Building #Task ID #Equipment #Equipment NameCategoryGroupShopFrequencyWork DescriptionEstimated DimensionsKnown HazardsEst Time to CompleteUnitExtendedEquipment and MaterialsStandards/ReferencesRemarksStill Required?Frequency OK?Any changes?
505001East Vent Plenum Drain ScreensDrain ScreensAMXGCorrosion Control180 DaysRemove grates from trench drains, remove filter screens, wash thoroughly, remove all loose debris, paint stripper sludge and residue from floor, reinstall filter screens, and replace over trenches.12' x 12' x 16'Confined Space. Cadmium, chromium, lead and chemical depaint (wet). Slip, trip and fall.8 hours179.00358.00Pressure washer, hoses, nozles, tools and PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.146/29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560/WR-ALC OI 91-25YY
505002West Vent Plenum Drain ScreensDrain ScreensAMXGCorrosion Control180 DaysRemove grates from trench drains, remove filter screens, wash thoroughly, remove all loose debris, and paint stripper sludge and residue from floor, reinstall filter screens, and replace over trenches.12' x 12' x 16'Confined Space. Cadmium, chromium, lead and chemical depaint (wet). Slip, trip and fall.8 hours179.00358.00Pressure washer, hoses, nozles, tools and PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.146/29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560/WR-ALC OI 91-25YY
505003Air Flow Tunnels (Long tunnel under hangar estimated 175 ft long x 6 ft wide x 8 ft tall)Air Flow TunnelAMXGCorrosion Control360 DaysRemove all loose debris, paint stripper sludge and residue from floor of tunnels, remove residue from walls, ceiling, and floor of tunnels down to bare concrete, clean overhead pipe drain and clean drain sump rooms, clean crossover duct(s) between both tunnels, remove all debris and residue in filter rooms including cleaning of reusable filters, clean each exhaust fan and discharge ducts, remove grates from trench drains, remove filter screens from trench, wash thoroughly, and reinstall grates over trenches.6 ft W x 8 ft H Approx 600 linear ftConfined Space. Cadmium, chromium, lead and chemical depaint (wet). Slip, trip and fall.32 hours - Four (4) 8-hour days with 6 workers790.00790.00Pressure washer, hoses, nozles, ladders, manlift, hepa vac, tools and PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.146/29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560/WR-ALC OI 91-25YY
545401Paint Chip Trench DrainTrench DrainAMXGCorrosion Control360 DaysRemove grates from trench drains, remove paint stripper sludge, blast media, and all other residue, remove filter screens and/or drain baskets from trench, wash thoroughly, reinstall and replace grates over trenches.162 ft L x 2 ft W 130 ft L x 2 ft W 186 ft L x 2 ft WCadmium, chromium, lead and chemical depaint (wet). Slip, trip and fall.4 hours79.0079.00Fork lift, pressure washer, tools and PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.1027/29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
545402Lift StationLift StationAMXGCorrosion Control90 DaysRemove debris from the water return area and place in appropriate containers. Remove debris and paint stripper sludge from main containment area so that it is not allowed to enter industrial waste drain. Replace and clean all pit covers.16 ft x 20 ft x 20 ftConfined Space. Cadmium, chromium, lead and chemical depaint (wet). Slip, trip and fall.16 hours300.001,200.00Pressure washer, Vacuum, rakes, tools and PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.146/29 CFR 1910.1027/29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560/WR-ALC OI 91-25YY
59 Paint5901Floor Trenches and Drain BasketsTrench DrainAMXGCorrosion Control360 DaysRemove grates from trench drains, remove screens, remove paint stripper sludge, and all other debris from trenches accumulated during paint/de-paint processes, remove drain baskets from trench, wash drain baskets and screens thoroughly, reinstal and replace grates over trenches.200 ft x 2 ft (2 each)Cadmium, chromium, lead and chemical depaint. Slip, trip and fall.4 hours79.0079.00Pressure washer, tools, PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.1027/29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
59P (Paint)5904Chem Strip Process in a facility designed for paint onlyPaint FacilityAMXGCorrosion ControlOn RequestRemove paint stripper sludge, debris, sediment and residue from hangar floor so that it is not allowed to enter the industrial waste drains.Cadmium, chromium, lead and chemical depaint (wet). Slip, trip, and fall5 days (crew of 5)42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560Changed 10/6/16 - Freq IncreaseYY
59D (dry -depaint facility)5905Filter WallsPlastic media facility not designed for sanding process. We have to clean sanding media once a year to prevent potential exposure to known hazards.AMXGCorrosion ControlAnnually On RequestRemove covers, vacuum out the bottom of all the filter banks, and replace covers. Prevent purging of dust that risks employee exposure to hazardous waste.Cadmium, chromium, lead and chemical depaint (dry).5 days (crew of 5)42 USC 6901/42 USC 7401/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560New 3/23/16YY
59D (dry -depaint facility)5906Sanding HangarPlastic media depaint facility not designed for sanding process. We have to clean once a year to prevent potential exposure to known hazards.AMXGCorrosion ControlAnnually On RequestRemove dust and debris from all the hangar walls and any attachments (wipe down walls up to 8 feet above the floor). Remove all dust and debris from reachable surfaces of 2 metal staircases, filter access platform, and floor.265'W x 181"L=47,965 sq. ft + 112' x 104'=11,648 sq. ft. = 59,613 sq. ft. totalCadmium, chromium, lead and chemical depaint (dry).6 days (crew of 7)42 USC 6901/42 USC 7401/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560New 10/6/16YY
8908902Chemical Strip ProcessPaint FacilityAMXGCorrosion ControlOn RequestRemove paint stripper sludge, debris, sediment and residue from hangar floor so that it is not allowed to enter the industrial waste drains. Clean drain baskets and sump to prevent flooding of hangar during chemical depaint process.Cadmium, chromium, lead and chemical depaint (wet). Slip. Trip and fall.5 days (crew of 5)42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560New 3/30/17
12512502-AHydrotron Sanding BoothSanding BoothAMXGC-5 Sheet Metal7 DaysRemove all dust, particles, and residue from walls, and floor of booth.12 ft x 12 ft x 10 ftDust with cadmium, chromium and lead above OSHA limits.2 hours450.00900.00Hepa vac, ladders, tools and PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
12512502-BHydrotron Sanding BoothSanding BoothAMXGC-5 Sheet Metal60 DaysInspect the mist eliminators for buildup of solids. Remove solid buildup by soaking in soapy solution power wash to remove all traces of soap. Clean fitting where the tube from the differential switch connects to the body of the dust collector. Clean float switch. Drain water from tank. Use supplied rake to pull sludge to the front of the unit and remove using wet-dry vacuum. Dispose of sludge properly (consult NFPA code). Check seals on acrylic door/panel.16 ft x 16 ft x 8 ftDust with cadmium, chromium and lead above OSHA limits.1 hour825.004,950.00Wet-dry vac, soapy solution, brushes, tools, PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
13713701Trench Drain - Bay 2Trench DrainAMXGCorrosion Control30 DaysRemove grates from trench drains, remove paint stripper sludge, blast media, and all other residue, remove filter screens and/or drain baskets from trench, wash thoroughly, and reinstall, wash grates and replace over trenches52 ft x 2 ft 16 ft x 2 ftPaint waste and debris. Chromated primer overspray.5 hours700.008,400.00Pressure washer and accessories, tools, PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.124/ 29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
13713702Trench Drain - Bay 1Trench DrainAMXGCorrosion Control30 DaysRemove grates from trench drains, remove paint stripper sludge, blast media, and all other residue, remove filter screens and/or drain baskets from trench, wash thoroughly, and reinstall, wash grates and replace over trenches52 ft x 2 ft 16 ft x 2 ftPaint waste and debris. Chromated primer overspray.4 hours600.007,200.00Pressure washer and accessories, tools, PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.124/ 29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
13713703Light Panels - Bay 2Paint BoothAMXGCorrosion Control180 DaysRemove all paint and residue from panels in booth through which light must pass, replace all covering over from panels in booth through which light must pass.18 sidelights 2' x 4' 20 toplights 2' x 2'Paint waste and debris. Chromated primer overspray.4 hours699.001,398.00Scraper, ladder, light cover, PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.124/ 29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
13713704Light Panels - Bay 3Paint BoothAMXGCorrosion Control180 DaysRemove all paint and residue from panels in booth through which light must pass, replace all covering over from panels in booth through which light must pass.16 sidelights globe 12 toplights 2' x 2'Dust with cadmium, chromium and lead above OSHA limits.4 hours699.001,398.00Scraper, ladder, light cover, PPE42 USC 6901/42 USC 7401/40 CFR 260/40 CFR 263/29 CFR 1910.124/ 29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
13713705Light Panels - Bay 4Paint BoothAMXGCorrosion Control180 DaysRemove all paint and residue from panels in booth through which light must pass, replace all covering over from panels in booth through which light must pass.20 sidelights globe 16 toplights 2' x 2'Paint waste and debris. Chromated primer overspray.4 hours699.001,398.00Scraper, ladder, light cover, PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.124/ 29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
13713706Light Panels - Bay 5Paint BoothAMXGCorrosion Control180 DaysRemove all paint and residue from panels in booth through which light must pass, replace all covering over from panels in booth through which light must pass.10 sidelights 2' x 4' 42 toplights 2' x 2'Paint waste and debris. Chromated primer overspray.4 hours699.001,398.00Scraper, ladder, light cover, PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.124/ 29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
13713707Media Recovery - Bay 4Recovery TrenchAMXGCorrosion Control360 DaysRemove grates and filter screens from floor recovery system, remove blast media and all other residue from floor recovery system, replace grating32 ft L x 60 ft WDust with cadmium, chromium and lead above OSHA limits.8 hours699.00699.00Pressure washer, tools, PPE42 USC 6901/42 USC 7401/40 CFR 260/40 CFR 263/29 CFR 1910.124/ 29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
13713708Trench Drain - Bay 5Trench DrainAMXGCorrosion Control180 DaysRemove grates from trench drains, remove paint stripper sludge, blast media, and all other residue, remove filter screens and/or drain baskets from trench, wash thoroughly, and reinstall, wash grates and replace over trenches104 ft L x 2 ft W (2 each)Paint waste and debris. Chromated primer overspray.3 hours699.001,398.00Pressure washer, tools, PPE42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.124/ 29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
36436401-AHydrotron Sanding BoothSanding BoothAMXGConsolidated Support Flight7 DaysRemove all dust, particles, and residue from walls, and floor of booth.10 ft Wide x 8 ft Tall x 10 ft DeepDust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901/42 USC 7401/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
36436401-BHydrotron Sanding BoothSanding BoothAMXGConsolidated Support Flight60 DaysInspect the mist eliminators for buildup of solids. Remove solid buildup by soaking in soapy solution power wash to remove all traces of soap. Clean fitting where the tube from the differential switch connects to the body of the dust collector. Clean float switch. Drain water from tank. Use supplied rake to pull sludge to the front of the unit and remove using wet-dry vacuum. Dispose of sludge properly (consult NFPA code). Check seals on acrylic door/panel.16 ft L x 16 ft W x
8 ft HDust with cadmium, chromium and lead above OSHA limits.1 hour$ 825.00$ 4,950.00Hepa vacuum, amended water, pressure washer, Wet-dry vac, tools, supplies, PPE42 USC 6901/42 USC 7401/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/29 CFR 1910.1025/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560YY
2036203601Hangar FloorPaint FacilityAMXGCorrosion ControlOn RequestRemove paint stripper sludge, debris, sediment and residue from hangar floor so that it is not allowed to enter the industrial waste drains.Cadmium, chromium, lead and chemical depaint (wet). Slip, trip and fall.5 days (crew of 5)42 USC 6901/40 CFR 260/40 CFR 263/29 CFR 1910.1027/ 29 CFR 1910.1026/NFPA 30/AFI 32-7042/RAFB ISWMP/RAFB HWMP/RAFB 01560
14014001RP8721Oil TankTankCMXGProp ShopOn RequestRemove liquids from tank into appropriate receptacle. Remove all residue from walls and bottom of tank. Remove residue from parts table assembly including table frame, grates, and rails.Rectangular tank holds 110 gallons of light weight oil & lift table1.5 hours42 USC 6901 (solid waste disposal), 40 CFR 260 (hazardous waste mgmt), 40 CFR 263 (hazardous waste transport), 29 CFR 1910.124, (OSHA/beryllium), 29 CFR 1910.1027 (OSHA/cadmium), 29 CFR 1910.1026 (OSHA/chromium), NFPA 30 (flammable/combustible liquids), AFI 32-7042 (AF waste mgmt), RAFB ISWMP (local solid waste mgmt), RAFB HWMP (local hazardous waste mgmt), RAFB 01560 (environmental)
14014002RP8723Finger Print Remover TankTankCMXGProp ShopOn RequestRemove liquids from tank into appropriate receptacle. Remove all residue from walls and bottom of tank. Remove residue from parts table assembly including table frame, grates, and rails.Rectangular tank holds 110 gallons of MIL-C-15074C corrosion preventive liquid & lift table1.5 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014003WR000253Water Wash Grinding Booth # 1Dust CollectorCMXGProp Shop7 DaysClean mist eliminators. Remove all dust, residue, and debris from unit. Drain tank.20 Ft Wide x 6 ft TallAluminum dust0.50 hour (30 minutes)42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014004WR000254Water Wash Grinding Booth # 2Dust CollectorCMXGProp Shop7 DaysClean mist eliminators. Remove all dust, residue, and debris from unit. Drain tank.20 Ft Wide x 6 ft TallAluminum dust0.50 hour (30 minutes)42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014005-AWR003106Three Stage Paint BoothPaint BoothCMXGProp Shop7 DaysClean all lights and replace light diffuser covers. Remove all dust, residue, and debris from ceiling, walls, personnel doors, roll-up doors, and floor (including door thresholds). Inspect and re-cover fire sprinklers with new paper bags as required. Remove all floor covering and tape from floor except under workbench and cabinet area. Replace floor covering and tape to cover all accessible floor space. Workbench and cabinets may remain in place during this cleaning.20 ft Wide x 19 ft TallPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014005-BWR003106Three Stage Paint BoothPaint BoothCMXGProp Shop90 DaysClean all lights and replace light diffuser covers. Remove all peel-coat from walls, ceiling and floor inside paint booth. Apply white water-based polymer emulsion peel-coat on walls and ceiling. Replace all floor covering and tape. Re-cover all fire sprinklers with new paper bags. Remove and limit build-up of paint to ensure visibility for reading gauges. Replace stage-1, stage-2, and stage-3 filters.20 ft Wide x 19 ft TallPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
7 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014005-CWR003106Three Stage Paint BoothPaint BoothCMXGProp ShopOn RequestReplace stage-1 filters. If requested while cleaning of that booth is underway, filters will be replaced at that time. If no cleaning is underway, filters will be replaced at the next cleaning time.
20 ft Wide x 19 ft TallPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014005-DWR003106Three Stage Paint BoothPaint BoothCMXGProp ShopOn RequestReplace stage-1 and stage-2 filters. If requested while cleaning of that booth is underway, filters will be replaced at that time. If no cleaning is underway, filters will be replaced at the next cleaning time.20 ft Wide x 19 ft TallPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014005-EWR003106Three Stage Paint BoothPaint BoothCMXGProp ShopOn RequestReplace stage-1, stage-2, and stage-3 filters. Replace ceiling filters. If requested while cleaning of that booth is underway, filters will be replaced at that time. If no cleaning is underway, filters will be replaced at the next cleaning time.20 ft Wide x 19 ft TallPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
4 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014006-AWR003566Robotic Blade Grinder Dust CollectorDust CollectorCMXGProp Shop2 Times WeeklyDrain the system and clean water level control box and tank section in accordance with ProVent's Operation and Maintenance Manual. Wipe down exterior.4'W x 5' TallAluminum dust1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014006-BWR003566Robotic Blade Grinder Dust CollectorDust CollectorCMXGProp Shop30 DaysRemove and clean target plate, clean scrub cone, clean mist eliminator, and clean exhaust fan blades in accordance with ProVent's Operation and Maintenance Manual.4'W x 5' TallAluminum dust3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014007-ARP10105Manual Blade Edge Grinding BoothGrinding BoothCMXGProp Shop2 Times weeklyDrain the system and clean water level control box and tank section in accordance with ProVent's Operation and Maintenance Manual. Wipe down exterior.7 ft wide FaceAluminum dust1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014007-BRP10105Manual Blade Edge Grinding BoothGrinding BoothCMXGProp Shop90 DaysClean target plates, clean scrub cones, clean mist eliminators, and clean exhaust fan blades in accordance with ProVent's Operation and Maintenance Manual.14'L x 10'W x 8' HAluminum dust4 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14014008Penetrant TankTankCMXGNDI Shop180 DaysRemove all liquids into appropriate receptacle and remove all residue from interior of tank including all installed features.75 gallons2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560New 2/25/16
14014009Emulsifier TankTankCMXGNDI Shop180 DaysRemove all liquids into appropriate receptacle and remove all residue from interior of tank including all installed features.75 gallons2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560added back to requirement - bjb 11/9/2017
14014019WR003566Robotic Grinding Room and EquipmentGrinding BoothCMXGProp Shop60 DaysRemove all metal dust, particles, and debris from all surfaces (equipment, cage, ceiling, walls, windows, floor, etc) within the room.114" L x 30" W x 82" DAluminum dust4 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Changed 3/31/16
14014020-AWR002937Sanding BoothSanding BoothCMXGCNC Machine Shop2 Times WeeklyRemove all dust, particles, and residue from walls, and floor of booth. Empty and clean all trays.1556" L x 55"W x 165"HDust with cadmium, chromium and lead above OSHA limits.1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560When will all the these be needed?
14014020-BWR002937Sanding BoothSanding BoothCMXGCNC Machine Shop30 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), and booth entrance facing.30"L x 3"W x 43"HDust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560""
14014020-CWR002937Sanding BoothSanding BoothCMXGCNC Machine Shop180 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), walls, and floor of booth. Empty and clean all trays. Remove all dust, particles, and residue from all exterior surfaces of the booth including walls, roof, filter housings, conduit, piping, catwalk, etc.96"L x 30"W x 66"HDust with cadmium, chromium and lead above OSHA limits.4 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.124, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560""
14214201-ASealant Spray BoothPaint BoothCMXGPlating ShopOn RequestRemove floor covering and tape. Replace all paper and tape to cover all floor space. Remove and replace door filters.101"L X 30"W x 48"HPaint waste and debris. Chromated primer overspray.5 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560""
14214243Alkaline Tank # 601TankCMXGPlating ShopOn requestRemove all liquids from tank into appropriate receptacle. Clean interior of tank including all installed or removed features.36"L x 30"W x 108"HContains 1840 L (490 gallons) of Sodium Hydroxide3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560YY
14214244Rinse Tank # 602TankCMXGPlating ShopOn RequestRemove all liquids from tank into appropriate receptacle. Clean interior of tank including all installed or removed features.40"L x 30"W x 108"H3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Not on current contractYNPer Shane Groves, 10/28/16 - Not expected to be needed beyond the first couple of months on new contract.
14214245HN03 Tank # 603TankCMXGPlating ShopOn RequestRemove all liquids from tank into appropriate receptacle. Clean interior of tank including all installed or removed features.40"L x 30"W x 108"HContains 1840 L (490 gallons) of Desmut (HNO3)3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560YNPer Shane Groves, 10/28/16 - Not expected to be needed beyond the first couple of months on new contract.
14214246Rinse Tank # 604TankCMXGPlating ShopOn RequestRemove all liquids from tank into appropriate receptacle. Clean interior of tank including all installed or removed features.40"L x 30"W x 108"H3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Not on current contractYNPer Shane Groves, 10/28/16 - Not expected to be needed beyond the first couple of months on new contract.
14214247Chromate Acid Anodize Tank # 605TankCMXGPlating ShopOn RequestRemove all liquids from tank into appropriate receptacle. Clean interior of tank including all installed or removed features.96"L x 30"W x 108"HContains 4920 L (1300 gallons) of Chromic Acid Anodize3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560YNPer Shane Groves, 10/28/16 - Not expected to be needed beyond the first couple of months on new contract.
14214248Chromate Acid Anodize Tank # 606TankCMXGPlating ShopEvery 3 yrs On RequestRemove all liquids from tank into appropriate receptacle. Clean interior of tank including all installed or removed features.96"L x 30"W x 108"HContains 4920 L (1300 gallons) of Chromic Acid Anodize3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560YNPer Shane Groves, 10/28/16 - Not expected to be needed beyond the first couple of months on new contract. Cleaned recently @ 10/16.
14214249Rinse Tank # 607TankCMXGPlating ShopOn RequestRemove all liquids from tank into appropriate receptacle. Clean interior of tank including all installed or removed features.40"L x 30"W x 108"H3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Not on current contractYNPer Shane Groves, 10/28/16 - Not expected to be needed beyond the first couple of months on new contract.
14214250Rinse Tank # 608TankCMXGPlating ShopOn RequestRemove all liquids from tank into appropriate receptacle. Clean interior of tank including all installed or removed features.36"L x 30"W x 108"H3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Not on current contractYNPer Shane Groves, 10/28/16 - Not expected to be needed beyond the first couple of months on new contract.
14214295WR000464

RP8979

RP8981

RP101099Hand Blast Systems (4 each)Blast EquipmentCMXGPlating Shop90 DaysRemove dust, particles, and residue from all exterior surfaces of the main unit of all four systems.various sizes of small equipmentDust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14214296WR000464

RP8979

RP8981

RP101099Hand Blast Systems (4 each)Blast EquipmentCMXGPlating Shop90 DaysRemove dust, particles, and residue from all exterior surfaces of all components of all four systems.various sizes of small equipmentDust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
14614601Trench DrainTrench DrainCMXGF-15 Water Pick7 DaysRemove trench grates. Remove all sludge and debris from trench into proper container. Remove and clean all filter screens and baskets and reinstall. Rinse trench clean. Wash and reinstall grates.2 Trenches - Each is XX Ft L x 12 In W x 18 In D2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Confirm Frequency for bridge contract
16916901-BAirless Degreaser (tank 2)Vapor DegreaserCMXGComposite RepairAnnually On RequestRemove all liquids from main tank, two water separators, and associated plumbing into appropriate receptacle for turn-in. Remove safety screens for access. Clean and passivate all interior features with Soda Ash alkali solution including cooling coils, all plumbing lines, brackets, safety screens, drain troughs, water separator interiors and lids, tank lid, walls, bottom, heating elements and manual parts sprayer. Assure alkali solution reaches all crevices and underside surfaces and plumbing lines. Lightly abrade all tank walls, drain troughs and flat surfaces using steel brush or abrasive Scotch-Brite or equivalent pads and alkali solution IAW tank manufacturer’s procedures. Once more, remove all liquids from main tank, two water separators, and associated plumbing into appropriate receptacle for turn-in. Thoroughly rinse with water to remove alkali solution from all interior features. Dispose of water in industrial waste system.3 Ft W x 12 Ft L x 11 Ft DContains 220 gallons of 3M HFE7100 Vapor Degreaser16 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Bridge Contract?
16916902Alkaline Tank (tank 3)TankCMXGComposite RepairOn RequestRemove all liquids into appropriate receptacle and clean interior of tank including all installed features.16'L x 3'W x 7'HContains 1850 gallons of Alkaline Cleaner4 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916905LNC Tank (tank 5)TankCMXGComposite RepairOn RequestRemove all liquids into appropriate receptacle and clean interior of tank including all installed features.16'L x 3'W x 7'H1850 gallons tank with heating elements & cooling coils contains Oakie Deoxidizer4 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916906Phosphoric Tank (tank 8)TankCMXGComposite RepairOn RequestRemove all liquids into appropriate receptacle and clean interior of tank including all installed features.16'L x 3'W x 7'H1850 gallons tan+J59+K59+K59:L594 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916907Spray Rinse Tank (tank 9)TankCMXGComposite RepairAnnually On RequestRemove all liquids into appropriate receptacle and clean interior of tank including all installed features.16'L x 3'W x 7'H4 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Not on current contract
16916909-AWR003749Dry Filter Paint Booth and RoomPaint BoothCMXGComposite Repair7 DaysClean all paint from light diffusers. Replace light diffuser covers. Remove all dust, residue, and debris from ceiling, walls, doors, and floor (including door thresholds). Inspect and re-cover fire sprinklers with new paper bags as required. Remove all floor covering and tape from floor. Replace floor covering and tape to cover all floor space.20'L x 15'W x 8'HPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916909-BWR003749Dry Filter Paint Booth and RoomPaint BoothCMXGComposite Repair90 DaysRemove all peel-coat from walls, ceiling and floor inside paint booth. Apply white water-based polymer emulsion peel-coat on walls and ceiling. Replace all floor covering and tape. Re-cover all fire sprinklers with new paper bags. Clean all lights and replace light diffuser covers. Remove and limit build-up of paint to ensure visibility for reading gauges. Replace filter stages 1, 2, and 3.20'L x 15'W x 8'HPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
12 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916909-CWR003749Dry Filter Paint Booth and RoomPaint BoothCMXGComposite RepairOn RequestReplace Stage 1 filters. If requested while cleaning of that booth is underway, filters will be replaced at that time. If no cleaning is underway, filters will be replaced at the next cleaning time.20'L x 15'W x 8'HPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916909-DWR003749Dry Filter Paint Booth and RoomPaint BoothCMXGComposite RepairOn RequestReplace Stages 1 and 2 filters. If requested while cleaning of that booth is underway, filters will be replaced at that time. If no cleaning is underway, filters will be replaced at the next cleaning time.20'L x 15'W x 8'HPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916909-EWR003749Dry Filter Paint Booth and RoomPaint BoothCMXGComposite RepairOn RequestReplace Stages 1, 2, and 3 filters. Replace intake filters. If requested while cleaning of that booth is underway, filters will be replaced at that time. If no cleaning is underway, filters will be replaced at the next cleaning time.20'L x 15'W x 8'HPaint waste and debris. Chromated primer overspray. Cadmium and Chromium3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916910-AWR002635Grit Blast Booth DoorsGrit Blast BoothCMXGComposite Repair2 Times WeeklyClean all dust, particles, and residue from outside and edges of all doors.4'W x 8'HPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916910-BWR002635Grit Blast BoothGrit Blast BoothCMXGComposite Repair90 DaysRemove all removable grates and screens from floor recovery system inside booth and behind booth. Remove all visible blast media and residue from floor recovery system. Replace grates. Clean all dust, particles, debris, and residue from the entire floor behind booth, especially around the hopper.34'L x 15'W x 12'HPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560Changed 3/31/16
16916912-AWR003743Sanding Booth EastSanding BoothCMXGComposite RepairDailyRemove all dust, particles, and residue from walls, and floor of booth. Empty and clean all trays.33'L x 15'W x 11'HDust with cadmium, chromium and lead above OSHA limits.1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916912-BWR003743Sanding Booth EastSanding BoothCMXGComposite Repair7 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), and booth entrance facing.33'L x 15'W x 11'HDust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916912-CWR003743Sanding Booth EastSanding BoothCMXGComposite Repair90 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), walls, and floor of booth. Empty and clean all trays. Remove all dust, particles, and residue from all exterior surfaces of the booth including walls, roof, filter housings, conduit, piping, catwalk, etc.33'L x 15'W x 11'HDust with cadmium, chromium and lead above OSHA limits.42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916912-DWRCentral Vacuum SystemVacuum CleanerCMXGComposite Repair7 DaysRemove, empty, and reinstall canisters. Clean all dust, particles and residue from vacuum systems' areas.4'W x 8'HDust with cadmium, chromium and lead above OSHA limits..25 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916913-AWR002935Sanding Booth South #1Sanding BoothCMXGComposite RepairDailyRemove all dust, particles, and residue from walls, and floor of booth. Empty and clean all trays.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916913-BWR002935Sanding Booth South #1Sanding BoothCMXGComposite Repair7 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), and booth entrance facing.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916913-CWR002935Sanding Booth South #1Sanding BoothCMXGComposite Repair90 daysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), walls, and floor of booth. Empty and clean all trays. Remove all dust, particles, and residue from all exterior surfaces of the booth including walls, roof, filter housings, conduit, piping, catwalk, etc.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.1.75 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916913-DWR00369Central Vacuum SystemVacuum CleanerCMXGComposite Repair7 DaysRemove, empty, and reinstall canisters. Clean all dust, particles and residue from vacuum systems' areas.4'W x 8'HDust with cadmium, chromium and lead above OSHA limits..25 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916914-AWR002936Sanding Booth South #2Sanding BoothCMXGComposite RepairDailyRemove all dust, particles, and residue from walls, and floor of booth. Empty and clean all trays.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916914-BWR002936Sanding Booth South #2Sanding BoothCMXGComposite Repair7 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), and booth entrance facing.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916914-CWR002936Sanding Booth South #2Sanding BoothCMXGComposite Repair90 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), walls, and floor of booth. Empty and clean all trays. Remove all dust, particles, and residue from all exterior surfaces of the booth including walls, roof, filter housings, conduit, piping, catwalk, etc.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.1.75 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916914-DWR003670Central Vacuum SystemVacuum CleanerCMXGComposite Repair7 DaysRemove, empty, and reinstall canisters. Clean all dust, particles and residue from vacuum systems' areas.4'W x 8'HDust with cadmium, chromium and lead above OSHA limits..25 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916915-AWR003026Sanding Booth WestSanding BoothCMXGComposite RepairDailyRemove all dust, particles, and residue from walls, and floor of booth. Empty and clean all trays.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916915-BWR003026Sanding Booth WestSanding BoothCMXGComposite Repair7 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), and booth entrance facing.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916915-CWR003026Sanding Booth WestSanding BoothCMXGComposite Repair90 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), walls, and floor of booth. Empty and clean all trays. Remove all dust, particles, and residue from all exterior surfaces of the booth including walls, roof, filter housings, conduit, piping, catwalk, etc.34'L x 19'W x 8'HDust with cadmium, chromium and lead above OSHA limits.1.75 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
16916915-DWR003668Central Vacuum SystemVacuum SystemCMXGComposite Repair7 DaysRemove, empty, and reinstall canisters. Clean all dust, particles and residue from vacuum systems' areas.4'W x 8'HDust with cadmium, chromium and lead above OSHA limits..25 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
18018005Trench DrainTrench DrainCMXGPaint Shop2 Times WeeklyRemove grates,remove all paint stripper sludge and blast media into proper container, remove and clean filter screen or trench basket and reinstall,rinse trench clean,wash and reinstall grates.2 each trenches approx 60 ft longPaint sludge from chemical depainting process2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
18018006Trench DrainTrench DrainCMXGPaint Shop2 Times WeeklyRemove grates,remove all paint stripper sludge and blast media into proper container, remove and clean filter screen or trench basket and reinstall,rinse trench clean,wash and reinstall grates.2 each trenches approx 60 ft longPaint sludge from chemical depainting process2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
18018007Trench DrainTrench DrainCMXGPaint Shop2 Times WeeklyRemove grates,remove all paint stripper sludge and blast media into proper container, remove and clean filter screen or trench basket and reinstall,rinse trench clean,wash and reinstall grates.50 ft long L-shaped trenchPaint sludge from chemical depainting process2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
18018008Trench DrainTrench DrainCMXGPaint Shop2 Times WeeklyRemove grates,remove all paint stripper sludge and blast media into proper container, remove and clean filter screen or trench basket and reinstall,rinse trench clean,wash and reinstall grates.125 ft long rectangular-shaped trenchPaint sludge from chemical depainting process2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
18018009Trench DrainTrench DrainCMXGPaint Shop7 DaysRemove grates,remove all paint stripper sludge and blast media into proper container, remove and clean filter screen or trench basket and reinstall,rinse trench clean,wash and reinstall grates.Approx 64 ft long L-shaped trench, connected w/IWC 18007Paint sludge from chemical depainting process2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
18018010Paint Stripping Tank (Estimated 18 ft long x 3 ft wide x 4 ft deep)TankCMXGPaint ShopOn RequestRemove all liquids into appropriate receptacle and remove all residue from interior of tank including all installed features.21'L x 5'W x 4'HMethylene Chloride, paint sludge3 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560went from 180 days to on request
18018011Paint Stripping Tank (Small)TankCMXGPaint ShopOn RequestRemove all liquids into appropriate receptacle and remove all residue from interior of tank including all installed features.Paint sludge from chemical depainting process2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560
18018012-ASanding BoothSanding BoothCMXGDepaint ShopDailyRemove all dust, particles, and residue from walls, and floor of booth. Empty and clean all trays.Dust with cadmium, chromium and lead above OSHA limits.1 hour42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560New 2/25/16
18018012-BSanding BoothSanding BoothCMXGDepaint Shop7 DaysRemove all dust, particles, and residue from ceiling, walls, 8 ft. high and lower.Dust with cadmium, chromium and lead above OSHA limits.2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560New 2/25/16
18018012-CSanding BoothSanding BoothCMXGDepaint Shop90 DaysRemove all dust, particles, and residue from ceiling (including all flat surface, conduit and light fixtures), walls, floor of booth, and booth entance facing. Empty and clean all trays. Remove all dust, particles, and residue from all exterior surfaces of the booth including walls, roof, filter housings, conduit, piping, catwalk, etc.Dust with cadmium, chromium and lead above OSHA limits.1.75 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560New 2/25/16
18018013-ADry Filter Paint BoothPaint BoothCMXGPaint Shop7 DaysClean all paint from light diffusers. Replace light diffuser covers. Remove all dust, residue, and debris from walls and floor. Inspect and re-cover fire sprinklers with new paper bags as required. Remove all floor covering and tape from floor. Replace floor covering and tape to cover all floor space.20 Ft W x 50 Ft D x 16 Ft H = 1,000 Sq FtPaint waste and debris. Chromated primer overspray. Cadmium and Chromium.
2 hours42 USC 6901, 40 CFR 260, 40 CFR 263, 29 CFR 1910.1027 , 29 CFR 1910.1026, NFPA 30, AFI 32-7042, RAFB ISWMP, RAFB HWMP, RAFB 01560New 10/6/16 - In use - Replaces 18001