Question No.
Reference (Sect/Para/Page) QUESTION GOVERNMENT RESPONSE
1 Section 01 01 00/1.2 statement of work/01 01 00-1 statement of work crack repair
Please clarify estimated quantity of crack repairs.
No known estimated quantity of cracks to repair since most of the roof surfaces are covered with roofing materials.
2 Section 07 50 00.20/part2-products/07 50 00.20-3
2.01 materials: all materials shall conform as listed below: The coating system shall pass the ASTM e108 and meet the requirements for class a, fire rated
Is Japanese product accepted?
As long as it meets ASTM E 108 or equivalent.
3 As-built drawings bldg-3542 and Roof Plan B-3542 (See attachment)
The scaffolding in the front of hangar door will limit access to hangar areas. Please confirm if this is acceptable.
Please provide the estimated time that you expect the hangar door access will be limited.
4 As-built drawings Bldg-925, rain gutters between two roof.(See attachment)
The contractor shall clean existing metal gutter then provide new waterproofing.
Please confirm this requirements does not include any repair/replacement of gutter for unforeseen aged deteriorations.
Clean and coat metal gutter as stated on the drawings.