Q A 3.pdf
PDF 11 KB Posted
- Solicitation number
- GS-01P-12-BZ-D-0015
About this file
Question and Answer 3
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FormSF30.pdf | ||
| Amendment 0004 Attachment 1 Addendum No. 1 Montpelier Federal Building - 07-19-12 1 .zip | ZIP file | |
| Q A 4.pdf | ||
| Q A 2.pdf | ||
| FormSF30.pdf | ||
| Sign In Site Visit 2.pdf | ||
| FormSF30.pdf | ||
| Q A 1.pdf | ||
| Notice of 2nd Site Visit.pdf | ||
| Preproposal Minutes Post.pdf | ||
| FormSF30.pdf | ||
| Per-Proposal Conf Notice.pdf | ||
| Pricing Worksheet Blank.xlsx | XLSX spreadsheet | |
| RFP Post Final.pdf | ||
| RFP Final No Spec.pdf | ||
| Pricing Worksheet Blank.xlsx | XLSX spreadsheet |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GSA New England Region
U.S. General Services Administration Thomas P. O'Neill, Jr. Federal Building 10 Causeway Street Boston, MA 02222 www.gsa.gov
DATE: 17 July 2012
Solicitation GS-01P-12-BZ-C-0015
Multiple Award, Indefinite Delivery/Indefinite Quantity (IDIQ) Contract for Construction Services for GSA Owned Federal Facilities in Vermont
Questions and Answers 03
26. Q: The latest RFI answers indicates that all work in the penthouse needs to take place 24/7 over a weekend. Asbestos abatement involves the removal of approximately 3,350 SF of duct insulation plus fitting insulation from the penthouse. Is it the intent to set-up, remove and acheive air clearence in this area in one weekend leaving the air handlers operational at the end of the weekend or will we be able to set-up smaller areas and work on a section at a time over several weekends?
A: The penthouse is a return air plenum room. This means that the room must have air clearance prior to normal operating hours. While not impossible, it will be difficult to have a containment area with the air handlers in operation due to the room being plenum. If the contractor wants to do the work in stages that is their choice, but they will need air clearances prior to normal building hours.