RFI_Questions_and_Responses_5_July_2017.pdf
PDF 221 KB Posted
- Attached to
- FA2550-17-R-1012 Solicitation Federal contract opportunity
- Solicitation number
- GLEN_12_1036_FA2550_17_R_1012
About this file
RFI #3 Responses
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFI__4_Questions_and_Responses.docx.pdf | ||
| Building_805_Concrete_Pavement_Details.pdf | ||
| General_Decision_Number.pdf | ||
| GLEN_15-2020_Site_Layout_Plan_showing_concrete_slab_in_question.pdf | ||
| RFI_Questions_and_Responses.pdf | ||
| GLEN_12-1036_RFIs.pdf | ||
| 5_Design_Guide_Version_March_2016.pdf | ||
| 4_Schriever_B800_Sanitary_Sewer_Specifications.pdf | ||
| 3_Schriever_B800_Sanitary_Sewer_Drawings.pdf | ||
| 8_WD_CO20160012.pdf | ||
| 1_12-1036_1442.pdf | ||
| 6_01_57_20.04_SAFB_Overreaching_Environmental.pdf | ||
| 2_GLEN_12-1036_SOW.pdf | ||
| 7_GLEN_12-1036_Form_66_Repair_Sewer_Industrial_Area.xls | XLS spreadsheet |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GLEN 12-1036 Sanitary Sewer RFI #3
RFI Questions and Responses
1. The current wage decision for this project is Heavy CO12 dated 2‐3‐2017 but there has been an update which is dated 6‐9‐2017. Will there be an amendment to revise the wage decision?
a. Government Response: The revision will be posted on FBO with this notice.
2. The Sewer Manhole detail on sheet 8, note 8; states all manhole exteriors shall be coated with waterproofing, however SMH-12 on sheet 5 is the only manhole to be called out as being coated. Can you please clarify if all manholes received exterior waterproofing or just SMH-12.
a. Government Response: Please provide exterior waterproofing for all new manholes.
3. The detail on Sheet 7 for the existing SMH-13 call for interior coating, is this the only manhole to receive interior coatings?
a. Government Response: Yes, SMH-13 is the only manhole to receive this interior coating.
4. Please confirm if the Lift Station, SMH-11 should receive interior and/or exterior coatings?
a. Government Response: Please provide exterior waterproofing for SMH-11.
5. What is the thickness of the concrete slab at the northeast end of Building 805?
a. Government Response: Thickness varies, please see attached details “Building
805 Concrete Pavement Details,” T = 6 inches.