F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

FIRE SUPPRESSION DESIGN NOTES

A FSC SHALL REMOVE ALL EXISTING SPRINKLER

PIPING, EQUIPMENT, HANGERS, AND ALL

ASSOCIATED APPURTENANCES BACK TO SERVICE

PIPE ENTRY TO BUILDING. FSC SHALL CAP PIPING

AT FLANGE.

B ALL PIPING IS AT THE UNDERSIDE OF STRUCTURE IN

EXPOSED STRUCTURE AREAS) UNLESS OTHERWISE

INDICATED ON DRAWINGS.

C REFER TO ARCHITECTURAL DRAWINGS FOR

REFLECTED CEILING PLANS AND GENERAL

TRADES CONSTRUCTION INFORMATION.

COORDINATE SPRINKLER LOCATIONS WITH CEILING

DEVICES (LIGHTING, GRILLES, ETC.) OBTAIN

ARCHITECTS APPROVAL OF SPRINKLER LAYOUT PRIOR

TO INSTALLATION. FINAL FINISHED APPEARANCE OF

WORK MUST BE APPROVED BY THE GOVERNMENT.

D EXERCISE SPECIAL CARE TO COORDINATE PIPING

AND EQUIPMENT LOCATIONS WITH ALL OTHER

TRADES.

E CONTRACTOR SHALL MAKE REQUIRED WATER

FLOW TESTS, LAYOUT FIRE SUPPRESSION

SYSTEMS, OBTAIN APPROVALS FROM THE

AUTHORITY HAVING JURISDICTION BEFORE STARTING

INSTALLATION OF SYSTEM.

F FIRE SUPPRESSION CONTRACTOR SHALL INSTALL

COMPLETE AUTOMATIC WET AND DRY PIPE

SPRINKLER SYSTEMS INDICATED ON DRAWINGS

THROUGHOUT THE BUILDING AS REQUIRED PER

IBC, IFC, UFC, NFPA 13 AND LOCAL INSPECTION

AGENCY GUIDELINES. BUILDING SHALL BE TOTALLY

SUPPRESSED.

G BASIS FOR DESIGN OF FIRE SUPPRESSION

SYSTEM(S) TO BE:

WET PIPE SYSTEMS:

1 LIGHT HAZARD (OFFICE AREAS) 1500

SQUARE FEET, DESIGN DENSITY 0.10

GPM/SQ. FT., 225 SQUARE FEET MAXIMUM

PER SPRINKLER, 500 GPM HOSE

ALLOWANCE.

2 PALLETIZED, SOLID-PILED, BIN BOX, OR

SHELF STORAGE OF PLASTIC AND RUBBER

COMMODITIES (NFPA 13, 15.2 FOR STORGE

HEIGHT OF 16 FEET, AND ROOF/CEILING

HEIGHT >30-35 FT, DESIGN DENSITY 0.73

GPM/SQ. FT., SPRINKLER COVERAGE BASED

UPON OPERATING PRESSURE AVAILABLE AT

SPRINKLER. RANGE OF COVERAGE

AREA/AVAILABLE PRESSURE 100(15.8 PSIG) -

196(60.5 PSIG) SQUARE FEET MAXIMUM PER

SPRINKLER, 500 GPM HOSE ALLOWANCE.

DRY PIPE SYSTEMS:

1 ORDINARY HAZARD GROUP I (ABOVE CEILING

AREAS OF STORAGE AREAS WHERE ROOF

HEIGHT EXCEEDS 35 FEET)1500 SQUARE

FEET, DESIGN DENSITY 0.15 GPM/SQ. FT., 130

SQUARE FEET MAXIMUM PER SPRINKLER, 250

GPM HOSE ALLOWANCE.

AREA OF OPERATION REDUCTIONS (FOR USE OF

QUICK RESPONSE SPRINKLERS) AND INCREASES

(FOR SLOPED CEILINGS AND DRY PIPE ZONES) WHERE

APPLICABLE SHALL BE CALCULATED PER NFPA

STANDARDS. VERIFY DENSITIES WITH GOVERNING

AUTHORITIES BEFORE PROCEEDING WITH DESIGN OF

SYSTEM(S). IF GOVERNING AUTHORITIES

REQUIREMENTS ARE MORE STRINGENT THOSE

REQUIREMENTS SHALL PREVAIL.

H PROVIDE THE FOLLOWING SPRINKLER TYPES,

UNLESS OTHERWISE NOTED ON THE DRAWINGS.

SPRINKLER HEADS TO BE LOCATED IN THE CENTER

OF A 2x2 CEILING TILE OR A 2x2 SECTION OF A 2x4

TILE.

1 SPRINKLERS IN OFFICE AREAS WITH CEILINGS

SHALL BE RECESSED PENDENT QUICK RESPONSE

TYPE WITH ESCUTCHEON PLATE AND WHITE FINISH

UNLESS OTHERWISE NOTED.

2 SPRINKLERS IN WAREHOUSE AREAS SHALL BE

EXTENDED COVERAGE "CONTROL MODE"

SPRINKLERS, HAVING A NOMINAL K-FACTOR OF 25.2.

3 PROVIDE DRY PENDANT RECESSED QUICK

RESPONSE SPRINKLERS WITH WHITE FINISH

THROUGHOUT ALL FINISHED AREAS SUPPLIED

FROM THE DRY PIPE SYSTEM(S).

4 PROVIDE DRY UPRIGHT SPRINKLERS ABOVE

CEILINGS IN WAREHOUSE.

I ALL PIPING AND EQUIPMENT SIZES SHOWN HAVE BEEN

CALCULATED BASED UPON EXISTING HYDRAULIC

CONDITIONS AND BASED UPON USING SPRINKLER

COVERAGE AREA/OPERATING PRESSURE OF 150 (35.4

PSIG) SQ FT. FSC MAY MODIFY PIPE AND/OR

EQUIPMENT SIZING AND SPACING OF SPRINKLERS AND

STANDPIPES PROVIDED HYDRAULIC CALCULATIONS

PERFORMED BY THE FSC INDICATES OTHER

PIPE/EQUIPMENT SIZES ARE ACCEPTABLE.

J ALL STANDPIPE HOSE VALVES SHALL BE INSTALLED AT

42" AFF.

K PIPE ROUTING AND ELEVATIONS INDICATED SHOWS

DESIGN INTENT. FSC SHALL COORDINATE PIPE ROUTING

WITH EXISTING CONDITIONS.

L PIPING GREATER THAN 6" DIAMETER SHALL BE ROUTED

WITHIN TEN (10) FEET OF STRUCTURAL COLUMNS.

M EXTERIOR PIPE ROUTING IS BASED UPON DRAWINGS

INDICATING EXISTING CONDITIONS. FSC SHALL

DETERMINE AND COORDINATE ROUTING AND REQUIRED

OFFSETS/INVERTS PRIOR TO BIDDING.

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F001

LEGEND & NOTES

Designer Author Checker

SCALE: NONE

FIRE KEYPLAN

SHEET DESCRIPTION

F001 LEGEND & NOTES

F002 FIRE SUPPRESSION SITE PLAN

F003 ROOF PLAN

F004 DETAILS

F100 OVERALL FIRE SUPPRESSION FLOOR PLAN

F200 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA A

F201 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA B

F202 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA C

F203 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA D

F204 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA E

F205 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA F

F206 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA G

F207 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA H

F208 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA I

F209 PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA J

4 8

4 2

3"PVC

48"CONC

8"VCP

2.5"

2"HPS

2"CPR

14"CI

10"CI

6"CI

10"UNK

6" & 10" STEEL

STORM PIPE

8"CI

6"HPS

3"HPS

4"VR

2"HPR

6"HPS

3"HPS

4"VR

2"HPR

6"HPS

3"HPS

4"VR

2"HPR

6"VCP

6"VCP

8"CI

8"HPS

8"HPS

3"HPS

8"VCP

8"CI

15"VCP

10"STL

6"STL

12"VCP

8"VCP

CI PIPE

12"VCP

10"VCP

8"HTHW-R

8"HTHW-S

10"HTHW

2.5"HPS

2"CPR

6"VCP

8"CI

6"STL

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F002

FIRE SUPPRESSION SITE PLAN

Designer Author Checker

1" = 80'-0"

FIRE SUPPRESSION SITE PLAN

PLAN NOTES

1 CONNECTION OF NEW 12" FS PIPING TO EXISTING

14" MAIN. EXISTING MAIN WILL NOT BE SHUTDOWN,

PROVIDE "HOT TAP" PER SPECIFICATIONS.

2 FSC TO OFFSET 12" MAIN AS REQUIRED TO

ACCOMMODATE CROSSING EXISTING PIPING AT

THIS LOCATION.

3 FSC SHALL OFFSET 12" MAIN BELOW UTILITIES AND

STORM DRAINAGE PIPING LOCATED UNDER/NEAR

ROADWAY. APPROXIMATE DEPTH OF BOTTOM

INVERT IS 8' BELOW FINISHED GRADE. REPAIR

PAVEMENT AS REQUIRED.

4 FSC TO PROVIDE THRUST RESTRAINT AS REQUIRED

BY SPECIFICATIONS AT THIS LOCATION.

5 FSC TO OFFSET 12" MAIN AS REQUIRED TO

ACCOMODATE CROSSING VARIOUS PIPING AT THIS

LOCATION. INVERT OF PIPING TO BE AT LEAST 2'-0"

BELOW BOTTON OF 48" CONCRETE PIPE.

6 EXISTING HYDRANT TO REMAIN. PROVIDE NEW DRY-

BARREL HYDRANT FOR FACILITY SYSTEM. CONNECT

TO NEW PIPING. PAINT TOP OF HYDRANT RED TO

DESIGNATE IT AS SERVING FACILITY.

7 PROVIDE VALVE BOX.

8 FSC TO OFFSET 12" BUILDING LOOP AS REQUIRED TO

ACCOMMODATE CROSSING OF UTILITY AND/OR

DRAINAGE PIPING IN THIS LOCATION. ANY

ABANDONED PIPING ENCOUNTERED SHALL BE

REMOVED TO FACILITATE INSTALLATION OF NEW

PIPE.

9 REMOVE ANY ABANDONED PIPING ENCOUNTERED AT

THIS LOCATION TO FACILITATE INSTALLATION OF

NEW PIPING.

10 AS MUCH AS POSSIBLE, FSC SHALL AVOID REMOVING

EXISTING TREES WHILE INSTALLING PIPING.

11 FSC SHALL ROUTE PIPING AS CLOSE AS POSSIBLE TO

EXISTING RUN ON MULTIPLE PIPING.

PLAN NOTES - CONTINUED

12 10" FIRE SUPPRESSION SUPPLY INTO BUILDING.

REFER TO INTERIOR PLANS FOR CONTINUATION..

13 10" BUILDING LOOP SECTIONAL SHUT OFF VALVE.

PROVIDE VALVE BOX. VALVE SHALL BE PIV.

14 POST INDICATOR VALVE.

15 REMOVE EXISTING FS PIPE FROM INSIDE BUILDING

TO BACK TO MAIN. REPLACE TEE IN MAIN WITH

STRAIGHT SECTION OF PIPE.

WATER SUPPLY

BUILDING 172: FOUR (4) FIRE PUMPS 1000 GPM, 100 PSIG

BUILDING 172A: 300,000 GALLON WATER RESEVOIR

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F003

ROOF PLAN

Designer Author Checker

1" = 40'-0"

ROOF PLAN

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F004

DETAILS

Designer Author Checker

SCALE: N.T.S.

THRUST BLOCK DETAIL

SCALE: N.T.S.

FIRE RISER

STORAGE

SPRINKLER

ZONE C1

(35651 SF)

ORDINARY

HAZARD 2

SPRINKLER

ZONE

(25134 SF)

STORAGE

SPRINKLER

ZONE B3

(39591 SF)

STORAGE

SPRINKLER

ZONE B2

(20041 SF)

STORAGE

SPRINKLER

ZONE B1

(27078 SF)

EXTERIOR

STORAGE

SPRINKLER

ZONE A1

(27530 SF)

STORAGE

SPRINKLER

ZONE A2

(27345 SF)

STORAGE

SPRINKLER

ZONE A3

(29805 SF)

LIGHT HAZARD

SPRINKLER ZONE

(8435 SF)

LIGHT HAZARD

SPRINKLER ZONE

WITHIN THIS AREA

(3263 SF)

LIGHT HAZARD

SPRINKLER ZONE WITHIN

THIS AREA (887 SF)

STORAGE

SPRINKLER

ZONE C2

(13040 SF)

LIGHT HAZARD

SPRINKLER ZONE

WITHIN THIS AREA

(5712 SF)

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F100

OVERALL FIRE SUPPRESSION FLOOR PLAN

Designer Author Checker

1" = 40'-0"

OVERALL FIRE SUPPRESSION FLOOR PLAN

Z

19.2

1916141196

3.8

Z.5

Y X.5

V.8

U.3

S.8 1 / F203

F S

10"

-4' - 6"

16' - 0"

8" S

16' - 0"

FDC FDC

F D

C

8"

10" 4"

FDC

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F200

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA A

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA A

PLAN NOTES

1 LOCATION OF VERTICAL RISER CHECK VALVE

CONTROLLING SPRINKLER ZONE A1.

2 PROVIDE LIGHT HAZARD ZONE SPRINKLERS.

SCALE: NONE

FIRE KEYPLAN

X

31.8

27.5

25.2

22.5

20.219.2 V.8

U.3

S.8

F

F

1 / F204 1 / F204

F

16' - 0"

FDC

8"

S

S S

S

S S

18' - 0"

26' - 0"

27' - 0"

17' - 0"

26' - 0"

27' - 0"18' - 0"

17' - 0"

DESIGN ZONE A1

PILED STORAGE HAZARD

INCLUDE 500 GPM HOSE STREAM ALLOWANCE

DESIGN ZONE A2

PILED STORAGE HAZARD/LIGHT HAZARD

INCLUDE 500 GPM HOSE STREAM ALLOWANCE

10"

2.5"

4"

18' - 0"

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F201

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA B

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA B

PLAN NOTES

1 PROVIDE LIGHT HAZARD ZONE SPRINKLERS.

2 4" PIPE TO 2.5" FIRE HOSE VALVES.

3 2.5" FIRE HOSE VALVE, MOUNTED AT 42" AFF. MOUNT

INSTALL VALVE TO MINIMIZE OBSTRUCTIONS.

SCALE: NONE

36 37 38

P

Q

R

S

T

U

V

W

X

Z

32 35

V.8

U.3

S.8

R.3

P.8

F

1 / F201

1 / F204

1 / F2051 / F205

F

FDC

FS

10" -4' - 6" 21' - 0"

8"

18' - 0"

18' - 0"

26' - 0"

8"

F D

C F

D C

F D

C

16' - 0"

16' - 0"

S

DESIGN ZONE B1

PILED STORAGE HAZARD/LIGHT HAZARD/DRY ZONE

INCLUDE 500 GPM HOSE STREAM ALLOWANCE

D D

D

24' - 0"

16' - 0"

18' - 0"

2.5"

2.5"

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F202

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA C

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA C

PLAN NOTES

1 LOCATION OF VERTICAL RISER CHECK VALVE

CONTROLLING SPRINKLER ZONE B1.

2 DRY SPRINKLER ZONE PIPING LOCATED ABOVE NEW

CEILING.

3 PROVIDE LIGHT HAZARD ZONE SPRINKLERS.

4 2.5" PIPE TO 2.5" FIRE HOSE VALVES.

5 2.5" FIRE HOSE VALVE, MOUNTED AT 42" AFF. MOUNT

INSTALL VALVE TO MINIMIZE OBSTRUCTIONS.

6 PROVIDE PIPING TO 2.5" FIRE HOUSE VALVES FROM THIS

POINT.

SCALE: NONE

4 5 7 8 10 12 13 15 17 18

1916141196

3.8

S.8

R.3

P.8

N.3

L.8

K.3

H.8

1 / F200 1 / F200 1 / F201

1 / F204

1 / F207

1 / F204

1 / F207

F D

C

FS

FS

-4' - 6"

-4' - 6"

16' - 0"

S S

16' - 0"

17' - 0"

26' - 0"

17' - 0"

10"

10"

2.5"

15' - 0"

4"

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F203

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA D

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA D

PLAN NOTES

1 SUPPLY SHALL FEED SPINKLERS FOR OFFICE SPACE.

2 LOCATION OF VERTICAL RISER CHECK VALVE

CONTROLLING SPRINKLER ZONE A2.

3 LOCATION OF VERTICAL RISER CHECK VALVE

CONTROLLING SPRINKLER ZONE A3.

4 PROVIDE LIGHT HAZARD ZONE SPRINKLERS.

5 2.5" PIPE TO 2.5" FIRE HOSE VALVES.

6 2.5" FIRE HOSE VALVE, MOUNTED AT 42" AFF. MOUNT

INSTALL VALVE TO MINIMIZE OBSTRUCTIONS.

7 PROVIDE PIPING TO 2.5" FIRE HOUSE VALVES FROM THIS

POINT.

SCALE: NONE

20 22 23 25 27 28 30 31

29262421

S.8

R.3

P.8

N.3

L.8

K.3

H.8

1 / F200

1 / F203

1 / F201 1 / F201

1 / F202

1 / F205

1 / F207

1 / F203

1 / F208 1 / F208

DESIGN ZONE A3

PILED STORAGE HAZARD

INCLUDE 500 GPM HOSE STREAM ALLOWANCE

17' - 0"

17' - 0"

26' - 0"

18' - 0"

26' - 0"

18' - 0"

27' - 0"

26' - 0"

17' - 0"

18' - 0"

26' - 0" 27' - 0"

26' - 0"17' - 0"

27' - 0"

26' - 0"

18' - 0"

2.5"

4"

2.5"

18' - 0"

18' - 0"

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F204

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA E

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA E

SCALE: NONE

FIRE KEYPLAN

PLAN NOTES

1 2.5" PIPE TO 2.5" FIRE HOSE VALVES.

2 2.5" FIRE HOSE VALVE, MOUNTED AT 42" AFF. MOUNT

INSTALL VALVE TO MINIMIZE OBSTRUCTIONS.

I

J K

L

M

N

P

32 35

N.3

L.8

K.3

H.8

1 / F2021 / F202

1 / F2091 / F209

1 / F204

F

1 / F208

DESIGN ZONE B2

PILED STORAGE HAZARD/DRY ZONE

INCLUDE 500 GPM HOSE STREAM ALLOWANCE

F D

C F

D C

FDC

FSS

-4' - 6"

8"

15' - 0"

16' - 0"

17' - 0"

18' - 0"

26' - 0"

27' - 0"

D

D D

10" 24' - 0"

17' - 0"

16' - 0"

10" 10"

10"

2.5"

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F205

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA F

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA F

PLAN NOTES

1 LOCATION OF VERTICAL RISER CHECK VALVE

CONTROLLING SPRINKLER ZONE B2.

2 LOCATION OF DRY PIPE VALVE CONTOLLING DRY

ZONE ABOVE NEW CEILING.

3 DRY SPRINKLER ZONE PIPING LOCATED ABOVE NEW

CEILING.

SCALE: NONE

0.05

0.1

0.2 0.3 0.4

0.5 0.6 0.7

0.8

0.9

AA

A

G

F

DESIGN ZONE C1

PILED STORAGE HAZARD

INCLUDE 500 GPM HOSE STREAM ALLOWANCE

8"

FDC

16' - 0"

25' - 0"

22' - 0"

F S

F S

-4' - 6"-4' - 6"

1 2

22' - 0"22' - 0"

2.5"

21' - 0"

10"

10"

2.5" 10"

22' - 0"

2.5"

10"

2.5"

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F206

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA G

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA G

PLAN NOTES

1 LOCATION OF VERTICAL RISER CHECK VALVE

CONTROLLING SPRINKLER ZONE C1.

2 LOCATION OF VERTICAL RISER CHECK VALVE

CONTROLLING SPRINKLER ZONE C1.

3 2.5" PIPE TO 2.5" FIRE HOSE VALVES.

4 2.5" FIRE HOSE VALVE, MOUNTED AT 42" AFF. MOUNT

INSTALL VALVE TO MINIMIZE OBSTRUCTIONS.

5 PROVIDE PIPING TO 2.5" FIRE HOUSE VALVES FROM

THIS POINT.

SCALE: NONE

4 5 7 8 10 12 13 15 17 18 20

A

G

2119161411963.8

H.8

1 / F203

F

F

1 / F2041 / F203

1 / F208

DESIGN ZONE C2

PILED STORAGE HAZARD

INCLUDE 500 GPM HOSE STREAM ALLOWANCE

8"

FDC

16' - 0"

25' - 0"

33' - 0"

26' - 0"

TYPICAL

10"

2.5"

10"

10"

2.5"

25' - 0"

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F207

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA H

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA H

PLAN NOTES

1 SPRINKLER PIPING TO RUN AT UNDERSIDE OF

SLOPED ROOF.

2 2.5" PIPE TO 2.5" FIRE HOSE VALVES.

3 2.5" FIRE HOSE VALVE, MOUNTED AT 42" AFF. MOUNT

INSTALL VALVE TO MINIMIZE OBSTRUCTIONS.

4 PROVIDE PIPING TO 2.5" FIRE HOUSE VALVES FROM

THIS POINT.

SCALE: NONE

22 23 25 27 28 30 31

A

B

C

D

E

F

G

32292624

H.8

GH

1 / F209

1 / F205

F

1 / F207

1 / F204

F

9DESIGN ZONE B3

PILED STORAGE HAZARD

INCLUDE 500 GPM HOSE STREAM ALLOWANCE

25' - 0"

33' - 0"

26' - 0"

30' - 0"

22' - 6"

1 1

TYPICAL

TYPICAL

DD

2.5"

10"

10"

24' - 0"

25' - 0"

10"

D

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F208

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA I

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA I

PLAN NOTES

1 SPRINKLER PIPING TO RUN AT UNDERSIDE OF

SLOPED ROOF.

2 DRY SPRINKLER ZONE PIPING LOCATED ABOVE NEW

CEILING.

3 2.5" PIPE TO 2.5" FIRE HOSE VALVES.

4 2.5" FIRE HOSE VALVE, MOUNTED AT 42" AFF. MOUNT

INSTALL VALVE TO MINIMIZE OBSTRUCTIONS.

SCALE: NONE

B

C

D

E

F

G

H

H.8

GH

1 / F2051 / F205

F

1 / F208

FS

F D

C

S

-4' - 6"

15' - 0"

D

D D

10"

10"

10"

10"

4" 2.5"

2.5"

D

2.5" 24' - 0"

14' - 0"

F200

"AREA A"

F201

"AREA B" F202

"AREA C"

F203

"AREA D"

F204

"AREA E"

F205

"AREA F"

F209

"AREA J"

F208

"AREA I"

F207

"AREA H"

F206

"AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

F209

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA J

Designer Author Checker

3/32" = 1'-0"

PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA J

PLAN NOTES

1 LOCATION OF VERTICAL RISER CHECK VALVE

CONTROLLING SPRINKLER ZONE B3.

2 DRY SPRINKLER ZONE PIPING LOCATED ABOVE NEW

CEILING.

3 2.5" PIPE TO 2.5" FIRE HOSE VALVES.

4 PROVIDE PIPING TO 2.5" FIRE HOUSE VALVES FROM THIS

POINT.

SCALE: NONE

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E001

INDEX AND LEGEND

EWH EWH Checker

SHEET LIST

SHEET DESCRIPTION

E001 INDEX AND LEGEND

E002 MOTOR AND LUMINAIRE SCHEDULES

E100 ELECTRICAL DEMOLITION FLOOR PLAN

E200 PARTIAL ELECTRICAL FLOOR PLAN - AREA A

E201 PARTIAL ELECTRICAL FLOOR PLAN - AREA B

E202 PARTIAL ELECTRICAL FLOOR PLAN - AREA C

E203 PARTIAL ELECTRICAL FLOOR PLAN - AREA D

E204 PARTIAL ELECTRICAL FLOOR PLAN - AREA E

E205 PARTIAL ELECTRICAL FLOOR PLAN - AREA F

E206 PARTIAL ELECTRICAL FLOOR PLAN - AREA G

E207 PARTIAL ELECTRICAL FLOOR PLAN - AREA H

E208 PARTIAL ELECTRICAL FLOOR PLAN - AREA I

E209 PARTIAL ELECTRICAL FLOOR PLAN - AREA J

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E002

MOTOR AND LUMINAIRE SCHEDULES

EWH EWH Checker

MARK

MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER

S E

E N

O T

E

NAMEPLATE

CHARACTERISTICS LOCATION

N E

M A

S

IZ

E

TYPE LOCATION

F U

R N

IS

H

E D

B Y

TYPE LOCATION

F U

R N

IS

H

E D

B Y

I N

T E

R L

O C

K W

IT

H

M O

T O

R N

O B

Y E

.C

M

N U

A L A

T S

T A

R T

E R

I N

T E

G R

A L W

IT

H

E Q

U

IP

M E

N T

F U

R N

IS

H

E D

B Y

S E

E N

O T

E

N U

M B

E R

O F

C O

N D

U C

T O

R S

W

IR

E S

IZ

E

G R

O U

N D

S

IZ

E

C O

N D

U

IT

S

IZ

E

H O

R S

E P

O W

E R

H

P

L O

A D k V

A

V

-1 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-1 P

H

V

-3 P

H

R O

O M

N U

M B

E R

ROOM NAME M

A

N U

A L

M A

G N

E T

IC

B U

IL

T

-I N

M O

T O

R O

/L

-S

P E

E D

V F

D

S E

E N

O T

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

R O

O M

N U

M B

E R

S E

E N

O T

E

D

IS

C S

W

IT

C H

M A

N U

A L S

T A

R T

E R

R E

C E

P T

A C

L E

F E

E D

E R

S W

O R

B R

E A

K E

R

N E

M A

T Y

P E

D

IS

C S

IZ

E

F U

S E

S

IZ

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

P A

N E

L B

O A

R D

S E

E N

O T

E

DPV1 DRY PIPE VALVE 1/4 0.72 ● ● ● EC ● ● EC PC 2 12 12 .75"

MOTORS, STARTERS, DISCONNECTS & CONTROLS

NOTES:

1.

LUMINAIRE SCHEDULE NOTES

1. FIXTURE TO BE PROVIDED WITH INTEGRAL MOTION SENSOR FOR CONTROL.

2. ALL EXIT SIGNS SHALL BE WIRED AHEAD OF ALL LOCAL SWITCHING.

3. REFER TO DRAWINGS FOR ADDITIONAL MOUNTING INFORMAITON.

4. FIXTURE TO BE PROVIDED WITH A BATTERY BALLAST WITH A MINIMUM OUTPUT

OF 1400 LUMENS FOR 90 MINUTES.

MARK

LAMPS

L O

A D

V

A

F

IX

T U

R E

V O

L T

A G

E

MANUFACTURER

CATALOG

NO. DESCRIPTION

OTHER

ACCEPTABLE

MANUFACTURERS DIFFUSING MEDIA

TRIM COLOR MOUNTING SIZE

S E

E N

O T

E

QUANTITY

W A

T T

S L

A M

P

C A

T A

L O

G N

O

COLOR W

H

IT

E

B L A

C K

A L U

M

IN

U M

B R

O N

Z E

S T

A N

D A

R D

S E

E N

O T

E

S-SURFACE R-RECESSED

SM-STEM MTD WM-WALL MTD

C-CHAIN MTD UC-UNDER CAB

CS-CEIL SURFACE D

IA

M E

T E

R

W

ID

T H

L E

N G

T H

D E

P T

H

F L U

O R

E S

C E

N T

I N

C A

N D

E S

C E

N T

H .I .D

0 0 9" 13" 2.37 5"

B1 4 32 F32T8/

SPX35

3500 121 120 LITHONIA SERIES "IB" HIGH BAY FLUORESCENT, NARROW

DISTRIBUTION WITH UPLIGHT,

MULTI-VOLT BALLAST, OCCUPANCY

SENSOR (PRE-WIRED)

METALUX,

COLUMBIA

SPECULAR

REFLECTOR

● C 24" 48" 6" 1,3

B2 3 32 F32T8/

SPX35

3500 92 120 LITHONIA SERIES

"2SP8"

FLUORESCENT TROFFER, FLUSH

STEEL, .125" THICK #12 ACRYLIC

LENS, MULTI-VOLT BALLAST,

ELECTRONIC RAPID START BALLAST

METALUX,

COLUMBIA

ACRYLIC LENS ● R 24" 48" 6"

B3 3 32 F32T8/

SPX35

3500 92 120 LITHONIA SERIES

"2SP8"

FLUORESCENT TROFFER, GYP.

CEILING MOUNTED, FLUSH STEEL,

.125" THICK #12 ACRYLIC LENS,

MULTI-VOLT BALLAST, ELECTRONIC

RAPID START BALLAST, BATTERY

BALLAST

METALUX,

COLUMBIA

ACRYLIC LENS ● R 24" 48" 6" 4

B4 3 F32T8/

SPX35

3500 92 120 LITHONIA SERIES

"2SP8"

FLUORESCENT TROFFER, FLUSH

STEEL, .125" THICK #12 ACRYLIC

LENS, MULTI-VOLT BALLAST,

ELECTRONIC RAPID START BALLAST,

BATTERY BALLAST

METALUX,

COLUMBIA

ACRYLIC LENS ● R 24" 48" 6" 4

X1 INTEGRAL

LED

3 120 LITHONIA SERIES "LX" EXIT SIGN WITH STENCIL FACE, RED

LETTERS, NICKEL-CADMIUM

BATTERY

SURE-LITES, DUAL

LITE

WHITE FACE WITH

RED LETTERS

● WM (ABOVE DOOR) 9" 13" 2.37

5"

LUMINAIRES BUSWAY SCHEDULE

NO TYPE VOLTAGE REMARKS

FB-A FEEDER SEE NOTE 1,2120/208V-3PH-4W

PB-A

PB-AA

PB-AB

PB-AC

PB-AD

PB-AE

PB-AF

PB-AG

PB-AH

PB-AI

PB-B

PB-BA

PB-BB

PB-C

PB-D

PB-E

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

PLUG-IN

120/208V-3PH-4W

208V-3PH-3W

208V-3PH-3W

208V-3PH-3W

120/208V-1PH-3W

120/208V-1PH-3W

208V-3PH-3W

208V-3PH-3W

208V-3PH-3W

208V-3PH-3W

480V-3PH-3W

480V-3PH-3W

480V-3PH-3W

120/208V-1PH-3W

208V-3PH-3W

120/208V-3PH-4W

AMPERAGE

1600A

1600A

375A

375A

375A

375A

225A

500A

375A

500A

1000A

225A

225A

225A

225A

225A

100A

BUSWAY SCHEDULE NOTES

1. CONTRACTOR IS TO VERIFY BUSWAY SIZE AND MANUFACTURER. PROVIDE

CUSTOM TAP BOXES WHERE REQUIRED.

2. CONTRACTOR SHALL SIZE ALL FEEDERS FOR COPPER WHERE REQUIRED TO

SPLIT BUSWAY FOR NEW WALLS.

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

SEE NOTE 1,2

0.2 0.3 0.4

0.5 0.6 0.7 0.8

0.9

AA

4 5 7 8 10 12 13 15 17 18 20 22 23 25 27 28 30 31

36 37 38

AA

B

C

D

E

F

GG

H

I

J K

L

M

N

P

Q

R

S

T

U

V

W

X

Z

3231.829

27.5

25.2

22.5

21 35

20.2

19.2

161411963.8

Z.5

Y

X.5

V.8 V.8

U.3

S.8

R.3

P.8

N.3

L.8

K.3

H.8

LP143

LP210

LP108

TO "PB-AG"

TO "PB-AF"

TO "PB-AE"/

"PB-AC"/ PB-AI

"PB-AH" "PB-AE"

"PB-AC"

"PB-AC"

"PB-AA"

"PB-AB"

"PB-AD"

"PB-AF"

"PB-AG"

"PB-AA"

"PB-AB"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E100

ELECTRICAL DEMOLITION FLOOR PLAN

Designer Author Checker

1" = 40'-0"

ELECTRICAL DEMOLITION FLOOR PLAN

1. REMOVE ALL WIRING DEVICES, EQUIPMENT, LIGHTING, ETC. IN

THIS AREA. REMOVE CONDUIT AND ASSOCIATED WIRING BACK

TO NEAREST JUNCTION BOX OR PANELBOARD. MARK ALL

UNSUED BREAKERS IN PANELBOARD AS SPARE.

2. EXISTING PANELBOARD SHALL REMAIN. MAINTAIN ALL

CONDUITS THAT FEED DEVICES OUTSIDE THE DEMO AREA.

3. EXISTING PANELBOARD TO BE REMOVED AND RELOCATED TO

ACCOMMODATE NEW WALL. REFER TO NEW WORK PLAN FOR

NEW LOCATION.

4. FUTURE LOCATION OF NEW WALL. EXISTING FEEDERS THIS

AREA TO REMAIN. CONTRACTOR SHALL MAKE ALL NECCESSARY

MODIFICATIONS TO FEEDERS TO ALLOW FOR PENETRATIONS

THROUGH NEW WALL. REFER TO POWER PLANS FOR

ADDITIONAL INFORMATION.

5. EXISTING BUS DUCT TO REMAIN. CONTRACTOR SHALL VERIFY

ALL LOCATIONS OF BUS DUCT THAT ARE AFFECTED BY THE

NEW WALLS. CONTRACTOR SHALL MAKE ALL NECESSASY

MODIFICATIONS TO EXISTING BUS DUCT TO ALLOW FOR

PENETRATION THROUGH NEW WALL. REFER TO NEW PLANS

FOR ADDITIONAL INFORMATION.

6. REMOVE EXISTING BUS DUCT AND CAP END TO ALLOW FOR

NEW WALL. REFER TO POWER PLANS FOR ADDITIONAL

INFORMATION.

7. REMOVE EXISTING BUS DUCT AND FEEDER AND PROVIDE BUS

TAP BOX AT END TO REFEED EXISTING BUS DUCT. REFER TO

NEW PLANS FOR ADDITIONAL INFORMATION.

NOTES

A. CONTRACTOR SHALL VERIFY ALL EXISTING EQUIPMENT,

DEVICES, LIGHT FIXTURES, CONDUITS, WIRE, ETC. THAT MAY BE

AFFECTED BY THE NEW WALLS. ALL DEVICES AFFECTED BY THE

NEW WALL SHALL BE SHIFTED TO AVOID THE NEW WALL AND

CONDUIT AND WIRE EXTENDED TO NEW LOCATION.

B. ALL EXISTING FEEDERS THAT GO THROUGH FUTURE WALLS

SHALL REMAIN. CONTRACTOR SHALL MAKE ALL NECCESSARY

MODIFICATIONS TO FEEDERS TO ALLOW FOR PENETRATIONS

THROUGH NEW WALL.

C. ALL EQUIPMENT, DEVICES, LIGHT FIXTURES, ETC. ARE TO

REMAIN UNLESS NOTED OTHERWISE.

GENERAL NOTES

19.2

1916141196

3.8

Z.5

Y X.5

V.8V.8

U.3

EE

EE

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

1 / E203

1 / E201

1 / E204

LOC

110110

EXISTING BUS DUCT

PIV

177177

B1 B1 B1 B1 B1 B1

PIV

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J""AREA I""AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E200

PARTIAL ELECTRICAL FLOOR PLAN - AREA A

EWH EWH Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA A

1. PROVIDE 1" CONDUIT OUT TO THE POST INDICATOR VALVE FOR FIRE

ALARM CONNECTION. STUB CONDUIT, WITH PULL STRING, UP INTO

BUILDING AT 4" A.F.F.. REFER TO FIRE SUPPRESSION SITE PLAN FOR

EXACT PIV LOCATION.

2. CONNECT NEW LUMINAIRES TO EXISTING LIGHTING CIRCUIT THIS

AREA.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE

LOCATIONS WITH NEW FIRE ALARM DEVICES. ADJUST FIRE

ALARM DEVICE TO AVOID EXISTING LIGHT FIXTURES.

KEYPLAN

X

3231.829

27.5

25.2

22.5

20.219.2

V.8V.8

U.3

EEEEEEEE

EEEEEEEE

EEEEEE

EEEEE

1 / E203 1 / E204 1 / E204 1 / E202

75 LOC

EXISTING BUS DUCT

B1B1

B1

NAC

"PB-AH"

"PB-AE"

PIV

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J""AREA I""AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E201

PARTIAL ELECTRICAL FLOOR PLAN - AREA B

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA B

1. CAP END OF EXISTING BUS DUCT. REFER TO BUSWAY

SCHEDULE FOR ADDITIONAL INFORMATION.

2. CONNECT NEW CIRCUIT TO NEAREST EXISTING 120V PANEL.

PROVIDE A NEW 20AMP/1-POLE BREAKER IN EXISTIN PANEL.

NEW BREAKER SHALL BE COMPATIBLE WITH EXISTING PANEL

AND SHALL HAVE THE SAME AIC RATING AS THE EXISTING

PANEL. COORDINATE EXACT BREAKER TYPE AND RATING WITH

EXISTING PANELBOARD PRIOR TO ORDERING.

3. PROVIDE TAP BOX AT END OF BUS AND CABLE THROUGH NEW

WALL TO TAP BOX ON OTHER SIDE. CONTRACTOR SHALL VERIFY

EXISTING BUS DUCT SIZE PRIOR TO ROUGH IN OF NEW FEEDER.

REFER TO BUSWAY SCHEDULE FOR ADDITIONAL INFORMATION.

4. PROVIDE 1" CONDUIT OUT TO THE POST INDICATOR VALVE FOR

FIRE ALARM CONNECTION. STUB CONDUIT, WITH PULL STRING,

UP INTO BUILDING AT 4" A.F.F.. REFER TO FIRE SUPPRESSION

SITE PLAN FOR EXACT PIV LOCATION.

5. CONNECT NEW LUMINAIRES TO EXISTING LIGHTING CIRCUIT

THIS AREA.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE

LOCATIONS WITH NEW FIRE ALARM DEVICES. ADJUST FIRE

ALARM DEVICE TO AVOID EXISTING LIGHT FIXTURES.

B. CONTRACTOR SHALL VERIFY EXACT SIZE OF ALL EXISTING BUS

DUCT PRIOR TO ORDERING TAP BOX.

C. WHERE IT IS NECESSARY TO PENETRATE THE NEW 4-HOUR WALL

THE CONTRACTOR SHALL PROVIDE ALL NECESSARY FIRE

STOPPING MATERIAL AND INSTALL IN ACCORDANCE WITH ALL UL

LISTING SO AS TO MAINTAIN THE 4-HOUR RATING OF THE WALL.

36 37 38

P

Q

R

S

T

U

V

W

X

Z

32 35

V.8V.8

U.3

S.8

R.3

P.8

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

EE

E E

EE

EE

EE

EE

EE

EE

EE

1 / E201

1 / E204

1 / E205

LOC

LOC

(TYPICAL ALL DEVICES

THIS AREA)

EXISTING BUS DUCT

PB-A

NAC

3 (TYPICAL ALL FIXTURES

THIS AREA)

LP143

177 177

177 177

177 177

X1

X1

X1

X1

LOC

B2 B2 B2 B2

B2

B2

B2 B2

B3

B1

FAP

X1

WP

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J""AREA I""AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E202

PARTIAL ELECTRICAL FLOOR PLAN - AREA C

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA C

1. FIRE ALARM DEVICES SHALL BE HUNG FROM STRUCTURE ABOVE

TO BE MOUNTED FLUSH WITH THE NEW CEILING APPROXIMATELY

23' A.F.F..

2. SEE SHEET E201 FOR INFORMATION..

3. ALL HIGH BAY FIXTURES TO BE LOWERED TO HANG BELOW THE

NEW CEILING THIS AREA. CONTRACTOR SHALL EXTEND EXISTING

CONDUIT AND WIRING TO ACCOMMODATE NEW CEILING. THE

NEW CEILING IS TO BE HUNG AT THE BOTTOM OF THE

STRUCTURAL TRUSSES APPROXIMATELY 23' A.F.F..

4. SEE SHEET E204 FOR INFORMATION.

5. CONNECT NEW CIRCUIT TO NEAREST EXISTING 120V PANEL.

PROVIDE A NEW 20AMP/1-POLE BREAKER IN EXISTIN PANEL.NEW

BREAKER SHALL BE COMPATIBLE WITH EXISTING PANEL AND

SHALL HAVE THE SAME AIC RATING AS THE EXISTING PANEL.

COORDINATE EXACT BREAKER TYPE AND RATING WITH EXISTING

PANELBOARD PRIOR TO ORDERING.

6. EXTEND CONDUIT AND WIRE TO EXISTING BUS PLUG AT EXISTING

BUS DUCT "PB-A". REFER TO BUSWAY SCHEDULE FOR

ADDITIONAL INFORMATION.

7. CONNECT NEW LUMINAIRES TO EXISTING LIGHTING CIRCUIT THIS

AREA.

8. CONNECT NEW EXIT SIGNS TO EXISTING LIGHTING CIRCUIT THIS

AREA. WIRE AHEAD OF ALL LOCAL SWITCHING.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE

LOCATIONS WITH NEW FIRE ALARM DEVICES. ADJUST FIRE ALARM

DEVICE TO AVOID EXISTING LIGHT FIXTURES.

B. CONTRACTOR SHALL VERIFY EXACT SIZE OF ALL EXISTING BUS

DUCT PRIOR TO ORDERING TAP BOX.

C. WHERE IT IS NECESSARY TO PENETRATE THE NEW 4-HOUR WALL

THE CONTRACTOR SHALL PROVIDE ALL NECESSARY FIRE

STOPPING MATERIAL AND INSTALL IN ACCORDANCE WITH ALL UL

LISTING SO AS TO MAINTAIN THE 4-HOUR RATING OF THE WALL.

19161411963.8

U.3

S.8

R.3

P.8

N.3

L.8

K.3

H.8

EE

EE

EE

EE

EE

EE

EE

EE

EE

EE

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

EEE

1 / E200 1 / E201

1 / E204

1 / E204

1 / E207

110110 110

LOC

LOC

LOC

(TYPICAL ALL DEVICES

THIS AREA)

EXISTING BUS DUCT

B1 B1 B1 B1 B1 B1

B1 B1 B1 B1 B1 B1 B1

E LP210

NAC

WP

177177

177177

177177

"PB-AD"

"PB-AF"

"PB-AG"

B1

PIV

B1 B1 B1 B1 B1 B1

B1 B1 B1 B1 B1 B1

B1

B1

B1

B1

B1

B1

B1

B1

EEEEEEEE

E

E

RESTROOM

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J""AREA I""AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E203

PARTIAL ELECTRICAL FLOOR PLAN - AREA D

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA D

1. FIRE ALARM DEVICES SHALL BE HUNG FROM STRUCTURE

ABOVE TO BE ALIGNED WITH THE BOTTOM OF OR BELOW THE

TRUSS STRUCTURE APPROXIMATELY 18'-6"' A.F.F..

2. CHAIN MOUNT FIXTURES FROM STRUCTURE ABOVE TO MATCH

THE SAME HEIGHT AS EXISTING FIXTURES (TYPICAL ALL NEW

B1 TYPE FIXTURES).

3. CIRCUIT FIXTURES BACK TO EXISTING PANEL LP210. PROVIDE

A NEW 20AMP/1-POLE BREAKER IN EXISTING PANEL FOR NEW

CIRCUIT. NEW BREAKER SHALL BE COMPATIBLE WITH EXISTING

PANEL AND SHALL HAVE THE AIC RATING AS THE EXISTING

PANEL. COORDINATE EXACT BREAKER TYPE AND RATING WITH

EXISTING PANELBOARD PRIOR TO ORDERING.

4. PROVIDE TAP BOX AT END OF BUS AND CABLE THROUGH NEW

WALL TO TAP BOX ON OTHER SIDE. CONTRACTOR SHALL

VERIFY EXISTING BUS DUCT SIZE PRIOR TO ROUGH IN OF NEW

FEEDER. REFER TO BUSWAY SCHEDULE FOR ADDITIONAL

INFORMATION.

5. PROVIDE 1" CONDUIT OUT TO THE POST INDICATOR VALVE FOR

FIRE ALARM CONNECTION. STUB CONDUIT, WITH PULL STRING,

UP INTO BUILDING AT 4" A.F.F.. REFER TO FIRE SUPPRESSION

SITE PLAN FOR EXACT PIV LOCATION.

6. CONNECT NEW CIRCUIT TO NEAREST EXISTING 120V PANEL.

PROVIDE A NEW 20AMP/1-POLE BREAKER IN EXISTING PANEL.

NEW BREAKER SHALL BE COMPATIBLE WITH EXISTING PANEL

AND SHALL HAVE THE AIC RATING AS THE EXISTING PANEL.

COORDINATE EXACT BREAKER TYPE AND RATING WITH

EXISTING PANELBOARD PRIOR TO ORDERING.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE LOCATIONS

WITH NEW FIRE ALARM DEVICES. ADJUST FIRE ALARM DEVICE TO

AVOID EXISTING LIGHT FIXTURES.

B. CONTRACTOR SHALL VERIFY EXACT SIZE OF ALL EXISTING BUS

DUCT PRIOR TO ORDERING TAP BOX.

C. WHERE IT IS NECESSARY TO PENETRATE THE NEW 4-HOUR WALL

THE CONTRACTOR SHALL PROVIDE ALL NECESSARY FIRE

STOPPING MATERIAL AND INSTALL IN ACCORDANCE WITH ALL UL

LISTING SO AS TO MAINTAIN THE 4-HOUR RATING OF THE WALL.

32292624

U.3

S.8

R.3

P.8

N.3

L.8

K.3

H.8

EEEEEEEEE

E

EEEEEEEE

EEEEEEEEE

E

EEEEEEEE

EEEEEEEEE

EEEEEEEEE

E

EEEEEEEE

EEEEEEEEE

EEEEEEEEE

EEEEEEEEE

1 / E203

1 / E201

1 / E202

1 / E205

1 / E202

1 / E209

1 / E205

1 / E2081 / E208

1 / E203

1 / E207

110110110

FACP

(TYPICAL ALL DEVICES

THIS AREA)

EXISTING BUS DUCT

MNS

LOC

LP143

177177

177177

177177

TO "PB-AG"

TO "PB-AF"

TO "PB-AE"/

"PB-AC"

TO "PB-AI"

"PB-AC"

"PB-AA"

"PB-AB"

EEEEEEEEE

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J""AREA I""AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E204

PARTIAL ELECTRICAL FLOOR PLAN - AREA E

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA E

1. FIRE ALARM DEVICES SHALL BE HUNG FROM STRUCTURE

ABOVE TO BE ALIGNED WITH THE BOTTOM OF OR BELOW THE

TRUSS STRUCTURE APPROXIMATELY 18'-6"' A.F.F..

2. PROVIDE TAP BOX AT END OF BUS AND CABLE THROUGH NEW

WALL TO TAP BOX ON OTHER SIDE. CONTRACTOR SHALL

VERIFY EXISTING BUS DUCT SIZE PRIOR TO ROUGH IN OF NEW

FEEDER. REFER TO BUSWAY SCHEDULE FOR ADDITIONAL

INFORMATION.

3. PROVIDE TAP BOX AT END OF BUS AND CABLE NEW FEEDER

TROUGH NEW WALL TO EXISTING BUS PLUG AT EXISTING BUS

DUCT "PB-A". CONTRACTOR SHALL VERIFY EXISTING WIRE SIZE

AND EXTEND CONDUIT AND WIRE FROM EXISTING BUS PLUG

TO NEW TAP BOX PRIOR TO ROUGH-IN. REFER TO BUSWAY

SCHEDULE FOR ADDITIONAL INFORMATION.

4. CAP END OF EXISTING BUS DUCT. REFER TO BUSWAY

SCHEDULE FOR ADDITIONAL INFORMATION.

5. CONTRACTOR SHALL PROVIDE NEW CONDUIT AND WIRE TO

MATCH EXISTING AND PENETRATE NEW WALL. REFER TO

DEMOLITION PLAN FOR ADDITIONAL INFORMATION. REFER TO

BUSWAY SCHEDULE FOR ADDITIONAL INFORMATION.

6. RELOCATE EXISTING PANEL TO NEW WALL. CONTRACTOR

SHALL EXTEND ALL EXISTING CONDUIT AND WIRE TO REFEED

ALL EXISTING ACTIVE CIRCUITS.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE LOCATIONS

WITH NEW FIRE ALARM DEVICES. ADJUST FIRE ALARM DEVICE TO

AVOID EXISTING LIGHT FIXTURES.

B. CONTRACTOR SHALL VERIFY EXACT SIZE OF ALL EXISTING BUS DUCT

PRIOR TO ORDERING TAP BOX.

C. WHERE IT IS NECESSARY TO PENETRATE THE NEW 4-HOUR WALL THE

CONTRACTOR SHALL PROVIDE ALL NECESSARY FIRE STOPPING

MATERIAL AND INSTALL IN ACCORDANCE WITH ALL UL LISTING SO AS

TO MAINTAIN THE 4-HOUR RATING OF THE WALL.

36 37 38

I

J

K

L

M

N

P

32 35

N.3

L.8

K.3

H.8

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E E

E E

E E

E E

E E

EE

E E

EE

E E

EE

1 / E202

1 / E2091 / E208

1 / E204

LO

C

FACP

(TYPICAL ALL DEVICES

THIS AREA)

EXISTING BUS DUCT

PB-A

MNS

LOC

B2

DPV1

3 (TYPICAL ALL FIXTURES

THIS AREA)

177 177

X1

PIV

B4

B2

EE

B1

E

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J""AREA I""AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E205

PARTIAL ELECTRICAL FLOOR PLAN - AREA F

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA F

1. FIRE ALARM DEVICES SHALL BE HUNG FROM STRUCTURE

ABOVE TO BE MOUNTED FLUSH WITH THE NEW CEILING

APPROXIMATELY 23' A.F.F..

2. CONNECT NEW FIXTURES TO EXISTING LOCAL LIGHTING

CIRCUIT.

3. ALL HIGH BAY FIXTURES TO BE LOWERED TO HANG BELOW

THE NEW CEILING THIS AREA. CONTRACTOR SHALL EXTEND

EXISTING CONDUIT AND WIRING TO ACCOMMODATE NEW

CEILING. THE NEW CEILING IS TO BE HUNG AT THE BOTTOM OF

THE STRUCTURAL TRUSSES APPROXIMATELY 23' A.F.F..

4. REFER TO SHEET E204 FOR INFORMATION.

5. CONNECT NEW CIRCUIT TO NEAREST EXISTING 120V PANEL.

PROVIDE A NEW 20AMP/1-POLE BREAKER IN EXISTIN PANEL.

NEW BREAKER SHALL BE COMPATIBLE WITH EXISTING PANEL

AND SHALL HAVE THE SAME AIC RATING AS THE EXISTING

PANEL. COORDINATE EXACT BREAKER TYPE AND RATING WITH

EXISTING PANELBOARD PRIOR TO ORDERING.

6. EXTEND EXISTING FEEDER TO EXISTING BUS PLUG AT BUS

DUCT "PB-A". REFER TO BUSWAY SCHEDULE FOR ADDITIONAL

INFORMATION.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE LOCATIONS

WITH NEW FIRE ALARM DEVICES. ADJUST FIRE ALARM DEVICE TO

AVOID EXISTING LIGHT FIXTURES.

B. CONTRACTOR SHALL VERIFY EXACT SIZE OF ALL EXISTING BUS

DUCT PRIOR TO ORDERING TAP BOX.

C. WHERE IT IS NECESSARY TO PENETRATE THE NEW 4-HOUR WALL

THE CONTRACTOR SHALL PROVIDE ALL NECESSARY FIRE

STOPPING MATERIAL AND INSTALL IN ACCORDANCE WITH ALL UL

LISTING SO AS TO MAINTAIN THE 4-HOUR RATING OF THE WALL.

0.2 0.3 0.4

0.5 0.6 0.7

0.8

0.9

AA

AA

GG

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

LOC

LOC

(TYPICAL ALL DEVICES

THIS AREA)

EXISTING BUS DUCT

NAC

WP

WP

LOC

PIV PIV

3 3

PIV

110 110 110 110

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J""AREA I"

"AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E206

PARTIAL ELECTRICAL FLOOR PLAN - AREA G

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA G

1. FIRE ALARM DEVICES SHALL BE HUNG FROM STRUCTURE ABOVE

TO BE ALIGNED WITH THE BOTTOM OF THE TRUSS STRUCTURE

APPROXIMATELY 23'-6"' A.F.F..

2. CONNECT NEW CIRCUIT TO NEAREST EXISTING 120V PANEL.

PROVIDE A NEW 20AMP/1-POLE BREAKER IN EXISTIN PANEL. NEW

BREAKER SHALL BE COMPATIBLE WITH EXISTING PANEL AND

SHALL HAVE THE SAME AIC RATING AS THE EXISTING PANEL.

COORDINATE EXACT BREAKER TYPE AND RATING WITH EXISTING

PANELBOARD PRIOR TO ORDERING.

3. PROVIDE 1" CONDUIT OUT TO THE POST INDICATOR VALVE FOR

FIRE ALARM CONNECTION. STUB CONDUIT, WITH PULL STRING,

UP INTO BUILDING AT 4" A.F.F.. REFER TO FIRE SUPPRESSION SITE

PLAN FOR EXACT PIV LOCATION.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE

LOCATIONS WITH NEW FIRE ALARM DEVICES. ADJUST FIRE

ALARM DEVICE TO AVOID EXISTING LIGHT FIXTURES.

4 5 7 8 10 12 13 15 17 18 20

G

2119161411963.8

H.8

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

EEE

EEE

1 / E208

1 / E2041 / E203

E

110110110110

LOC

LOC

(TYPICAL ALL DEVICES

THIS AREA)

EXISTING BUS DUCT

B1 B1 B1 B1 B1 B1 B1

B1 B1 B1 B1 B1 B1 B1

E

LP108

NAC

WP

WP

30 30

"PB-AB"

X1

PIV

B1

B1 B1

B1

RESTROOM

N

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J"

"AREA I""AREA H""AREA G"

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E207

PARTIAL ELECTRICAL FLOOR PLAN - AREA H

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA H

1. FIRE ALARM DEVICES SHALL BE HUNG FROM STRUCTURE

ABOVE TO BE ALIGNED WITH THE BOTTOM OF THE TRUSS

STRUCTURE APPROXIMATELY 23'-6"' A.F.F..

2. CHAIN MOUNT FIXTURES FROM STRUCTURE ABOVE TO MATCH

THE SAME HEIGHT AS EXISTING FIXTURES (TYPICAL ALL NEW B1

TYPE FIXTURES).

3. CIRCUIT FIXTURES BACK TO EXISTING PANEL LP108. PROVIDE A

NEW 20AMP/1-POLE BREAKER IN EXISTING PANEL FOR NEW

CIRCUIT. NEW BREAKER SHALL BE COMPATIBLE WITH EXISTING

PANEL AND SHALL HAVE THE SAME AIC RATING AS THE EXISTING

PANEL. COORDINATE EXACT BREAKER TYPE AND RATING WITH

EXISTING PANELBOARD PRIOR TO ORDERING. IF AN EXISTING

20AMP/1-POLE SPARE BREAKER EXISTS IT IS ACCEPTABLE TO

REUSE IT.

4. REFER TO SHEET E203 FOR INFORMATION.

5. CONNECT NEW CIRCUIT TO NEAREST EXISTING 120V PANEL.

PROVIDE A NEW 20AMP/1-POLE BREAKER IN EXISTING PANEL.

NEW BREAKER SHALL BE COMPATIBLE WITH EXISTING PANEL

AND SHALL HAVE THE AIC RATING AS THE EXISTING PANEL.

COORDINATE EXACT BREAKER TYPE AND RATING WITH

EXISTING PANELBOARD PRIOR TO ORDERING.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE

LOCATIONS WITH NEW FIRE ALARM DEVICES. ADJUST FIRE

ALARM DEVICE TO AVOID EXISTING LIGHT FIXTURES.

B. CONTRACTOR SHALL VERIFY EXACT SIZE OF ALL EXISTING BUS

DUCT PRIOR TO ORDERING TAP BOX.

C. WHERE IT IS NECESSARY TO PENETRATE THE NEW 4-HOUR

WALL THE CONTRACTOR SHALL PROVIDE ALL NECESSARY FIRE

STOPPING MATERIAL AND INSTALL IN ACCORDANCE WITH ALL

UL LISTING SO AS TO MAINTAIN THE 4-HOUR RATING OF THE

WALL.

22 23 25 27 28 30 31

33 34

AA

B

C

D

E

F

GG

32292624

H.8

GH

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

EEEEE

E

E

EEEEEEE

1 / E209

1 / E2051 / E2041 / E204

1 / E207

110110110

(TYPICAL ALL DEVICES

THIS AREA)

EXISTING BUS DUCT

X1 X1

3 (TYPICAL ALL FIXTURES

THIS AREA)

177177

177177

"PB-AC"

"PB-AA"

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J"

"AREA I""AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E208

PARTIAL ELECTRICAL FLOOR PLAN - AREA I

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA I

1. FIRE ALARM DEVICES SHALL BE HUNG FROM STRUCTURE ABOVE

TO BE ALIGNED WITH THE BOTTOM OF THE TRUSS STRUCTURE

APPROXIMATELY 23' A.F.F..

2. EXISTING FEEDERS TO BE MODIFIED TO PENETRATE THROUGH

NEW WALL IN THIS AREA. REFER TO DEMOLITION PLAN FOR

ADDITIONAL INFORMATION.

3. ALL HIGH BAY FIXTURES EAST OF THE NEW WALL TO BE

LOWERED TO HANG BELOW THE NEW CEILING THIS AREA.

CONTRACTOR SHALL EXTEND EXISTING CONDUIT AND WIRING TO

ACCOMMODATE NEW CEILING. THE NEW CEILING IS TO BE HUNG

AT THE BOTTOM OF THE STRUCTURAL TRUSSES APPROXIMATELY

23' A.F.F..

4. PROVIDE TAP BOX AT END OF BUS AND CABLE THROUGH NEW

WALL TO TAP BOX ON OTHER SIDE. CONTRACTOR SHALL VERIFY

EXISTING BUS DUCT SIZE PRIOR TO ROUGH IN OF NEW FEEDER.

REFER TO BUSWAY SCHEDULE FOR ADDITIONAL INFORMATION.

5. REFER TO SHEET E204 FOR INFORMATION.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE LOCATIONS

WITH NEW FIRE ALARM DEVICES. ADJUST FIRE ALARM DEVICE TO

AVOID EXISTING LIGHT FIXTURES.

B. CONTRACTOR SHALL VERIFY EXACT SIZE OF ALL EXISTING BUS

DUCT PRIOR TO ORDERING TAP BOX.

C. WHERE IT IS NECESSARY TO PENETRATE THE NEW 4-HOUR WALL

THE CONTRACTOR SHALL PROVIDE ALL NECESSARY FIRE

STOPPING MATERIAL AND INSTALL IN ACCORDANCE WITH ALL UL

LISTING SO AS TO MAINTAIN THE 4-HOUR RATING OF THE WALL.

AA

B

C

D

E

F

GG

H

H.8

GH

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E E

E E

E E

E E

E E

E

E

EXISTING

PDC-B

EXISTING

PDC-A

EXISTING

PDC-A

EXISTING FENCE

1 / E205

1 / E208

LOC

(TYPICAL ALL DEVICES

THIS AREA)

DPV1

2 (TYPICAL ALL FIXTURES

THIS AREA)

177 177

177 177

177 177

PIV

PIV

"AREA A" "AREA B"

"AREA C"

"AREA D" "AREA E"

"AREA F"

"AREA J"

"AREA I""AREA H""AREA G"

N

WRIGHT-PATTERSON AIR FORCE BASE

C

I V I L

ENG I NEER

I N

G

88TH ABW

AFUS

5732 Springboro Pike Dayton, Ohio 45449-2842

TEL: (937) 293-2022

FAX: (937) 293-9697

CHIEF-ENG. CONST. CHIEF-ENG. SECTION COORDINATOR

mlange@edge-tinney.com

DATE NO REVISION BYBYREVISIONNODATE

DATECHECKEDDRAWNDESIGNEDPLOT

PROJECT NUMBER ZHTV 09-0006

REPAIR FIRE CODE DEFICIENCIES, FACILITY 30013

OF

FOR CONSTRUCTION

WPAFB

E209

PARTIAL ELECTRICAL FLOOR PLAN - AREA J

Designer Author Checker

3/32" = 1'-0"

PARTIAL ELECTRICAL FLOOR PLAN - AREA J

1. FIRE ALARM DEVICES SHALL BE HUNG FROM STRUCTURE ABOVE

TO BE MOUNTED FLUSH WITH THE NEW CEILING APPROXIMATELY

23' A.F.F..

2. ALL HIGH BAY FIXTURES TO BE LOWERED TO HANG BELOW THE

NEW CEILING THIS AREA. CONTRACTOR SHALL EXTEND EXISTING

CONDUIT AND WIRING TO ACCOMMODATE NEW CEILING. THE

NEW CEILING IS TO BE HUNG AT THE BOTTOM OF THE

STRUCTURAL TRUSSES APPROXIMATELY 23' A.F.F..

3. PROVIDE 1" CONDUIT OUT TO THE POST INDICATOR VALVE FOR

FIRE ALARM CONNECTION. STUB CONDUIT, WITH PULL STRING,

UP INTO BUILDING AT 4" A.F.F.. REFER TO FIRE SUPPRESSION SITE

PLAN FOR EXACT PIV LOCATION.

NOTES

A. CONTRACTOR SHALL VERIFY EXISTING LIGHT FIXTURE

LOCATIONS WITH NEW FIRE ALARM DEVICES. ADJUST FIRE

ALARM DEVICE TO AVOID EXISTING LIGHT FIXTURES.

Extract TS001
Extract A001
Extract D100
Extract D101
Extract D102
Extract D103
Extract D500
Extract A002
Revised A003
Final Drawings Work File
TS001
A001
D100
D101
D102
D103
D500
A002
A003
A101
A102
A200
A400
A401
A402
A403
A404
A501
A502
A503
A504
A505
A506
A507
2010-06024-Fire Supression 100% CD
2010-06024 Electrical 100% CD
heapy drawings.pdf
F001 - LEGEND & NOTES
F002 - FIRE SUPPRESSION SITE PLAN
F003 - ROOF PLAN
F004 - DETAILS
F100 - OVERALL FIRE SUPPRESSION FLOOR PLAN
F200 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA A
F201 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA B
F202 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA C
F203 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA D
F204 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA E
F205 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA F
F206 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA G
F207 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA H
F208 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA I
F209 - PARTIAL FIRE SUPPRESSION FLOOR PLAN - AREA J
E001 - INDEX AND LEGEND
E002 - MOTOR AND LUMINAIRE SCHEDULES
E100 - ELECTRICAL DEMOLITION FLOOR PLAN
E200 - PARTIAL ELECTRICAL FLOOR PLAN - AREA A
E201 - PARTIAL ELECTRICAL FLOOR PLAN - AREA B
E202 - PARTIAL ELECTRICAL FLOOR PLAN - AREA C
E203 - PARTIAL ELECTRICAL FLOOR PLAN - AREA D
E204 - PARTIAL ELECTRICAL FLOOR PLAN - AREA E
E205 - PARTIAL ELECTRICAL FLOOR PLAN - AREA F
E206 - PARTIAL ELECTRICAL FLOOR PLAN - AREA G
E207 - PARTIAL ELECTRICAL FLOOR PLAN - AREA H
E208 - PARTIAL ELECTRICAL FLOOR PLAN - AREA I
E209 - PARTIAL ELECTRICAL FLOOR PLAN - AREA J