Attachment 7 - Appendix D - Heat Load Calculation (Amendment 2).pdf

PDF 676 KB Posted

Attached to
Solicitation for Bldg. 168 Boiler, Heat Distribution, and Ventilation Replacement on Spangdahlem AB
Solicitation number
FA560625B0001
Issued by

About this file

This document is a detailed heating load calculation for a facility, breaking down thermal requirements for five different areas: Bay 1/2 + 0.5Hall, Bay 3 + 0.5Hall, Classroom 1st floor, Admin Area, and Instructor 2nd Floor. The calculation provides comprehensive thermal analysis at an external design temperature of -10°C with a 10K temperature differential, specifying heating load in watts for various building components including floors, walls, ceilings, and windows.

The total project heating load is 90,683 watts, with individual area requirements ranging from 2,142 watts (Classroom 1st floor) to 48,120 watts (Bay 1/2 + 0.5Hall). Each area's analysis includes detailed measurements of square meters, heat load, and U-values for different building elements such as concrete floors, wooden beam ceilings, walls, and windows. The calculations account for factors like air exchange, ground/ceiling interfaces, wall compositions, and thermal insulation characteristics, providing a comprehensive thermal performance assessment for the facility's different zones.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Raumbezeichnung Raumtemperatur A Heizlast Heizlast/m²

°C m² W W Bay 1/2 + 0.5Hall 15 164 48,120 293 Bay 3 + 0.5Hall 15 88 24,252 276 Classroom 1st floor 20 20 2,142 107 Admin Area 20 86 11,917 139 Instructor 2nd Floor 20 35 4,253 122 Summe Heizlast Projekt 393 90,683

Bauherr: Auftragsnummer: Datum: Auslegungstemperatur: ∆T:

-10°C 10K

Höhe Heizlast (Watt) Temperatur

4.5 44,556 15

3,564 Zzgl. Zusatzaufheizleistung 8% gem TAB 445.1 (8h, 0.5, h, 2)

48,120 qm Heizlast Watt Typ U-Wert

164 5,018 Zuluftraum 0.8

1680 15,100 Abgasabsaugung 2400 m³/h Nennvolumenstrom bei 0.7 Gleichzeitigkeit, dT 25K qm Heizlast Watt Bauart U-Wert

164 5,125 Betonfußboden, ohne Wärmedämmung qm Heizlast Watt Bauart U-Wert

164 5,125

Holzbalkendecke / Steildach, ca.3 - 6 cm Wärmedämmung / Flachdach, ca.5 cm Wärmedämmung und 30cm Kiesschüttung qm Heizlast Watt Bauart U-Wert

70 375 Beton, Naturstein, ca.3 - 6 cm Wärmedämmung

0.6 qm Heizlast Watt Bauart Anzahl U-Wert

50 6,250 Im Wesentlichen aus Metall 1 4 qm Heizlast Watt Bauart U-Wert

58 150 Beton, Naturstein, ca.3 - 6 cm Wärmedämmung

0.6 qm Heizlast Watt Bauart Anzahl U-Wert

50 6,250 Im Wesentlichen aus Metall 1 4 qm Heizlast Watt Bauart U-Wert

62 1,163 Beton, Naturstein, ca.3 - 6 cm Wärmedämmung

0.6

Projekt:

Bay 1/2 + 0.5Hall

Luftwechsel

Boden/Kellerdecke an Erdreich

Wand an Außenluft

Decke/Dach an Außenluft

Wand an Außenluft

Fenster/Türen

Wand an Außenluft

Fenster/Türen

Höhe Heizlast (Watt) Temperatur

4.5 22,455 15

1,796 Zzgl. Zusatzaufheizleistung 8% gem TAB 445.1 (8h, 0.5, h, 2)

24,252 qm Heizlast Watt Typ U-Wert

88 2,693 Zuluftraum 0.8

840 7,300 Abgasabsaugung 1200 m³/h Nennvolumenstrom bei 0.7 Gleichzeitigkeit, dT 25K qm Heizlast Watt Bauart U-Wert

88 2,750 Betonfußboden, ohne Wärmedämmung qm Heizlast Watt Bauart U-Wert

88 2,750

Holzbalkendecke / Steildach, ca.3 - 6 cm Wärmedämmung / Flachdach, ca.5 cm Wärmedämmung und 30cm Kiesschüttung qm Heizlast Watt Bauart U-Wert

40 281 Beton, Naturstein, ca.3 - 6 cm Wärmedämmung

0.6 qm Heizlast Watt Bauart Anzahl U-Wert

25 3,125 Im Wesentlichen aus Metall 1 4 qm Heizlast Watt Bauart U-Wert

28 56 Beton, Naturstein, ca.3 - 6 cm Wärmedämmung

0.6 qm Heizlast Watt Bauart Anzahl U-Wert

25 3,125 Im Wesentlichen aus Metall 1 4 qm Heizlast Watt Bauart U-Wert

20 375 Beton, Naturstein, ca.3 - 6 cm Wärmedämmung

0.6

Projekt:

Bay 3 + 0.5Hall

Luftwechsel

Boden/Kellerdecke an Erdreich

Wand an Außenluft

Decke/Dach an Außenluft

Wand an Außenluft

Fenster/Türen

Wand an Außenluft

Höhe Heizlast (Watt) Temperatur

2.5 2,142 20 qm Heizlast Watt Typ U-Wert

20 306 Normale Raumnutzung, undichte Fenster

0.6 qm Heizlast Watt Bauart U-Wert

20 750 Betonfußboden, ohne Wärmedämmung qm Heizlast Watt Bauart U-Wert

20 563 Hohlsteindecken mit Zementglattstrich

1.5 qm Heizlast Watt Bauart U-Wert

12 225 Beton, Naturstein, ca.3 - 6 cm Wärmedämmung

0.6 qm Heizlast Watt Bauart Anzahl U-Wert

2 165 Doppelverglasung 1 2.2 qm Heizlast Watt Bauart U-Wert

38 79 Hohlziegel, Porenbeton 1.4 qm Heizlast Watt Bauart Anzahl U-Wert

2 54 Im Wesentlichen aus Holz, Holzwerkstoffen oder Kunststoff

1 2.9

Projekt:

Classroom 1st floor

Luftwechsel

Boden/Kellerdecke an Erdreich

Decke/Dach an unbeheizten Raum

Wand an Außenluft

Fenster/Türen

Wand an eingeschränkt beheizten Raum

Höhe Heizlast (Watt) Temperatur

2.5 11,917 20 qm Heizlast Watt Typ U-Wert

86 1,754 Zuluftraum 0.8 qm Heizlast Watt Bauart U-Wert

86 3,225 Betonfußboden, ohne Wärmedämmung qm Heizlast Watt Bauart U-Wert

86 3,225

Holzbalkendecke / Steildach, ca.3 - 6 cm Wärmedämmung / Flachdach, ca.5 cm Wärmedämmung und 30cm Kiesschüttung qm Heizlast Watt Bauart U-Wert

105 2,250 Beton, Naturstein, ca.3 - 6 cm Wärmedämmung

0.6 qm Heizlast Watt Bauart Anzahl U-Wert

5 413 Doppelverglasung 1 2.2 qm Heizlast Watt Bauart U-Wert

40 1,050 Hohlziegel, Porenbeton 1.4

Decke/Dach an Außenluft

Wand an Außenluft

Fenster/Türen

Wand an unbeheizten Raum

Projekt:

Admin Area

Luftwechsel

Boden/Kellerdecke an Erdreich

Höhe Heizlast (Watt) Temperatur

2.5 4,253 20 qm Heizlast Watt Typ U-Wert qm Heizlast Watt Bauart U-Wert

35 1,313 Betonfußboden, ohne Wärmedämmung qm Heizlast Watt Bauart U-Wert

35 1,313

Holzbalkendecke / Steildach, ca.3 - 6 cm Wärmedämmung / Flachdach, ca.5 cm Wärmedämmung und 30cm Kiesschüttung qm Heizlast Watt Bauart U-Wert

62 1,628 Hohlziegel, Porenbeton 1.4

Decke/Dach an Außenluft

Wand an unbeheizten Raum

Projekt:

Instructor 2nd Floor

Luftwechsel

Boden/Kellerdecke an unbeheizten Raum