Grand Vista Hotel _ UNE2665R02.pdf

PDF 4 MB Posted

Attached to
EV Charging Station-Grand Vista-Helenwood, TN
Solicitation number
RFP-DCFC-Helenwood-TN-001
Issued by
Sullivan County, Tennessee

About this file

This is a design-build project specification document for the installation of a 180 kW DC electric vehicle charging station at Grand Vista Hotel, located at 11597 Scott Highway, Helenwood, Tennessee 37755. The project involves the installation of two ABB Terra 184 dual-port CCS DC fast chargers, providing a total of 360 kW capacity with all four ports capable of charging simultaneously. The scope of work encompasses a complete design-build delivery model requiring the contractor to perform site surveys, geotechnical investigations, and provide a full professional engineer-sealed design package from a Tennessee-licensed engineer. The project includes utility coordination with Plateau Electric Cooperative for service application and capacity verification of the existing 500 kVA pole-mounted transformer, along with installation of a new utility pole, metering infrastructure, and all associated electrical distribution components. Civil work comprises four EV parking stalls (three standard and one ADA-accessible with designated access aisle), concrete charger slab foundations, steel bollards, site trenching, asphalt work, and accessible routes. The anticipated construction period is March 1 through April 30, 2027. All permits, inspections, local authority approvals, and Tennessee 811 locates are the contractor's responsibility. The project requires phased construction to maintain active hotel operations, guest access, fire lane availability, and coordination of work hours with the site host.

The contract is structured as a fixed-price lump sum arrangement with 10% retainage. Contractor qualifications must include a Tennessee State Electrical License and EVITP certification. The deliverables include commissioning and testing of every charging port, connection to the owner's network and OCPP 2.0.1 services, comprehensive EV signage and site finishing, electrical labeling, and emergency disconnect capability. The contractor must provide a five-year warranty, a five-year operations and maintenance plan including quarterly preventive maintenance and 24/7 remote monitoring, and a five-year service level agreement guaranteeing 97% uptime per port with 24/7 driver support available in English and Spanish. All utility fees and make-ready costs are included within the lump sum price. The charging stations must support CCS1 minimum with NACS-capable equipment welcome, operate on open access protocols, and accept contactless card/RFID and QR code payments.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VICINITY MAP

COMMERCIAL

GRAND VISTA HOTEL COMMERCIAL : 11597 SCOTT HWY, HELENWOOD, TN 37755

(2) 180 KW DC ELECTRIC VEHICLE CHARGING STATION

11597 Scott Hwy, Helenwood, TN 37755

11597 Scott Hwy, Helenwood, TN 37755

N

NOWNER : INSTALLER :

INSTALLATION OF THE NEW ELECTRIC VEHICLE CHARGING

STATION (EVCS) USED FOR ELECTRIC VEHICLE CHARGING.

EVSE IS INTEGRATED WITH THE NEW METER

SCOPE OF WORK:

GRAND VISTA HOTEL

11597 SCOTT HWY,

HELENWOOD, TN 37755

EQUIPMENT SUMMARY :

02 QTY - ABB TERRA 184 DUAL PORT CCS DC FAST CHARGERS

SHEET INDEX :

T-01 COVER SHEET

G-01 GENERAL NOTES

EV-01 SITE MAP & PROPERTY LAYOUT

EV-02 SITE PLAN

C-01 ELEVATION VIEW & FOUNDATION DETAILS (A) - DISCONNECT

C-02 ELEVATION VIEW & FOUNDATION DETAILS (B) - EV CHARGER

EV-03 ELECTRICAL THREE-LINE DIAGRAM

EV-04 SYSTEM LABELING DETAILS

EV-05 EV CHARGER DATA SHEET

EV-06 AC DISCONNECT DATA SHEET-1

EV-07 AC DISCONNECT DATA SHEET-2

2021 INTERNATIONAL BUILDING CODE

2021 INTERNATIONAL FIRE CODE

2021 INTERNATIONAL EXISTING BUILDING CODE

2017 NATIONAL ELECTRICAL CODE

CODE REQUIRED:

UNIVERSAL EV LLC

305 W SPRING CREEK PKWY,

SUITE 100 B, PLANO, TX 75023

T-01

01 AK AD 08.24.26

02 VP AD 08.25.26

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

http://www.nordicasia.net

G-01

GENERAL NOTES :

1. INSTALLATION SHALL COMPLY WITH ALL APPLICABLE LAWS, CODES,

GOVERNMENT REGULATIONS, UTILITY COMPANY REQUIREMENTS, ETC. OF ALL

AUTHORITIES HAVING JURISDICTION IN EFFECT AT THE TIME OF THE BUILDING

PERMIT.

2. WHERE CONFLICTS EXIST BETWEEN CODES, STANDARDS OR THIS SPECIFICATION,

THE HIGHER REQUIREMENT SHALL APPLY.

3. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE SAFETY OF HIS WORKERS,

ALL CONSTRUCTION MEANS, METHODS,TECHNIQUES, SEQUENCES AND

PROCEDURES FOR COORDINATING THE WORK UNDER THIS CONTRACT.

4. CONTINUOUSLY MAINTAIN THE CONSTRUCTION PREMISES IN A NEAT AND

ORDERLY CONDITION. DAMAGE TO FINISHES SHALL BE PROPERLY RESTORED.

5. EVSE ENCLOSURE SHALL BE NEMA RATED.

6. EVSE CORD LENGTH SHALL NOT EXCEED 25'.

7. EVSE CHARGING STATIONS HAS 4 DOORS I.E. FRONT, REAR, LEFT AND RIGHT.

CLEAR 24” DISTANCE ON THE FOUR SIDES OF A CHARGER TO BE MAINTAINED FOR

AIR CIRCULATION FOR COOLING AND OPENING PANEL FOR MAINTENANCE.

8. MECHANICAL AND ELECTRICAL SUPPORT COMPONENTS, INCLUDING STRUT AND

HARDWARE, SHALL BE HOT DIPPED GALVANIZED OR EQUIVALENT

ELECTROPLATED FINISH.

9. ALL GROUNDED CONDUCTORS ARE WHITE AND EQUIPMENT GROUNDING

CONDUCTORS ARE GREEN OR BARE PER (NEC 200-6 (A), EX 5).

10. LIQUID TIGHT FLEXIBLE METAL CONDUIT IS GENERALLY SUITABLE FOR

INSTALLATION IN WET AND DRY LOCATIONS. SHOULD IT BE EMPLOYED, SUPPORTS

WILL BE NO MORE 12 INCHES FROM BOXES (JUNCTION BOX, CABINETS, OR

CONDUIT FITTING) AND NO MORE THAN 54 INCHES APART PER NEC.

11. ALL CONDUCTORS BELOW 100A SHALL BE COPPER, UNLESS OTHERWISE NOTED.

12. IN ORDER TO PROVIDE ACCESSIBLE OPERATION OF EVSE, A 3’ BY 3’ (MINIMUM)

HANDICAPPED ACCESSIBLE OPERATING AREA MUST BE KEPT CLEAR OF VEHICLES

AND SNOW BETWEEN THE NOSE OF THE VEHICLE AND THE EVSE.

13. RELIABLE PROTECTIVE GROUNDING MUST BE PROVIDED. IT IS RECOMMENDED TO

HAVE SEPARATE DEDICATED GROUND EXCLUSIVELY FOR THE CHARGER

CONSIDERING THE SAFETY ASPECTS. THE GROUND RESISTANCE SHOULD BE LESS

THAN OR EQUAL TO 4ΩCOPPER CABLE OF IN ACCORDANCE WITH NEC SHALL BE

USED TO CONNECT CHARGE HOUSING TO EXTERNAL GROUND.

14. THE RACEWAY SHALL NOT BE LESS THAN TRADE SIZE 1 (NOMINAL 1-INCH INSIDE

DIAMETER). THE RACEWAY SHALL ORIGINATE AT THE MAIN SERVICE OR

SUB-PANEL AND SHALL TERMINATE INTO A LISTED CABINET, BOX OR ENCLOSURE

IN CLOSE PROXIMITY TO THE PROPOSED LOCATION OF THE EV SPACE.

15. LOCATION OF INSTALLATION IS NOT LOCATED WHERE EXCESSIVE WATER

RUN-OFFS, POOLING OR FLOODING MAY OCCUR.

16. EXTERIOR SIGNS AND ZONING CONCERNS PER SITE REQUIREMENTS.

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

EV CHARGE

ONLY

BOLLARDS

MAIN SERVICE

DISCONNECT

UTILITY METER

PR

O

PE

R

TY

L

IN

E

PROPERTY LINE

ELECTRIC VEHICLE

PARKING

FIRE LANE

DRIVEWAY

SC

O

TT

H

W Y

B C-02

EV SIGNBOARD

CHARGER SLAB FOUNDATION

5' 11'

19'

18'

ACD-1ACD-2

MET MSD

113'-7"

244'-8"

2'

-1

'-2

'-2

87'-8"

'-1

211'-1"

6'

-1

PROPERTY LINE

PROPERTY LINE PROPERTY LINE

PR

O

PE

R

TY

L

IN

E

DRIVEWAY DRIVEWAY

DRIVEWAY

ELECTRIC VEHICLE SUPPLY

EQUIPMENT LEVEL-3 - 1 & 2

(TERRA 184 DUAL PORT CCS)

C C-01

A C-01

FUSED AC DISCONNECT-1&2

41'-10"

1'-10"

SC

O

TT

H

W Y

NEW UTILITY POLE P2

EXISTING 500KVA POLE MOUNTED

TRANSFORMER ON P1 POLE

8' PR

O

PE

R

TY

L

IN

E

96'-8"

8'8'8'

2'-11"

20'-11"

EV-01

PROPERTY LAYOUT

SITE MAP

N

E

S

W270

350 0 10

4O

170180190

NOTE:

1. Do not let the flammable, explosive or flammable materials, chemicals, flammable vapors, and other dangerous goods close to charging station.

Scale - 1" = 45'

- EV parking

LEGENDS :-

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

11597 Scott Hwy, Helenwood, TN 37755

01 AK AD 08.24.26

02 VP AD 08.25.26

EV CHARGE

ONLY

BOLLARDS

MAIN SERVICE

DISCONNECT

UTILITY METER

ELECTRIC VEHICLE

PARKING

FIRE LANE

EV SIGNBOARD

CHARGER SLAB

FOUNDATION

8' 8' 8' 5' 11'

19'

18'

ACD-1ACD-2

MET MSD

DRIVEWAY

ELECTRIC VEHICLE SUPPLY

EQUIPMENT LEVEL-3 - 1 & 2

(TERRA 184 DUAL PORT CCS)

A C-01

FUSED AC

DISCONNECT-1&2

41'-10"

1'-10"

EXISTING 500KVA POLE MOUNTED

TRANSFORMER ON P1 POLE

C C-01

B C-02

8'

NEW UTILITY POLE P2

96'-8"

2'-11"

20'-11"

EV-02

SITE PLAN

N

E

S

W270

350 0 10

4O

170180190

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

- EV parking

LEGENDS :-

01 AK AD 08.24.26

02 VP AD 08.25.26

12"x12"x5' WIRING - GUTTER BOX

(HAMMOND, C3RWT1260)

GROUND

LEVEL

LIN

E

LO

AD

RESERVED FOR UTILITY

LIN

E

LO

AD

400A FUSED

DISCONNECT-1

LIN

E

LO

AD

600A FUSED

DISCONNECT

400A FUSED

DISCONNECT-2

6'

8' 8'

7' 7'

3' -9

10"

3' -1

0"

5' (M ax .6

'-7

FRONT VIEW REAR VIEW SIDE VIEW

3'

CONCRETE PIER

3" INTERMEDIATE

METAL CONDUIT (IMC)

UNISTRUT

U BOLTS

TOP VIEW

U BOLT

3" POST

PLATE

SS HEXAGONAL BOLTS

UNISTRUT RAIL

4'

TOP VIEW

CONCRETE

FOUNDATIONBOLLARDS

Ø5.5"

1'-8"

GROUND

LEVEL

1'-8"

1' -8

CAP

ULINE H-9089 5.5" DIA DUCTILE

IRON STEEL PIPE BOLLARD

SECTION VIEW

CONCRETE

FOUNDATION

C-01

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

ELEVATION VIEW & FOUNDATION DETAILS (A) - DISCONNECT

FOUNDATION DETAILS (C) -BOLLARDS U BOLT CONNECTION DETAILS

NOTE:

1) Measure the distance from the finished grade to the center of the meter base. This height must be between 4.5 feet and 5.5 feet, as required by the utility provider.

2) Service disconnects should be installed at a height between 4 feet and 6 feet 7 inches above the finished floor or grade for accessibility and ease of use.

Per the National Electrical Code (NEC), the maximum allowable height for the center of the service disconnecting means (SDM) handle is 6 feet 7 inches (2.0 meters) above the floor or ground.

2' -1

1"

1'-10"

6' -3

1'-10"2'-11"

2'-6" 2"5"

3'-1" 1'-7"2" 2"

2'

6' -7

EXISTING ASPHALT

GRADE

3'-2" 2'-6"

EXISTING ASPHALT

GRADE

6"

FRONT VIEWSIDE VIEW

CHARGER SLAB

FOUNDATION (FRONT)

CHARGER SLAB

FOUNDATION (SIDE)

HOLES TO INSTALL

THE EVSE TO

GROUND/FOUNDATION

(M10 BOLT)

EVSE CABINET

FOOTPRINT

M25 CABLE GLANDS

EVSE BASE FOOTPRINT

CHARGER SLAB

FOUNDATION CHARGER SLAB

FOUNDATION

SLEEVE

ANCHORS

SLEEVE

ANCHORS

Grade Level

Electric Cables (in Conduit)

A

Width Determined by Number of Electric

Conduit

C-02

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

NOTE:

1. Charger slab foundation shall be of concrete slab with the dimensions of 3'-2" length x 2'-6" width, to accommodate the weight and dimensions of the EV charger base.

ELEVATION VIEW & FOUNDATION DETAILS (B) - EV CHARGER

UNDERGROUND ELECTRICAL

CONDUIT - SECTION DRAWING

#2 AWG Bare Green (CU)

Acorn Clamp

8'

5/8" X 8' (Cu) Grounding Electrode Rod

Grade Level

EV-03

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

GROUND ROD

CONNECTION

DRAWING - DETAIL A

(2) 180 kW DC ELECTRIC VEHICLE CHARGING STATION THREE-LINE DIAGRAM

(N)-NEW

(E)-EXISTING

NOTE:

1. Raceways and associated conductors installed for Direct Current Fast Charging (DCFC) stations must be capable of accommodating 480V dedicated branch circuits.

2. All conductor's ampacity is based on 75°C rated insulation.

ELECTRIC VEHICLE

CHARGER -1 (N)

ABB Terra 184 Dual Port CCS DC Fast Charger

ELECTRIC VEHICLE

CHARGER -2 (N)

ABB Terra 184 Dual Port CCS DC Fast Charger

ORANGE - L2

BROWN - L1

GREEN - GROUND

UTILITY

METER

YELLOW - L3

CT

SENSOR

TRANSFORMER

500KVA (E)

CT CABINET (N)

277/480V, 600A Rated

FUSED

AC DISCONNECT 1&2 (N)

600V, 400A Rated,

(3) 300A (Class J) Fuses, Fused Metallic, Visible, Lockable, and labeled

Disconnect (VLLD)

65 KAIC, NEMA 3R

(SIEMENS HF365NRA)

4" PVC

(3)#500 kcmil THWN (AL) (1)#2 AWG THWN Ground (CU)

4" PVC

(3)#500 kcmil THWN (AL) (1)#2 AWG THWN Ground (CU)

WIRE WAY (N)

12"X12"X5'

NEMA 3R

2 X 4" PVC

2 X (4) #500 kcmil THWN (AL)

MAIN

SERVICE DISCONNECT (N)

600V, 600A Rated,

(3) 600A (Class J) Fuses, Fused Metallic Visible, Lockable, and labeled

Disconnect (VLLD)

65 KAIC, NEMA 3R

(SIEMENS HF366NRA)

WIRE WAY (N) - NEMA 3R

2 X (3)#500 kcmil THWN (AL) 2 X (1)#2 AWG THWN Ground (CU)

#2 AWG Bare Green (CU)

(2) 5/8" X 8' (CU) (Minimum) Rod-Type Grounding Electrode

Detail - A

Supply Side Bonding Jumper

Main Bonding Jumper

2 X (4)#500 kcmil THWN (AL) 2 X (1)#2/0 AWG THWN Ground (CU)

WIRING AND CONDUIT SCHEDULE

ID DESCRIPTION VOLTAGE

(V)

Full Load Amperage

(A)

Full Load Amperage X

1.25% (A)

OCPD

rating (A)

Multiple conductor

Derate

Temperature Derate

Max ONE

WAY

LENGTH

(ft)

WIRE SIZE

Wire

Ampacity (A)

GROUND WIRE

TYPE R/1000FT V LOSS % TEMP

MAX

TOTAL NO OF

CONDUCTORS

NO. OF

CURRENT

CARRYING

CONDUCTOR

CONDUIT

ELECTRIC VEHICLE

CHARGER-1&2 TO

FUSED AC

DISCONNECT 1&2

480 230.00 287.50 300 1.00 0.94 25 #500 Kcmil (AL) 310 #2 AWG (CU) THWN 0.0424 0.09% 32C 4 3 4" PVC Min

FUSED AC

DISCONNECT 1&2 TO

MAIN SERVICE

DISCONNECT

480 230.00 287.50 300 1.00 0.94 5 #500 Kcmil (AL) 310 #2 AWG (CU) THWN 0.0424 0.02% 32C 4 3 4" PVC Min

EV-04

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

SYSTEM LABELING DETAILS

NOTE:

1. The enclosure must be NEMA-rated as per NEC 110.28.

2. Cord length will reach vehicle's inlet without excessive slack and must be no more than 25' in length as per NEC 625.17.

3. Equipment operating above 50 volts must be protected against physical damage as per NEC 110.27.

4. For EVCS greater than 60 amperes, a separate disconnect is required and should be installed concurrently with conduit and visible from EVCS as per NEC 625.23.

5. Conductors should be sized to support 125% of the rated equipment as per load NEC 625.21.

CAUTION

DANGER OF ELECTRIC SHOCK

DO NOT TOUCH THE APPARATUS

WITH WET HAND.

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

EV-05

EV-06

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

EV-07

IN

ST

AL

LE

R

O W

N

ER

G

R

AN

D V

IS

TA

H O

TE

L

SC

O

TT

H W

Y, H

EL

EN

W O

O D

, T N

U N

IV

ER

SA

L

EV

L

LC

W

S

PR

IN

G

C R

EE

K

PK

W

Y, SU

IT

E

B, P

LA

N

O , T

X

VER DRAWN

BY

CHK'D

BY DATE

00 SR AD 05.15.26

Sheet No

Job ID

Page No

UNE-26-65

of 11

Revision REV-02

DESIGNED BY

www.nordicasia.net

NORDIC ASIA

http://www.nordicasia.net

11597 Scott Hwy, Helenwood, TN 37755, United States-001
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-002
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-E001
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-E002
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-E003
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-S001
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-E004 SLD
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-E005
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-E006
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-003
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1
11597 Scott Hwy, Helenwood, TN 37755, United States-EV-09
11597 Scott Hwy, Helenwood, TN 37755, United States - OLE1

File details come from the government source that posted it. Updated .