLICABLE
7'-0" A.F.F
TYP, MATCH
EXISTING WHERE
APPLICABLE
ELEVATION
UNISTRUT, BY
CASEWORK MFR.
CEILING, RE:
ARCH DRAWINGS
EXISTING
STRUCTURE, VIF.
WIREMOLD, BY
CASEWORK MFR.
1' - 7"
MATCH EXISTING,
WHERE APPLICABLE
RE: ENLARGED LAB PLANS
BRACE AS REQ'D -
BOTH DIRECTIONS
CABLE TRAY, BY
CASEWORK MFR.
CEILING
PENETRATION
COLLAR, BY
CASEWORK MFR.
Project Number:
Drawn By:
Reviewed By:
Approved By:
Issue Date
GENERAL SERVICES ADMINISTRATION
ROCKY MOUNTAIN REGION
MOUNTAIN PLAINS SERVICE CENTER (8PSMP)
P.O. BOX 25546
BUILDING 41
DENVER FEDERAL CENTER
DENVER, CO 80225
303-236-2854
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211 Telephone: 303-294-9448
FAX: 303-294-0762
Architect
Iron Horse Architects 475 17th Street, Suite 720
Denver, CO, 80202 Telephone: 720-855-7572
Laboratory Planning
Martin Martin 12499 West Colfax Avenue
Lakewood, CO, 80215 Telephone: 303-431-6100
Structural Engineering
Farnsworth Group 4755 Forge Road, Suite 150
Colorado Springs, CO, 80907 Telephone: 303-692-8838
Mechanical Engineering
MEP Engineering 6402 South Troy Circle, Suite 100
Centennial, CO, 80111-6439 Telephone: 303-936-1633
Electrical Engineering
Jensen Hughes Associates, Inc 520 Courtney Way, Suite A
Lafayette, CO, 80026 Telephone: 303-439-0485
Fire Protection
Advanced Consulting Engineers, Inc 3900 S. Wadsworth Blvd., Suite 595
Lakewood, CO, 80235 Telephone: 720-981-4150
Code Consultant
Parametrix, Inc 7186 South Highland Drive
Salt Lake City, UT, 84121 Telephone: 801-733-5900
Cost Estimator
GSA PROJECT NO. N10565510
Seal
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF THE UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
Do not remove this notice.
Properly destroy or return document when no longer needed.
100% Construction Documents 15 APRIL 2016
No.
/2
/2
:5 :0
P
M
LF-801
DETAILS
201505.000
Author
Checker
Approver
EPA BUILDING 25
CO-LOCATION PROJECT
DENVER FEDERAL CENTER
BUILDING 25, LAKEWOOD, CO
12" = 1'-0"LF-801
TYPICAL DRIP EDGE SECTION2
6" = 1'-0"LF-801
PVC AIR DELIVER SYSTEM3
3/4" = 1'-0"LF-801
VENTED ISLAND - 1A-270 - R8 ORGANIC PREP5
1 1/2" = 1'-0"LF-801
Overhead Service Carrier6
1 Addendum 01 27 MAY 2016
4 Addendum 03 30 SEPT 2016
Addendum 05
| AD05 Specifications.pdf |
| 23 34 16 - Centrifugal HVAC Fans |
| 23 36 05 - Venturi Air Valves |
| 23 81 01 - CABINET, DUCT AND UNIT HEATERS |
| 23 82 16 - Air Coils |
| 23 82 19 - FAN COIL UNITS AD05 |
| AD05 Drawings.pdf |
| Sheets |
| A-101A - LEVEL 1 FLOOR PLAN - AREA 1A |