ASHE_18-1058_Drawings.pdf
PDF 2 MB Posted
- Attached to
- ASHE 18-1058 Repair Fac. 940A for 57RQS Beddown
- Solicitation number
- FA568218R0016
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI_Q&A.pdf | ||
| ASHE_18-1058_Drawings_REV1.pdf | ||
| FA568218R00160001.pdf | ||
| ASHE_18-1058_Technical_Specifications_REV1.pdf | ||
| ASHE_18_1058_REV.1_CCEB_Blank.xlsx | XLSX spreadsheet | |
| FA568218R0016.pdf | ||
| ASHE_18_1058_CCEB_Blank.xlsx | XLSX spreadsheet | |
| ASHE_18-1058_Schedule_of_Material_Submittals.pdf | ||
| ASHE_18-1058_Technical_Specifications,_Jan_2018.pdf | ||
| Additional_Requirements,_January_2018.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASHE 18-1058
bldg 940A South view
ASHE 18-1058
bldg 940A East view
47-2
CH.2
47-1
ASHE 18-1058 REPAIR FAC # 940A FOR 57RQS
47-3
M E
C H
A N
R
M
A H
U
CH.1
M t
Legend
Mt.00
28.20
R
R
R
R
R
N
R
Lt new holes
Steel Bumpers 15cm dia
Blast door to remove and replace
B u m p e r s
DECON equipm.
to remove
New metal flasdhing on membrane roof
ANT. restore exist. antenna pole on the roof.
New concrete slab Mt 6.5x29.0
ANT.
Vynil floor to be replaced exist.
slab save concr.
ramp new
0.0
+0.6 Mt mt5x2 raise exist. metal covers.
block opening
New stainless steel rail, 50 mm dia.
2ea metal plates to remove and replace with new aluminum grids
2ea metal plates to remove and replace with new aluminum grids restoration of walls and ceramic floor
CH.2
ASHE 18-1058 REPAIR FAC # 940A FOR 57RQS
M E
C H
A N
R
M
A H
U
CH.1
M t
Mt.00
10 20
28.20
N
ELECTR. Legend
B u m p e r s
ANT.
exist.
slab save concr.
slope new mt5x2
Office trailer
20x8 ft
ELECT.RM
New MDP, 50Hz 3ph+N, 400V
New trailers panel.
New MDP, remove existing
New lights 2x36W. W.P. IP66, stainless steel.
EMC
Elect.Met. Tubing, 80mm Dia wiring 4x35+T
ARMAG trailer 27x10 ft.
(8.2x3.0 mt.)
New line from substation 947 exist. line exist. elect.panel exist. elect.panel
New line
4x35+T exist. line
2x36W
Alum.box IP66
Alum. box IP66 mm310x260x120 new second. elect.panel p
A p
A p
A p
THIS SCHEME IS INTENDED AS OPERATING PRINCIPLE.
CONTRACTOR SHALL DEVELOP AND SUBMIT A DETAILED SCHEME.
WITH THE TYPE OF BREAKERS USED.
p p
A p
A e x i s t
S e c o n d p a n e l t o n e w t r a i l e r s
P a n e l s p a r e s p a r e e l e c t r o o m s e r v i c e s
New MDP, 50Hz 3ph+N, 400V e x i s t
S e c o n d p a n e l
N e w l i n e f r o m s u b s t a t i o n x
T n e w b r e a k e r
ASHE 18-1058 REPAIR FAC # 940A FOR 57RQS
K A p
A
M E
C H
A N
R
M
A H
U
M t
Mt.00
10 20
28.20
NEW GROUNDING SYSTEM
ANT.
concr.
slope new mt5x2
Equipotential copper plate, pre-holed, mm 8x80x600
ELECT.RM
copper wire 75 Sq.mm
Ground pit with cast iron cover
3P+N+T interlocked outlet IP67 aluminum body type Palazzoli Alupres complete of Plug.
THIS SCHEME IS INTENDED AS OPERATING PRINCIPLE.
CONTRACTOR SHALL DEVELOP AND SUBMIT A DETAILED SCHEME.
WITH THE TYPE OF MATERIALS USED.
0 2
P
N
T
A
P
N
T
A
P
H
V
T
A
P
H
V
T
A e x t l i g h t s
A u t M a n
New Trailers Panel, 50Hz 3ph+N, 400V +G
Thermal-magnetic breakers Icu=25KA
CH.2
M E
C H
A N
R
M
A H
U
CH.1
M t
Mt.00
10 20
28.20
N
COMM Legend
B u m p e r s
ANT.
exist.
slab save concr.
slope new mt5x2
2ea CAT6 LAN outlets.
2ea LAN cable TIA568A.
OSP
OSP
Cable Head
ARMAG trailer 27x10 ft.
(8.2x3.0 mt.)
Office trailer
20x8 ft
ISP
ISP Comm Rack
2in. (50mm) El.Met.Cond.
2"-1/2 EMC
Alum. box IP67 mm410x315x150
Alum. box IP67 mm410x315x150
Wire Mesh tray mm150x60
ANT. Install 100mm PVC conduit to rm 54.
new conduit
2"-1/2 EMC
ELECT.RM
| 940A photo1 |
| 940A ph2 |
| 940A1 civil |
| 940A1 Elec |
| 940A1 elecMDP |
| 940A1 Ground |
| 940A1 trailer SDP |
| 940A1-Comm |
File details come from the government source that posted it.