The document details the utility power sources, short circuit current capabilities, and overcurrent protection settings for three on-site switching stations (Alpha, Bravo, and Charlie) supplied by American Electric Power Texas (AEP Texas) at 69 kilovolts. The utility provides three-phase fault currents ranging from 808.9 to 982.1 MVA and single-line-to-ground fault currents ranging from 574.6 to 757.9 MVA across the three AEP Texas supply lines. Overcurrent protection is implemented through main breaker/relay systems on each feeder, with detailed specifications provided for Alpha Switchgear using GE SR 760 relays (1200/5 CT ratio, 0.3 tap pickup, U4 Extremely Inverse curve), Bravo Switchgear using SEL-751 relays (240/1 CT ratio, 1.25 tap pickup, U3 Very Inverse curve), and Charlie Switchgear using SEL-751 relays (120/1 CT ratio, 2.5 tap pickup, U3 Very Inverse curve). All switchgear includes both phase and neutral protection settings with instantaneous trip capabilities ranging from 10 to 29.17 ampere multiples. The base operates an on-site diesel generator standby plant connected to the Bravo switching station to provide backup power during commercial outages. Medium voltage protection employs SEL and GE relays at the substation level, while low voltage distribution uses a combination of solid-state trip (SST) devices from manufacturers including Sentron, Digi-Trip, Seltronic, Micrologic, and Spectra RMS.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Dyess AFB
Electrical Distribution System Description
3-4
3.3.2 Available Short Circuit Current
The Utility provides the main source of short circuit currents available throughout the circuit. Refer to Table 3-1 for a summary of the available short circuit current. These values are used as the basis for the short circuit study.
Table 3-1 Utility Main Substation Short Circuit Current
Utility Short Circuit Type
Voltage Reference Fault Current
AEP Texas Alpha 69kV Line
Three Phase 69 kV 982.1 MVA
Single line to ground
69 kV 727.1 MVA
AEP Texas Bravo 69kV Line
Three Phase 69 kV 973.7 MVA
Single line to ground
69 kV 757.9 MVA
AEP Texas Charlie 69kV
Line
Three Phase 69 kV 808.9 MVA
Single line to ground
69 kV 574.6 MVA
3.3.3 Overcurrent Protection
Overcurrent protection is provided by a main breaker/relay on each feeder and/or distribution equipment. (Refer to Table 3-2, Table 3-3, and Table 3-4). For additional Neutral / Ground Overcurrent Protection settings, refer to Appendix R – Compiled OCPD Information Table.
Table 3-2 Dyess AFB Alpha Switchgear Overcurrent Protection Data
Relay FDR A1 FDR A2 Model GE SR 760 GE SR 760
CT ratio 1200/5 1200/5
Phase Settings Tap (pickup) 0.3 (360A) 0.3 (360A)
Dyess AFB Alpha Switchgear Overcurrent Protection Data
3-5
Time dial setting 1.2 1.2
Curve shape U4 Extremely Inverse
U4 Extremely Inverse
Instantaneous None None
Neutral Settings CT ratio 1000/5 1000/5
Tap (pickup) 0.15 (150A) 0.15 (150A)
Time dial setting 1.2 1.2
Curve shape U4 Extremely Inverse
U4 Extremely Inverse
Instantaneous None None
Table 3-3 Dyess AFB Bravo Switchgear Overcurrent Protection Data
Relay FDR B1 FDR B2 FDR B3 FDR B4 Model SEL-751 SEL-751 SEL-751 SEL-751
CT ratio 240/1 240/1 240/1 240/1
Phase Settings
Tap (pickup) 1.25 (173.205A)
1.25 (173.205A)
1.25 (173.205A)
1.25 (173.205A)
Time dial setting 2.85 2.85 2.85 2.85
Curve shape U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
Instantaneous 12 (1662.77A) 15 (2078.46A) 15 (2078.46A) 10 (1385.64A)
Neutral Settings Tap (pickup) 0.5 (69.282A) 0.5 (69.282A) 0.5 (69.282A) 0.5 (69.282A)
Time dial setting 2 2 2 2
3-6
Curve shape U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
U3 Very
Instantaneous None None None None
Relay RLY-S-G1-1 RLY-S-G1-2 RLY-SW-EG1-
UTILBKR
Model SEL-751 SEL-751 GE SR 750
CT ratio 240/1 240/1 1200/5
Phase Settings Tap (pickup) 2 (277.128A) 2 (277.128A) 0.68 (816A)
Time dial setting 2.5 2.5 6
Curve shape U3 Very Inverse
U3 Very Inverse
IAC Short Inverse
Instantaneous None None None
Neutral Settings Tap (pickup) 0.5 (69.282A) 0.5 (69.282A) 0.11 (132A)
Time dial setting 3.25 3.25 10.9
Curve shape U3 Very Inverse
U3 Very Inverse
U4 Extremely
Instantaneous None None None
Table 3-4 Dyess AFB Charlie Switchgear Overcurrent Protection Data
Relay FDR C1 FDR C2 FDR C3 FDR C4 Model SEL-751 SEL-751 SEL-751 SEL-751
CT ratio 120/1 120/1 120/1 120/1
Phase Settings Tap (pickup) 2.5 (300A) 2.5 (300A) 2.5 (300A) 2.5 (300A)
3-7
Time dial setting 2.85 3.23 3.1 3
Curve shape U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
Instantaneous 29.17 (3500.4A)
29.17 (3500.4A)
29.17 (3500.4A) 29.17
(3500.4A)
Neutral Settings Tap (pickup) 1 (120A) 1 (120A) 1 (120A) 1 (120A)
Time dial setting 4.8 4.8 4.8 4.8
Curve shape U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
Instantaneous 8.33 (999.6A)
0.2 sec Delay
8.33 (999.6A)
0.2 sec Delay
8.33 (999.6A)
0.2 sec Delay
8.33 (999.6A)
0.2 sec Delay
Relay FDR C5 FDR GPR-C- G1
FDR GPR-C-
G2
FDR IPR-C-
C7
Model SEL-751 SEL-751 SEL-751 SEL-751
CT ratio 120/1 1200/5 1200/5 1200/5
Phase Settings Tap (pickup) 2.5 (300A) 2.5 (600A) 2.5 (600A) 2.5 (600A)
Time dial setting 3 2.85 2.85 2.85
Curve shape U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
Instantaneous 29.17 (3500.4A)
29.17 (7000.8A)
29.17 (7000.8A) 29.17
(7000.8A)
Neutral Settings Tap (pickup) 1 (120A) 1 (120A) 1 (120A) 1 (120A)
Time dial setting 4.8 4.8 4.8 4.8
3-8
Curve shape U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
U3 Very Inverse
Instantaneous 8.33 (999.6A)
0.2 sec Delay
8.33 (1999.2A)
0.2 sec Delay
8.33 (1999.2A)
0.2 sec Delay
8.33 (1999.2A)
0.2 sec Delay
3.3.4 Utility Source (Substations)
Dyess Air Force Base (AFB) operates and maintains three on-site switching stations, designated Alpha, Bravo, and Charlie. These stations are powered by adjacent substations managed by American Electric Power Texas (AEP Texas). The base also features an on-site diesel generator (DG) standby plant, which is connected to the Bravo switching station. The DG plant serves as a standby power source for the main base, ensuring power supply to Bravo and Charlie in the event of a commercial power outage.
3.3.5 Switchgear Protection
At the Substation, SEL and GE relays are used for protection at the medium voltage level.
Throughout the rest of the distribution system, there is a combination of relays and fuses used for protection at the medium voltage level.
At the low voltage level, there are a combination of SSTs used. These include Sentron, Digi-Trip, Seltronic, Micrologic and Spectra RMS. Figure 3-4 shows an example of one of these relays. Some of these relays contain a ground element.
These relays fall into the Solid-State Trip (SST) category unlike an Intelligent Electronic Device (IED) category. SST provides no analytical assistance, historical databasing, or event recording.