2007-HUM.pdf
PDF 5 MB Posted
- Solicitation number
- FA813726R0017
About this file
WWYK 070051 Repair Humidification System Building 3708 - Design and Installation Documentation
This document is a comprehensive set of architectural and engineering design drawings for the repair and installation of a humidification system in Building 3708 at Tinker Air Force Base, Oklahoma. The project encompasses mechanical, electrical, and plumbing systems with detailed specifications for equipment installation, piping layouts, and control systems. Key equipment includes a steam generator (Aerco SS3CE rated at 1800 pounds/hour @ 15 PSIG or 1950 pounds/hour @ 100 PSIG steam), water softeners (North Star NST25ED with 8 GPM service flow rate and 25,000 maximum grain capacity), steam distribution manifolds (Nortec components), and a blowdown separator (Lattner 810 with 1" inlet). The system comprises nine Air Handling Units (AHU-3 through AHU-9) with associated equipment schedules, mechanical piping plans across multiple areas, mechanical AHU equipment roof plans, and detailed equipment and fixture schedules.
The design documentation includes mechanical abbreviations and symbols legend, equipment specifications with manufacturers and catalog numbers, schedule of materials with pipe fittings valves and insulation specifications, isometric details for plumbing and steam piping, typical distribution configurations at AHUs, steam and water converter details with system controls, electrical symbols and legends, lighting fixture and power control plan symbols, fire alarm system symbols, telephone/data system symbols, and electrical roof plan layouts. The project appears to be a complete as-built package delivered by FPM group, with all drawings indicating 100% as-built status and detailed notes addressing construction responsibility, verification requirements, equipment scheduling, material quality standards, and coordination procedures between contractors and the government contracting officer.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MARK DISCRIPTION APPLICATION MANUFACTURER CATALOG FITTINGS CW HW WASTE VENT REMARKS
FS-1 DRAIN SINK FLOOR WADE 9014 -- -- 4" -- CAST IRON 8" ROUND WITH 6"
SUMP, A.R.E. INTERIOR, ALUMINUM
DOME STRAINER AND NICKEL
BRONXE TOP
PLUMBING FIXTURE SCHEDULE
MARK DISCRIPTION MANUFACTURER CATALOG REMARKS
SG-1 STEAM GENERATOR AERCO SS3CE GENERATOR SHALL BE RATED AT:
1800 POUND/HOUR @ 15 PSIG STEAM
1950 POUND/HOUR @ 100 PSIG STEAM
WS-1, 2 WATER SOFTENER NORTH STAR NST25ED SERVICE FLOW RATE 8 GPM, 25,000 MAX
GRAIN CAPACITY, SALT STORAGE CAPACITY
300 LB, FULL FLOW BYPASS VALVE, METER
RANGE 0-100 GPM
SDM-1- 6 STEAM DISTIBUTION MANIFOLD NORTEC REFER TO NORTEC REPLACEMENT STEAM MANIFOLDS AND FOR
AHU OPTION SCHEDULE COMPONETS AHU'S 3,4,5,6, 8 AND 9
BS-1 BLOWDOWN SEPERATOR LATTNER 810 1" INLET
EQUIPMENT SCHEDULE
| G-1 |
| M-1 |
| M-2 |
| M-3 |
| M-4 |
| M-5 |
| M-6 |
| M-7 |
| M-8 |
| M-9 |
| M-10 |
| M-11 |
| M-12 |
| M-13 |
| M-14 |
| P-1 |
| P-2 |
| E-1 |
| E-2 |
File details come from the government source that posted it. Updated .