Bldg_641_Cable_Reroute_Plan.pptx

PPTX presentation 793 KB Posted

Attached to
Cable Re-Route Bldg 641 Federal contract opportunity
Solicitation number
FA4800-17-Q-0019
Issued by
Department of the Air Force Air Combat Command

About this file

Drawings for Cable Re-Route Bldg 641

View the file

Other files for this federal contract opportunity

Other files attached to Cable Re-Route Bldg 641, newest first.
File Type Posted
QUESTIONS_AND_ANSWERS-Rev1.docx DOCX document
Engineering_Technical_Letter_02-12.pdf PDF
QUESTIONS_AND_ANSWERS.docx DOCX document
Langley_AFB_Telecommunications_Building_Cabling_Systems_Standards.docx DOCX document
Bldg_641_Cable_Reroute_Plan_(101)_(002).pptx PPTX presentation
Tab_1a_-_OSP_Cable_Specification_Jul_17.docx DOCX document
Combined_Synopsis1.docx DOCX document
Bldg_641_Cable_SOO_(revised_).docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CURRENT

ROUTE

PROPOSED

ROUTE

COMM

ROOM

LEGEND

CURRENT ROUTE (DUCT)

CURRENT ROUTE (NOT SURVEYED)

PROPOSED ROUTE (DUCT)

COMM ROOM

MAINTENANCE HOLE

6410693, 1-12

T-641 CA02, 1-100

CURRENT

ROUTE

NOTES:

1. TEST EXISTING BASE COPPER AND FIBER BACK FOR BASELINE

2. PULL EXISTING BASE COPPER AND FIBER BACK TO MAINTENANCE HOLE (MH74)

3. INSTALL TWO NEW 4 INCH SCHEDULE 80 PVC CONDUITS TO COMM ROOM - WITH GRADUAL

SWEEP, INTO CRAWL SPACE BELOW COMM ROOM, AND PROVIDE SWEEPING PENETRATION

INTO COMM ROOM NEAR TELECOMM BACKBOARD

4. FURNISH AND INSTALL 3-CELL CLOTH, COLLAPSIBLE, MESH TYPE INNERDUCT IN FIRST DUCT

5. INSTALL 100-PAIR COPPER CABLE IN FIRST DUCT, RACK AND SPICE IN MH71 - TERMINATE

IN COMM ROOM

6. INSTALL 12-STRAND SINGLEMODE FIBER OPTIC CABLE IN MESH INNERDUCT, RACK, AND

TERMINATE IN F.641 AND F.693 COMM ROOMS

7. GROUND, TEST, LABEL, DUCT SEAL, PROVIDE PULL STRING IN SPARE DUCTS AND

INNERDUCTS, AND PROVIDE AS-BUILT DRAWINGS

DEMOLISH/REMOVE ABANDONED NASA INFRASTRUCTURE

DEMOLISH/REMOVE ABANDONED NASA INFRASTRUCTURE

SPARE

CONDUIT DETAIL

LEGEND

CONDUIT STUB UPS INTO COMM ROOM

100-PAIR COPPER CABLE

12-STRAND SM FIBER CABLE

MESH INNERDUCT

NOTES:

1. STUB CONDUITS INTO COMM ROOM

2. EXTEND CABLE TRAY TO BASE TELECOM BACKBOARD

3. TERMINATE 100-PAIR COPPER CABLE TO GFCI BUILDING ENTRANCE TERMINAL (BET)

4. RUN 12-STRAND SINGLEMODE FIBER CABLE TO EXISTING FIBER OPTIC DISTRIBUTION

PANEL (FODP) IN COMM EQUIPMENT CABINET, TERMINATE TO SC TYPE CONNECTORS

5. DEMOLISH AND REMOVE ABANDONED NASA INFRASTRUCTURE

ABANDONED NASA

INFRASTRUCTURE

BASE COMM EQUIPMENT RACKS

WINDOW

BASE TELECOM BACKBOARD

(BACKBONE CABLES)

BASE TELECOM BACKBOARD

(COPPER BET)

NASA TELECOM BACKBOARD

FODP

CONDUIT DETAIL IS NOTIONAL ONLY / EXACT LOCATION WILL BE COORDINATED WITH 633 CS/SCOW

NOT TO SCALE

image1.jpg image2.jpg image3.jpg image4.jpg image5.jpg image6.jpg image7.jpg image8.jpg image9.jpg

File details come from the government source that posted it. Updated .