This is a design-build project specification document for the installation of a 180 kW DC electric vehicle charging station at Grand Vista Hotel, located at 11597 Scott Highway, Helenwood, Tennessee 37755. The project involves the installation of two ABB Terra 184 dual-port CCS DC fast chargers, providing a total of 360 kW capacity with all four ports capable of charging simultaneously. The scope of work encompasses a complete design-build delivery model requiring the contractor to perform site surveys, geotechnical investigations, and provide a full professional engineer-sealed design package from a Tennessee-licensed engineer. The project includes utility coordination with Plateau Electric Cooperative for service application and capacity verification of the existing 500 kVA pole-mounted transformer, along with installation of a new utility pole, metering infrastructure, and all associated electrical distribution components. Civil work comprises four EV parking stalls (three standard and one ADA-accessible with designated access aisle), concrete charger slab foundations, steel bollards, site trenching, asphalt work, and accessible routes. The anticipated construction period is March 1 through April 30, 2027. All permits, inspections, local authority approvals, and Tennessee 811 locates are the contractor's responsibility. The project requires phased construction to maintain active hotel operations, guest access, fire lane availability, and coordination of work hours with the site host.
The contract is structured as a fixed-price lump sum arrangement with 10% retainage. Contractor qualifications must include a Tennessee State Electrical License and EVITP certification. The deliverables include commissioning and testing of every charging port, connection to the owner's network and OCPP 2.0.1 services, comprehensive EV signage and site finishing, electrical labeling, and emergency disconnect capability. The contractor must provide a five-year warranty, a five-year operations and maintenance plan including quarterly preventive maintenance and 24/7 remote monitoring, and a five-year service level agreement guaranteeing 97% uptime per port with 24/7 driver support available in English and Spanish. All utility fees and make-ready costs are included within the lump sum price. The charging stations must support CCS1 minimum with NACS-capable equipment welcome, operate on open access protocols, and accept contactless card/RFID and QR code payments.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP
COMMERCIAL
GRAND VISTA HOTEL COMMERCIAL : 11597 SCOTT HWY, HELENWOOD, TN 37755
(2) 180 KW DC ELECTRIC VEHICLE CHARGING STATION
11597 Scott Hwy, Helenwood, TN 37755
11597 Scott Hwy, Helenwood, TN 37755
N
NOWNER : INSTALLER :
INSTALLATION OF THE NEW ELECTRIC VEHICLE CHARGING
STATION (EVCS) USED FOR ELECTRIC VEHICLE CHARGING.
EVSE IS INTEGRATED WITH THE NEW METER
SCOPE OF WORK:
GRAND VISTA HOTEL
11597 SCOTT HWY,
HELENWOOD, TN 37755
EQUIPMENT SUMMARY :
02 QTY - ABB TERRA 184 DUAL PORT CCS DC FAST CHARGERS
SHEET INDEX :
T-01 COVER SHEET
G-01 GENERAL NOTES
EV-01 SITE MAP & PROPERTY LAYOUT
EV-02 SITE PLAN
C-01 ELEVATION VIEW & FOUNDATION DETAILS (A) - DISCONNECT
C-02 ELEVATION VIEW & FOUNDATION DETAILS (B) - EV CHARGER
EV-03 ELECTRICAL THREE-LINE DIAGRAM
EV-04 SYSTEM LABELING DETAILS
EV-05 EV CHARGER DATA SHEET
EV-06 AC DISCONNECT DATA SHEET-1
EV-07 AC DISCONNECT DATA SHEET-2
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2017 NATIONAL ELECTRICAL CODE
CODE REQUIRED:
UNIVERSAL EV LLC
305 W SPRING CREEK PKWY,
SUITE 100 B, PLANO, TX 75023
T-01
01 AK AD 08.24.26
02 VP AD 08.25.26
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
http://www.nordicasia.net
G-01
GENERAL NOTES :
1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE LAWS, CODES,
GOVERNMENT REGULATIONS, UTILITY COMPANY REQUIREMENTS, ETC. OF ALL
AUTHORITIES HAVING JURISDICTION IN EFFECT AT THE TIME OF THE BUILDING
PERMIT.
2. WHERE CONFLICTS EXIST BETWEEN CODES, STANDARDS OR THIS SPECIFICATION,
THE HIGHER REQUIREMENT SHALL APPLY.
3. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE SAFETY OF HIS WORKERS,
ALL CONSTRUCTION MEANS, METHODS,TECHNIQUES, SEQUENCES AND
PROCEDURES FOR COORDINATING THE WORK UNDER THIS CONTRACT.
4. CONTINUOUSLY MAINTAIN THE CONSTRUCTION PREMISES IN A NEAT AND
ORDERLY CONDITION. DAMAGE TO FINISHES SHALL BE PROPERLY RESTORED.
5. EVSE ENCLOSURE SHALL BE NEMA RATED.
6. EVSE CORD LENGTH SHALL NOT EXCEED 25'.
7. EVSE CHARGING STATIONS HAS 4 DOORS I.E. FRONT, REAR, LEFT AND RIGHT.
CLEAR 24” DISTANCE ON THE FOUR SIDES OF A CHARGER TO BE MAINTAINED FOR
AIR CIRCULATION FOR COOLING AND OPENING PANEL FOR MAINTENANCE.
8. MECHANICAL AND ELECTRICAL SUPPORT COMPONENTS, INCLUDING STRUT AND
HARDWARE, SHALL BE HOT DIPPED GALVANIZED OR EQUIVALENT
ELECTROPLATED FINISH.
9. ALL GROUNDED CONDUCTORS ARE WHITE AND EQUIPMENT GROUNDING
CONDUCTORS ARE GREEN OR BARE PER (NEC 200-6 (A), EX 5).
10. LIQUID TIGHT FLEXIBLE METAL CONDUIT IS GENERALLY SUITABLE FOR
INSTALLATION IN WET AND DRY LOCATIONS. SHOULD IT BE EMPLOYED, SUPPORTS
WILL BE NO MORE 12 INCHES FROM BOXES (JUNCTION BOX, CABINETS, OR
CONDUIT FITTING) AND NO MORE THAN 54 INCHES APART PER NEC.
11. ALL CONDUCTORS BELOW 100A SHALL BE COPPER, UNLESS OTHERWISE NOTED.
12. IN ORDER TO PROVIDE ACCESSIBLE OPERATION OF EVSE, A 3’ BY 3’ (MINIMUM)
HANDICAPPED ACCESSIBLE OPERATING AREA MUST BE KEPT CLEAR OF VEHICLES
AND SNOW BETWEEN THE NOSE OF THE VEHICLE AND THE EVSE.
13. RELIABLE PROTECTIVE GROUNDING MUST BE PROVIDED. IT IS RECOMMENDED TO
HAVE SEPARATE DEDICATED GROUND EXCLUSIVELY FOR THE CHARGER
CONSIDERING THE SAFETY ASPECTS. THE GROUND RESISTANCE SHOULD BE LESS
THAN OR EQUAL TO 4ΩCOPPER CABLE OF IN ACCORDANCE WITH NEC SHALL BE
USED TO CONNECT CHARGE HOUSING TO EXTERNAL GROUND.
14. THE RACEWAY SHALL NOT BE LESS THAN TRADE SIZE 1 (NOMINAL 1-INCH INSIDE
DIAMETER). THE RACEWAY SHALL ORIGINATE AT THE MAIN SERVICE OR
SUB-PANEL AND SHALL TERMINATE INTO A LISTED CABINET, BOX OR ENCLOSURE
IN CLOSE PROXIMITY TO THE PROPOSED LOCATION OF THE EV SPACE.
15. LOCATION OF INSTALLATION IS NOT LOCATED WHERE EXCESSIVE WATER
RUN-OFFS, POOLING OR FLOODING MAY OCCUR.
16. EXTERIOR SIGNS AND ZONING CONCERNS PER SITE REQUIREMENTS.
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
EV CHARGE
ONLY
BOLLARDS
MAIN SERVICE
DISCONNECT
UTILITY METER
PR
O
PE
R
TY
L
IN
E
PROPERTY LINE
ELECTRIC VEHICLE
PARKING
FIRE LANE
DRIVEWAY
SC
O
TT
H
W Y
B C-02
EV SIGNBOARD
CHARGER SLAB FOUNDATION
5' 11'
19'
18'
ACD-1ACD-2
MET MSD
113'-7"
244'-8"
2'
-1
'-2
'-2
87'-8"
'-1
211'-1"
6'
-1
PROPERTY LINE
PROPERTY LINE PROPERTY LINE
PR
O
PE
R
TY
L
IN
E
DRIVEWAY DRIVEWAY
DRIVEWAY
ELECTRIC VEHICLE SUPPLY
EQUIPMENT LEVEL-3 - 1 & 2
(TERRA 184 DUAL PORT CCS)
C C-01
A C-01
FUSED AC DISCONNECT-1&2
41'-10"
1'-10"
SC
O
TT
H
W Y
NEW UTILITY POLE P2
EXISTING 500KVA POLE MOUNTED
TRANSFORMER ON P1 POLE
8' PR
O
PE
R
TY
L
IN
E
96'-8"
8'8'8'
2'-11"
20'-11"
EV-01
PROPERTY LAYOUT
SITE MAP
N
E
S
W270
350 0 10
4O
170180190
NOTE:
1. Do not let the flammable, explosive or flammable materials, chemicals, flammable vapors, and other dangerous goods close to charging station.
Scale - 1" = 45'
- EV parking
LEGENDS :-
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
11597 Scott Hwy, Helenwood, TN 37755
01 AK AD 08.24.26
02 VP AD 08.25.26
EV CHARGE
ONLY
BOLLARDS
MAIN SERVICE
DISCONNECT
UTILITY METER
ELECTRIC VEHICLE
PARKING
FIRE LANE
EV SIGNBOARD
CHARGER SLAB
FOUNDATION
8' 8' 8' 5' 11'
19'
18'
ACD-1ACD-2
MET MSD
DRIVEWAY
ELECTRIC VEHICLE SUPPLY
EQUIPMENT LEVEL-3 - 1 & 2
(TERRA 184 DUAL PORT CCS)
A C-01
FUSED AC
DISCONNECT-1&2
41'-10"
1'-10"
EXISTING 500KVA POLE MOUNTED
TRANSFORMER ON P1 POLE
C C-01
B C-02
8'
NEW UTILITY POLE P2
96'-8"
2'-11"
20'-11"
EV-02
SITE PLAN
N
E
S
W270
350 0 10
4O
170180190
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
- EV parking
LEGENDS :-
01 AK AD 08.24.26
02 VP AD 08.25.26
12"x12"x5' WIRING - GUTTER BOX
(HAMMOND, C3RWT1260)
GROUND
LEVEL
LIN
E
LO
AD
RESERVED FOR UTILITY
LIN
E
LO
AD
400A FUSED
DISCONNECT-1
LIN
E
LO
AD
600A FUSED
DISCONNECT
400A FUSED
DISCONNECT-2
6'
8' 8'
7' 7'
3' -9
10"
3' -1
0"
5' (M ax .6
'-7
FRONT VIEW REAR VIEW SIDE VIEW
3'
CONCRETE PIER
3" INTERMEDIATE
METAL CONDUIT (IMC)
UNISTRUT
U BOLTS
TOP VIEW
U BOLT
3" POST
PLATE
SS HEXAGONAL BOLTS
UNISTRUT RAIL
4'
TOP VIEW
CONCRETE
FOUNDATIONBOLLARDS
Ø5.5"
1'-8"
GROUND
LEVEL
1'-8"
1' -8
CAP
ULINE H-9089 5.5" DIA DUCTILE
IRON STEEL PIPE BOLLARD
SECTION VIEW
CONCRETE
FOUNDATION
C-01
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
ELEVATION VIEW & FOUNDATION DETAILS (A) - DISCONNECT
FOUNDATION DETAILS (C) -BOLLARDS U BOLT CONNECTION DETAILS
NOTE:
1) Measure the distance from the finished grade to the center of the meter base. This height must be between 4.5 feet and 5.5 feet, as required by the utility provider.
2) Service disconnects should be installed at a height between 4 feet and 6 feet 7 inches above the finished floor or grade for accessibility and ease of use.
Per the National Electrical Code (NEC), the maximum allowable height for the center of the service disconnecting means (SDM) handle is 6 feet 7 inches (2.0 meters) above the floor or ground.
2' -1
1"
1'-10"
6' -3
1'-10"2'-11"
2'-6" 2"5"
3'-1" 1'-7"2" 2"
2'
6' -7
EXISTING ASPHALT
GRADE
3'-2" 2'-6"
EXISTING ASPHALT
GRADE
6"
FRONT VIEWSIDE VIEW
CHARGER SLAB
FOUNDATION (FRONT)
CHARGER SLAB
FOUNDATION (SIDE)
HOLES TO INSTALL
THE EVSE TO
GROUND/FOUNDATION
(M10 BOLT)
EVSE CABINET
FOOTPRINT
M25 CABLE GLANDS
EVSE BASE FOOTPRINT
CHARGER SLAB
FOUNDATION CHARGER SLAB
FOUNDATION
SLEEVE
ANCHORS
SLEEVE
ANCHORS
Grade Level
Electric Cables (in Conduit)
A
Width Determined by Number of Electric
Conduit
C-02
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
NOTE:
1. Charger slab foundation shall be of concrete slab with the dimensions of 3'-2" length x 2'-6" width, to accommodate the weight and dimensions of the EV charger base.
ELEVATION VIEW & FOUNDATION DETAILS (B) - EV CHARGER
UNDERGROUND ELECTRICAL
CONDUIT - SECTION DRAWING
#2 AWG Bare Green (CU)
Acorn Clamp
8'
5/8" X 8' (Cu) Grounding Electrode Rod
Grade Level
EV-03
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
GROUND ROD
CONNECTION
DRAWING - DETAIL A
(2) 180 kW DC ELECTRIC VEHICLE CHARGING STATION THREE-LINE DIAGRAM
(N)-NEW
(E)-EXISTING
NOTE:
1. Raceways and associated conductors installed for Direct Current Fast Charging (DCFC) stations must be capable of accommodating 480V dedicated branch circuits.
2. All conductor's ampacity is based on 75°C rated insulation.
ELECTRIC VEHICLE
CHARGER -1 (N)
ABB Terra 184 Dual Port CCS DC Fast Charger
ELECTRIC VEHICLE
CHARGER -2 (N)
ABB Terra 184 Dual Port CCS DC Fast Charger
ORANGE - L2
BROWN - L1
GREEN - GROUND
UTILITY
METER
YELLOW - L3
CT
SENSOR
TRANSFORMER
500KVA (E)
CT CABINET (N)
277/480V, 600A Rated
FUSED
AC DISCONNECT 1&2 (N)
600V, 400A Rated,
(3) 300A (Class J) Fuses, Fused Metallic, Visible, Lockable, and labeled
Disconnect (VLLD)
65 KAIC, NEMA 3R
(SIEMENS HF365NRA)
4" PVC
(3)#500 kcmil THWN (AL) (1)#2 AWG THWN Ground (CU)
4" PVC
(3)#500 kcmil THWN (AL) (1)#2 AWG THWN Ground (CU)
WIRE WAY (N)
12"X12"X5'
NEMA 3R
2 X 4" PVC
2 X (4) #500 kcmil THWN (AL)
MAIN
SERVICE DISCONNECT (N)
600V, 600A Rated,
(3) 600A (Class J) Fuses, Fused Metallic Visible, Lockable, and labeled
Disconnect (VLLD)
65 KAIC, NEMA 3R
(SIEMENS HF366NRA)
WIRE WAY (N) - NEMA 3R
2 X (3)#500 kcmil THWN (AL) 2 X (1)#2 AWG THWN Ground (CU)
#2 AWG Bare Green (CU)
(2) 5/8" X 8' (CU) (Minimum) Rod-Type Grounding Electrode
Detail - A
Supply Side Bonding Jumper
Main Bonding Jumper
2 X (4)#500 kcmil THWN (AL) 2 X (1)#2/0 AWG THWN Ground (CU)
WIRING AND CONDUIT SCHEDULE
ID DESCRIPTION VOLTAGE
(V)
Full Load Amperage
(A)
Full Load Amperage X
1.25% (A)
OCPD
rating (A)
Multiple conductor
Derate
Temperature Derate
Max ONE
WAY
LENGTH
(ft)
WIRE SIZE
Wire
Ampacity (A)
GROUND WIRE
TYPE R/1000FT V LOSS % TEMP
MAX
TOTAL NO OF
CONDUCTORS
NO. OF
CURRENT
CARRYING
CONDUCTOR
CONDUIT
ELECTRIC VEHICLE
CHARGER-1&2 TO
FUSED AC
DISCONNECT 1&2
480 230.00 287.50 300 1.00 0.94 25 #500 Kcmil (AL) 310 #2 AWG (CU) THWN 0.0424 0.09% 32C 4 3 4" PVC Min
FUSED AC
DISCONNECT 1&2 TO
MAIN SERVICE
DISCONNECT
480 230.00 287.50 300 1.00 0.94 5 #500 Kcmil (AL) 310 #2 AWG (CU) THWN 0.0424 0.02% 32C 4 3 4" PVC Min
EV-04
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
SYSTEM LABELING DETAILS
NOTE:
1. The enclosure must be NEMA-rated as per NEC 110.28.
2. Cord length will reach vehicle's inlet without excessive slack and must be no more than 25' in length as per NEC 625.17.
3. Equipment operating above 50 volts must be protected against physical damage as per NEC 110.27.
4. For EVCS greater than 60 amperes, a separate disconnect is required and should be installed concurrently with conduit and visible from EVCS as per NEC 625.23.
5. Conductors should be sized to support 125% of the rated equipment as per load NEC 625.21.
CAUTION
DANGER OF ELECTRIC SHOCK
DO NOT TOUCH THE APPARATUS
WITH WET HAND.
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
EV-05
EV-06
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
EV-07
IN
ST
AL
LE
R
O W
N
ER
G
R
AN
D V
IS
TA
H O
TE
L
SC
O
TT
H W
Y, H
EL
EN
W O
O D
, T N
U N
IV
ER
SA
L
EV
L
LC
W
S
PR
IN
G
C R
EE
K
PK
W
Y, SU
IT
E
B, P
LA
N
O , T
X
VER DRAWN
BY
CHK'D
BY DATE
00 SR AD 05.15.26
Sheet No
Job ID
Page No
UNE-26-65
of 11
Revision REV-02
DESIGNED BY
www.nordicasia.net
NORDIC ASIA
http://www.nordicasia.net
| 11597 Scott Hwy, Helenwood, TN 37755, United States-001 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-002 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-E001 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-E002 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-E003 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-S001 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-E004 SLD |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-E005 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-E006 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-003 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States-EV-09 |
| 11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1 |