19ba3_Additional_Information_2.docx
DOCX document 12 KB Posted
- Attached to
- Modernize C4 Restrooms/Break Area Federal contract opportunity
- Solicitation number
- FA875119BA003
About this file
Questions and Answers #2
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 221316_FL_-_Sanitary_Waste_and_Vent_Piping_RFI_5.pdf | ||
| 19ba3_Additional_Information_5.docx | DOCX document | |
| Solicitation_Amendment_2_FA875119BA0030002_SF_30.pdf | ||
| 19ba3_Additional_Information_4.docx | DOCX document | |
| Solicitation_Amendment_FA875119BA0030001_SF_30.pdf | ||
| 19ba3_Additional_Information_3.docx | DOCX document | |
| A_-_18841_Rome_AF_B-3_asbestos_lead.pdf | ||
| 19ba3_Additional_Information_1.docx | DOCX document | |
| Solicitation_-_FA875119BA003.pdf | ||
| 19ba3_Attach_3_AFRL_RI_Suppl_Rqmts.pdf | ||
| 19ba3_Attach_5_RRS_Visit_Authorization_Rqst.pdf | ||
| 19ba3_Attach_4_Wage_Decision.pdf | ||
| 19ba3_Attach_1_Project_Specifications.pdf | ||
| 19ba3_Attach_1a_Project_Specs_Addendum_1.doc | DOC document | |
| 19ba3_Attach_2_Project_Drawings.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA875119BA003
REQUEST FOR INFORMATION #2 – POSTED 12 AUGUST 2019
Question 1. Referencing Drawings A-002, AE501&502, please clarify the required partition heights and the elevation of structure above for connection of MEP hangers and ceiling support system .
Answer 1. Partition type 980 demising the Shared Restroom (C4-B) and ADA Toilet (C4-A) from the Employee Break Room (B4-E) shall extend to the structural deck above - approximately 22'-2" AFF.
Partition type 920 demising the East Corridor from the ADA Toilet rooms (C4-C and C4-A) and Vestibule (C4-VEST) shall extend to the structural deck above - approximately 22'-2" AFF.
Also for clarification, any partition, not specifically called out above, shall be of metal stud and GWB extended to 10'-0" AFF.
Unless noted above, all partition types that receive sound attenuation / mineral fiber insulation (see Section 081213, 2.4E) to extend insulation 6" AFC. All unsupported insulation above the ceilings shall be held in place per notes on sheet A-002.
Note: Rather than extending sound insulation to deck for all type 920 partitions not specifically identified above, it is acceptable for insulation to be laid on top of the ceilings of all toilet stalls in the Shared Restroom (C4-B) and ADA toilets (C4-A & C4-C) instead.
Question 2. Is there an asbestos/HAZMAT survey?
Aanswer 2. Yes, attached separately.