Debris Sampling Report.pdf
PDF 340 KB Posted
- Attached to
- Ryan Center Duct Cleaning
- Solicitation number
- FA4800-25-Q-0049
About this file
This document is a Mold Bulk Report from Eurofins Built Environment Testing for Inspection Experts Inc., detailing mold analysis results for six samples collected from various locations in RC Hampton, VA. The samples were analyzed using nonviable methodology (CEI Method 120) on August 22, 2025, with the report issued on August 29, 2025.
The analysis identified multiple types of mold and fungal matter across different sampling locations, including Aspergillus/Penicillium-like spores, Cladosporium, Hyphal Fragments, Pithomyces, and Alternaria. Sample locations ranged from a desk under a TV in room 201, AFRC 3rd Floor, C105 1st Floor, A119-19 1st Floor, a filter in the Mechanical Room on the 3rd Floor, and a coffee area near Vilari. The Mold Growth Ratings (MGR) varied from 1-3, indicating trace amounts to up to 50% surface coverage of fungal matter, suggesting potential past or active mold growth in these areas.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Diagram Legend.jpg | JPG image | |
| 2nd Fl - Area A.jpg | JPG image | |
| 2nd Fl - Area C.jpg | JPG image | |
| 3rd Fl - Area F(1).jpg | JPG image | |
| 3rd Fl - Area F(2).jpg | JPG image | |
| 1st Fl- Area D.jpg | JPG image | |
| 2nd Fl - Area B.jpg | JPG image | |
| 3rd Fl - Area E(2).jpg | JPG image | |
| Statement of Work - Ryan Center HVAC Cleaning as of 26 SEP 25.pdf | ||
| 1st Fl - Area B.jpg | JPG image | |
| 1st Fl - Area C.jpg | JPG image | |
| 3rd Fl - Area E(1).jpg | JPG image | |
| Solicitation Amendment FA480025Q00490001 SF 30.pdf | ||
| Q and A - Ryan Center Duct Cleaning.pdf | ||
| 1st Fl - Area A.jpg | JPG image | |
| 2nd Fl - Area D.jpg | JPG image | |
| Statement of Work - Ryan Center HVAC Cleaning Updated.pdf | ||
| Ryan Center Duct Cleaning RFIs.pdf | ||
| Wage Determination Rev 31 08 July 2025.pdf | ||
| Statement of Work - Ryan Center HVAC Cleaning.pdf | ||
| Solicitation - FA480025Q0049.pdf |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CLIENT PROJECT:
LAB CODE:
August 29, 2025
Praveen Gopallawa Inspection Experts Inc.
9250 Rumsey Rd #106 Columbia, MD 21045
RC Hampton. VA, RC Mold Testing 684540-1
Dear Praveen, Enclosed are mold analysis results for bulk samples received at our laboratory on August 22, 2025. The samples were analyzed for mold spores using nonviable methodology.
Thank you for your business and we look forward to continuing good relations.
Kind Regards, Tianbao Bai, Ph.D., CIH Laboratory Director
AIHA LAP 290960
2752 Pleasant Road Suite 100A, • Fort Mill, SC 29708 • (803) 526-5146
MOLD BULK REPORT
By: Nonviable Methodology
Prepared for
Inspection Experts Inc.
CLIENT PROJECT: RC Hampton. VA, RC Mold Testing
LAB CODE: 684540-1
TEST METHOD: CEI Method 120
REPORT DATE: 08/29/25
2752 Pleasant Road Suite 100A, • Fort Mill, SC 29708 • (803) 526-5146
SampleSampleSampleSample BackgroundBackgroundBackgroundBackground Client IDClient IDClient IDClient ID Lab IDLab IDLab IDLab ID LocationLocationLocationLocation DebrisDebrisDebrisDebris MGRMGRMGRMGR IdentificationIdentificationIdentificationIdentification
01010101 3663744 Desk under TV in 201 1 2 Aspergillus/Penicillium - Like
1 Hyphal Fragments
02020202 3663745 AFRC - 3rd Floor 2 1 Cladosporium
2 Hyphal Fragments
1 Pithomyces
1 Non-specified spore
2 Aspergillus/Penicillium - Like
03030303 3663746 C105 - 1st Floor 1 1 Aspergillus/Penicillium - Like
2 Hyphal Fragments
04040404 3663747 A119-19 1st Floor 1 3 Aspergillus/Penicillium - Like
3 Hyphal Fragments
05050505 3663748 Filter - Mech Room - 3rd Floor
1 3 Alternaria
3 Hyphal Fragments
4 Aspergillus/Penicillium - Like
06060606 3663749 Coffee Area near Vilari 2 3 Hyphal Fragments
4 Aspergillus/Penicillium - Like
Client: Inspection Experts Inc.
9250 Rumsey Rd #106 Columbia, MD 21045
Project:
Method:
MOLD BULK REPORT
By: Nonviable Methodology
684540-1 08/22/25 08/27/25 08/29/25
Lab Code:
Date Received:
Date Analyzed:
Date Reported:
RC Hampton. VA, RC Mold Testing
CEI Method 120
2752 Pleasant Road Suite 100A, • Fort Mill, SC 29708 • (803) 526-5146 Page 1 of 3
LEGEND
MGR = MOLD GROWTH RATING:
0 - No fungal matter was detected; Debris present is not consistent with fungal matter.
1 - Trace amount of fungal matter detected; A few random appearances of fungal matter indicated. Probably due to settling. Does not indicate active growth.
2 - Up to 25% of the sample surface is covered with fungal matter; Probably indicates active growth at some point in time.
3 - 26%-50% of the sample surface is covered with fungal matter; Indicates active growth at some point in time.
4 - 51%-75% of the sample surface is covered with fungal matter; Indicates active growth at some point in time.
5 - >75% of the sample surface is covered with fungal matter; Indicates active growth at some point in time.
BACKGROUND DEBRIS:
0 - None Detected. No debris observed.
1 - Trace. Field of view obscured < 5%.
2 - Light. Field of view obscured 5% to 25%.
3 - Moderate. Field of view obscured 25% to 75%.
4 = Heavy. Field of view obscured 75% to 90%.
5 - Very Heavy. Field of view obscured >90%.
METHOD:METHOD:METHOD:METHOD: CEI Method 120
All samples received in acceptable condition. Information provided by customer includes customer sample ID, location and volume. Analytical results are not corrected for field and laboratory blanks.
Eurofins Built Environment Testing East, LLC bears no responsibility for client sampling methods and makes no warranty representation regarding the accuracy of client-supplied information in preparing and presenting analytical results. Eurofins Built Environment Testing East, LLC maintains liability limited to the cost of analysis, except for Eurofins Built Environment Testing East, LLC’s own willful misconduct or gross negligence. Interpretation of the analytical results is the sole responsibility of the customer. Test results relate only to the items tested and cannot be extrapolated to anything larger than their original intent. This report may not be reproduced, except in full, without written approval by Eurofins Built Environment Testing East, LLC.
Darby Blanton Analyst
DATA QA:
Eva Leslie 8/29/2025
APPROVED BY:
Tianbao Bai, Ph.D., CIH Laboratory Director
2752 Pleasant Road Suite 100A, • Fort Mill, SC 29708 • (803) 526-5146 Page 3 of 3
SUBMITTED BY INVOICE TO
Client Sample ID Number
RES Job #: 684540
CONTACT INFORMATION SERIES
ASBESTOS LABORATORY REQUESTED ANALYSIS VALID MATRIX CODES LAB NOTES
CHEMISTRY LABORATORY
MICROBIOLOGY LABORATORY
**Turnaround times establish a laboratory priority, subject to laboratory volume and are not guaranteed. Additional fees apply for afterhours, weekends and holidays.**
Laboratory Analysis Instructions
(Sample ID's must be unique)
Company: Inspection Experts Inc. Company: Inspection Experts Inc.
Address: 9250 Rumsey Rd Address: 9250 Rumsey Rd
#106 #106
Columbia, MD 21045 Columbia, MD 21045
Project Number and/or P.O. #: RC Mold Testing Project Zip Code:
Project Description/Location: RC Hampton. VA, RC Mold Testing
Contact: Praveen Gopallawa -1 Micro Standard Phone: (701) 552-3066
Fax:
Cell:
Final Data Deliverable Email Address:
pgopallawa@ieinc.net (+ 7 ADDNL. CONTACTS)
PLM / PCM / TEM DTL RUSH PRIORITY STANDARD Air = A Bulk = B
Dust = D Food = F
Paint = P Soil = S
Dust RUSH PRIORITY STANDARD
*PRIOR NOTICE REQUIRED FOR SAME DAY TAT
Surface = SU Swab = SW
Tape = T Wipe = W
Metals RUSH PRIORITY STANDARD Drinking Water = DW
Waste Water = WW
Organics* SAME DAY RUSH PRIORITY STANDARD **ASTM E1792 approved wipe media only**
Viable Analysis** PRIORITY STANDARD
**TAT DEPENDENT ON SPEED OF MICROBIAL GROWTH
Medical Device Analysis RUSH STANDARD
Mold Analysis RUSH PRIORITY STANDARD
Special Instructions:
MD samples
1 01 X SW
2 02 X SW
3 03 X SW
4 04 X SW
5 05 X SW
6 06 X SW
P L
M
T E
M
P C
M
D U
S T
M E
TA
L
S
O R
G A
N
IC
S
V
IA
B L
E S
M E
D
IC
A L
M O
L D
B u lk
M o ld A n al ys is
(A S
T M
D
-1
7)
S am pl e
V ol um e
(L
A re a
S am pl e
Te m pe ra tu re
C
Le ng th (o r A liq uo ts
) x W id th
(o r A re a/
A liq uo t)
M at rix C od e of
C on ta in er s
D at e C ol le ct ed m m
/d d/ yy
T im e C ol le ct ed hh :m m
ASBESTOS CHEMISTRY MICROBIOLOGY ICO
Eurofins Built Environment Testing East, LLC establishes a unique Lab Sample ID, for each sample, by preceding each unique Client Sample ID with the laboratory RES Job Number.
Eurofins Built Environment Testing East, LLC will analyze incoming samples based on information received and will not be responsible for errors or omissions in calculations resulting from the inaccuracy of original data. By signing, client/company representative agrees that submission of the following samples for requested analysis as indicated on this Chain of Custody shall consitute an analytical services agreement with payment terms of NET 30 days. Failure to comply with payment terms may result in a 1.5% monthly interest surcharge.
Relinquished By:
Date/Time: 08/22/2025 14:37:59 Sample Condition: Acceptable
Received By:
Candice Wilkins Date/Time: 08/22/2025 15:10:52 Carrier: Fed-Ex
Eurofins Built Environment Testing East, LLC Effective
(919) 481-1413 https://www.eurofinsus.com/builtenv730 SE Maynard Rd, Cary, NC 27511
Client Sample ID Sample Note Quantity Sampler(s)
01 Desk under TV in 201
02 AFRC - 3rd Floor
03 C105 - 1st Floor
04 A119-19 1st Floor
05 Filter - Mech Room - 3rd Floor
06 Coffee Area near Vilari
Inspection Experts Inc.
Sample Notes
RES #: 684540
Project Number and/or P.O. #: RC Mold Testing
Project Description/Location: RC Hampton. VA, RC Mold Testing
Client Sample ID Sample Location
01 Desk under TV in 201
02 AFRC - 3rd Floor
03 C105 - 1st Floor
04 A119-19 1st Floor
05 Filter - Mech Room - 3rd Floor
06 Coffee Area near Vilari
Inspection Experts Inc.
Sample Locations
RES #: 684540
Project Number and/or P.O. #: RC Mold Testing
Project Description/Location: RC Hampton. VA, RC Mold Testing
File details come from the government source that posted it. Updated .