RFI- 7.18.2019
Q. Is there room for two containers?
A. Physical space is not the driving issue. Our firm power budget is 400A @ 480 3ph and pulling additional power from our substation is not within our budget forecast.
One container of this design may be fairly close to the power budget, but they should run performance estimates against our specification – I think we are looking for more CFM at higher pressures than Tunnel 9 was, i.e. more ‘roughing’ capacity than low-end boost.