Questions Answered Reno.xlsx

XLSX spreadsheet 86 KB Posted

Attached to
Wake Island (WI) B. 1120 Restoration
Solicitation number
FA521525R0009
Issued by

About this file

This file is a Questions and Answers (Q&A) document for a federal contract opportunity to restore Building 1120 on Wake Island. The solicitation, issued by the Department of the Air Force Pacific Air Forces, requires comprehensive renovation of the building, including demolition of existing interior walls, installation of new mechanical and electrical systems, painting, flooring, and other infrastructure improvements. Key project details include a proposal due date of 12 September 2025 at 10:00 AM AKDT, with offers valid until 30 September 2025.

The Q&A document reveals significant existing building conditions, including gutted interior spaces, no functional utilities, suspected asbestos in certain areas, and extensive concrete spalling. The renovation scope involves complete system replacements, including electrical, plumbing, HVAC, fire alarm, and communication systems. Contractors are expected to submit shop drawings for newly installed utilities, remove all existing wood framing, install steel stud walls, and perform comprehensive renovations while navigating complex logistical challenges associated with a remote island location. The project requires two-person staffing (Superintendent + QC/SSHO) and adherence to specific technical requirements outlined in the Statement of Work.

View the file

Other files

File Type Posted
25 AUG 25- RENO Questions.pdf PDF
25 AUG 25- RENO Questions.xlsx XLSX spreadsheet
Bldg B_C_1120 1963.pdf PDF
1120 (C 520) Air Conditioning.pdf PDF
c_520_1120_Mechanical 1967.pdf PDF
Electrial Site Plan.PDF PDF
1120 Photo Log.pdf PDF
Wake Island Concrete and Masonry Structures Feb 2020.pdf PDF
Utilities.pdf PDF
A_All Buildings 1963 (C_520_1120).pdf PDF
B1120 floorplan draft V3_Redacted Update.pdf PDF
Location Map c_1120.PDF PDF
20170412 Wake Island Assessment Pre-Final Report 2017.pdf PDF
1118 and 1120 Structural Assessment and Repairs 2022.pdf PDF
Amendment 01 - Question Set 1.docx DOCX document
Solicitation - FA521525R0009.pdf PDF
Attachment 1 - WI Restor Building 1120 SOW.pdf PDF
Attachment 2B - AF 103 Template.pdf PDF
Attachment 3 - 11 AF Satellite and Ground Terminal Request (Fillable).pdf PDF
Attachment 5 - 611th Tank Inventory Template.docx DOCX document
Attachment 6 - AF3000-3064-3065.pdf PDF
Attachment 9 - B1120 floorplan.pdf PDF
Attachment 10B - Wake Island Cargo Processing Guide.pdf PDF
Attachment 10C - WI Base Support Letter.pdf PDF
Attachment 12A - B1120 Exterior photos portfilio.pdf PDF
Attachment 2A - 611 CES Dig Permit Process 2024.pdf PDF
Attachment 7 - DD Form 1354.pdf PDF
Attachment 11 - WI Master Plan and Design Guide.pdf PDF
Attachment 12B - B1120 Interior photos portfolio.pdf PDF
Attachment 13 - Wage Determination.pdf PDF
Attachment 4 - eSSS PRSC Commercial Satellite Terminal Policy Memorandum.pdf PDF
Attachment 8 - AF FORM 813 B1120.pdf PDF
Attachment 10A - SAR Request.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Project Information
Wake Island Bldg. 1120 Renovations
Questions
QUESTION #DOCUMENTSUBSECTIONCONTRACTOR QUESTIONRESPONSE
1A-101Keynote 11Keynote states to "SEE WALL ASSEMBLY". Please provide wall assembly.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
2DrawingsAllPlease provide clear Civil, Structural, Architectural, Mechanical, and Electrical drawings?See attached asbuilts
3DrawingsAllPlease provide clear drawings, that give additional detail or clarification for wall types, structural connections, elevations.See attached asbuilts
4DrawingsAllPlease provide dimensions of the opening for the infill? Is the infill typical at each opening?See attached asbuilts
5DrawingsAllPlease provide interior dimensions, with elevations, wall and ceiling heights?See attached asbuilts
6A-101Keynote 13 & 141. Is it to be assumed that only 50% of the existing windows are reusable and will be reinstalled?
2. If more than 50% of the windows are found to be non-reusable before removal, will the contractor be compensated for the purchase and shipping of new replacement windows through a change order or other mechanism?This document is labeled "draft floorplan" It's purpose is to show the floor plan only
7SOW3.1.11Please provide Hazmat Survey Assessment?None exists
8A-101Keynote 15Keynote states to "SEE WALL ASSEMBLY". Please provide Wall Assembly.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
9A-101Keynote 17Keynote states to "SEE MECHANICAL". Please provide Mechanical.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
10A-101Keynote 19Keynote states to "SEE FIRE ALARM DRAWINGS". Please provide FIRE Alarm Drawings.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
11A-101Keynote 21Keynote states, "NEW ALUMINUM HANDRAIL AT STAIR, TYPICAL". What is "TYPICAL"?This document is labeled "draft floorplan" It's purpose is to show the floor plan only
12A-101Keynote 22Keynote states, AC UNIT ON CONC PAD, TYPICAL, SEE MECHANICAL." What is "TYPICAL"? Please provide Mechanical.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
13A-101Keynote 23Keynote states "NEW CONCRETE PAD HERE, MATCH EXISTING PAD SIZES. SEE MECHANICAL." What are the existing pad sizes? Please Provide Mechanical.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
14SOW3.2.3.1, 3.2.3.2Are as-builts for the existing electrical and communications systems available?All known asbuilts are attached
15A-1011/201The floor plan, A-101, calls out detail 1 on A-201. Please provide A-201.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
16A-1012/201The floor plan, A-101, calls out detail 2 on A-201. Please provide A-201.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
17A-1013/201The floor plan, A-101, calls out detail 3 on A-201. Please provide A-201.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
18A-1014/201The floor plan, A-101, calls out detail 4 on A-201. Please provide A-201.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
19A-1011/A-301The floor plan, A-101, calls out detail 1 on A-301. Please provide A-301.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
20A-1012/A-301The floor plan, A-101, calls out detail 2 on A-301. Please provide A-301.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
21A-1013/A-301The floor plan, A-101, calls out detail 3 on A-301. Please provide A-301.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
22A-1011/A-302The floor plan, A-101, calls out detail 1 on A-302. Please provide A-302.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
23A-1012/A-302The floor plan, A-101, calls out detail 2 on A-302. Please provide A-302.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
24A-1012/A-400The floor plan, A-101, calls out detail 2 on A-400. Please provide A-400.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
25A-1011/A-500The floor plan, A-101, calls out detail 1 on A-500. Please provide A-500.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
26A-1012/A-500The floor plan, A-101, calls out detail 2 on A-500. Please provide A-500.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
27A-1013/A-500The floor plan, A-101, calls out detail 3 on A-500. Please provide A-500.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
28A-1015/A-502The floor plan, A-101, calls out detail 5 on A-502. Please provide A-502.This document is labeled "draft floorplan" It's purpose is to show the floor plan only
29SOW3.2.2.1What are the finish and opening requirements for the Pharmacy, Clinic Office, Supply, Utility Room, Hallway, and Laundry RM, included in the SOW?See 3.2.2.5
30SOW3.2.3.2.1In lieu of as-builts can a mechanical equipment list be provided for existing mechanical equipment?There is no functional mechainical equirment B1120
31SOW3.2.3.1, 3.2.3.2In lieu of as-builts please provide photos, locations, amperages, voltages, feeder size and circuit counts for all main and sub panels in bldg. 1120.There is no functional electrical system in B1120
32SOW3.2.3.1, 3.2.3.2Please confirm voltage and fuse size of 4X main disconnect which is to remain.See asbuilts attached
33SOW3.2.3.1, 3.2.3.2Does bldg. 1120 have a Lightning Protection System that will require any demo/re-installation or recertification?No lightning protection system is known for B1120.
34SOW3.2.6.2With the fire alarm system being installed in 2018, are system as-builts available?No fire alarm as builts are known.
35SOW3.2.6.2.1SOW states it is the contractors responsibility to repair or replace components, as required, to put the fire alarm system back into service and to ensure the system reports correctly to Wake Central monitoring. Are there any known deficiencies in the system currently, to include but not limited to, device or panel deficiencies? Is the system currently reporting back to monitoring correctly?The status of the fire alarm system is unknown
36SOW3.2.6.2.1Will the contractor be responsible for any upgrades to the system due to changes in fire alarm code after 2018?
37SOW3.2.7Please clearly identify the "common areas Inside" that will need (2) telephone lines or provide a total count of telephone lines needed for "common areas inside".Laundry room and med clinic
38SOW3.2.7Is the "existing central building" referenced in 3.2.7 referring to bldg. 1120 or a separate building?Other nearby buildings (ex 1118) which have comms lines wired in.
39SOW3.2.7Will each sleeping room require (1) tv cable/outlet or (2)?1
40SOW3.2.8.1Please clarify what EPA Air Quality Emissions requirements are needed for the 25kW backup generator. Emission packages are not typically provided or available for 25kW generators or typically required for emergency/standby generators.Disgard is EPA requirement are not applicatable
41SOW3.2.8.1Please provide the required run time or gallon capacity for the generator day tank.24 hr run time for installed generator
42SOW3.2.8.1Please provide the amperage of the (2) 240v outlets required in the "exterior treatment room".30 amp
43SOW3.2.8.3Will electrical connections be required for the evaporators in pharmacy, supply and treatment rooms, if so can electrical requirements be provided?Yes, electrical requirements for the Split unit can be determined by split unit configuration to be installed; see SOW 3.2.4.2
44SOW3.2.8.4Please provide the amperage of the (2) 240v outlets required in the "treatment room".30 amp
45SOW3.2.9.2.1Can photos, with locations, be provided of the existing dryer disconnects in bldg. 1116?Photos can not be provided in this short suspense. Standard commerial connections are fine.
46SOWStaffingThe Statement of Work typically outlines required site staffing roles such as Superintendent, Quality Control (QC) Manager, and Site Safety and Health Officer (SSHO). However, this task order does not specify staffing requirements. Please confirm the following:

1. What are the minimum required site staffing positions for this task order?

2. Are the following roles required to be present full-time on site?

• Superintendent

• QC Manager

• SSHO

3. It is typically stated whether one, two or three individuals are required per task order the following personnel mixes are acceptable:

•One Person: Superintendent/QC/SSHO performed by single qualified individual •Two Person: Superintendent + QC/SSHO (dual role) or Superintendent/SSHO (dual role) + QC •Three Person: Superintendent + QC + SSHO

What are the staffing requirements for this project?Two Person; Superintendent +QC/SSHO
4712B12BBased on the photos, there is furniture and personal items remaining in the building. Is the GC responsible for the moving and relocation of these items or will it be the responsibility of others? If it is the GC's responsibly, please provide photos, with location, and list of items to be moved.Furniture is to be disposed. No list exists. Photos of Furnature is shown in SOW attachment 09
48SOW3.2.2.2Please confirm whether the areas exhibiting spalling and/or cracked concrete have been previously identified. If so, please provide the following:
1.Quantification of affected areas (square footage or linear footage as applicable).
2.Clear identification of these areas on:
•Floorplans
•Elevation drawings (if available)
3.Indicate whether any repair details or specifications are provided for these conditions.
This information is critical for accurate scope assessment, material planning, and scheduling.Total extent of spalling is unknown. This is due to exterior wall infills covering much of the of areas likely to have spalling. Interior collumns have been shown in the photos with a tape for scale. "rotten" concrete is to me removed, the effected area formed and repoured to match unspalled conditions.
49DrawingsAllThere are multiple different sized doors throughout to building. To get accurate sizing and count can a door schedule be provided?See SoW 3.2.2.2.5-6 and 3.2.8
50SOW & Interior photos3.2.2.4 & 3.2.2.8Can photos, with locations, of the bathrooms and showers be provided? This will determine if it is possible to remove the existing wood partitions between showers, without disturbing cement asbestos board sheathing.Photos can not be provided in this short suspense.
51SOW3.2.2.3The construction documents do not clearly specify the required materials for the infill sheathing system, interior side and exterior side. Please confirm the approved sheathing material(s) to be used for the infill wall assemblies, including any fire rating, moisture resistance, or structural performance requirements.Exterior Wall infill assembly : exterior 5/16" Cement BD, painted to match building exterior, fastened 6' OC, air barrier, 3 5/8' metal studs @ 16' OC (coat IAW SOW) R13 insulation, Interior 5/8' paperless gyp BD
52SOW3.2.2.3Please confirm whether the existing exterior wall infills and windows in the Treatment Room, Pharmacy, and Laundry Room are to be replaced as part of the current scope of work. The construction documents do not clearly indicate whether these components are to be replaced.All exterior wall infills are to be replaced.
53SOW3.2.2.4The SOW states, "For purpose of this contract, it is assumed that the existing two layers of 3/8” thick (or single layer of ¾” thick) gypsum board on one side of existing wood studs…".

The solicitation references assumed existing gypsum board conditions, but the provided photo documentation does not clearly identify:

- Locations of existing gypsum board assemblies

- Quantities or approximate square footage of gypsum board to remain or be removed

- Visual confirmation (photos) of the referenced assemblies To ensure accurate planning, estimating, and execution, please provide:

- Annotated drawings or floor plans indicating gypsum board locations

- Estimated quantities (square footage or linear footage) per area

- Supplemental photo documentation showing representative conditions of the gypsum board on wood stud assembliesAll existing gyp board is to be demo'd. SOW states, "Replace all interior walls shown in the plans which are not currently made of concrete, or have cement asbestos board sheathing, with steel stud framed walls sheathed with 5/8” thick type X, mold resistant gypsum board on both sides at all locations where walls were shown on the provided draft building floorplan (attachment 09).
54SOW3.2.2.4Paragraph 3.2.2.4 specifies:

• “Replace all interior walls shown in the plans… with steel stud framed walls,”

• "Remove as much termite damaged framing as can be done without disturbing the cement asbestos board sheathing on the restroom sides of the walls."

These directives appear to conflict.

Please clarify the following:

1. Is the intent to demolish all wood framing and reframe walls with steel studs (Hallways, Rooms)?

2. Is the intent to leave the walls that have gypsum, with the possibility that the may contain ACM?

2. Remove only termite damaged wood framed walls without disturbing ACM. Please clearly identify locations.

3. Please clearly identify any and all walls to remain.The intent is to demolish all wood framing. And reframe with steel stud IAW 3.2.2.4. The expection to this is the cement asbestos board on the restroom side walls. For wood studs near the asbestos cemement board, remove and replace as much as possible with out distrubing the asbestos cement. The only wall that may remain is as small a section possible of the wall associated with the asbestos cement.
55SOW3.2.2.5The requirement is for plastic or stainless steel signage? Each material has a significant price difference. To obtain a more accurate pricing, can a selection be made at this time?Plastic is prefered to prevent rust
56PhotosStairwaysPlease provide photos, with locations of all the stairways?See draft floor plan for locations. All availible pictures have been provided.
57SOW3.2.2.14What material is required for the window blinds referenced in the SOW (e.g., vinyl, fabric, aluminum, wood)?vinyl or fabric.
58SOW3.2.2.3Are the exterior walls required to be painted?Painted. See question 51.
59SOW3.2.2.4Have the existing walls, with gypsum, been tested for ACM?Building is gutted. The only known ACM is the asbestos cement board assocaiated with the restrooms.
60A-101Clinic Exterior WallThe construction documents do not clearly define the specifications for the wall leading into the Clinic Office from the exterior.See Question 51.
61GeneralStructuralTo accurately plan and coordinate plumbing piping in the treatment room and laundry room and assess broader project implications, please confirm the following:
1.Is the existing structure constructed on a slab-on-grade foundation?
2.If so, please provide:
•Structural as-built drawings showing slab layout, thickness, reinforcement, and any embedded utilities
•Slab details, including control joints, penetrations, and any known obstructions or limitations for core drilling or trenchingSee asbuilts attached
62Attachment 12BIMG_20241202_121353623.jpgInterior photos show that numerous floor tiles are in poor condition, exhibiting signs of delamination, cracking, and loosening. Given the age and condition of the materials, we are requesting clarification on the following:
1.Do the existing floor tiles and associated mastic contain asbestos or are they presumed to contain ACM?
2.If ACM is present or presumed, is abatement required prior to any construction or demolition activities?

3. If it is to be abated, who is responsible for conducting the abatement—Owner, GC, or a third-party contractor?

4.Will an asbestos survey or testing be provided to confirm material composition prior to work commencement?ACM is not known or suspected in association the existing VCT. Abatement is not expected. No testing exists.
63SOW3.1.11 & 3.2.2.13.1.11 States that there is suspected Hazmat in the areas of the building.

3.2.2.1 states to demolish ceiling in the first floor corridor.

Section 3.1.11 identifies areas of the building with suspected hazardous materials (Hazmat), while Section 3.2.2.1 directs demolition of the ceiling in the first floor corridor. To ensure safe and compliant execution of demolition activities, please confirm:

1. Whether the ceiling materials in the first floor corridor should be treated as potentially containing hazardous materials, given the general Hazmat concerns noted in 3.1.11.

2. If so, please provide Hazmat survey results or documentation specific to the corridor ceiling3.1.11 states suspected ACM, "Some joint compound, wall and ceiling sheathing in the rest rooms & bathrooms, and the boiler insulation in building 1120 is suspected ACM. Lead and PCB content of paint is unknown" Out side of these rooms ACM is not suspected. No ACM/LBP data exists for B1120.
64SOWGeneralAre there any thermal or acoustic requirements for new walls?
65SOWGeneralAre there any thermal or acoustic requirements for new infills?See Question 51.
66SOWGeneralThe SOW states to install vinyl cove base around bases of all walls. If there is existing cove base, is the intent to leave it, as the mastic might contain ACM?ACM is not known or suspected in association with the vinyl base cove. Minimal exististing base cove is present. Remaining base cove expected to be removed during spalling repairs.
67A-101Sleeping RoomFirst floor rooms, between the "Laundry Rm" and the "Men's Bathroom", do not have numbers. Is this intentional or are they supposed to be "Sleeping Rooms"? If they are "Sleeping Rooms, please provide and updated floor plan, with associated room numbers.Updated with room numbers. See attahced
68SOW3.2.4.2The SOW requires the provision and installation of mini-split air conditions in a similar configuration to existing system. What is the existing system configuration? Please provide mechanical as-builts, along with an equipment schedule.See asbuilts attached
69PhotosUtility RoomPlease provide photos of the Utility Room.All available photos have been provided.
70PhotosLaundry RoomPlease provide photos of the Laundry Room.There is no existing laundry room. Per the SoW the contractor is to renovate the "laundry" shown in draft floorplan into the laundry room IAW the SOW
71SOWRequestTo accurately estimate labor hours and plan for demolition activities, please provide any available drawings or documentation that detail the current site conditions. Specifically, we are requesting:

1. Floor plans or elevations showing existing wall locations

2. Notes indicating which walls have already been removedSee the attached pictures showing that most walls have been striped down to the studs. All remaining, wood framing would is to be demo'd
72SOW3.2.2.7The SOW states to install VCT in areas where it is missing, please provide floor plans, with locations and approximate area in square feet (SF).Gov't estminates 500 SF of missing tiles
73SOW2.1Will IBC or other building code be used to determine extent of required fire protection or fire separations?See SOW 2.1
74SOW3.1.8Does completion time include design time?Yes
75SOW3.2.3.1What is the amperage, voltage, and phase rating of the existing disconnect to remain?Unknown
76SOW3.2.3.1Is there existing conduit penetrations that are to be reused? How many and what trade size?Unknown
77SOW3.2.3.2May NM(Romex) cable be used in concealed areas?Not in conduit. Conduit is needed as B1120 is concrete
78SOW3.2.3.2May emergency lighting units (bugeyes) with battery back up be sufficient for emergency lighting with back up power systems?If it meets code yes
79SOW3.2.3.2What is soft white light? Typically for residential we use either 3000K or 3500K fixtures.3000K or 3500K works
80SOW3.2.3.2.2NM(Romex) is typical in residential applications. Would that be acceptable in lieu of conduit?Conduit is needed.
81SOW3.2.7Will comm cabling be allowed in j-hooks where routed in accessible, concealed areas?Conduit is needed.
82SOW3.2.8.1Where will the generator be housed or will we need to design it in a weatherproof enclosure?Weatherproof enclosure is expected and needed.
83SOW3.2.8.1How much run time is needed for the generator? Will the day tank be the only source of fuel or will it be connected to another fuel storage tank? Will we be designing/installing the fuel piping if required?24 hours of run time. Day tank will be the only tank.
84SOW3.2.8.1Would a sub-base fuel tank be acceptable over a separate day tank?No
85SOW3.2.8.4Are these the same (2) 240V plugs called out in 3.2.8.1? Are separate disconnects required? Per NEC plug connections are acceptable as a means of disconnect when required.Yes. Acknowledged
86SOW3.2.8.4What amperage rating is required for these 240V plugs?30 amp
87SOW3.2.9.3Can we get a picture of the nameplate or information on washer/dryers?Not availble due to short suspense
88SOW3.2.7Can it be confirmed that no SIPRNet or other secure lines will be required.Confirmed
89SOW3.2.2.7 & 3.2.2.10The SOW contains conflicting instructions regarding treatment of concrete floors:

- Section 3.2.2.7 states: “Install VCT in areas where it is missing on the room floors.”

- Section 3.2.2.10 states: “Paint all concrete floors which do not have floor coverings.”

Please clarify which areas are to receive VCT and which are to receive paint. Additionally, please confirm:

- Are all floors concrete?

- Specific rooms or zones on the floor plan that require painting.

- Total square footage (SF) of concrete floors to be painted.

- Type of paint or coating to be used (e.g., epoxy, acrylic, urethane).All floors are concrete. 3.2.2.10 is refering to painting the restroom floors. Armorseal floor paint or equalivent. Roughly 800 SF is expected
90SOW3.2.2.5The Statement of Work specifies that Sleeping Room doors are to be painted. However, it does not explicitly mention whether the door frames associated with these doors are included in the painting scope.Door frames are to be painted
91SOW3.2.2.6The Statement of Work specifies painting of Sleeping Room doors, but does not clearly define the scope for “Other Doors” or their associated frames.

Please confirm the following:

1.Are “Other Doors” (e.g., Hallway Doors, Treatment Room, Clinic Office, etc.) required to be painted under this contract? Please list.
2.Are the associated doorframes to be painted as well?All doors and doorframes are required to be painted.
92SOW3.2.2.4The SOW states:

“For purpose of this contract, it is assumed that the existing two layers of 3/8” thick (or single layer of ¾” thick) gypsum board on one side of existing wood studs when combined with similar sheathing, or new 5/8” type X gypsum board on the opposite side of the wall, meets this requirement.”

Please confirm the preferred method.Contractor may pick either method, but 5/8 type X gyp board is perfered.
93RFIRequestInterior pictures were provided showing craked and spalling concrete columns as well as other interior conditions. Is it possible to receive a floor plan showing where each photo was taken?Photo are of the columns down the centerline of th building
94RFIRequestHas a structural survey been completed by a 3rd party engineer of B1120. Can this be shared with the contractorsSeveral structural surveys have been done. See attached folder "Strctrl asmt bidder Qs"
95RFIRequestIs there currently power (electric) running to B1120 which contractors can tie into for construction power. If power is available can details of this electrical service be providedB1120 Currently does not have power.
96RFIRequestCan the location of the on-island construction waste landfill be provided, in relation to B1120?Contractor is expected to remove all construction generated waste off island
97RFI4.3Please provide detailed information regarding all existing above ground, underground, concrete encased, subfloor, water, waste water/sanitary sewer piping systems for the project, specifically:

• Nearest service connection point (location and connection type)

• Identification of each pipe (e.g., sanitary sewer, storm drain, domestic water)

• Pipe sizes (diameter and material type)

• Horizontal and vertical location of piping, including invert elevations and slopes where applicableSee attached asbuilts
98RFIRequestPlease provide complete documentation for all existing electrical systems, including above ground, underground, concrete encased, and subfloor installations. Specifically, we are requesting the following:
•Reflected Ceiling Plans (RCP):

Showing all light fixtures, exit signs, occupancy sensors, and ceiling-mounted electrical devices.

• One-Line Diagrams:

For all electrical distribution systems, including service entrance, transformers, panels, and subpanels.

• Full Building Electrical Plans:

Including:

•Light fixtures and their control systems
•All fixed electrically powered equipment
•Switches, receptacles, and home runs
•Equipment schedules and circuiting information
•Panel Schedules:

For all electrical panels, including:

•Panel name and location
•Circuit numbers and descriptions
•Connected loads and spare capacity
•Voltage and phase informationSee attached asbuilts
99Ahtna's Email 8/13/25Regarding 4.3.12 & 4.3.17The call outs for "Plans” under section 4.3.12 and 4.3.17 indicate that the USAF is looking for the contractor to design the plumbing and electrical systems for the B1120 restoration. Nowhere in the SOW or Solicitation does it mention that this project is a “Design Build Project”. If the intent of the USAF is to have engineered designed and stamped drawings for the restoration work, please clearly state in the RFP.B1120 is gutted. There is no functional water, electrical, HVAC, or other utilities in B1120. Contractor is expected to submit “shop drawings” for the newly installed utilities. The drawings may or may not be stamped but the government needs drawings of the newly installed items.
100Ahtna's Email 8/13/25Regarding 4.3.12 & 4.3.17If the intent of the USAF is to not have the contractor to provide engineered Plans as submittals, please clarify at what level of detail does these plans need to be, and in what format will then need to be submitted.B1120 is gutted. There is no functional water, electrical, HVAC, or other utilities in B1120. Contractor is expected to submit “shop drawings” for the newly installed utilities. The drawings may or may not be stamped but the government needs drawings of the newly installed items.
101Ahtna's Email 8/13/25Regarding 4.3.12 & 4.3.17If it is the intent of the USAF to receive engineered Plans as submittals, will the USAF issue an addendum to all bidders stating bidders are to include costs for design of the mechanical and electrical systems in the RFP pricing.B1120 is gutted. There is no functional water, electrical, HVAC, or other utilities in B1120. Contractor is expected to submit “shop drawings” for the newly installed utilities. The drawings may or may not be stamped but the government needs drawings of the newly installed items.
102SOW3.2.5.2.3Are existing toilets wall mount, tankless commercial grade? Is theUnknown
103SOWRequestAre DDC controls for building systems, if present, required as part of the SOW?DCC are not present. Controls installed for this contract will be isolated to the system or unit,( i.e. FACP or AC spit unit, etc).
104SOWRequestAre cameras and/or access control systems required as part of the SOW?No
105RFIRequestGiven the remote location and complex logistics associated with construction projects on Wake Island—including transportation constraints, shipment of materials, and coordination challenges—planning and execution require an elevated level of clarity and foresight.

To support effective project delivery and minimize delays or rework, we respectfully request approval for a second round of Q&A following the initial response to submitted RFIs. This would allow the project team to:

•Clarify any ambiguities in the initial responses
•Address follow-up questions that arise during implementation planning
•Ensure alignment across all stakeholders before mobilization
106SOWRequestWill a reasonable extension to the bid submission date be granted to allow sufficient time for responses to outstanding RFI questions?