GFI_Fire Alarm System Tested Components.pdf
PDF 60 KB Posted
- Solicitation number
- 040ADV-26-R-0021
- Issued by
-
Government Publishing Office
About this file
This document contains fire alarm system testing results for four buildings, presenting pass/fail data for various alarm components across each facility.
Building A tested 919 total items with 896 passing and 23 failing, representing a 97.5% pass rate. Smoke detectors comprised the largest component category with 615 units tested (10 failures). Other notable components included pull stations (77 tested, 1 failure), batteries (75 tested, 0 failures), and expander panels (38 tested, 0 failures). Components with higher failure rates included duct detectors (4 failures of 13 tested) and heat detectors (3 failures of 14 tested).
Building B demonstrated superior performance with 276 total items tested and only 2 failures, achieving a 99.3% pass rate. Smoke detectors again represented the largest category with 173 units tested (1 failure). All annunciators, batteries, heat detectors, horn/strobes, phone stations, power supplies, pull stations, speakers, and strobes achieved perfect pass rates. Only smoke detectors and speaker/strobes each recorded one failure.
Building C tested 907 total items with 887 passing and 20 failing, yielding a 97.8% pass rate. Smoke detectors dominated the testing with 661 units tested (7 failures). Pull stations showed the highest failure concentration with 8 failures among 55 tested units. Batteries, phones stations, horn/strobes, and strobes each recorded between 1-2 failures across their respective test populations.
Building D tested the smallest sample with 220 total items and 6 failures, achieving a 97.3% pass rate. Smoke detectors (123 tested, 2 failures) and pull stations (19 tested, 3 failures) comprised the primary test categories. Amplifiers, batteries, duct detectors, expander panels, horn/strobes, speakers, and strobes all achieved perfect pass rates.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING A FIRE ALARM SYSTEM TESTED ITEMS
Passed Failed Annunciator 1 0
Battery 75 0 Duct Detector 9 4
Emergency Power Supply 4 0 Expander Panel 38 0 Heat Detector 11 3 Horn/Strobe 9 1
Phone Station 32 3 Pull Station 77 1
Smoke Detector 615 10 Speaker/Strobe 13 0
Speaker 1 0 Strobe 11 1 Total 896 23 Grand Total 919
BUILDING B FIRE ALARM SYSTEM TESTED ITEMS
Annunciator 2 0
Battery 14 0 Heat Detector 12 0 Horn/Strobe 9 0
Phone Station 19 0 Power Supply 7 0
Pull Station 19 0 Smoke Detector 173 1 Speaker/Strobe 9 1
Speaker 1 0 Strobe 9 0 Total 274 2 Grand Total 276
BUILDING C FIRE ALARM SYSTEM TESTED ITEMS
Annunciator 1 0
Battery 56 2 Control Panel 1 0
Expander Panel 35 0 Heat Detector 2 0 Horn/Strobe 8 1
Phone Station 35 1 Power Supply 20 0
Pull Station 47 8 Smoke Detector 661 7 Speaker/Strobe 12 0
Strobe 9 1 Total 887 20 Grand Total 907
BUILDING D FIRE ALARM SYSTEM TESTED ITEMS
Amplifier 14 0 Battery 22 0
Duct Detector 3 0 Expander Panel 7 0
Horn/Strobe 1 0 Phone Station 15 1
Pull Station 19 3 Smoke Detector 123 2
Speaker 5 0 Strobe 5 0 Total 214 6 Grand Total 220