RFI for FA8601-09-B-0011.xls

XLS spreadsheet 52 KB Posted

Attached to
Replace HVAC and Fire Suppression system
Solicitation number
FA8601-09-B-0011
Issued by

About this file

RFI

View the file

Other files

File Type Posted
RFIs 26 August 2009.pdf PDF
Addendum_2.pdf PDF
Amendment 4.pdf PDF
Amendment 2.pdf PDF
Site visit roster 13 August 09.pdf PDF
Amendment 3.pdf PDF
Wage Decision OH29 Mod 21 08-07-09.doc DOC document
U0001.pdf PDF
Amendment 1.doc DOC document
Wage Determination.doc DOC document
Combined Spec.pdf PDF
Addendum 1 040204 —
Solicitation.pdf PDF
HVAC RENOVATION OF FACILITY 20018A Drawings.pdf PDF
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

3400 Kettering Boulevard Dayton, Ohio 45439 (937)293-6138 Fax(937)293-6301 3400 Kettering Boulevard Dayton, Ohio 45439 (937)293-6138 Fax(937)293-6301

REQUEST FOR INFORMATION
ORIGINATOR:Andy FogtJOB:FA8601-09-B-0011
RFI NO.:1DWG.NO.FP001DETAIL NO:Note D.SPEC. NO.283176-2.3.2
PROBLEM:Sheet FP001 Note D of the General Notes calls for all initiating,SLC and notification circuits to be
wired Class A. Specification #283176 Paragraph 2.3.2 Notes b,c, and d call for the circuits to be Class B.
Please clarify the requirement for this project
SIGNED:DATE:8/21/09
SOLUTION:
All initiating, SLC and notification circuits are to be wired Class B per Specification 28 31 76, paragraph 2.3.2.
Note D on drawing sheet FP001 is wrong.
CHANGE ORDERPre-BidCLARIFY ONLY
BY:Thomas Moshier, 88 ABW/CECWDATE:8/21/09
BY:DATE:
BY:DATE: