Monday, July 18, 2022
RFI
Renovate Chapel Kitchen, B58 - Project #CZQZ 14-0068:
I. Are the new Light fixtures LED? Are they 1’X4’ or 2’X4’ (recessed in grid ceiling)?
II. Can the power for the new Mini-split HVAC Unit come from the existing relocated panel?
A. The existing unit in the kitchen does not have sufficient ampacity to feed the new mini-split.
III. Will a Fire Pull Station need to be added by the door existing the kitchen to outside to meet Fire Code?
IV. Will the existing Heat Detectors be reused?
V. What is going to happen with the old Dishwasher? If a new Dishwasher is to be installed what are the power requirements?
VI. Will all 120-volt receptacles in the kitchen and coffee bar to be GFCI receptacles?
VII. Will the (3) new outlets above countertops be feed from the relocated Electrical
Panel?
VIII. Are there any requirements to upgrade the existing Exhaust Hood or is it to remain with no changes?
G. Kenny Combs (575) 607-6800
CEI, LLC
(Electrical Contractor)
1706 S. Roosevelt Rd. 3, Portales, NM 88130
(575) 607-0710 – combselect@gmail.com EE98 NM License# 401758 mailto:combselect@gmail.com 1184009150C Typewritten Text LED are required. 2' x 4' are typical on Base and preferred.
1184009150C Typewritten Text Yes, can come from existing panel.
1184009150C Typewritten Text Only electrical upgrades in support of the mini-split are acceptable.
1184009150C Typewritten Text Pull Station shall only be included if necessary to meet code.
1184009150C Typewritten Text Existing detectors may be reused only if in good condition.
1184009150C Typewritten Text Existing dishwasher not within scope.
1184009150C Typewritten Text GFCI receptacles only required if necessary to meet code.
1184009150C Typewritten Text Correct.
1184009150C Typewritten Text Existing exhaust hood not within scope.