Bldg_641_Cable_Reroute_Plan_(101)_(002).pptx
PPTX presentation 578 KB Posted
- Attached to
- Cable Re-Route Bldg 641 Federal contract opportunity
- Solicitation number
- FA4800-17-Q-0019
About this file
Cable Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| QUESTIONS_AND_ANSWERS-Rev1.docx | DOCX document | |
| Engineering_Technical_Letter_02-12.pdf | ||
| QUESTIONS_AND_ANSWERS.docx | DOCX document | |
| Langley_AFB_Telecommunications_Building_Cabling_Systems_Standards.docx | DOCX document | |
| Tab_1a_-_OSP_Cable_Specification_Jul_17.docx | DOCX document | |
| Combined_Synopsis1.docx | DOCX document | |
| Bldg_641_Cable_Reroute_Plan.pptx | PPTX presentation | |
| Bldg_641_Cable_SOO_(revised_).docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MH74
MH71
MH70A
MH70
MH66
MH24
MH P12A
LEGEND
PROPOSED CABLE ROUTE
NEW DUCT ROUTE
EXISTING DUCT ROUTE
EXISTING MAINT. HOLE
DUCT ROUTE TO ABANDON
CURRENT
ROUTE
PROPOSED
ROUTE
COMM
ROOM
LEGEND
CURRENT ROUTE (DUCT)
CURRENT ROUTE (NOT SURVEYED)
PROPOSED ROUTE (DUCT)
COMM ROOM
MAINTENANCE HOLE
6410693, 1-12
T-641 CA02, 1-100
CURRENT
ROUTE
NOTES:
1. TEST EXISTING BASE COPPER FOR BASELINE
2. PULL EXISTING BASE COPPER BACK TO MAINTENANCE HOLE (MH71) / FIBER BACK TO F.635
3. INSTALL TWO NEW 4 INCH SCHEDULE 80 PVC CONDUITS TO COMM ROOM - WITH GRADUAL
SWEEP, FROM MH74 INTO EXISTING JUNCTION BOX AND INTO COMM ROOM
4. FURNISH AND INSTALL 3-CELL CLOTH, COLLAPSIBLE, MESH TYPE INNERDUCT IN FIRST DUCT
5. INSTALL 100-PAIR COPPER CABLE IN FIRST DUCT, RACK AND SPLICE IN MH71 - TERMINATE
IN COMM ROOM
6. INSTALL 12-STRAND SINGLEMODE FIBER OPTIC CABLE IN MESH INNERDUCT, RACK, AND
TERMINATE IN F.641 AND F.693 COMM ROOMS
7. GROUND, TEST, LABEL, DUCT SEAL, PROVIDE PULL STRING IN SPARE DUCTS AND
INNERDUCTS, AND PROVIDE AS-BUILT DRAWINGS
DEMOLISH/REMOVE ABANDONED NASA INFRASTRUCTURE
EXISTING JUNCTION BOX PENETRATION INTO COMM ROOM
(TO REMAIN)
DEMOLISH/REMOVE ABANDONED NASA INFRASTRUCTURE
SPARE
CONDUIT DETAIL
LEGEND
CONDUIT STUB UPS INTO COMM ROOM
100-PAIR COPPER CABLE
12-STRAND SM FIBER CABLE
MESH INNERDUCT
NOTES:
1. STUB CONDUITS INTO COMM ROOM
2. EXTEND CABLE TRAY TO BASE TELECOM BACKBOARDS
3. TERMINATE 100-PAIR COPPER CABLE TO GFCI BUILDING ENTRANCE TERMINAL (BET)
4. RUN 12-STRAND SINGLEMODE FIBER CABLE TO EXISTING FIBER OPTIC DISTRIBUTION
PANEL (FODP) IN COMM EQUIPMENT CABINET, TERMINATE TO SC TYPE CONNECTORS
5. DEMOLISH AND REMOVE ABANDONED NASA INFRASTRUCTURE
ABANDONED NASA
INFRASTRUCTURE
BASE COMM EQUIPMENT RACKS
WINDOW
BASE TELECOM BACKBOARD
(BACKBONE CABLES)
BASE TELECOM BACKBOARD
(COPPER BET)
NASA TELECOM BACKBOARD
FODP
CONDUIT DETAIL IS NOTIONAL ONLY / EXACT LOCATION WILL BE COORDINATED WITH 633 CS/SCOW
NOT TO SCALE
image1.jpg image2.jpg image3.jpg image4.jpg image5.jpg image6.jpg image7.jpg image8.jpg