Investigation R1north_UPS_2024-07-02.pdf
PDF 2 MB Posted
- Attached to
- 673CS R1 NORTH UPS
- Solicitation number
- FA500024Q0055
About this file
This document appears to be an investigation report for the UPS system at the R1 North communication site in Anchorage, Alaska. The report states that the current UPS system was installed in 2003 and has not been maintained, with numerous batteries in poor condition. The key recommendations are to replace all 48 batteries, inspect and clean the Eltek Valere controller, and establish a maintenance contract to ensure proper upkeep.
The related federal contract opportunity is for the 673rd Communications Squadron to replace the end-of-life batteries supporting the R1 North ALMR site. The government intends to award a firm-fixed price contract for the contractor to provide all management, tools, supplies, equipment, and labor necessary to repair and service the onsite Eltek UPS. This includes removing and disposing of the current batteries, providing and installing 48 new sealed VRLA batteries, visually inspecting the UPS components, performing cleaning and inspections, and providing a detailed field report.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Q and A MFR.pdf | ||
| Wiring Diagram LB1738024C1-02.pdf | ||
| Combo- Solicittion.pdf | ||
| R1 North UPS mx PWS.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R1North 37th St Anchorage, AK 99501
Date Tue 02/07/2024 Job # Prepared By Steven Rector
Weather
6:00 AM
53° Overcast
Wind: 4 MPH | Precipitation: .0'' | Humidity: 75%
12:00 PM
59° Overcast
Wind: 5 MPH | Precipitation: .0'' | Humidity: 58%
4:00 PM
63° Partially cloudy
Wind: 11 MPH | Precipitation: .0'' | Humidity: 52%
General Notes
1. Conducted a site visit with Mr. Lorenz and Comm to take a look at the UPS for R1 North. The current system was installed in 2003 and no maintenance has been done on the system since it was installed. Numerous batteries are visibly swollen and all the batteries are dead. Recommend replacing all 48 batteries, inspect and clean and the Eltek Valere controller. I was not able to test the controller, so upon contractors recommendation the controller might need to be replaced due to its age. Also establish a maintenance contract to ensure proper up keep of the system per manufactory recommendation.
Location R1 North Communication building Eltek Valere System Controller System: BC2000 DC input : 10.5 5-56VDC/0-600A DC Output : 10.5-56VDC/0-600A
The current batteries have been replaced with GNB Absolyte GP battery.
https://www.solarelectricsupply.com/solar-batteries/gnb-absolyte-gp-industrial-sealed-battery
Battery Type GNB Absoyte IIP Type : 100A-15 696 Ampere Hours 8HR to 1.75 Volts per Cell Non-spillable battery Steven Rector | 03/07/24 | 08:33AM
02/07/24 | 01:03PM02/07/24 | 01:03PM 02/07/24 | 01:03PM02/07/24 | 01:03PM 02/07/24 | 01:03PM02/07/24 | 01:03PM 02/07/24 | 01:03PM02/07/24 | 01:03PM
1 of 2 | R1North https://raken.s3.amazonaws.com/processed/2024/07/03/b56c34e3-851c-4cee-8a7f-e8c77e92d3a4?=1720025156073 https://raken.s3.amazonaws.com/processed/2024/07/03/43a09451-3783-4874-af36-5c14a59a8952?=1720025156073 https://raken.s3.amazonaws.com/processed/2024/07/03/52871618-447e-4b83-9975-fcaa7e31981b?=1720025156074 https://raken.s3.amazonaws.com/processed/2024/07/03/4f5e26eb-2379-403b-b0d0-634cef45213c?=1720025156074
02/07/24 | 01:04PM02/07/24 | 01:04PM 02/07/24 | 01:04PM02/07/24 | 01:04PM 02/07/24 | 01:12PM02/07/24 | 01:12PM 02/07/24 | 01:12PM02/07/24 | 01:12PM
02/07/24 | 01:12PM02/07/24 | 01:12PM 02/07/24 | 01:12PM02/07/24 | 01:12PM
I, Steven Rector, have reviewed and completed this report.
Steven Rector | 03/07/24 | 08:05AM
2 of 2 | R1North https://raken.s3.amazonaws.com/processed/2024/07/03/3fafe964-7d53-4493-a10b-1f685a9464fb?=1720025156074 https://raken.s3.amazonaws.com/processed/2024/07/03/0275883c-5deb-44fb-9076-0e552e7f8036?=1720025156074 https://raken.s3.amazonaws.com/processed/2024/07/03/f18e4984-d754-45d4-a91f-68c65ef13eb3?=1720025156074 https://raken.s3.amazonaws.com/processed/2024/07/03/2a735c86-2585-4838-b97e-744302475491?=1720025156074 https://raken.s3.amazonaws.com/processed/2024/07/03/88a443c2-364a-4e5b-a4a4-e60071472a3f?=1720025156074 https://raken.s3.amazonaws.com/processed/2024/07/03/9a966941-9c1b-4d91-ab43-4bb3c82a52ed?=1720025156074