Floyd_Little_Moisture_Probing_Report.pdf
PDF 668 KB Posted
- Attached to
- Floyd Little Athletic Center Flooring
- Solicitation number
- 2026-ITB-369
- Issued by
- New Haven County, Connecticut
About this file
This is a moisture probing test report prepared by Materials Testing, Inc. for the City of New Haven Engineering Department regarding the Floyd Athletic Center Improvements project. The report documents the results of ASTM F2170 relative humidity testing conducted on the interior concrete slab of the Floyd Athletic Center located at 480 Sherman Parkway in New Haven, Connecticut. Materials Testing, Inc. drilled 44 pre-selected areas in the concrete slab on February 7, 2025, at 10:30 AM, at a depth of 4 inches into an approximately 10-inch-thick slab. Relative humidity measurements were recorded on February 10, 2025, at 11:00 AM using a calibrated RapidRH Model L6 instrument. The testing was conducted under ambient conditions of 71°F and 41% humidity.
The moisture probing results reveal significant variation across the tested areas, with relative humidity readings ranging from 70% to 98%. Several test locations (1, 2, 8, 10, 11, 12, 13, 29, 34, 35, and 44) could not be recorded due to water-filled holes after drilling or damaged sensors, indicating notable groundwater presence in certain areas of the slab. Elevated humidity readings, particularly in the range of 87% to 98%, were documented in multiple locations, with the highest concentrations in the central and eastern portions of the measured area. These results are critical for the planned moisture mitigation work specified in the Floyd Little Athletic Center Flooring project, which includes slab-on-grade moisture mitigation as a key component prior to installation of new resilient flooring in hallways, atriums, vestibules, and stairways.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MATERIALS TESTING, INC.
55 LAURA STREET • NEW HAVEN, CONNECTICUT 06512 • (203)468-5216
WWW.MTIES.COM
DATE: 02-10-2025
REPORT NO: S-1000
CLIENT: City of New Haven - Engineering Dept.
200 Orange Street, Room 504
New Haven, CT 06510
Attn: Mr. Zach Shapiro, PE
PROJECT: Floyd Athletic Center Improvements
PO No. 20251613-00
480 Sherman Parkway
New Haven, CT
SUBJECT: ASTM F2170 “STANDARD TEST METHOD FOR DETERMINING RELATIVE HUMIDITY IN
CONCRETE FLOOR SLABS USING IN SITU PROBES”
DATE OF DRILLING: 02-07-25 TIME OF DRILLING: 10:30 AM
DATE OF MEASUREMENT: 02-10-25 TIME OF MEASUREMENT: 11:00 AM
INSTRUMENT: RapidRH Model L6 LAST CALIBRATION: 10-01-2024
SLAB THICKNESS: approx. 10"
DEPTH OF DRILLING: 4"
AMBIENT AIR TEMPERATURE ABOVE THE PROBES: 71 EF
AMBIENT HUMIDITY ABOVE THE PROBES: 41 %
On 02-07-25 RH sleeves were placed in 44 pre-selected areas of the interior concrete slab of the Floyd
Athletic Center. The results were recorded and are listed on the next page.
Note: See attached drawing for location of RH sleeves (* Indicates ground water present)
Temperature Relative Humidity Observations 1 - - Water filled hole after drilling 2 - - Water filled hole after drilling
3 68 EF 71%
4 67 EF 78%
5 68 EF 78%
6 68 EF 79%
7 68 EF 78%
8 - - Water filled hole after drilling
9 68 EF 70%
10 - - Water filled hole after drilling 11 - - Water filled hole after drilling 12 - - Water filled hole after drilling 13 - - Water filled hole after drilling
14 70 EF 93%
15 70 EF 87%
16 69 EF 87%
17 70 EF 91%
18 70 EF 93%
19 71 EF 93%
20 70 EF 94%
21 68 EF 79%
22 68 EF 79%
23 71 EF 88%
24 70 EF 83%
25 70 EF 85%
26 71 EF 88%
27 70 EF 92%
28 71 EF 94%
29 - - Damaged sensor
30 71 EF 98%
31 71 EF 97%
32 71 EF 89%
33 71 EF 97%
34 - - Water filled hole after drilling 35 - - Water filled hole after drilling
36 71 EF 88%
37 70 EF 89%
38 70 EF 88%
39 70 EF 89%
40 71 EF 95%
41 71 EF 94%
42 71 EF 94%
43 71 EF 95%
44 - - Water filled hole after drilling
Test reports may not be reproduced, except in full, without the express permission of Materials Testing, Inc. Results only relate to items tested. When information is provided by others and included in the report, there is potential for affecting the validity of results.
Basketball court
22 21 20 19