RFI_Q&A.pdf
PDF 469 KB Posted
- Attached to
- ASHE 18-1058 Repair Fac. 940A for 57RQS Beddown
- Solicitation number
- FA568218R0016
About this file
Q&A
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ASHE_18-1058_Drawings_REV1.pdf | ||
| FA568218R00160001.pdf | ||
| ASHE_18-1058_Technical_Specifications_REV1.pdf | ||
| ASHE_18_1058_REV.1_CCEB_Blank.xlsx | XLSX spreadsheet | |
| FA568218R0016.pdf | ||
| ASHE_18_1058_CCEB_Blank.xlsx | XLSX spreadsheet | |
| ASHE_18-1058_Drawings.pdf | ||
| ASHE_18-1058_Schedule_of_Material_Submittals.pdf | ||
| ASHE_18-1058_Technical_Specifications,_Jan_2018.pdf | ||
| Additional_Requirements,_January_2018.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA568216R0016
Questions & Answers
With reference to item 6.5 Comm works:
Q1: Is the SOW pictures #3 the new layout or the existing one?
A: The picture#3 is only a sample how to install 24Ports and Cable management panels.
Q2: Is the Juniper switch shown on picture #3 must be provided or is it existing?
A: Contractor must furnish and install a new Juniper switch.
Q3: Item 6.5 states 6ea new patch panels meanwhile in the picture #3 only 5ea are shown. Please clarify
A: Item 6.5 requires 6ea 24ports patch panels and 6ea cable management; Contractor can re-use existing 19" rack. Contractor must furnish and install 6ea 24Ports and 6ea Cable Management.
With reference to item 6.7 Comm works:
Q4: Is each 51 comm drops composed by 2 RJ45 outlets or 4 RJ45 outlets? Is the total of RJ45 CAT 6 outlets 102?
A: As specified in it 6.7, each box is "Dual outlets"; It means 51ea boxes and therefore 102ea RJ45.