Physical Access Control System (PACS) Requirement
HHS / OMHA
20140702
Objective
The objective of this task is to design, install, and maintain the onsite PACS infrastructure, which will operate with the LENEL OnGuard 2013 (version 6.6.287) system already in operation at HHS.
No security assessment is required. This has already been completed by HHS.
OMHA will specify the required security controls and their locations. However, OMHA does not have the expertise to develop a design document, comprehensive bill of materials, wiring diagrams, etc.
Components
All components subject to evaluation by the Federal Identity, Credential, and Access Management (FICAM) Program (http://www.idmanagement.gov/about-fips-201-ep-program) must appear on the FIPS 201 Approved Product List (http://www.idmanagement.gov/approved-products-list).
All card readers shall support both contactless PIV card presentation and personal identification number (PIN). The only currently approved reader with this capability is the HID RPK40 Keypad Reader.
OMHA will provide product data sheets for a number of components (some may not be required for this project) that were known to be approved and/or interoperable with the LENEL OnGuard 2013 system as of 2/27/2014. This data is informational and the use of these components is not mandatory. Should the vendor choose to use any of these components, the vendor is responsible for verifying current approval.
Installation and Maintenance
The installation vendor shall have experience with Federal requirements related to FIPS-201, HSPD-12, and FICAM. For example, the vendor will have to know if/when the PIN should be validated at the card reader or the access control panel.
A list of known qualified HSPD-12 service providers can be found at http://www.idmanagement.gov/qualified-hspd-12-service-providers).
Installation bids shall include testing, training, and capabilities/SLAs for in-warranty and out of warranty emergency service and regular maintenance for all onsite components including wiring.
Deliverables
Onsite system design Wiring diagram(s) Identification of facility requirements such as power taps, LAN connections, etc.
Comprehensive bill of materials including but not limited to:
Major system components Minor system components Cabling/wiring Software and licenses required and recommended for use onsite Non-networked computers (all networked computers to be supplied by HHS) http://www.idmanagement.gov/about-fips-201-ep-program http://www.idmanagement.gov/approved-products-list http://www.idmanagement.gov/qualified-hspd-12-service-providers http://www.idmanagement.gov/qualified-hspd-12-service-providers
Tab 1 Index
Tab 2 Access Control
1 Lenel SWC-32ES OnGuard Software
2 Lenel LNL-2200 Intelligent Dual Reader Controller
3 Lenel LNL-1320 Dual Reader Interface Module
4 Lenel LNL-AL600ULX-4CB6 Enclosure with Power Supply
5 Lenel CTX-6 Hardware Enclosure
6 Bosch DS-161 PIR Request to Exit Sensor
7 GE 1078-M Door Contact
8 Altronix AL600ULACMCB Lock Power Supply
9 HID 6136CKN000700G30.0 iCLASS RPK40 MultiCLASS Reader
10 Dortronics 7286-PT5-MP23 Door Prop Alarm
11 Dortronics 5216-MP23DA/RxE1 Push Button Switch
12 Dell Power Edge T110 II Tower Server
13 Dell OptiPlex 3010
Tab 3 Intercom
1 Aiphone JK-1MED Master Station
2 Aiphone JK-DA Door Sub-station
Tab 4 Video
1 Axis 0443-004 P5544 PTZ Dome Camera
2 Dell Power Edge R720xd Network Video Server
Tab 5 Intrusion
1 Bosch 9412GV4 Control Panel
2 Bosch D1255 Keypad
3 Bosch DS9360 Motion Detector
Index frank.brindisi Rectangle frank.brindisi Rectangle
PERPETUAL INNOVATION
Unsurpassed Integrated Access & Video Security Performance
With over 20,000 installations in over 90 countries and a track record of performance that clearly leads the industry, OnGuard is the PROVEN smarter security solution. Today, we’re advancing our benchmark uni�ed experience for unsurpassed integrated access control and video management. 92 of the Fortune 100 companies utilize Lenel® products, a testament to our robust dependability and continuous innovation.
In terms of OPEN architecture, Lenel pioneered the “open” concept for security solutions. We initiated the Open Access Alliance Program in 1998 because we knew then, as we know now, that open systems deliver greater value. Today we continue to advance our capabilities to allow you to achieve ultimate integration �exibility in every aspect – from video management to con�guration from a single UI, operating systems to databases, hardware to IP networks and beyond. No one provides a truly uni�ed experience like Lenel.
Which gets us to the power of CHOICE – delivering the versatility that only hardware and software independence can offer. It’s ease of integration with more devices, �exibility for the future, and scalability that grows with your needs. You always have more options to integrate cutting-edge, third party products into your OnGuard system.
OnGuard Integrated Security Solutions The Intelligent Choice for Today and Tomorrow
With over 20,000 installations in over 90 countries and a track record of performance that clearly leads the industry, OnGuard is the PROVEN smarter security solution. Today, we’re advancing our benchmark uni�ed experience for unsurpassed integrated access control and video management. 92 of the Fortune 100 companies utilize Lenel® products, a testament to our robust dependability and continuous innovation.
In terms of OPEN architecture, Lenel pioneered the “open” concept for security solutions. We initiated the Open Access Alliance Program in 1998 because we knew then, as we know now, that open systems deliver greater value. Today we continue to advance our capabilities to allow you to achieve ultimate integration �exibility in every aspect – from video management to con�guration from a single UI, operating systems to databases, hardware to IP networks and beyond. No one provides a truly uni�ed experience like Lenel.
Which gets us to the power of CHOICE – delivering the versatility that only hardware and software independence can offer. It’s ease of integration with more devices, �exibility for the future, and scalability that grows with your needs. You always have more options to integrate cutting-edge, third party products into your OnGuard system.
Just as your needs are always evolving, Lenel and
OnGuard also advance continuously, building and supporting the most innovative and tightly integrated access/video software security solutions in the world, empowering our customers to better protect and manage their people, property and assets. And with customers ranging from small businesses monitoring four doors to global enterprise installations spread across several continents, we truly understand the value of �exible scalability.
The Original Information Management Solution
Today’s providers talk about how security data, once contextualized and analyzed, can become the information needed to empower better business decisions. OnGuard’s history of providing valuable ways to optimize your data continues to evolve powerfully.
• OnGuard allows you to aggregate, visualize and share disparate data from diverse aspects of your system seamlessly and coherently – no other solution provides as rich or detailed an environment.
• No competitive solution can deliver the breadth and depth of access/video integration OnGuard offers
• OnGuard now provides enhanced intrusion-based features including local I/O area alarm state, burglary veri�ed alarm support and work late support.
• With OnGuard’s truly integrated approach, you can employ
IP video as a powerful, proactive tool to complement its after-the-fact and analysis advantages.
• With OnGuard, you can seamlessly synthesize data from access control, video and other sensors.
• OnGuard offers a single uni�ed platform, single database server, and single user interface.
• Know every aspect and see all the data for any event in real time, from alarms to video.
Best-of-Breed Integration and Functionality
It’s still true: no other system gives you as much power and
�exibility to manage everything more ef�ciently than
OnGuard, with full support and functionality for every level of complexity, including –
• Prior/legacy capital investments
• Acquisitions and mergers of different systems
• Contracts and standards in force
• Specialized product capabilities
• Almost any hardware or software component you wish to add, thanks to our extensive APIs and SDKs.
• Varying volumes of cardholders, access control readers, alarm inputs/outputs, client workstations, and digital video cameras.
Smarter, Seamless Integration for Today and Tomorrow
Next-generation capabilities continue to be added to
OnGuard, delivering the power of reliability that answers today’s security and integrated access/video demands. And now, our set-up assistant quickly and automatically guides you through faster installations, reducing “clicks” by 60%.
OnGuard: Continuously Evolving
Ultimate Security Suite Components
The most comprehensive security integration platform offers applications relevant to every major industry, tools for integration with any critical business application, and the most extensive device support available anywhere.
OnGuard is available in a variety of languages, including
Spanish, French, Chinese, Arabic, German and Hebrew, among others.
OnGuard Enterprise
The industry’s leading multi-server, synchronized database solution, ideal for enterprises spread across multiple geographies.
OnGuard Access
Advanced access control application including a feature-rich alarm monitoring module, IP-enabled controllers to provide appropriate door security everywhere.
OnGuard Area Access Manager
Decentralize administration of access permissions to the department level and directly control cardholder access to speci�c physical areas.
OnGuard ID CredentialCenter
The one-stop solution for enrolling and producing ID credentials – from badge design to assigning physical access levels.
OnGuard Visitor
Dependable, cost-effective, web-enabled visitor management to manage and track visitors in all facilities via standard desktop technology.
OnGuard Integration Toolkit
Develop interfaces to any business information system and exchange critical data between OnGuard and external systems.
OnGuard Fire & Intrusion
Extend your OnGuard solution to manage events from �re and intrusion panels, as well as central station receivers.
It’s the expert support and services you need, delivered where, when and how you need them, including –
A diverse portfolio of services that enhance the planning, deployment and lifecycle support of your OnGuard security and video system.
• Professional Engineering Services
• Custom Solutions
• Remote Managed Services
• Embedded Services
Professional instructors responsible for managing course development, assessments and certi�cation programs design to provide our VAR’s and customers with the knowledge and understanding of all Lenel security related products and hardware platforms.
Experienced technical support staff that provides the highest level of product support and customer satisfaction available at all hours of the day.
• Technical Support
• Software Upgrade and Support
Lenel Services
OnGuard VideoManager
The native video client for OnGuard, OnGuard VideoManager provides event-driven video viewing and integrated alarm management.
OnGuard IntelligentVideo
Bene�t from advanced analytics capabilities for everyday monitoring. Con�gure to detect incident or circumstances not readily obvious to the untrained eye. Available free-of-charge for recorded video or licensed for live video.
Lenel provides customers an unsurpassed range of integrated access and video security options. Choose from three fully-featured video management software solutions, all integrated with OnGuard. Prism™, OnGuard
VideoManager and SkyPoint offer a variety of options from standalone video surveillance to multi-site, integrated command-and-control with advanced analytics capabilities.
These offerings meet the needs of the widest range of customers. The Lenel NVR recording platform is the foundation of the OnGuard and Prism video solutions that allows migration continuity as customer's needs evolve.
The SkyPoint IP-video and security platform delivers video management for streaming, recording and management of an unlimited number of cameras at multiple sites. The latest version adds alerts and video analysis capabilities formerly available only on full, enterprise-scale solutions.
The native video client for OnGuard, OnGuard
VideoManager provides event-driven video viewing and integrated alarm management.
Bene�t from advanced analytics capabilities for everyday monitoring. Con�gure to detect incident or circumstances not readily obvious to the untrained eye. Available free-of-charge for recorded video or licensed for live video.
More Choices For Seamless, Integrated Video
IntelligentVideo
VideoManager
6.62013
Lenel’s Prism is an open IP video management solution based on an advanced, intuitive and operator-friendly user interface.
Built using the latest IT and video surveillance industry standards, Prism integrates seamlessly with OnGuard delivering a single point-of-device con�guration, video push from
OnGuard to Prism and Prism video callup on Alarm. Prism provides a feature-rich set of tools that maximize the use of the video workspace, enabling users to ef�ciently manage surveillance with a range of user actions (real-time, forensic, and event-driven) and improving the timeliness and accuracy of operator response. Bene�ts include fast, high-quality user decisions, reduced training costs, more ef�cient use of personnel and more.
• Single point-of-device con�guration, event/alarm monitoring and system administration
• Uni�ed live and recorded video viewing
• Event-driven monitoring
• Multiple investigation tools
• Work�ow/case management tool
Lenel NVR is a common recording platform that underpins both Prism and OnGuard VideoManager. Key features include fast video retrieval response times, enhanced H.264 and HD support, adoption of industry-standard RTP/RTSP, the ability to run in virtual environments and support of hundreds of 3rd party camera models.
7.0
7.07.0
(866) 788-5095
Speci�cations subject to change without notice.
© 2013 Lenel Systems International, Inc. All rights reserved. Lenel and OnGuard are registered trademarks of Lenel Systems International, Inc. All other trademarks and copyrights are the property of their respective owners.
OG13_BR_030413
lenel.com/OnGuard
A ccess C ontrol
LNL-2220
The LNL-2220 Intelligent Dual Reader Controller (IDRC) by Lenel provides a single board solution for interfacing one or two doors to an OnGuard system. In addition, other I/O and reader interface modules can be added on the LNL-2220’s downstream port to expand its capabilities. The LNL-2220 revolutionizes access control system architecture by allowing Ethernet connection directly from an entry location to the OnGuard server, while still providing the security, functionality, and modularity of Lenel’s proven hardware platform. The LNL-2220 is scalable for any access control application, from the most basic to the most sophisticated. In the event of communication loss, the LNL-2220 allows nearly all local functionality to continue unimpaired until the server connection is restored.
Utilizing its native Ethernet communications and an advanced 32-bit processor, the LNL-2220 can communicate upstream to the host computer through its Ethernet port (with a throughput up to eight times greater than the fastest serial connections), or at up to 115.2 Kbps using RS-232 communication directly or through an external dial-up modem. The LNL-2220 can store up to 250,000 cardholders in non-volatile flash memory, and supports selective download for larger cardholder databases. The downstream RS-485 two-wire port can be used to connect up to 32 devices (maximum 64 doors).
Two on-board reader ports support Data1/Data0, Clock/Data, Bioscrypt RS-485 readers and the bidirectional RS-485 Open Supervised Device Protocol (OSDP) communications. Each LNL-2220 supports up to eight different card formats. The LNL-2220 includes eight inputs that support normally open, normally closed, supervised, and unsupervised circuits. In addition, four output relays support fail-safe or fail-secure operation.
Features and Functionality Controller Functionality
■ On-board Ethernet 10/100Base-T port provides up to 8 times greater throughput than serial-to-Ethernet converters. DHCP and fixed IP addressing supported.
■ DNS device naming through DHCP extended commands
■ 6 MB of available on-board, non-volatile flash memory
■ Battery-backed, non-volatile storage of 50,000 events
■ Firmware stored in flash memory, background download of firmware updates supported
■ Supports up to 16 different formats (8 card formats and 8 asset formats)
■ Biometric template storage support for Schlage Recognition Systems®, Bioscrypt®, and Identix®.
■ Direct connection of Bioscrypt RS-485 devices
■ Enhanced anti-passback capabilities
■ Up to 32,000 access level permissions
■ 255 holidays with grouping, 255 timezones, each with 6 intervals
■ Elevator control support for up to 128 floors
■ Individual extended held open and strike times (ADA required)
■ Up to 9-digit user PIN codes
■ 20 status LEDs
■ 2 dedicated inputs for tamper and power failure status
■ 12 or 24 VDC input power
■ Advanced Encryption Standard (AES) 128-bit algorithm for communications
Reader Interface Functionality
■ Supports Data1/Data0, Clock/Data and Lenel OSDP-compatible RS-485 readers and keypads
■ 4 Form-C relay outputs, 5 A at 30 VDC
■ Door contact supervision (open/closed) and REX push-button monitor for each door
■ Strike control and auxiliary output for each door
■ Bicolor reader status LED support plus beeper control, or 2-wire LED support
■ On-board regulator allows 12 VDC reader power from 24 VDC power source
Intelligent Dual Reader Controller cc es s
C on tr ol
LNL-2220
LNL-1300
Up to 32 Single Reader Interface Modules
LNL-2220
Intelligent
System Controller
OnGuard Security Server
CORPORATE HEADQUARTERS LOCAL AREA NETWORK (TCP/IP)
LNL-1100
Input Control Module
(Up to 16 Inputs per
LNL-1100)
LNL-1200
Output Control Module
(Up to 16 Outputs per
LNL-1200)
RS-485 multidrop
Controller Options
LNL-2220
Dial-Up Modem
LNL-56KEXT
LNL-DC336K
Specifications Primary Power (DC or AC)
DC input:
Event Memory and Clock Backup Communication Ports
Primary (Ethernet) Port:
Alternate Upstream Port 1:
Downstream Port 2:
Inputs Tamper and Power Fail Monitors:
Door position, REX, and AUX:
Outputs Relay outputs:
Reader Power DC output:
Reader Port Compatibility
Environmental Temperature:
Humidity:
Mechanical
Dimensions:
Weight:
Approvals
6 MB On-board flash memory available for cardholder & asset database, 50,000 event battery backed RAM for event log
56 K external modem with cables 12 VDC-powered/33.6 K external modem
* The LNL-2220 is for use in low voltage, power-limited, class 2 circuits only.
12 or 24 VDC ± 15%. 500 mA maximum 3 V lithium, type BR2325, BR2330, CR2330
10/100Base-T Ethernet high-speed port RS-232 9600 to 115.2 Kbps async RS-485 (2-wire) 9600 to 38.4 Kbps async
Unsupervised, dedicated 8, each programmable as normally open or normally closed, supervised or unsupervised circuits
4 Form-C 5 A at 30 VDC relay outputs: 2 strike, 2 auxiliary
12 VDC, 125 mA regulated when 24 VDC powered, or 12 to 24 VDC 125 mA current limited Wiegand Data1/Data0, Magnetic Clock/Data, F/2F single-wire protocol, Bioscrypt RS-485, OSDP (Open Supervised Device Protocol RS-485)
Operating: 32° to 158° F (0° to 70° C) Storage: -67° to 185° F (-55° to 85° C) 0 to 95% RHNC
6 x 8 x 1 in. (152 x 203 x 25 mm) 9 oz. (255 g) nominal UL 294 and 1076-listed, CE-marked, ROHS compliant Advanced Encryption Standard (AES) 128-bit communication algorithm, NIST certification pending ccess C ontrol
LNL-1320 Series 2
Lenel Systems International offers a Dual Reader Interface (DRI) module for access control solutions. Most access control card readers, keypads, or readers with keypads that use standard
Wiegand Data1/Data0 or Clock/Data communication are supported, as are those that support the bidirectional RS-485 Open Supervised Device Protocol (OSDP). Lock, unlock, and facility code offline access modes are supported on all readers connected to the DRI. Each DRI supports up to eight different card formats as well as issue codes for both magnetic and Wiegand card formats.
The DRI provides a vital link between the Intelligent System Controller (ISC) and the card reader attached to the interface. As many as 32 DRI modules can be multidropped using RS-485 2-wire or 4-wire communication up to 4,000 feet per port away from the ISC. Each DRI module is individually addressed for increased reporting capabilities with OnGuard access control software applications. The DRI includes eight inputs that support normally open, normally closed, supervised, and non-supervised circuits. In addition, six output relays support fail-safe or fail-secure operation.
Features and Functionality
■ 12 or 24 VDC power supply
■ Supports Data1/Data0, Clock/Data and Lenel OSDP-compatible RS-485 readers and keypads
■ Downloadable firmware
■ Six Form-C 5 A at 30 VDC relay outputs
■ Up to 16 different formats (8 card formats and 8 asset formats)
■ Issue code support for magnetic and Wiegand formats
■ Door contact supervision (open/closed)
■ REX push-button monitor
■ Strike control output
■ Bicolor reader status LED support and 2-wire LED support
■ Beeper control
■ Dedicated tamper and power failure circuits
■ Support for offline reader access mode
■ On-board jumpers for termination
■ On-board regulator allows 12 VDC reader support from 24 VDC power source
■ DIP switch-selectable addressing
Dual Reader Interface Module es s
C on tr ol
LNL-1320 Series 2
Power Supplies & Enclosures
LNL-AL400ULX
LNL-AL600ULX-4CB6
ABT-12
Specifications Primary Power (DC)
DC input:
Reader Power
DC output:
Reader Port Compatibility
Environmental Temperature:
Humidity:
Mechanical
Dimension:
Weight:
Approvals
Lenel UL-listed 4 A, 110 VAC power supply - 12 or 24 VDC 4 A output (switch-selectable), 120 VAC input, continuous supply current with enclosure (12 x 16 x 4.5 in. / 305 x 406 x 114 mm), lock and open frame transformer, tamper switch, UPS-capable (battery optional), UL-listed Lenel UL Listed Power Supply - 12 or 24 VDC 6 A output (switch-selectable), 120 VAC (1.6 amps) input, continuous supply current with enclosure (18 x 24 x 4.5 in. / 457 x 610 x 114 mm), lock and open frame transformer, tamper switch, UPS-capable (battery optional), UL-listed Battery kit - 12 VDC, 12 AH battery (PS-12120)
* The DRI is for use in low voltage, power-limited, class 2 circuits only.
12 or 24 VDC ± 15%. 450 mA
12 VDC, 125 mA regulated or 12 to 24 VDC 125 mA current limited Wiegand Data1/Data0 Magnetic Clock/Data F/2F single-wire protocol Open Supervised Device Protocol (RS-485)
Operating: 0° to +70° C (32° to 158° F) Storage: -55° to +85° C (-67° to 185° F) 0 to 95% RHNC
6 x 8 x 1 in. (152 x 203 x 25 mm) 10 oz. (290 g) nominal UL 294 and 1076-listed, CE-marked, ROHS compliant
OnGuard Security Server
RS-485 multidrop
LNL-1300
Single Reader Interface Module
LNL-1100
Input Control Module
(Up to 16 Inputs per
LNL-1100)
LNL-1200
Output Control Module
(Up to 16 Outputs per
LNL-1200)
LNL-1320
Dual Reader Interface Module
Intelligent System Controller
CORPORATE HEADQUARTERS LOCAL AREA NETWORK (TCP/IP)
es s
C on tr ol
LNL-AL600ULX-4CB6
The LNL-AL600ULX-4CB6 is a power-limited supply/charger that will convert a 115 VAC 60 Hz input, into a non-power-limited 12 VDC or 24 VDC output (see specifications)
Features
■ LNL-CTX-6 enclosure (gray with Lenel logo)
■ Offline power supply (AL600ULXL) mounted on custom Lenel bracket
■ Power limited distribution module (PD4-CB)
■ Tamper switch
■ Lenel lock with two keys
■ 48 stand-offs and 48 screws
■ Battery leads
■ Installation instructions
■ Can accommodate up to 6 Lenel Access Control modules
Specifications
■ UL 294 and 1076-listed
■ Switch selectable 12 VDC or 24 VDC non-power limited output
■ Input 115 VAC 60 Hz, 1.9 amp
■ Maximum charge current 0.7 amp
■ 6 amps continuous supply current at 12 VDC or 24 VDC
■ Filtered and electronically regulated outputs
■ 100 mV peak output voltage ripple
■ 4 individual circuit breaker outputs
■ Surge protected outputs
■ Built-in charger for sealed lead acid or gel type batteries (Optional ABT-12)
■ Automatic switchover to standby battery when AC fails
■ Zero voltage drop when switched over to battery backup
■ AC input and DC output LED indicators
■ AC fail supervision (form C contacts)
■ Low battery and battery presence supervision (form C contact)
■ Thermal overload protection
■ Short circuit protection
■ Primary circuit switch for incoming 115 VAC
■ Power supply board dimensions: 4.3 x 7 x 1.8 in. (108 x 178 x 44 mm)
■ Enclosure dimensions: 24 x 18 x 4.5 in. (610 x 457 x 114 mm)
Ordering Information Part Number:
LNL-AL600ULX-4CB6
ABT-12
LNL-CTX-6
UL-Listed, Multi-Agency Power Supply/Charger
Description:
115 VAC configuration Battery backup option Cabinet only, with lock 24 x 18 x 4.5 in. (610 x 457 x 114 mm)
LNL- CTX-6
Lenel Systems International, Inc.
1212 Pittsford-Victor Road Pittsford NY 14534 USA [tel] +1.585.248.9720 [fax] +1.585.248.9185 [web] www.lenel.com rev. 0603
Always Includes LNL-CTX-6 enclosure (Gray with Lenel logo) Tamper switch Lenel Lock with two keys Forty-eight stand-offs and Forty-eight screws Installation Instructions UL294 and UL1076 approvals Can accommodate up to 6 Lenel Access Control Ordering Information Part Number
LNL-CTX-6
Description Cabinet only, with Lock [24" H x 18" W x 4.5" D]
Security you can rely on
Request-to-Exit Detectors
39158H
The Detection Series consists of the DS160 and DS161 Detectors specifically designed for Request-to-Exit (REX) applications. With features such as built-in timers, door monitor with sounder alert, and pointable coverage, the DS160 and DS161 have the flexibility to meet the most stringent REX requirements. The exclusive Sequential Logic Input (SLI) provides added security that is not offered in any other REX device.
� Features
� Basic Functions
Sequential Logic Input (SLI)
The SLI terminal allows connection of a second device to require sequential detection. This eliminates the possibility that an object that is slid through the door or underneath the door will activate the detector. This input can also be used to lock the detector if motion is present outside the premises.
Door monitor
The detector can monitor a door contact to allow special control of the internal relay. For example, if the door is opened within the relay time period, the detector can be programmed to halt the timer. If the door is not opened within a specific time period, the relay can be programmed to deactivate.
Sounder alert
An integrated sounder can be programmed to activate if the door is left open too long. The sounder volume is fully adjustable to 85 dB.
Keycard input
The keycard input allows the detector relay to be controlled from an external source, such as an access control system or card reader.
� Certifications
� Patents and Trademarks
� Planning The coverage is dependent on mounting height. Typically, the coverage is 8 ft. x 10 ft. (2.4 m x 3 m).
Typical coverage patterns for the detector at a height of 7.5 ft. (2.3
m) are shown. The coverage pattern increases/decreases with height and detector alignment.
Front View
DS160/DS161 High Performance Request-to-Exit Sensors
• Door monitor with sounder alert
• Sequential Logic Input (SLI)
• Internal vertical pointability
• Wrap-around coverage pattern with precise pattern control
• Up to 64 second adjustable latch time
• Selectable relay trigger mode
• Selectable fail safe/fail secure modes
• Adjustable sounder volume
• Activation LED
UL Standard UL294, Access Control System Units
4,764,755
Top View
Side View
Pattern on Floor
� Technical Specifications
� Hardware Options
Alarm Output 2 Form "C" relay contacts each rated 1A @ 30 VAC or VDC for resistive loads
Enclosure Design
Dimensions (HxWxD): 1.80 in. x 6.75 in. x 1.75 in.
(4.5 cm x 17.1 cm x 4.4 cm)
Material: High impact ABS plastic enclosure
Environmental Considerations
Operating Temperature: -20°F to +120°F (-29°C to +49°C) For UL Certificated installations, +32°F to +120°F (0°C to +49°C)
Mounting
Location: Surface mount
Indicators 1 activation LED
Radio Frequency Interference (RFI) Immunity
No alarm or setup on critical frequencies in the range from 26 MHz to 1000 MHz at 50 v/m
Relay Latch Time Adjustable from 0.5 seconds to 64 seconds.
Power Loss Default Programmable fail-safe or fail-secure modes.
Power Requirements 12 to 30 VAC, 12 to 30 VDC, 8 mA nominal standby current, 39 mA @ 12 VDC in alarm
Timer Mode Programmable resettable (accumulative) or non-resettable (counting) mode.
TP160/TP161 Trim Plates
A trim plate that allows mounting the detector over a standard single gang box.
TP160: light gray, TP161: black
DS160 Surface Mount Detector in Light Grey Enclosure Prod. ID DS160
DS161 Surface Mount Detector in Black Enclosure Prod. ID DS161
Bosch Security Systems 130 Perinton Parkway Fairport NY 14618 Phone: (888) 289-0096 Fax: (585) 223-9180 www.boschsecurity.us
Specifications are subject to change without notice 39158H
ACMCB Series Access Power Controllers with Power Supplies Installation Guide Models Include:
•AL400ULACMCB • AL600ULACMCB
- 4 amp @ 12VDC - 6 amp @ 12VDC or 24VDC.
or 3 amp @ 24VDC. - PTC Outputs
- PTC Outputs
• AL1012ULACMCB • AL1024ULACMCB
- 10 amp @ 12VDC. - 10 amp @ 24VDC.
- PTC Outputs - PTC Outputs
Rev. 092503
For a red enclosure, add an “R” suffix to the part # e.g. AL600ULACMCBR
- 2 - ACMCBseries
Overview:
These units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. Outputs are activated by an open col-lector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm discon-nect feature is individually selectable for any or all of the eight (8) outputs.
ACMCB Series Configuration Reference Chart:
AL400ULACMCB 4 3 8 Yes 1.9 amp 3.5A / 250V
AL600ULACMCB 6 6 8 Yes 1.9 amp 3.5A / 250V
AL1012ULACMCB 10 --- 8 Yes 1.9 amp 3.5A / 250V
AL1024ULACMCB --- 10 8 Yes 4.4 amp 10A / 250V
Specifications:
• Power supply input options:
a) One (1) common power input for ACM8CB and lock power (factory installed).
b) Two (2) isolated power inputs (external power supply is required).
(current is determined by the power supply connected, not to exceed a maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
• Eight (8) independently controlled Fail-Safe and/or Fail-Secure power outputs.
• Eight (8) auxiliary power outputs (unswitched) (PTC protected outputs are rated 2.5 amp).
• ACM8CB board main fuse is rated at 10 amp.
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit..
• Alarm output relay indicates that FACP input is triggered (form “C” contact rated @ 1 amp 28VDC not evaluated by UL).
• Green LED indicates when FACP disconnect is triggered.
• Filtered and electronically regulated outputs (built-in power supply).
• Built-in charger for sealed lead acid or gel type batteries.
• AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge current .7 amp.
AL1024ULXB (Power Supply Board) maximum charge current 3.6 amp.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Thermal and short circuit protection with auto reset.
• AC input and DC output LED indicators.
• AC fail supervision (form "C" contact).
Altronix Model Number 11
5V
AC 6
0H z
In pu t
(c ur re nt d ra w
V
D C T ot al
O ut pu t
Cur re nt (a m p)
V
D C T ot al
O ut pu t
Cur re nt (a m p)
O ut pu ts
Cla ss
R at ed
Po wer
L im ite d
A ge nc y
List in gs
U L L ist in gs a nd
Fi le
N um be rs
Po wer
S up pl y
Boa rd
In pu t F us e Rat in g
UL File # BP6714 UL Listed for Access Control
System Units (UL 294).
“Signal Equipment” Evaluated to
CSA Standard C22.2 No.205-M1983
ACMCBseries - 3 -
• Battery fail and battery presence supervision (form "C" contact).
• Enclosure accommodates up to two (2) 12AH batteries.
Enclosure dimensions: 15.5"H x 12"W x 4.5"D
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 10).
Secure enclosure to earth ground. It is recommended to first review the following tables to facilitate installation:
Output Voltage and Stand-by Specifications Charts (pg. 3) Typical Application Diagram (pg. 5) LED Diagnostics (pg. 6) Terminal Identification Tables (pg. 7) Hook-up Diagrams (pg. 8)
2. Set output voltage:
AL400ULACMCB and AL600ULACMCB set desired DC output voltage by setting switch SW1 to the appropriate position on the power supply board.
AL1012ULACMCB is 12VDC and AL1024ULACMCB is 24VDC (Output Voltage and Stand-by Specification Charts below).
3. Measure voltage before connecting devices. This helps avoid potential damage.
Output Voltage and Stand-by Specification Charts:
AL400ULACMCB
Voltage Switch Stand-by 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
Position Battery
12VDC SW1 - Closed 40 AH 3.5 amp / 3.5 amp .5 amp / 3.5 amp
24VDC SW1 - Open 40 AH 2.75 amp / 2.75 amp .75 amp / 2.75 amp
AL600ULACMCB
Voltage Switch Stand-by 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
Position Battery
12VDC SW1 - Closed 40 AH 5.5 amp / 5.5 amp .5 amp / 5.5 amp
24VDC SW1 - Open 40 AH 5.75 amp / 5.75 amp .75 amp / 5.75 amp
AL1012ULACMCB
Voltage Switch Stand-by 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
Position Battery
12VDC N/A 40 AH 9.5 amp / 9.5 amp .5 amp / 9.5 amp
AL1024ULACMCB - (refer to AL1024ULACMCB Battery Size Calculation Worksheet, pg. 9) Voltage Stand-by 15 mins. Stand-by / 4 hr. Stand-by / 24 hr. Stand-by / 60 hr. Stand-by /
Battery 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm
24VDC 12 AH 7.7 amp / 9.7 amp 1.2 amp / 9.7 amp ------------------------- -------------------------
Voltage Stand-by 15 mins. Stand-by / 4 hr. Stand-by / 24 hr. Stand-by / 60 hr. Stand-by / Battery 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm & 5 mins. Alarm
24VDC 65 AH ------------------------- 7.7 amp / 9.7 amp 1.2 amp / 9.7 amp 200mA / 9.7 amp
- 4 - ACMCBseries
4. Connect AC (Fig. 2, pg. 6):
Connect unswitched AC power (115VAC 60Hz) to terminals marked [L, G, N]. Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground. Keep power limited wiring separate from non-power limited wiring (115VAC 60Hz Input, Battery Wires). Minimum .25” spacing must be provided.
5. Output options (Fig. 1, pg. 5):
The unit will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs.
(a) Switched Power outputs:
Connect the negative (-) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO].
(b) Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc.
6. Input trigger options (Fig. 1, pg. 5):
(a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs.
Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (-) to the terminal marked [GND].
7. Fire Alarm Interface options (Figs. 4 through 8, pg. 8):
A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will trigger selected outputs. To enable FACP Disconnect for an output open the corresponding switch [SW1-SW8].
To disable FACP disconnect for an output close the corresponding switch [SW1-SW8].
(a) Normally Open [NO] input:
For non-latching hook-up (Fig. 5, pg. 8). For latching hook-up (Fig. 6, pg. 8).
(b) Normally Closed [NC] input:
For non-latching hook-up (Fig. 7, pg. 8). For latching hook-up (Fig. 8, pg. 8).
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -].
Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition).
Jumper J3 must be cut (Fig. 4, pg. 8).
8. FACP Dry form “C” output (Fig. 1A, pg. 5):
Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.
9. Battery Connections (Fig. 2, pg. 6):
For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked [- BAT +] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation.
10. Battery and AC Supervision output (Fig. 2, pg. 6):
It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] and [Power Fail] supervisory relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting. Cut “AC delay” jumper to delay report 6 hour.
Note: A tamper switch must be installed and connected to the appropriate notification device to report a trouble condition when the enclosure door is open.
11. Multiple power supply inputs (Fig. 1, pg. 5):
When using two (2) power supplies jumpers J1 and J2 (located to the left of the power/control terminals) must be cut (Fig. 1B, pg. 5 & Fig. 3 pg. 8). Connect power for the ACM8CB to the terminals marked [- Control +] and connect power for the locking devices to the terminals marked [- Power +]. When using DC power supplies polarity must be observed. When using AC power supplies polarity need not be observed.
Note: For UL compliance the additional power supply must be power limited, UL Listed for Access Control
Systems and accessories.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
ACMCBseries - 5 -
NC C NO COM
OUTPUT 1
LED1
F1
NC C NO COM
OUTPUT 2
IN GND
IN GND
IN GND
IN GND
IN GND
IN GND
IN GND
MAIN
IN GND
LED2 LED3 LED4 LED5 LED6 LED7 LED8
J2 J1
TRG
NC C NO COM
OUTPUT 3
NC C NO COM
OUTPUT 4
NC C NO COM
OUTPUT 5
NC C NO COM
OUTPUT 6
NO
C
N
IN
P
T
R
ET
NC C NO COM
OUTPUT 7
NC C NO COM
OUTPUT 8
Po we r
Co nt ro l
F2 F3 F6 F7 F8F4 F5
J3
J2 J1
3.5A 250V 3.5A 250V 3.5A 250V3.5A 250V 3.5A 250V3.5A 250V3.5A 250V 3.5A 250V
FA
CP
IN
TE
RF
AC
E
10A 250V
NC
NO
C
KEYPADNORMALLY OPEN
N.O. DOOR
RELEASING DEVICE
ACCESS CONTROL
PANEL
OUTPUT
RELAY
MAG.
LOCK
MAG.
LOCK
ELECTRIC
STRIKE
ELECTROMAGNETIC
DOOR HOLDERS
AC or DC
POWER
SUPPLY
(optional)
AC or DC
POWER
SUPPLY
(req'd.)
FACP
(Fire Alarm Control Panel)
UL Listed
POWER SUPPLY
For this application corresponding fuse F8 must be removed.
SW
SW
SW
SW
SW
SW
SW
SW
FACP Interface Enabled
FACP Interface Disabled
SW1-SW8
FACP Dry Form "C" Output
FA
CP
(Output Voltage and Stand-by Specification Charts, pg. 3).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [- BAT +] to insure that there is no break in the battery connection wires.
Note: AL400ULXB, AL600ULXB, AL1012ULXB (Power Supply Board) maximum charge current is .7 amp.
AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp.
Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.
Typical Application Diagram:
Fig. 1 Fig. 1A
Fig. 1B
- 6 - ACMCBseries
LED Diagnostics:
Power Supply Board
LED
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output. Loss of AC. Discharged battery.
ACM8 Access Power Controller
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) energized. Output relay(s) de-energized.
Trg (Green) FACP input triggered (alarm condition). FACP normal (non-alarm condition).
D
L G N
ALTRONIX CORP.
BKLYN, N.Y. 11220
MADE IN USA
B
A T
AC FAILBAT FAIL
Battery and AC Supervision Circuit
(power limited)
Battery connection (non-power limited)
Door
Wire Strap (from Enclosure to Door)
DC Output to devices (power limited)
Fire Alarm Interface
Insulating Barrier
Inputs (power limited) unswitched 115VAC power mains
(non-power limited)
Power Supply Board CAUTION: De-energize unit prior to servicing.
For continued protection against fire hazard replace fuse with the same type and rating .
Replace fuse cover before energizing.Green Lead
Green Lead
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
12VDC Rechargeable Battery (optional)
12VDC Rechargeable Battery (optional)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Fig. 2
ACMCBseries - 7 -
Terminal Identification Tables:
Power Supply Board Terminal Function/Description Legend
L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground.
- DC + AL400ULACMCB - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board (power limited).
AL600ULACMCB - 12VDC/24VDC @ 6 amp to ACM8CB board (power limited).
AL1012ULACMCB - 12VDC @ 10 amp to ACM8CB board (power limited).
AL1024ULACMCB - 24VDC @ 10 amp to ACM8CB board (power limited).
AC FAIL Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay NC, C, NO normally energized when AC power is present. Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs., cut “AC delay” jumper and reset power to unit.
BAT FAIL Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally NC, C, NO energized when DC power is present. Contact rating 1 amp @ 28VDC.
A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACMCB), 24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACMCB).
- BAT + Stand-by battery connections. AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge current is .7 amp. AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp.
ACM8CB Access Power Controller Terminal Function/Description Legend
- Power + 12VDC or 24VDC input from power supply board.
- Control + These terminals can be connected to a separate power limited, UL listed power supply to provide isolated operating power for the ACM8 (jumpers J1and J2 Must be removed).
TRIGGER From normally open and/or open collector sink trigger inputs INPUT 1- INPUT 8 (request to exit buttons, exit pir’s, etc.).
IN, GND
OUTPUT 1-OUTPUT 8 12 to 24 volts AC/DC trigger controlled outputs:
NC, C, NO, COM Fail-Safe [NC positive (+) & COM Negative (-)], Fail-Secure [NO positive (+) & COM Negative (-)], Auxiliary output [C positive (+) & COM Negative (-)] (When using AC power supplies polarity need not be observed), NC, C, NO become form “C” 5 amp 24VAC/VDC rated dry outputs when fuses are removed. Contacts shown in a non-triggered state.
FACP INTERFACE Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open, T, + INPUT -- normally closed from an FACP output circuit (Fig. 4 through 8 , pg. 8).
FACP INTERFACE Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting.
NC, C, NO (This output has not been evaluated by UL).
- 8 - ACMCBseries
Hook-up Diagrams:
JUMPER
N.C. DRY
TRIGGER
INPUT
TRG
J3
RF
AC
E
Fig. 5 Normally Open - Non-Latching FACP trigger input:
N.C. TRIGGER
INPUT
N.C. RESET
SWITCH
JUMPER
TRG
J3
Fig. 6 Normally Open FACP Latching trigger input with reset:
(This output has not been evaluated by UL)
Fig. 7 Normally Closed - Non-Latching FACP trigger input:
Fig. 8 Normally Closed - Latching FACP trigger input with reset:
(This output has not been evaluated by UL)
Fig. 4 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition):
Fig. 3 Optional hook-up using two (2) isolated power supply inputs:
J2 J1
CUT JUMPERS
J1 AND J2
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(LOCK POWER)
ISOLATED POWER INPUT
12 OR 24 VAC OR VDC
(ACM8CB POWER)
CUT
JUMPER J3
FROM FACP
OUTPUT
CIRCUIT+
FACP
OUTPUT EOL
TRG
RF
AC
E
N.O. TRIGGER
INPUT
TRG
RF
AC
E
N.C. RESET
SWITCH
N.O.
TRIGGER
INPUT
JUMPER
TRG
ACMCBseries - 9 -
AL1024ULACMCB Battery Size Calculation Worksheet.
A. AL1024ULACMCB internal current consumption (standby) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .35 A
B. Load current consumption (standby) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ A
C. Standby time required (hours) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ H
D. Battery capacity required for standby (A+B)*C _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
E. AL1024ULACMCB internal power consumption (Alarm) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .35 A
F. Load current consumption (Alarm) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ A
G. Alarm duration (Hours, example:15 Min=.25 Hour) (Alarm) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ H
H. Battery capacity required for Alarm (E+F)*G _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
I. Total calculated battery capacity D+H _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
J. Battery capacity required I*1.8 (safety factor) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ AH
Note: AL1024ULACMCB power supply is designed to work with batteries up to 65AH. Please note, line [I] must not exceed 36AH. You have to reduce either standby current consumption or standby time in order to comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size.
- 10 - ACMCBseries
.875"
1"
0 0
10.75" 1.5" 6" 10.5"
2"
0 1.25" 4.5"12"
15.5"
4.5"
4.5"
1.25"
1.25"
14.25"
13.5"
10"
6.625"
TOP & BOTTOM
Enclosure Dimensions:
15.5”H x 12”W x 4.5”D
The multiCLASS™ family of card readers is designed for customers upgrading their current card system from the most popular proximity technologies to iCLASS® credentials. With the RP40, RPK40 and RP15 readers, the customer has the ability to transition to smart cards over time while incorporating the use of multiple card technologies within a single building or across multiple facilities.
The multiCLASS reader line provides enhanced security through mutual authentication and data encryption. HID, Indala and other popular proximity technologies are supported by multiCLASS. Save on system configuration costs by keeping system upgrade simple. Whether reading proximity, iCLASS or multi-technology cards, identical user identification data formats are sent to the panel. Unlike competitor products, HID multiCLASS readers support all HID and Indala Proximity formats, including Corporate 1000, long and FlexSecur.
Only the multiCLASS family of products provides true iCLASS security, the ease of proximity technology, the power of smart cards and the confidence of choosing HID, the worldwide leader in access control.
Unique Read Selection w Enable iCLASS, proximity or both technologies at the same time.
w Multiple data outputs available when multi-technology card is presented depending on preference.
w Configuration cards configure the reader to custom installation requirements.
w Reads: 125 kHz – HID, Indala or AWID Proximity
13.56 MHz – iCLASS, ISO 15693 CSN (MyD, ICODE, Tag-it), ISO 14443A CSN (MIFARE®, DESFire®), US Government PIV, ISO 14443B CSN, FeliCa™ IDm
Seamless Upgrade w Same HID and Indala Proximity reader features and format compatibilities.
w Same wiring, power and interface as many popular proximity readers in the market today.
w All Corporate 1000 formats can be migrated.
w For additional security, our iCLASS Elite program is available with iCLASS credentials.
w Wiegand or Clock-and-Data outputs easily interface with existing access control panels.
w The RPK40 combines a contactless card presentation with a personal identification number (PIN) to support dual factor authentication of identity.
w The RP15 is a mullion form factor drop-in replacement for the HID MiniProx.
13.56 MHz Contactless and 125 kHz Proximity Card Readers • 6125, 6136, 6145 w Simple Migration – From the most popular proximity technologies to iCLASS®.
w Powerful Options – Provides flexible options for processing multi-technology cards and configuring the reader’s audio/visual characteristics.
w GSA-approved – Included in the U.S. General Services Administration (GSA) FIPS 201 Approved Products…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .