Subject: Questions & Answers for RFP FA5270-15-R-0031 – 18 Aug 2015
Qustion 1: According to work road requirements Appendix B, Naha Port, (page 42). There are 2 buildings #305, on other hand in Price exhibit, there is one space for putting price for Bldg#305.
Do we have to estimate 2 of Buildings quotes into 1 quote for price exhibit?
Answer: Appendix B are revised, Bldg. 305, Naha Port (Detectors).
Question 2: According to Revised PWS para1.1.2, it says” All fire alarm systems need monthly periodic inspection as un-monitored.” Do we have to estimate all fire alarm systems such as smoke detectors, heat detectors, smoke/heat detectors, fire alarm control panels, pull/push switches, bell/horns, strobe/indicate lamps as following to Table 2-1 “Detection and Alarm system”work road requirements and ITM at Appendix B? We believe that detector is one of fire alarm system. from which devices are you taking into consideration for fire alarm systems?
Answer: Fire alarm control panels and annunciator equipment of all fire alarm systems need monthly periodic inspection as un-monitored systems in accordance with the Table 2-1 identified in ITM Appendix B. Updated PWS (18 Aug 15) para 1.1.2 to include Fire alarm control panels and annunciator equipment IAW UFC 3-601-02. Frequency inspections for all other Fire Alarm Systems are identified in ITM Appendix B Table 2-1
File details come from the government source that posted it. Updated .