This is a technical data sheet for the CAPSOL CC-EXP-LEDM Explosion Proof LED Text Display, a visible notification system designed for hazardous environments.

The CC-EXP-LEDM is a 1.2-inch letter height LED display engineered for aircraft hangars, fuel cells, ammunition plants, chemical plants, and other hazardous locations. The unit is UL classified for Class I Divisions 1&2 Groups B, C, D; Class II Divisions 1&2 Groups E, F, G; and Class III applications, with NEMA 4/7/9 ratings and UL 1638 listing. The display measures 22 7/8" x 22 7/8" x 10 ½" deep, weighs 180 pounds, and operates at temperatures between -14°F to 122°F with 95% humidity tolerance. Power options include PoE (42.5-57VDC) or 24 VDC, with wattage ranging from 5.5W-40W depending on operational mode. The system features LED strobe lights at 135 candelas, rated sound output of 2W/1m at 86±3dB, 10/100/1000 LAN connectivity with fiber optic options, two configurable control relays, and four configurable inputs with terminal block connections for 18-12 AWG wire. Operation requires the CC-LEDController to initiate messages, with additional capability through the CAPSOLControl operating system. The unit is designed and assembled in America using U.S. and imported components. CAPSOL, founded in 2013, specializes in threat identification and early notification systems.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CAPSOL Explosion Proof LED Text Display Specifications

CAPSOL’s EXP-LEDM Explosion Proof LED Display is perfect providing visible notification for hazardous areas. The 1.2’ letter height provides exceptional visibility in an alarm condition in all locations.

An excellent choice for aircraft hangars, fuel cells, ammunition plants, chemical plants and other hazardous environments, the Enclosure is UL Classified for use in Class I, Div 1&2 Groups B,C,D. Class II, Div 1&2 Groups E,F,G and Class III. Rated for NEMA 4/7/9 applications. LED Display is UL 1638 Listed.

WHO WE ARE: Since 2013, we have been developing systems to identify potential threats and provide early notification. The

CAPSOLSuite is designed to gather, identify, and process data as early as possible to mitigate a threat. Notifying all affected people quickly and clearly makes lives safer.

19939 W. 162ND ST, OLATHE, KS 66062

913-203-1110 : WWW.CAPSOL.ORG

CC-EXP-LEDM LED Text Display Technical Data Sheet

POWER INPUT Powered by PoE (42.5-57VDC) Powered by 24 VDC Wattage Wattage Booting Up (intermittent duty, MAX) 40W/1A 28W/1.2A Alert in Progress 24W/.6A 20W/.9A Standby (with Time Display in Green) 7.5W/.2A 5.5W/.23A LED Strobe Light Intensity * 135CD 135CD Rated Sound Output 2W/1m 2W/1m Audio Output Non-Amplified Non-Amplified Sounds** 86+- 3dB - Event Alarm, End of Alert Sound, and System Test Announcement

*LED Intensity Per Side. LED Strobe Lights can be disabled in programming and are non-syncable. Strobes lights flash for approximately 5 seconds when activated using the CC-LEDControl-SA.

Length of strobe light activation is programable in the CAPSOLControl operating system interfaced with CC-LEDControl-SA.

** Programmable in CC-LEDControl interfaced with CC-LEDControl-WKS.

Communications PoE IEEE802. 3bt. 42.5 - 57vdc Type A (4,5 + / 7, 8 -) Type B (1,2 + / 3, 6 -) LAN 10/100/1000 Network Connectivity FIBER Options available The CC-EXP-LEDM Display requires the use of CC-LEDController to initiate messages.

The CAPSOLControl operating system provides additional messaging capability as well as access to relays and inputs.

Mechanical and Environmental Overall Size 22 7/8” x 22 7/8” x 10 ½” Deep Shipping Weight 180 lbs.

Operating Temperature -14° to 122°F (-10° to 50°C) Humidity 95% RH, non-condensing at 92°F (33°C).

Conformal coating NEMA7 Enclosure Control Relays 2 – (Configurable with CAPSOLControl WKS) Inputs – 4 (Configurable with CAPSOLControl WKS) Connections - Terminal block for 18 AWG to 12 AWG Letter Height 1.2” dual line during a message

Designed and assembled in America with US and imported parts.