WWYK 070051 Repair Humidification System Building 3708 - Design and Installation Documentation

This document is a comprehensive set of architectural and engineering design drawings for the repair and installation of a humidification system in Building 3708 at Tinker Air Force Base, Oklahoma. The project encompasses mechanical, electrical, and plumbing systems with detailed specifications for equipment installation, piping layouts, and control systems. Key equipment includes a steam generator (Aerco SS3CE rated at 1800 pounds/hour @ 15 PSIG or 1950 pounds/hour @ 100 PSIG steam), water softeners (North Star NST25ED with 8 GPM service flow rate and 25,000 maximum grain capacity), steam distribution manifolds (Nortec components), and a blowdown separator (Lattner 810 with 1" inlet). The system comprises nine Air Handling Units (AHU-3 through AHU-9) with associated equipment schedules, mechanical piping plans across multiple areas, mechanical AHU equipment roof plans, and detailed equipment and fixture schedules.

The design documentation includes mechanical abbreviations and symbols legend, equipment specifications with manufacturers and catalog numbers, schedule of materials with pipe fittings valves and insulation specifications, isometric details for plumbing and steam piping, typical distribution configurations at AHUs, steam and water converter details with system controls, electrical symbols and legends, lighting fixture and power control plan symbols, fire alarm system symbols, telephone/data system symbols, and electrical roof plan layouts. The project appears to be a complete as-built package delivered by FPM group, with all drawings indicating 100% as-built status and detailed notes addressing construction responsibility, verification requirements, equipment scheduling, material quality standards, and coordination procedures between contractors and the government contracting officer.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MARK DISCRIPTION APPLICATION MANUFACTURER CATALOG FITTINGS CW HW WASTE VENT REMARKS

FS-1 DRAIN SINK FLOOR WADE 9014 -- -- 4" -- CAST IRON 8" ROUND WITH 6"

SUMP, A.R.E. INTERIOR, ALUMINUM

DOME STRAINER AND NICKEL

BRONXE TOP

PLUMBING FIXTURE SCHEDULE

MARK DISCRIPTION MANUFACTURER CATALOG REMARKS

SG-1 STEAM GENERATOR AERCO SS3CE GENERATOR SHALL BE RATED AT:

1800 POUND/HOUR @ 15 PSIG STEAM

1950 POUND/HOUR @ 100 PSIG STEAM

WS-1, 2 WATER SOFTENER NORTH STAR NST25ED SERVICE FLOW RATE 8 GPM, 25,000 MAX

GRAIN CAPACITY, SALT STORAGE CAPACITY

300 LB, FULL FLOW BYPASS VALVE, METER

RANGE 0-100 GPM

SDM-1- 6 STEAM DISTIBUTION MANIFOLD NORTEC REFER TO NORTEC REPLACEMENT STEAM MANIFOLDS AND FOR

AHU OPTION SCHEDULE COMPONETS AHU'S 3,4,5,6, 8 AND 9

BS-1 BLOWDOWN SEPERATOR LATTNER 810 1" INLET

EQUIPMENT SCHEDULE

G-1
M-1
M-2
M-3
M-4
M-5
M-6
M-7
M-8
M-9
M-10
M-11
M-12
M-13
M-14
P-1
P-2
E-1
E-2