JA-5_FTQW_18-1019_Final_Drawings_22x34.pdf

PDF 4 MB Posted

Attached to
CDC Fire Alarm System Federal contract opportunity
Solicitation number
FA500419BA012
Issued by
Department of the Air Force Pacific Air Forces

About this file

Final Drawings 22x34

View the file

Other files for this federal contract opportunity

Other files attached to CDC Fire Alarm System, newest first.
File Type Posted
Solicitation_-_FA500419BA012.pdf PDF
JA-3_Final_Documents_Vol_2.pdf PDF
JA-4_FTQW_18-1019_Final_Drawings_11x17.pdf PDF
JA-7_Submittal_Register.pdf PDF
JA-6_Wage_Determination.pdf PDF
JA-1_Synopsis_of_Work.pdf PDF
MFR_Change_of_Solicitation_Number.pdf PDF
JA-2_Final_Documents_Vol_1.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NORTH ARROWS

ROOM NUMBER

SCALE

TITLE

SHEET LOCATION

DETAIL NUMBER

A A4

SHEET LOCATION

SECTION NUMBER

DETAIL NUMBER

OFFICE

SHEET LOCATION

A

A4

G000 TITLE SHEET

G001 GENERAL INFORMATION

DWG

DRAWING TITLE

SCALE

GOVERNING CODES :

2015 INTERNATIONAL BUILDING CODE - IBC

2015 INTERNATIONAL FIRE CODE - IFC

2016 NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS

2017 NFPA 70 - NATIONAL ELECTRICAL CODE - NEC

2016 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE

2015 NFPA 101 LIFE SAFETY CODE

UFC 1-200-01 GENERAL BUILDING REQUIREMENTS (20 JUNE 2016, CHANGE 1, 01 FEB 2018)

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES (8 AUG 2016, CHANGE 2, 25 MARCH 2018)

UFC 4-021-01 MASS NOTIFICATION SYSTEMS (8 FEB DRAFT REVISION 2017)

UFC 4-470-14 CHILD DEVELOPMENT CENTERS (1 AUGUST 2002)

AUTHORITY HAVING JURISDICTION

EIELSON AFB

F001 LEGENDS, SCHEDULES AND DETAILS

F002 ADDITIONAL DETAILS

F003 ADDITIONAL DETAILS

F100 FIRE ALARM SITE PLAN

F101 FIRE ALARM DEMO PLAN AREAS A & B

F102 FIRE ALARM DEMO PLAN AREA C

F103 FIRE ALARM DEMO PLAN MEZZANINE

F201 FIRE ALARM PLAN AREAS A & B

F202 FIRE ALARM PLAN AREA C

F203 FIRE ALARM PLAN MEZZANINE

PROJECT

NORTH

TRUE

NORTH

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

E001 LEGENDS, SCHEDULES AND DETAILS

111111111

1 1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1

111111111111111

1 1 1 1

111111

1 1 1

1111111111

1 1 1 1 1 1 1

1 1 1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1 1

1 1 1 1 1 1 1 1

1 1 1 1 1 1 1

1 1 1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1 1

1 1 1 1 1 1 1 1

1 1 1

1 HOUR RATED WALL

2 HOUR RATED WALL (FLOOR TO ROOF)

1 HOUR RATED CEILING

2 HOUR RATED CEILING

2 2 2 2 2

2 2

1 1 1 1 1 1 1

1 1

LEGEND

(E) FIRE

DEPARTMENT

CONNECTION

ORDINARY GROUP 1 HAZARD

LIGHT HAZARD(E) KITCHEN HOODS

MULTI-PURPOSE

TRAINING ROOM

STOR.

PRESCHOOL

129127

PRESCHOOL

CORRIDOR

PRESCHOOL

PRESCHOOL

PRESCHOOL

138140

PRESCHOOL

ASSIST.

DIRECTOR

STOR.

ADMIN

105AISOL.

STORAGE

RECEPTION

CORRIDOR

DIRECTOR

STOR.

168MEN

WOMEN

LAUNDRY

STAFF

LOUNGE

PRETODDLERS

PRETODDLERS

PRETODDLERS

INFANTS

CORRIDOR

114108 110

JAN.

INFANTS

VESTIBULE

COVERED

ENTRY

TRAINING

& CONF.

PATRON

WAITING

TE

LE

MECHANICAL

ELECTRICAL

TODDLERS

150 149

CORRIDOR

KITCHEN

TODDLERS

TODDLERS

REFRIG./

FREEZER

DRY

STORAGE

SCULLERY

STORAGE

TODDLERS

154 153

1 1 1 1 1

PRESCHOOL WINGTODDLER WING

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N A

L A

S K

A14 MAR 2018

FIRE PROTECTION SYMBOL LEGEND

NOTE KEY - INDICATES NOTES APPLICABLE ON EACH SHEET

PANELBOARD: FLUSH MOUNTED, SURFACE MOUNTED

JUNCTION BOX

EQUIPMENT CONNECTION

FIRE ALARM CONTROL PANEL: SURFACE MOUNTED, REMOTE ANNUNCIATOR

PANEL

FIRE ALARM/MNS COMBINATION SPEAKER/STROBE

UP 6'-9" TO BOTTOM OF DEVICE. 15 CANDELA, UON (CD=CANDELA RATING)

EXISTING FIRE ALARM COMBINATION CHIME/STROBE, CEILING MOUNTED

EXISTING FIRE ALARM COMBINATION CHIME/STROBE, WALL MOUNTED

STROBE ONLY 15 CANDELA, UON; UP 80" TO BOTTOM OF DEVICE, UON

(CD=CANDELA RATING)

MANUAL PULL STATION' UP 4'-0" UON

PHOTOELECTRIC DETECTOR - CEILING MOUNTED UON

DUCT MOUNTED PHOTOELECTRIC DETECTOR

EXISTING INDIVIDUAL ADDRESSABLE MODULE

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

SPRINKLER SYSTEM FLOW SWITCH CONNECTION

SPRINKLER SYSTEM TAMPER SWITCH CONNECTION

MAGNETIC DOOR HOLD DEVICE

CONCEALED CONDUIT

EXPOSED CONDUIT

J

FACP RAP

P

CD

FIRE ALARM REMOTE ANNUNCIATORFAA

FIRE PROTECTION PLAN1

F001 NO SCALE

FIRE ALARM/MNS HORN ONLY

UP 6'-9" TO BOTTOM OF DEVICE.

EXISTING DEVICE OR EQUIPMENT(E)

DEMOLISH EXISTING DEVICE OR EQUIPMENT(D)

LOW AMBIENT TEMPERATURE SWITCH - SET TO +40° F

TS EMERGENCY MESSAGE TEXT DISPLAY SIGN (TEXT SIGN)

FIRE ALARM COMBINATION SPEAKER/STROBE, CEILING MOUNTED

DEMOLISHED ITEMS SHOWN WITH LIGHT DASHED LINES

SPRINKLER OR ALARM BELL

WEATHERPROOFWP

GENERAL PROJECT PHASING NOTES

1. FOR THIS PROJECT THE MAJORITY OF THE DEMOLITION EFFORTS TO BE PERFORMED

INSTALLATION OF THE NEW FIRE ALARM / MASS NOTIFICATION SYSTEM EQUIPMENT HAS

OCCURRED TO MITIGATE OUTAGES FOR THESE REQUIRED LIFE SAFETY SYSTEMS AT THE

FACILITY. THE CDC REQUIRES AN OPERATIONAL FIRE ALARM SYSTEM AT ALL TIMES THE

FACILITY IS OPEN FOR BUSINESS.

2. EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN PLACE UNALTERED AS MUCH AS POSSIBLE, FULLY FUNCTIONAL AND OPERATIONAL DURING THE INSTALLATION OF THE NEW FIRE ALARM /

MASS NOTIFICATIONS SYSTEMS. INSTALLATION OF ANY NEW EQUIPMENT SHALL NOT IMPACT

FULL FUNCTIONALITY OF EXISTING SYSTEM UNLESS A LIMITED OUTAGE IS SPECIFICALLY

GRANTED BY THE CONTRACTING OFFICER. WHERE AN OUTAGE IS REQUIRED, OUTAGE TO BE

REQUESTED TO OCCUR OUTSIDE OF NORMAL BUSINESS HOURS OF THE FACILITY AND/OR

SCHEDULED WHEN FACILITY IS NOT NORMALLY OPEN.

3. CONTRACTOR SHALL INSTALL COMPLETE NEW FIRE ALARM / MASS NOTIFICATION SYSTEM AND

TEST/INSPECT NEW SYSTEM THEN MAKE APPROPRIATE PREPARATIONS TO ENSURE TIMELY

TRANSITION BETWEEN EXISTING FIRE ALARM AND NEW SYSTEM. THESE SYSTEMS INCLUDE FIRE

SPRINKLER MONITORING SWITCHES, ROLL DOWN FIRE DOOR ACTUATORS, DOOR HOLD DEVICES,

ETC. TRANSITION FOR THESE COMMON DEVICES FROM EXISTING SYSTEM TO NEW MAY ONLY

OCCUR DURING PERIODS WHICH ARE OUTSIDE OF THE FACILITIES NORMAL OPERATIONAL

HOURS. CDC ADMINISTRATION AND CONTRACTING OFFICER SHALL BE NOTIFIED MINIMUM OF 48

HOURS PRIOR TO TRANSITION. CONTRACTOR WILL NEED TO RECEIVE APPROVAL PRIOR TO

STARTING WORK.

4. FACILITY DURING THIS TRANSITION PERIOD MAY HAVE BOTH EXISTING AND NEW SYSTEMS

OPERATIONAL CONCURRENTLY, WHERE IN THIS INSTANCE EACH SYSTEM MAY HAVE THE ABILITY

TO BOTH REPORT FIRE ALARM STATUS TO THE D21 AND PROVIDE LOCAL ALERTS TO THE

OCCUPANTS.

5. ONCE THE NEW FIRE ALARM AND MASS NOTIFICATION SYSTEM HAS COMPLETED FINAL TESTING, IS OPERATING NORMALLY, AND CERTIFIED, THE EXISTING FIRE ALARM SYSTEM TO BE

DEMOLISHED AS NOTED ON THE DEMOLITION DRAWINGS AND IN THE SPECIFICATIONS.

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N

A L

A S

K

A14 MAR 2018

1.

2.

3.

4.

5.

6.

EVACUATION SIGNALS ARE AUDIBLE AND VISIBLE ALARMS

ASSOCIATED WITH THE FIRE PROTECTION SYSTEM (ALARM AND

SUPPRESSION). THEY WILL EMIT A TEMPORAL CODE 3 AUDIBLE

ALARM FOLLOWED BY A DIGITAL VOICE MESSAGE AS WELL AS

VISIBILY FLASH FROM CLEAR STROBES AND ILLUMINATE A LED

TEXT SIGN LOCATED ABOVE EACH EXIT DOOR WITH THE WORD

"EVACUATE."

ANNOUNCEMENT SIGNALS ARE AUDIBLE AND VISIBLE ALARMS

ASSOCIATED WITH BOTH THE MASS NOTIFICATION SYSTEM (MNS)

AND THE GIANT VOICE SYSTEM (GVS). THEY WILL EMIT AN AUDIBLE

DIGITAL VOICE, EITHER PRE-RECORDED OR LIVE, MESSAGE AS

WELL AS VISIBLY FLASH FROM CLEAR STROBES AND ILLUMINATE A

LED TEXT SIGN LOCATED ABOVE EACH EXIT DOOR WITH THE WORD

"ANNOUNCEMENT."

THE EVACUATION SIGNALS AND ANNOUNCEMENT SIGNALS WILL

UTILIZE THE SAME DEVICE FOR DELIVERING BOTH THEIR AUDIBLE

AND VISIBLE ALARMS.

MAIN ACU MIC

LOC MIC

MASS NOTIFICATIONS

GIANT VOICE

FIRE ALARM

PUBLIC ADDRESS

SYSTEM OUTPUTS

CONTROL UNIT ANNUNCIATION NOTIFICATION CONTROL

FUNCTIONS MONACO D21 REPORTING

ACTUATE C

OMMON A

LA

RM S

IG

NAL I

NDIC

ATOR A

ND A

UDIBLE

DIS

PLA

Y A

LA

RM D

EVIC

E

ACTUATE S

UPERVIS

ORY IN

DIC

ATOR A

ND A

UDIBLE

ACTUATE C

OMMON TROUBLE

S

IG

NAL I

NDIC

ATOR A

ND A

UDIBLE

SILE

NCE P

ANEL A

ND FACILI

TY A

UDIB

LE

(V

IS

UAL A

LE

RTS R

EMAIN

ACTIV

ATE "E

VACUATE" M

ESSAGE O

N TEXT A

LE

RT S

IG

NS - P

ER W

IN

G

ZONE 11

) T

RANSMIT S

YSTEM D

IS

ABLE

S W

ITCH SUPERVISORY

DIS

PLA

Y S

UPERVISORY D

EVIC

E

DIS

PLA

Y TROUBLE

C

ONDITIO

N

CONTROL P

ANEL R

ETURNS TO N

ORMAL (

VISUAL A

LE

RTS STOP)

ACTUATE A

LL

N

OTIFIC

ATIO

N A

PPLIA

NCES - P

ER W

IN

G +

ALL

EXTERIO

R

ACTIV

ATE FIR

E V

OIC

E M

ESSAGE - P

ER W

IN

G

ACTIV

ATE "A

NNOUNCEMENT" M

ESSAGE O

N TEXT A

LE

RT S

IG

NS - B

OTH W

IN

GS

ACTIV

ATE E

XTERIO

R W

ATER FLO

W

A

LA

RM BELL

ACTIV

ATE LO

CAL M

ASS N

OTIFIC

ATIO

N V

OIC

E M

ESSAGE - B

OTH W

IN

GS

ACTIV

ATE R

EMOTE M

ASS N

OTIFIC

ATIO

N V

OIC

E M

ESSAGE - B

OTH W

IN

GS

DE-E

NERGIZE M

AGNETIC

D

OOR H

OLD

ERS

ZONE 1)

TRANSMIT M

AIN

S

PRIN

KLE

R R

IS

ER W

ATER FLO

W A

LA

RM

ZONE 2)

TRANSMIT S

PRIN

KLE

R TAMPER S

WITCH S

UPERVIS

ORY

ZONE 3)

TRANSMIT M

ANUAL P

ULL

S

TATIO

N A

LA

RM - T

ODDLE

R W

IN

G

ZONE 4)

TRANSMIT M

ANUAL P

ULL

S

TATIO

N A

LA

RM - P

RESCHOOL W

IN

G

ZONE 5)

TRANSMIT S

MOKE D

ETECTOR A

LA

RM - T

ODDLE

R W

IN

G

ZONE 7)

TRANSMIT S

PRIN

KLE

R R

OOM LO

W

TEMPERATURE S

UPERVISORY

ZONE 8)

TRANSMIT M

NS O

VERRID

E O F A

CTIV

E FIR

E A

LA

RM SUPERVIS

ORY

ZONE 10

) T

RANSMIT C

OMMON TROUBLE

ZONE 9)

TRANSMIT G

ENERAL S

UPERVISORY

SYSTEM INPUT

MANUAL FIRE ALARM PULL STATION - PRESCHOOL WING

SYSTEM RESET

WATER FLOW (MAIN SPRINKLER RISER)

SPRINKLER VALVE TAMPER

LOW TEMPERATURE IN SPRINKLER ROOM

SMOKE DETECTOR - PRESCHOOL WING

SMOKE DETECTOR - TODDLER WING

FIRE ALARM LOW BATTERY

FIRE ALARM AC POWER FAILURE

OPEN CIRCUIT

GROUND FAULT

SYSTEM SILENCE

N O

TI

FI

C A

TI

O

N D

E V

IC

E

S C

O N

TR

O

L E

Q U

IP

M

E N

T M

A S

S N

O

TI

FI

C

A

TI

O N

BYPASS ACTIVE

LOCAL MASS NOTIFICATION MSG (PRE-RECORDED OR MIC)

REMOTE MASS NOTIFICATION MSG (PRE-RECORDED OR MIC)

MASS NOTIFICATION MSG OVERRIDES ACTIVE FIRE ALARM

FIRE ALARM / MNS MATRIX1

F002 NO SCALE

WRAP CONNECTION

WITH COAX SEAL

HOSE CLAMPS

SECURED TO

ANTENNA MAST

COAX CABLE

INSIDE MAST

ANTENNA

MAST

ANTENNA WHIP

SET SCREW

LOADING COIL

RUBBER GASKET

COLLAR

GROUND

RADIALS (4)

(2) SET SCREWS

PER RADIAL

BULKHEAD

ADAPTER

MOUNTING BRACKET

LOCK WASHER

3/4" HEX NUT

HOSE CLAMPS

#8 SOLID BARE COPPER GROUNDING WIRE

FROM ARRESTOR GROUNDING BOLT TO

BUILDING GROUND IAW NEC ARTICLE 810

COAX CABLE 12" SERVICE LOOP

#8 SOLID BARE COPPER

GROUNDING WIRE FROM

BUSHING TO ARRESTOR

GROUNDING BOLT

COAX CABLE TO

TRANSCEIVER

LIGHTNING ARRESTOR

ENCLOSURE

COAX CABLE FROM

ANTENNA, 6" MINIMUM

BEND RADIUS

LIGHTNING

ARRESTOR

COPPER TERMINAL STUD

3/4" CONDUIT TO

TRANSCEIVER

1" RIGID CONDUIT

FROM ANTENNA

3/4" RIGID CONDUIT

#8 SOLID BARE COPPER GROUNDING

WIRE FROM ARRESTOR GROUNDING

BOLT TO BUILDING GROUND IAW NEC

ARTICLE 810

BUILDING

WALL O

U

TS

ID

E

IN

S

ID

E

ANTENNA & MOUNTING DETAILS3

F002 NO SCALE

ANTENNA GROUNDING DETAILS2

F002 NO SCALE

ZONES 12

-16

) S

PARE

MANUAL FIRE ALARM PULL STATION - TODDLER WING

ZONE 6)

TRANSMIT S

MOKE D

ETECTOR A

LA

RM - P

RESCHOOL W

IN

G

FIRE ALARM / MNS RISER1

F003 NO SCALE

163164165166166107 101108110109111

102102 102168124121 122120119117116

114114

114 102

105169148149150 149153 152154155157158159160161

164164

167108111114

117 123 125 102 102 102 102

106151153

157157

P

MEZ

145144141 144139 138137136134134131 146143140139132

136136

142134 135133

136127129130 136128

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N A

L A

S K

A14 MAR 2018

128 126

ZN 2 ZN 3 ZN 4 ZN 5 ZN 6 ZN 7 ZN 8 ZN 9 ZN 10MONACO REPORTING ZONES

TEXT ALERT SIGN

CORRIDOR 102

TEXT ALERT SIGN

CORRIDOR 102

TEXT ALERT SIGN

CORRIDOR 114

TEXT ALERT SIGN

CORRIDOR 157

TEXT ALERT SIGN

CORRIDOR 136

TEXT ALERT SIGN

CORRIDOR 136

MNS

CONTROLLER

WHELEN

FIRE ALARM

TRANSCEIVER

MONACO BT-XF

VOICE FIRE ALARM & MNS

CONTROL PANEL

POWER SOURCE

24VDC SPRINKLER BELL

101 107 109 109 112 112EXT

WP

EXT

WP

116 116 118 118 EXT

WP

120114 114 114 122 125 102 102 102

EXT

WP

166 164 162 162 159 161 EXT

WP

157 155 155 152EXT

WP

152 151EXT

WP

151 157 EXT

WP

148 148 106 103 105 105 157 157

LOCAL

OPERATOR

CONSOLE

(LOC)

FIRE ALARM

REMOTE

ANNUNCIATOR

FIRE ALARM

REMOTE

ANNUNCIATOR

EXT

WP

EXT

WP

137EXT

WP

137 141EXT

WP

141 EXT

WP

142 146 EXT

WP

136 136126 126 130EXT

WP

130 130 EXT

WP

136136 142 146

PRESCHOOL WING DEVICES - (1) SLC LOOP

MAIN BUILDING AND TODDLER WING DEVICES - (2) SLC LOOPS

MAIN BUILDING

AND

TODDLER WING

NOTIFICATION DEVICES

PRESCHOOL WING

NOTIFICATION DEVICES

MNS

ANTENNA

MONACO

ANTENNA

ZN 1 ZN 11

ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N A

L A

S K

A14 MAR 2018

FIRE ALARM SITE PLAN 1

F100 1' = 20'

PLAY AREA FENCED PERIMETER

PLAY AREA FENCED PERIMETER

(E) FIRE DEPARTMENT CONNECTION

(D) FIRE ALARM SPRINKLER BELL

(D) FIRE ALARM SPRINKLER BELL

ROLL DOWN

FIRE DOOR

(E) FIRE DEPARTMENT

CONNECTION TO

REMAIN

ASSIST.

DIRECTOR

STOR.

ADMIN

105A

ISOL.

105STORAGE

RECEPTION

TRAINING

& CONF.

PATRON

WAITING

TELE.

MECHANICAL

ELECTRICAL

TODDLERS

150 149

CORRIDOR

KITCHEN

TODDLERS

TODDLERS

REFRIG./

FREEZER

DRY

STORAGE

SCULLERY

TOP

STORAGE

TODDLERS

154 153

162.1

MONACO TRANSMITTER ANTENNA

ROLL DOWN

FIRE DOOR

CORRIDOR

DIRECTOR

STOR.

MEN

WOMEN

LAUNDRY

STAFF

LOUNGE

PRETODDLERS

PRETODDLERS

PRETODDLERS

INFANTS

CORRIDOR

108 110

JAN.

INFANTS

VESTIBULE

COVERED

ENTRY

AREA B

AREA A

FIRE ALARM DEMO PLAN - AREA A1

F101 1/8" = 1'-0"

FIRE ALARM DEMO PLAN - AREA B2

F101 1/8" = 1'-0"

KEYPLAN

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N

A L

A S

K

A14 MAR 2018

EXISTING FACP AND

MONACO TRANSMITTER

EXISTING

FIRE ALARM

ANNUNCIATOR PANEL

SPECIFIC NOTES

REMOVE DOOR, FRAME, AND HARDWARE.1

ALL FIRE ALARM EQUIPMENT SHOWN WITH LIGHT DASHED LINES TO BE DEMOLISHED.

ALL FIRE ALARM EQUIPMENT SHOWN WITH LIGHT DASHED LINES TO BE DEMOLISHED.

STOR.

129127

CORRIDOR

PRESCHOOL

PRESCHOOL

PRESCHOOL

138140

PRESCHOOL

MULTI-PURPOSE

TRAINING ROOM

PRESCHOOL

PRESCHOOL

AREA C

FIRST FLOOR FIRE ALARM DEMO PLAN - AREA C1

F102 1/8" = 1'-0"

KEYPLAN

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N

A L

A S

K

A14 MAR 2018

SPECIFIC NOTES

PRESERVE EXISTING DOOR HOLD DEVICES FOR RECONNECTION TO NEW FIRE ALARM

SYSTEM.

REMOVE EXISTING RECESSED FIRE EXTINGUISHER AND CABINET. PATCH WALL AND

PAINT TO MATCH EXISTING CONSTRUCTION.

ALL FIRE ALARM EQUIPMENT SHOWN WITH LIGHT DASHED LINES TO BE DEMOLISHED.

200°

200°

200°

200°

200° 200°

200°

200°

200° 200°

200° 200°

200°

200°

200°

200°

200°

P

P

P

P

CATWALK

PATCH DUCTWORK AIRTIGHT AS

REQUIRED FROM DUCT SMOKE

DETECTOR REMOVAL, TYP.

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N A

L A

S K

A14 MAR 2018

FIRE ALARM DEMO PLAN - MEZZANINE1

F103 3/32" = 1'-0"

ROLL DOWN

FIRE DOOR

FIRE DEPARTMENT

CONNECTION

ASSIST.

DIRECTOR

STOR.

ADMIN

105A

ISOL.

STORAGE

RECEPTION

TRAINING

& CONF.

PATRON

WAITING

MECHANICAL

ELECTRICAL

TODDLERS

150 149

CORRIDOR

KITCHEN

TODDLERS

TODDLERS

REFRIG./

FREEZER

DRY

STORAGE

SCULLERY

TOP

STORAGE

TODDLERS

MONACO TRANSMITTER ANTENNA

ROLL DOWN

FIRE DOOR

CORRIDOR

DIRECTOR

STOR.

MEN

WOMEN

123LAUNDRY

STAFF

LOUNGE

PRETODDLERS

PRETODDLERS

PRETODDLERS

111 113

INFANTS

CORRIDOR

108 110

JAN.

INFANTS

VESTIBULE

COVERED

ENTRY

AREA B

AREA A

6' -0

PLYWOOD SURFACE UP TO 8' AFF

MONACO

BT-XM

O & M

CABINET

BATTERY

CABINET

WHELEN

CONTROL PANEL

FA/MNS PANEL

RELOCATE

RECEPTACLE

ON EXISTING

WALL

FIRE ALARM PLAN - AREA A1

F201 1/8" = 1'-0"

FIRE ALARM PLAN - AREA B2

F201 1/8" = 1'-0"

KEYPLAN

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

WP

W P

W P

W P

TS

TS

TS

TS

WP

WP

WP

WP

SPECIFIC NOTES

PROVIDE MAGNETIC DOOR HOLD AND INTERFACE RELAY FOR KITCHEN DOOR CONNECTED TO FIRE ALARM SYSTEM. LOCATE SMOKE DETECTOR ABOVE DOOR TO BE COMPLIANT WITH DOOR CLOSE SYSTEM, BUT MITIGATE NUISANCE ALARMS.

CONTRACTOR FIELD VERIFY DOOR OPENING. PROVIDE 45 MINUTE FIRE RATED HOLLOW METAL DOOR AND FRAME. FRAME TO BE CONTINUOUSLY WELD FACES TO MATCH EXISTING, 16-GAGE. PROVIDE 18 GAGE, LEVEL 2 HEAVY DUTY, MODEL 1 - FULL FLUSH WITH NARROW LITE. DOOR AND FRAME SHALL BE FACTORY PRIMED FOR FIELD PAINTING. PROVIDE HARDWARE COMPATIBLE WITH EXISTING HARDWARE. COORDINATE DOOR, FRAME AND HARDWARE WITH MAG HOLD. PATCH AND REPAIR WALL TO MATCH

EXISTING 1-HOUR RATED ASSEMBLY.

HARDWARE - DOOR 162.1

(3) HINGES

(1) LOCKSET LEVER STANLEY (BEST) 9K OR SCHLAGE. MATCH EXISTING FINISH, KEY SYSTEM AND HARDWARE PROFILE OF

EXISTING BUILDING.

(1) DOOR CLOSER

(1) PERIMETER GASKETING

(1) 34" X 34" ARMOR PLATE (HALLWAY SIDE)

PROVIDE FIRE RATED PLYWOOD OR EXTERIOR GRADE PLYWOOD WITH INTUMESCENT PAINT FOR MOUNTING FIRE ALARM

EQUIPMENT WITHIN ELEC 163.

FIRE ALARM EQUIPMENT ELEVATIONS3

F201 NO SCALE

Mitchell S. O'Bryant

No. FP14690

D E S I G N A

L A

S K

A14-Mar-2019

MULTI-PURPOSE

TRAINING ROOM

STOR.

PRESCHOOL

129127

PRESCHOOL

CORRIDOR

PRESCHOOL

PRESCHOOL

PRESCHOOL

138140

PRESCHOOL

AREA C

FIRST FLOOR FIRE ALARM PLAN - AREA C1

F202 1/8" = 1'-0"

KEYPLAN

601 C ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N A

L A

S K

A14 MAR 2018

SPECIFIC NOTES

NEW FIRE ALARM SYSTEM TO RECONNECT TO EXISTING DOOR HOLD DEVICES WITH

INTERFACE RELAYS

TS

WP WP

WP

WP

WPWPWP

WP

TS

CATWALK

ollege R oad Fairbanks AK 99701 907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

Mitchell S. O'Bryant

No. FP14690

D E S I G N A

L A

S K

A14 MAR 2018

FIRE ALARM PLAN - MEZZANINE1

F203 3/32" = 1'-0"

WHELEN ANTENNA

MONACO ANTENNA

NOTES:

1. ANTENNA LOCATED ON THE GABLE END OF THE UPPER ROOF NEAR THE PEAK

AND BOTH ANTENNAS TO BE SEPARATED BY A MINIMUM OF SIX (6) FEET.

2. CABLE DISTANCE FROM ANTENNA TO TRANSPONDERS IN ELECTRICAL ROOM

ESTIMATED TO BE GREATER THAN 100 FEET, UTILIZE LOW LOSS COAXIAL

CABLE.

WHELEN & MONACO TRANSPONDERS IN

ELECTRICAL ROOM BELOW THIS POINT.

ANTENNA CABLES

TO BUILDING 3134

TO FIRE STATION #2

ELECTRICAL

MDP

PANEL M

PANEL E

601 C ollege R oad Fairbanks AK 99701

907.452.1241

A rchitects

S urveyors

E ngineers

A E

C C designalaska.com

ELECTRICAL PLAN1

E001 NO SCALE

ELECTRICAL SYMBOL LEGEND

NOTE KEY - INDICATES NOTES APPLICABLE ON EACH SHEET

PANELBOARD: FLUSH MOUNTED, SURFACE MOUNTED

JUNCTION BOX

EQUIPMENT CONNECTION

J

ALL BRANCH CIRCUITS 2#12, 1/2" C. TO 20A., 1P. CIRCUIT BREAKER UON

e.g. A-30(4 #8, 3/4" C. TO 40/3) INDICATES CIRCUIT BREAKER

30 IN PANEL 'A' FEEDS TO EQUIPMENT FROM A 40 A. 3P. CIRCUIT

BREAKER WITH 4 #8 AWG WIRES RUN IN 3/4" CONDUIT.

A. NO. OF WIRES (IF OTHER THAN 2) INDICATED BY NO. OF SLASHES

( = TWO 'HOT' WIRES AND TWO NEUTRAL WIRES )

B. HOME-RUN DESIGNATION: 'A' = PANELBOARD NOTATION, '-2,4' =

CIRCUIT NUMBERS

C. INSTALL INSULATED GROUNDING CONDUCTOR, SIZED IN

ACCORDANCE WITH NEC REQUIREMENTS IN ALL FEEDER AND

BRANCH CIRCUIT CONDUITS.

SYMBOLS SHOWN ABOVE ARE DRAWN AS THEY ARE USED ON THE

DRAWINGS TO INDICATE NEW WORK OR NEW LOCATIONS OF EXISTING

EQUIPMENT. EXISTING EQUIPMENT TO BE ABANDONED IN PLACE,

REMOVED OR RELOCATED IS SHOWN USING THE SAME SYMBOLS BUT

DRAWN WITH DASHED LINES.

(E) PANEL 'E'

CKT

P TRIP LOAD SERVED LOAD

TYPE

LOAD

(VA) BUS

LOAD

(VA)

LOAD

TYPE LOAD SERVED TRIP P CKT

NO.NO.

1 3 70 SUPPLY AIR FAN M 0 A 0 M EXHAUST FAN 70 3 2

3 " " M 0 B 0 M " " 4

5 " " M 0 C 0 M " " 6

7 3 40 KITCHEN AIR HANDLER M 0 A 0 S (D) SPARE 40 3 8

9 " " M 0 B 0 S " " 10

11 " " M 0 C 0 S " " 12

13 1 20 SPARE S 0 A 0 M Q DOT UNIT HRV 20 20 1 14

15 1 20 MECH ROOM EXHAUST FAN M 0 B 0 S SPARE 20 1 16

17 1 20 WATER HEATERS S 0 C 0 M GLYCOL MAKE UP PUMP 20 1 18

MAIN: 225 AMPS MLO PHASE A: 0 VA 0.0 A CONNECTED: 0 VA NOTES

TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 0 VA 0.0 A AMPS: 0.0 A

AIC: 10,000 RMS SYMM. AMPS PHASE C: 0 VA 0.0 A VOLTAGE: 208 V

N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:

LIGHTING 0 VA 0.0 A L = LIGHTING (LOAD X 125%)

RECEPTACLES 0 VA 0.0 A R = RECEPTACLES (NEC 220.44)

EQUIPMENT (CONTINUOUS) 0 VA 0.0 A C = EQUIPMENT (CONTINUOUS) X 125%

EQUIPMENT (NON-CONTINUOUS) 0 VA 0.0 A E = EQUIPMENT (NON-CONTINUOUS) X 100%

MOTORS 0 VA 0.0 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)

TOTAL DEMAND LOAD 0 VA 0.0 A F = FEEDERS

MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION

SURFACE RM ELEC

(R) PANEL 'E'

CKT

P TRIP LOAD SERVED LOAD

TYPE

LOAD

(VA) BUS

LOAD

(VA)

LOAD

TYPE LOAD SERVED TRIP P CKT

NO.NO.

1 3 70 SUPPLY AIR FAN M 0 A 0 M EXHAUST FAN 70 3 2

3 " " M 0 B 0 M " " 4

5 " " M 0 C 0 M " " 6

7 3 40 KITCHEN AIR HANDLER M 0 A 1,200 E (N) FACP 20 1 8

9 " " M 0 B 1,200 E (N) MNS 20 1 10

11 " " M 0 C 1,200 E (N) TRANSMITTERS 20 1 12

13 1 20 SPARE S 0 A 0 M Q DOT UNIT HRV 20 20 1 14

15 1 20 MECH ROOM EXHAUST FAN M 0 B 0 S SPARE 20 1 16

17 1 20 WATER HEATERS S 0 C 0 M GLYCOL MAKE UP PUMP 20 1 18

MAIN: 225 AMPS MLO PHASE A: 1,200 VA 10.0 A CONNECTED: 3,600 VA NOTES

TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 1,200 VA 10.0 A AMPS: 10.0 A

AIC: 10,000 RMS SYMM. AMPS PHASE C: 1,200 VA 10.0 A VOLTAGE: 208 V

N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:

LIGHTING 0 VA 0.0 A L = LIGHTING (LOAD X 125%)

RECEPTACLES 0 VA 0.0 A R = RECEPTACLES (NEC 220.44)

EQUIPMENT (CONTINUOUS) 0 VA 0.0 A C = EQUIPMENT (CONTINUOUS) X 125%

EQUIPMENT (NON-CONTINUOUS) 3,600 VA 10.0 A E = EQUIPMENT (NON-CONTINUOUS) X 100%

MOTORS 0 VA 0.0 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)

TOTAL DEMAND LOAD 3,600 VA 10.0 A F = FEEDERS

MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION

SURFACE RM ELEC

SPECIFIC NOTES

REMOVE EXISTING SPARE BREAKER TO MAKE ROOM FOR NEW BREAKERS

PROVIDE NEW CIRCUIT BREAKERS, RED IN COLOR WITH LOCKABLE FUNCTIONS FOR FIRE

ALARM/MNS SYSTEMS.

Donald L. Hopkins

No. EE10582

D E S I G N A

L A

S K

A03/13/19

G000
G001
F001
F002
F003
F100
F101
F102
F103
F201
F202
F203
E001