This document is a Combined Synopsis/Solicitation for a Request for Quotations (RFQ) for fire alarm system testing and maintenance services. The Department of the Air Force Pacific Air Forces is seeking quotes from small business vendors for this requirement under NAICS code 561621. Responses and questions must be submitted electronically by the due dates of August 28, 2024 and August 30, 2024, respectively. This acquisition will utilize simplified acquisition procedures and is a 100% Small Business Set-Aside. The solicitation incorporates the FAR provisions and clauses in effect through Federal Acquisition Circular 2024-05.

View the file

Other files for this federal contract opportunity

Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm & Life Safety Inspection and Testing Report

Date: 09/19/2022

Time: 8:00:00 AM

Service Organization Property Name (User)

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B10

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Hwy, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: Leeroy Wymer

License No: 220247 Telephone: (907) 854-3770

Telephone: (808) 682-1000

Monitoring Entity Approving Agency

Contact: Civil Engineer Operations Contact: N/A

Telephone: (808) 697-4316 Telephone: N/A

Monitoring Account Ref. No: N/A

Type of Transmission Service

Communicator: N/A Weekly

Manufacturer: N/A Monthly

Model Number: N/A Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: N/A Other (Specify)

Control Unit Manufacturer: Edwards Model No: EST3

Circuit Styles: B, B

Number of Circuits: 9

Software Revision: V5.32

Last Date System Had Any Service Performed: 09/19/2022

Last Date that Any Software or Configuration Was Revised: 09/19/2022

ALARM INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity Circuit Style Device Types

2 B Heat Detector, Edwards

2 B Pull Station, Radionics

1 B Smoke Detector, Edwards

Alarm Verification feature is disabled X enabled

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Quantity Circuit Style Appliances

1 B Bell

38 B Horn/Strobe, Edwards

No. of alarm notification appliance circuits: 8

Are circuits monitored for integrity? Yes No

SUPERVISORY SIGNAL INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity Circuit Style Devices

N/A N/A N/A

SIGNALING LINE CIRCUITS

Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1)

Quantity B Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120V Amps 20A

Overcurrent Protection: Breaker Amps 20A

Location (of Primary Supply Panelboard): Mechanical Room 110

Disconnecting Means Location: FP Panel Breaker #1

(b) Secondary (Standby): Batteries Storage Battery: Amp-Hr Rating 51Ah

Calculated capacity to operate system, in hours: X 24 60

Engine-driven generator dedicated to fire alarm system: N/A

Location of fuel storage: N/A

TYPE BATTERY

Battery Type Manufacturer Model Number Voltage Amps

Sealed Lead Acid Power-Sonic PS-1270 12 7

Sealed Lead Acid Power-Sonic PS-1270 12 7

Sealed Lead Acid Power-Sonic PS-1270 12 7

Sealed Lead Acid Leoch DJM1250 12 51

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701

Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE Yes No Who Time

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit Pass

Interface Equipment Pass

Lamps/LEDS Pass

Fuses Pass

Primary Power Supply Pass

Trouble Signals Pass

Disconnect Switches Pass

Ground Fault Monitoring Pass

SECONDARY POWER

TYPE Visual Functional Comments

Battery Condition

Pass

Load Voltage

Discharge Test

N/A

Charger Test

Specific Gravity

TRANSIENT SUPPRESSORS

REMOTE ANNUNCIATORS N/A

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Speakers N/A

Voice Clarity

INITIATING AND SUPERVISORY DEVICES TESTS AND INSPECTIONS

Location & S/N Device Type

Visual Check

Functional Test

Factory Setting

Measured Setting Pass Fail

2nd fl room 111 across restroom Heat Detector

2nd fl room 111 in restroom Heat Detector

1st fl main entrance lobby Pull Station

2nd fl main entrance lobby Pull Station

2nd fl hallway in closet above panel Smoke Detector

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Comments: N/A

EMERGENCY COMMUNICATIONS EQUIPMENT Visual Functional Comments

Phone Set N/A

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Call-in Signal N/A

System Performance N/A

INTERFACE EQUIPMENT Visual

Device Operation

Simulated Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Supervisory Signal N/A N/A

Supervisory Restoration N/A N/A

NOTIFICATION THAT TESTING IS COMPLETE Yes No Who Time

Building Management Leeroy 4:00P

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Other (Specify) N/A N/A

The following did not operate correctly: N/A

System restored to normal operation: Pass Date: 09/19/2022 Time: 4:00:00 PM

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Alston Chamizo Date: Time:

Signature:

Name of Owner or Representative: Leeroy Wymer Date: Time:

Signature:

DESCRIPTION:

CALL TYPE:

WORK PERFORMED: 09/19/2022

D. IJima C. Yoshino

8 Hours Each

ACTIONS TAKEN:

Building 10:

-Test and inspected the following devices:

1 Control Panel 3 Expander Panel 4 Batteries 1 Smoke Detectors 2 Heat Detectors 2 Pull Station 38 Horn/Strobes

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-All devices passed test and inspection.

FOLLOW UP ACTIONS:

-No follow up actions necessary.

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220247-1

DATE: 09/21/2022

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B10 2022 FA T&I

9 - MAINTENANCE

IS JOB COMPLETE? No DISC/CREDIT: $0.00

SALES TAX: $0.00

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/20/2022 11:31AM

Employee: Alston Chamizo Date: 09/20/2022 11:31AM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts remainig unpaid after the due date, plus attorney's fees if collection proceedings are instituted.

Date: 08/25/2022

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B8

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: LeeRoy Wymer

License No: 220198 Telephone: (907) 854-3770

Communicator: N/A Weekly

Manufacturer: N/A Monthly

Model Number: N/A Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: N/A Other (Specify)

Control Unit Manufacturer: N/A Model No: N/A

Circuit Styles: B, B

Number of Circuits: 2

Software Revision: N/A

Last Date System Had Any Service Performed: N/A

Last Date that Any Software or Configuration Was Revised: N/A

1 B Duct Detector, Edwards

4 B Heat Detector, Edwards

1 B Pull Station, Radionics

1 B Horn/Strobe, Edwards

No. of alarm notification appliance circuits: 1

SIGNALING LINE CIRCUITS

Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1)

Quantity 1 Style(s) B

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage N/A Amps N/A

Overcurrent Protection: N/A Amps N/A

Location (of Primary Supply Panelboard): N/A

Disconnecting Means Location: N/A

(b) Secondary (Standby): N/A Storage Battery: Amp-Hr Rating N/A

Calculated capacity to operate system, in hours: N/A 24 N/A 60

Engine-driven generator dedicated to fire alarm system: N/A

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit N/A

Interface Equipment Pass

Lamps/LEDS N/A

Fuses N/A

Primary Power Supply N/A

Trouble Signals N/A

Disconnect Switches N/A

Ground Fault Monitoring N/A

SECONDARY POWER

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Left of AHU Duct Detector

Left Front Heat Detector

Left Rear Heat Detector

Right Front Heat Detector

Right Rear Heat Detector

Check

Functional Test

Factory Setting

Measured

Entrance Pull Station

Comments: Building fire alarm system is controlled by the FACP in building 10. Will apply pass sticker to building 10.

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Operation

Simulated Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Other (Specify) N/A N/A

The following did not operate correctly: N/A

System restored to normal operation: Pass Date: 08/25/2022 Time: 4:00:00 PM

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Alston Chamizo Date: Time:

Signature:

WORK PERFORMED: 08/25/2022

A. Chamizo D. Ijima

2 Hours Each

ACTIONS TAKEN:

-Test and inspected the following devices:

1 Duct Detector 4 Heat Detector 1 Pull Station 1 Horn/Strobe

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-All devices passed test and inspection.

-This FACP is located in building 10 and will be stickered for building 8 when tested.

FOLLOW UP ACTIONS:

-Continue with the scheduled test and inspection.

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220198-1

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B8 2022 FA T&I

10 - SERVICE

IS JOB COMPLETE? No DISC/CREDIT: $0.00

SALES TAX: $0.00

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/02/2022 09:10 AM

Date: 09/02/2022 09:10 AM

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Date: 08/26/2022

Time: 11:50:02 AM

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B9

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: LeeRoy Wymer

License No: Telephone: 9078543770

Telephone: 8086821000

Contact: Contact:

Telephone: Telephone:

Monitoring Account Ref. No:

Communicator: Weekly

Manufacturer: Monthly

Model Number: Quarterly

Communicator: Semiannually

Manufacturer: Annually

Model Number: Other (Specify)

Control Unit Manufacturer: Model No:

Circuit Styles:

Number of Circuits:

Software Revision:

Last Date System Had Any Service Performed:

Last Date that Any Software or Configuration Was Revised:

Duct Detector, Edwards

Heat Detector, Edwards

Pull Station, Radionics

Alarm Verification feature is disabled enabled

Horn/Strobe, Radionics

No. of alarm notification appliance circuits:

SIGNALING LINE CIRCUITS

Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1)

Quantity Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage Amps

Overcurrent Protection: Amps

Location (of Primary Supply Panelboard):

Disconnecting Means Location:

(b) Secondary (Standby): Storage Battery: Amp-Hr Rating

Calculated capacity to operate system, in hours: 24 60

Engine-driven generator dedicated to fire alarm system:

Location of fuel storage:

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity

Building Occupants

Building Management

Other (Specify)

AHJ Notified of Any Impairments

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit

Interface Equipment

Lamps/LEDS

Fuses

Primary Power Supply

Trouble Signals

Disconnect Switches

Ground Fault Monitoring

SECONDARY POWER

REMOTE ANNUNCIATORS

NOTIFICATION APPLIANCES

Audible

Visible

Speakers

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Left Wall Duct Detector

Front Left of Entrance Heat Detector

Front Right of Entrance Heat Detector

Rear Left of Entrance Heat Detector

Rear Right of Entrance Heat Detector

Check

Functional Test

Factory Setting

Measured

Main Entrance Pull Station

Comments:

Phone Set

Phone Jacks

Off-Hook Indicator

Amplifier(s)

Type Generator(s)

Call-in Signal

System Performance

Operation

Simulated Operation Time & Date

SPECIAL HAZARD SYSTEMS

Special Procedures:

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal

Alarm Restoration

Trouble Signal

Supervisory Signal

Supervisory Restoration

Building Management

Monitoring Agency

Building Occupants

Other (Specify)

The following did not operate correctly:

System restored to normal operation: Date: 08/26/2022 Time: 11:50:02 AM

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Alston Chamizo Date: Time:

Signature:

Name of Owner or Representative: LeeRoy Wymer Date: Time:

WORK PERFORMED: 08/26/2022

A. Chamizo D. Ijima

2 Hours Each

ACTIONS TAKEN:

-Test and inspected the following devices:

1 Duct Detector 4 Heat Detector 1 Pull Station 1 Horn/Strobe

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-All devices passed test and inspection.

-This FACP is located in building 39009 and will be stickered for building 9 when tested.

FOLLOW UP ACTIONS:

-Continue with the scheduled test and inspection.

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220197-1

DATE: 09/13/2022

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B9 2022 FA T&I

10 - SERVICE

IS JOB COMPLETE? No DISC/CREDIT: $0.00

SALES TAX: $0.00

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/13/2022 12:01 PM

Date: 09/02/2022 09:25AM

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Date: 09/01/2022

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B13

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: Leeroy Wymer

License No: 220196 Telephone: (907) 854-3770

Communicator: Radio Weekly

Manufacturer: King Fisher Monthly

Model Number: Star Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: N/A Other (Specify)

Control Unit Manufacturer: Simplex Model No: 4010ES

Circuit Styles: A, A

Number of Circuits: 3

Software Revision: N/A

Last Date System Had Any Service Performed: 09/01/2022

Last Date that Any Software or Configuration Was Revised: 09/01/2022

1 A Duct Detector

4 A Pull Station, Simplex

1 A Smoke Detector, Simplex

1 A Waterflow Switch, Simplex

11 A Horn/Strobe, Simplex

3 A Strobe, Simplex

No. of alarm notification appliance circuits: 2

1 A Tamper Switch, Simplex

Quantity 1 Style(s) A

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120V Amps 20A

Overcurrent Protection: Breaker Amps 20A

Location (of Primary Supply Panelboard): Workroom

Disconnecting Means Location: Panel 2DP, Ckt#9

(b) Secondary (Standby): Batteries Storage Battery: Amp-Hr Rating 33Ah

Calculated capacity to operate system, in hours: X 24 60

Engine-driven generator dedicated to fire alarm system: N/A

Location of fuel storage:

Sealed Lead Acid First Power LFP1233 12V 33Ah

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit Pass

Interface Equipment Pass

Lamps/LEDS Pass

Fuses Pass

Primary Power Supply Pass

Trouble Signals Pass

Disconnect Switches Pass

Ground Fault Monitoring Pass

SECONDARY POWER

Fail

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Workroom AHU Duct Detector

Loading Dock Exit Pull Station

Main Entrance Near FACP Pull Station

Warehouse Near Dropdown Door Pull Station

Warehouse Near Exit Ramp Pull Station

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Main Entrance Above FACP Smoke Detector

Exterior Riser Closet Waterflow Switch

Exterior Riser Closet Tamper Switch

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Operation

Simulated Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Other (Specify) N/A N/A

The following did not operate correctly:

Device Type Location Manufacturer Model Comment

Battery Main Entrance FACP First Power LFP1233 Failed load test

System restored to normal operation: Fail Date: 09/01/2022 Time: 4:00:00 PM

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Alston Chamizo Date: Time:

Signature:

WORK PERFORMED: 09/01/2022

A. Chamizo D. Ijima

5 Hours Each

ACTIONS TAKEN:

-Test and inspected the following devices:

1 Control Panel 2 Batteries 1 Smoke Detectors 1 Duct Detector 4 Pull Stations 1 Waterflow 1 Tampers 11 Horn/Strobes

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-Batteries for FACP failed load test and will need to be replaced.

FOLLOW UP ACTIONS:

-Continue with the scheduled test and inspection.

MATERIALS NEEDED:

-(2x) 12V 33Ah Batteries

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220196-1

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B13 2022 FA T&I

10 - SERVICE

IS JOB COMPLETE? No DISC/CREDIT: $0.00

SALES TAX: $0.00

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/02/2022 09:33 AM

Employee: Alston Chamizo Date: 09/02/2022 09:33 AM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Date: 09/06/2022

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B19

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: Leeroy Wymer

License No: 220202 Telephone: (907) 854-3770

Telephone: (808) 682-1000 Telephone: N/A

Manufacturer: King Fisher Monthly

Model Number: Star Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: N/A Other (Specify)

Control Unit Manufacturer: Simplex Model No: 4101ES

Circuit Styles: A, A

Number of Circuits: 3

Software Revision: n/a

Last Date System Had Any Service Performed: 09/06/2022

Last Date that Any Software or Configuration Was Revised: 09/06/2022

2 A Pull Station, Simplex

2 A Smoke Detector, Simplex

1 A Waterflow Switch, Simplex

8 A Horn/Strobe, Simplex

2 A Strobe, Simplex

No. of alarm notification appliance circuits: 2

1 A Tamper Switch, Simplex

Quantity 1 Style(s) A

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120V Amps 20A

Overcurrent Protection: Breaker Amps 20A

Location (of Primary Supply Panelboard): Next to FACP

Disconnecting Means Location: Dedicated breaker

(b) Secondary (Standby): Batteries Storage Battery: Amp-Hr Rating 50Ah

Calculated capacity to operate system, in hours: X 24 60

Engine-driven generator dedicated to fire alarm system: N/A

Sealed Lead Acid First Power LFP1250 12V 50Ah

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit Pass

Interface Equipment N/A

Lamps/LEDS Pass

Fuses Pass

Primary Power Supply Pass

Trouble Signals Pass

Disconnect Switches Pass

Ground Fault Monitoring Pass

SECONDARY POWER

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Lobby Exit Near Storage Pull Station

Lobby Near Main Entrance Pull Station

Lobby Above Annunciator Smoke Detector

Storage Above FACP Smoke Detector

Check

Functional Test

Factory Setting

Measured

Exterior Riser Closet Tamper Switch

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Operation

Simulated Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Battery Storage FACP First Power LFP1250 Failed load test

System restored to normal operation: Fail Date: 09/06/2022 Time: 4:00:00 PM

Name of Inspector: Alston Chamizo Date: Time:

Signature:

WORK PERFORMED: 09/06/2022

A. Chamizo D. Ijima

6 Hours Each

ACTIONS TAKEN:

-Test and inspected the following devices:

1 Control Panel 1 Annunciator 2 Batteries 2 Smoke Detectors 2 Pull Stations 1 Waterflow 1 Tampers 8 Horn/Strobes 2 Strobes

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-Batteries for FACP failed load test and will need to be replaced.

MATERIALS NEEDED:

-(2x) 12V 50Ah Batteries

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220195-1

DATE: 09/06/2022

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B19 2022 FA T&I

10 - SERVICE

IS JOB COMPLETE? No DISC/CREDIT: $0.00

SALES TAX: $0.00

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/06/2022 12:00 PM

Date: 09/06/2022 12:00 PM

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Date: 08/30/2022

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B35

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: LeeRoy Wymer

License No: 200202 Telephone: (907) 854-3770

Manufacturer: King Fisher Monthly

Model Number: KF-APT Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: N/A Other (Specify)

Control Unit Manufacturer: Edwards Model No: EST 3

Circuit Styles: B, B

Number of Circuits: 4

Software Revision: V5 32

Last Date System Had Any Service Performed: 07/06/20

Last Date that Any Software or Configuration Was Revised: 07/06/2021

1 B Pull Station, Radionics

4 B Smoke Detector, Edwards

10 B Horn/Strobe, Edwards

No. of alarm notification appliance circuits: 3

SIGNALING LINE CIRCUITS

Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1)

Quantity 1 Style(s) B

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120V Amps 20A

Overcurrent Protection: Breaker Amps 20A

Location (of Primary Supply Panelboard): Mechanical Room 107

Disconnecting Means Location: Panel FP, Ckt#1

(b) Secondary (Standby): Batteries Storage Battery: Amp-Hr Rating 26Ah

Calculated capacity to operate system, in hours: X 24 60

Engine-driven generator dedicated to fire alarm system: N/A

Sealed Lead Acid Leoch DJW12-26Ah 12V 26Ah

Sealed Lead Acid Ultra Tech UT 1270 12V 7Ah

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit Pass

Interface Equipment Pass

Lamps/LEDS Pass

Fuses Pass

Primary Power Supply Pass

Trouble Signals Pass

Disconnect Switches Pass

Ground Fault Monitoring Pass

SECONDARY POWER

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

UPS Room 103 Duct Detector

Operations Room 109 Pull Station

Operations Room 109 Underfloor 1 Smoke Detector

Operations Room 109 Underfloor 2 Smoke Detector

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

UPS Battery 110 Smoke Detector

UPS Room 103 Smoke Detector

Comments: Four smoke detectors (2 in Operations Room, 1 in Battery Room, and 1 in UPS room) were removed. The devices are not listed in the report since removed. Devices will need to be installed, programmed, and tested.

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Operation

Simulated Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Battery Hallway FACP Leoch DJW12-26Ah Failed load test

Battery Hallway FEP Ultra Tech UT 1270 Failed load test

System restored to normal operation: Fail Date: 08/30/2022 Time: 4:00:00 PM

Name of Inspector: Alston Chamizo Date: Time:

Signature:

WORK PERFORMED: 08/30/2022

A. Chamizo D. Ijima

6 Hours Each

ACTIONS TAKEN:

-Test and inspected the following devices:

1 Control Panel 1 Expander Panel 2 Batteries 4 Smoke Detectors 1 Duct Detector 1 Pull Stations 10 Horn/Strobes

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-Batteries for FACP and FEP failed load test and will need to be replaced.

-Four smoke detectors were missing at locations were plans indicated.

-These four smokes should be above the underfloor smokes and will need to be installed.

FOLLOW UP ACTIONS:

-Continue with the scheduled test and inspection.

MATERIALS NEEDED:

-(2x) 12V 26Ah -(2x) 12V 7Ah Batteries If not found:

-(4x) SIGA-OSD -(4x) SIGA-SB4

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220202-1

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B35 2022 FA T&I

10 - SERVICE

IS JOB COMPLETE? No DISC/CREDIT: $0.00

SALES TAX: $0.00

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/02/2022 11:42 AM

Employee: Alston Chamizo Date: 09/02/2022 11:42 AM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Date: 08/31/2022

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B38

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: Leeroy Wymer

License No: 220201 Telephone: (907) 854-3770

Manufacturer: King Fisher Monthly

Model Number: KF-APT Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: N/A Other (Specify)

Control Unit Manufacturer: Edwards Model No: EST 3

Circuit Styles: B, B

Number of Circuits: 5

Software Revision: V5.32

Last Date System Had Any Service Performed: 09/05/17

Last Date that Any Software or Configuration Was Revised: 09/05/2017

6 B Pull Station, Radionics

17 B Smoke Detector, Edwards

1 B Waterflow Switch, Edwards

17 B Horn/Strobe, Edwards

No. of alarm notification appliance circuits: 4

4 B Tamper Switch, Edwards

Quantity 1 Style(s) B

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120V Amps 20A

Overcurrent Protection: Breaker Amps 20A

Location (of Primary Supply Panelboard): Switch Gear Room

Disconnecting Means Location: Panel FP, Ckt#1

(b) Secondary (Standby): Batteries Storage Battery: Amp-Hr Rating 40Ah

Calculated capacity to operate system, in hours: X 24 60

Engine-driven generator dedicated to fire alarm system: N/A

Sealed Lead Acid Leoch DJW12-26 12V 26Ah

Sealed Lead Acid Ultra Tech UT 1270 12V 7Ah

Sealed Lead Acid Peak PK12V40 12V 40Ah

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit Pass

Interface Equipment Pass

Lamps/LEDS Pass

Fuses Pass

Primary Power Supply Pass

Trouble Signals Pass

Disconnect Switches Pass

Ground Fault Monitoring Pass

SECONDARY POWER

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Mezzanine Storage Room 201 AHU Duct Detector

Control Room 102 Pull Station

Generator Room 101 Near Fire Protection Room Pull Station

Generator Room 101 Near Rear Exit Pull Station

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Hallway Near Office Pull Station

Switchgear Room 105 Exit Near Smoke 12 Pull Station

Switchgear Room 105 Exit Near Smoke 9 Pull Station

Control Room 102 Breakroom 1 Smoke Detector

Control Room 102 Breakroom 2 Smoke Detector

Control Room 102 Near Control Console 1 Smoke Detector

Control Room 102 Near Control Console 2 Smoke Detector

Switchgear Room 105 1 Smoke Detector

Switchgear Room 105 10 Smoke Detector

Switchgear Room 105 11 Smoke Detector

Switchgear Room 105 12 Smoke Detector

Switchgear Room 105 2 Smoke Detector

Switchgear Room 105 3 Smoke Detector

Switchgear Room 105 5 Smoke Detector

Switchgear Room 105 6 Smoke Detector

Switchgear Room 105 7 Smoke Detector

Switchgear Room 105 8 Smoke Detector

Switchgear Room 105 9 Smoke Detector

Switchgear Room 105 Above FACP Disconnect Smoke Detector

Switchgear Room 105 Near Entrance to Hallway Smoke Detector

Fire Protection Room Fire Sprinkler Riser Waterflow Switch

Fire Protection Room Fire Sprinkler Riser Tamper Switch

Fire Protection Room Low Pressure Tamper Switch

Fire Protection Room Preaction Tamper Tamper Switch

Fire Protection Room Riser Tamper Switch

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Operation

Simulated Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Other (Specify)

Battery Control Room 102 FACP Leoch DJW12-26 Failed load test

Battery Control Room 102 FEP Ultra Tech UT 1270 Failed load test

Battery Control Room 102 Preaction Peak PK12V40 Failed load test

System restored to normal operation: Fail Date: 08/31/2022 Time: 4:00:00 PM

Name of Inspector: Alston Chamizo Date: Time:

Signature:

WORK PERFORMED: 08/31/2022

A. Chamizo D. Ijima

6 Hours Each

ACTIONS TAKEN:

-Test and inspected the following devices:

2 Control Panel 1 Expander Panel 6 Batteries 17 Smoke Detectors 1 Duct Detector 6 Pull Stations 1 Waterflow 4 Tampers 17 Horn/Strobes

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-Batteries for FACP, Preaction Panel, and FEP failed load test and will need to be replaced.

FOLLOW UP ACTIONS:

-Continue with the scheduled test and inspection.

MATERIALS NEEDED:

-(2x) 12V 40Ah Batteries -(2x) 12V 26Ah Batteries -(2x) 12V 7Ah Batteries

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220201-1

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B38 2022 FA T&I

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/02/2022 09:35 AM

Employee: Alston Chamizo Date: 09/02/2022 09:35 AM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Date: 08/29/2022

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B41

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: Leeroy Wymer

License No: 220200 Telephone: (907) 854-3770

Manufacturer: King Fisher Monthly

Model Number: KF-APT Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: N/A Other (Specify)

Control Unit Manufacturer: Edwards Model No: EST 3

Circuit Styles: B, B

Number of Circuits: 5

Software Revision: V5.32

Last Date System Had Any Service Performed: 06/30/2017

Last Date that Any Software or Configuration Was Revised: 06/30/2017

4 B Duct Detector, Edwards

5 B Heat Detector, Edwards

3 B Smoke Detector, Edwards

1 B Waterflow Switch, Edwards

18 B Horn/Strobe, Edwards

SIGNALING LINE CIRCUITS

Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1)

Quantity 1 Style(s) B

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120V Amps 20A

Overcurrent Protection: Breaker Amps 20A

Location (of Primary Supply Panelboard): Electrical Room 105

Disconnecting Means Location: Panel FP, Ckt#2

(b) Secondary (Standby): Batteries Storage Battery: Amp-Hr Rating 26Ah

Calculated capacity to operate system, in hours: X 24 60

Engine-driven generator dedicated to fire alarm system: N/A

Sealed Lead Acid Leoch DJW12-26 12V 26Ah

Sealed Lead Acid Ultra Tech UT 1270 12V 7Ah

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit Pass

Interface Equipment Pass

Lamps/LEDS Pass

Fuses Pass

Primary Power Supply Pass

Trouble Signals Pass

Disconnect Switches Pass

Ground Fault Monitoring Pass

SECONDARY POWER

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Gym Room 111 Duct Detector

Hallway Near FACP Duct Detector

Mech Room 105 Duct Detector

Substation Room 116 Duct Detector

Gym Storage Room 106 Heat Detector

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Substation Room 116 1 Heat Detector

Substation Room 116 2 Heat Detector

Substation Room 116 3 Heat Detector

Substation Room 116 4 Heat Detector

Gym Room 111 Smoke Detector

Hallway Above FACP Smoke Detector

Room 107 Above FEP Smoke Detector

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Operation

Simulated Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Battery Room 107 FACP Battery Cabinet Leoch DJW12-26 Failed load test

Battery Room 107 FEP 1 Ultra Tech UT 1270 Failed load test

System restored to normal operation: Fail Date: 08/29/2022 Time: 4:00:00 PM

Name of Inspector: Alston Chamizo Date: Time:

Signature:

WORK PERFORMED: 08/29/2022

A. Chamizo D. Lanuza

7 Hours Each

ACTIONS TAKEN:

Building 41:

-Test and inspected the following devices:

1 Control Panel 1 Expander Panel 4 Batteries 3 Smoke Detectors 4 Duct Detectors 5 Heat Detectors 1 Pull Station 1 Waterflow Switch 18 Horn/Strobes

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-Pairs for both the FACP and FEP are over 5 years installed and failed load test.

-When waterflow was tested, the alarm was received but the electronic bell did not activate.

-Bell will need to be replaced and tested.

FOLLOW UP ACTIONS:

-Continue with the scheduled test and inspection.

MATERIALS NEEDED:

-(2x) 12V 26Ah -(2x) 12V 7Ah -(1x) 24V Bell

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220200-1

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B41 2022 FA T&I

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/02/2022 09:30 AM

Employee: Alston Chamizo Date: 09/02/2022 09:30 AM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Date: 08/25/2022

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B39005

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: LeeRoy Wymer

License No: 220199 Telephone: (907) 854-3770

Manufacturer: King Fisher Monthly

Model Number: KF-APT Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: Other (Specify)

Control Unit Manufacturer: Edwards Model No: EST 3

Circuit Styles: B, B

Number of Circuits: 5

Software Revision: V5.32

Last Date System Had Any Service Performed: 08/25/2022

Last Date that Any Software or Configuration Was Revised: 08/25/2022

3 B Pull Station, Radionics

12 B Smoke Detector, Edwards

7 B Horn/Strobe, Edwards

SIGNALING LINE CIRCUITS

Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1)

Quantity 1 Style(s) B

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120V Amps 20A

Overcurrent Protection: Breaker Amps 20A

Location (of Primary Supply Panelboard): By room 102

Disconnecting Means Location: Panel FP, Ckt#2

(b) Secondary (Standby): Batteries Storage Battery: Amp-Hr Rating 26Ah

Calculated capacity to operate system, in hours: X 24 60

Engine-driven generator dedicated to fire alarm system: N/A

Sealed Lead Acid Leoch DJM1250 12V 26Ah

Sealed Lead Acid Edwards UT 1272F1 12V 7Ah

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit Pass

Interface Equipment Pass

Lamps/LEDS Pass

Fuses Pass

Primary Power Supply Pass

Trouble Signals Pass

Disconnect Switches Pass

Ground Fault Monitoring Pass

SECONDARY POWER

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Check

Functional

Test

Factory

Setting

Measured

Setting Pass Fail

Main Entrance Pull Station

Storage Room 107A Pull Station

Technical Equipment R107 Pull Station

Electrical R105 Smoke Detector

High Smoke 1 Smoke Detector

Check

Functional

Test

Factory

Setting

Measured

Setting Pass Fail

High Smoke 2 Smoke Detector

High Smoke 3 Smoke Detector

High Smoke 4 Smoke Detector

Storage R107 Underfloor Smoke Detector

Storage R107A Underfloor Smoke Detector

Storage Room R105A Smoke Detector

Technical Equipment Underfloor 1 Smoke Detector

Technical Equipment Underfloor 2 Smoke Detector

Technical Equipment R102 Near Entrance Smoke Detector

Technical Equipment R102 Near Toilet Smoke Detector

Comments: Need to replace batteries at FEP 1 to pass test and inspection.

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Operation

Simulated

Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Battery Electrical Room R105 FACP Leoch DJM1250 Failed load test

System restored to normal operation: Fail Date: 08/26/2022 Time: 4:00:00 PM

Name of Inspector: Alston Chamizo Date: Time:

Signature:

WORK PERFORMED: 08/25/2022

A. Chamizo D. Ijima

7 Hours Each

ACTIONS TAKEN:

-Test and inspected the following devices:

1 Control Panel 1 Annunciator 1 Expander Panel 4 Batteries 12 Smoke Detectors 3 Pull Stations 7 Horn/Strobes

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-Batteries for FACP failed load test and will need to be replaced.

-When waterflow was tested, the alarm was received but the electronic bell did not activate.

-Bell will need to be replaced and tested.

FOLLOW UP ACTIONS:

-Continue with the scheduled test and inspection.

MATERIALS NEEDED:

-(2x) 12V 26Ah Batteries -(1x) 24V Bell

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220199-1

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B39005 2022 FA T&I

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/02/2022 09:16 AM

Employee: Alston Chamizo Date: 09/02/2022 09:16 AM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Date: 08/26/2022

Name: Phoenix Pacific (Hawaii), Inc. Name: KPST B39009

Address: 2045 Lauwiliwili Street Ste. 101 / Kapolei, HI 96707 Address: Farrington Highway, Makaha, HI 96792

Representative: Alston Chamizo Owner Contact: Leeroy Wymer

License No: 220194 Telephone: (907) 854-3770

Manufacturer: King Fisher Monthly

Model Number: KF-APT Quarterly

Communicator: N/A Semiannually

Manufacturer: N/A Annually

Model Number: N/A Other (Specify)

Control Unit Manufacturer: Edwards Model No: EST 3

Circuit Styles: A

Number of Circuits: 2

Software Revision: V3.7

Last Date System Had Any Service Performed: 07/13/2022

Last Date that Any Software or Configuration Was Revised: 07/13/2022

1 B Aspirating Detector, Xtralis

4 B Heat Detector, Edwards

4 B Pull Station, Edwards

7 B Smoke Detector, Edwards

5 B Horn/Strobe, Edwards

No. of alarm notification appliance circuits: 1

SIGNALING LINE CIRCUITS

Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1)

Quantity 1 Style(s) B

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 120V Amps 20A

Overcurrent Protection: Breaker Amps 20A

Location (of Primary Supply Panelboard): Main Room

Disconnecting Means Location: Panel TP-22

(b) Secondary (Standby): Batteries Storage Battery: Amp-Hr Rating 35Ah

Calculated capacity to operate system, in hours: X 24 60

Engine-driven generator dedicated to fire alarm system: N/A

Sealed Lead Acid AJC DS7(T1) 12V 7Ah

Sealed Lead Acid Full River DC35-12 12V 70Ah

Sealed Lead Acid Ultra Tech UT 12120 12V 12Ah

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

Monitoring Entity CEO 8:00A

Building Occupants Staff 8:00A

Building Management Leeroy 8:00A

Other (Specify) N/A N/A

AHJ Notified of Any Impairments N/A N/A

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit Pass

Interface Equipment Pass

Lamps/LEDS Pass

Fuses Pass

Primary Power Supply Pass

Trouble Signals Pass

Disconnect Switches Pass

Ground Fault Monitoring Pass

SECONDARY POWER

NOTIFICATION APPLIANCES

Audible Pass

Visible Pass

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Comm Room Aspirating Detector

Generator Room Above Generator Heat Detector

Generator Room Closer to Pull Station Heat Detector

Vehicle Bay Near Entrance Heat Detector

Check

Functional Test

Factory Setting

Measured Setting Pass Fail

Vehicle Bay Near Exit Heat Detector

Generator Room Pull Station

Main Entrance Pull Station

Outside Vehicle Bay Pull Station

Vehicle Bay Pull Station

Antenna Pedestal Smoke Detector

Main Entrance Air Lock Smoke Detector

High Above Sky Crane Smoke Detector

High Above Stair to Catwalk Smoke Detector

High Left of Vehicle Bay Smoke Detector

High Main Entrance Above FACP Smoke Detector

High Right of Vehicle Bay Smoke Detector

Comments: Alarm could not be silenced on alarm silence possibly due to a second active alarm. VESDA unit FIRE 1 alarm on the panel does not activate the alarm.

Phone Jacks N/A

Off-Hook Indicator N/A

Amplifier(s) N/A

Type Generator(s) N/A

Operation

Simulated Operation Time & Date

N/A N/A N/A N/A N/A

SPECIAL HAZARD SYSTEMS

N/A N/A N/A N/A N/A

Special Procedures: N/A

Comments: N/A

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal N/A N/A

Alarm Restoration N/A N/A

Trouble Signal N/A N/A

Monitoring Agency CEO 4:00P

Building Occupants Staff 4:00P

Battery FACP Near Main Entrance AJC DS7(T1) Failed load test

System restored to normal operation: Fail Date: 08/26/2022 Time: 4:00:00 PM

Name of Inspector: Alston Chamizo Date: Time:

Signature:

WORK PERFORMED: 08/26/2022

A. Chamizo D. Ijima

8 Hours Each

ACTIONS TAKEN:

-Test and inspected the following devices:

1 Control Panel 1 Annunciator 1 Expander Panel 6 Batteries 7 Smoke Detectors 4 Heat Detectors 4 Pull Stations 5 Horn/Strobes

-Verified messages on activations.

-Labelled and scanned each device for Building Reports.

-Batteries for FACP failed load test and will need to be replaced.

-When waterflow was tested, the alarm was received but the electronic bell did not activate.

-Bell will need to be replaced and tested.

FOLLOW UP ACTIONS:

-Continue with the scheduled test and inspection.

MATERIALS NEEDED:

-(2x) 12V 7Ah Batteries -(1x) 24V Bell

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

220194-1

CLIENT LOCATION: KAENA POINT SATELLIT TRACKING

Kaena Point Farrington Hwy Makaha , HI 96792

BILLED TO:

KAENA POINT SATELLIT TRACKING

P.O. BOX 868

WAIANAE , HI 96792-0868

KAENA POINT SATELLITE TRACKING - B39009 2022 FA T&I

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 09/02/2022 09:22 AM

Employee: Alston Chamizo Date: 09/02/2022 09:22 AM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts

Bldg 10 - FA testing - Sep 2022
KPST-B10
220247-1 - Job Work Order_3
Building 8 - FA testing - Aug 2022
KPST-B8
220198-1 - Job Work Order
Building 9 - FA testing - Aug 2022
KPST-B9
220197-1 - Job Work Order_2
Building 13 - FA testing - Sep 2022
KPST-B13
220196-1 - Job Work Order
Building 19 - FA testing - Sep 2022
KPST-B19
220195-1 - Job Work Order
Building 35 - FA testing - Aug 2022
KPST-B35
220202-1 - Job Work Order
Building 38 - FA testing - Aug 2022
KPST-B38
220201-1 - Job Work Order

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .