Dyess_AFB A-Sub Relay Settings.pdf

PDF 105 KB Posted

Attached to
Replace Substation Alpha Relay B11912 Amendment 0002
Solicitation number
FA466126R0010
Issued by

About this file

This is a technical specification document describing the electrical distribution system at Dyess Air Force Base.

The document details the utility power sources, short circuit current capabilities, and overcurrent protection settings for three on-site switching stations (Alpha, Bravo, and Charlie) supplied by American Electric Power Texas (AEP Texas) at 69 kilovolts. The utility provides three-phase fault currents ranging from 808.9 to 982.1 MVA and single-line-to-ground fault currents ranging from 574.6 to 757.9 MVA across the three AEP Texas supply lines. Overcurrent protection is implemented through main breaker/relay systems on each feeder, with detailed specifications provided for Alpha Switchgear using GE SR 760 relays (1200/5 CT ratio, 0.3 tap pickup, U4 Extremely Inverse curve), Bravo Switchgear using SEL-751 relays (240/1 CT ratio, 1.25 tap pickup, U3 Very Inverse curve), and Charlie Switchgear using SEL-751 relays (120/1 CT ratio, 2.5 tap pickup, U3 Very Inverse curve). All switchgear includes both phase and neutral protection settings with instantaneous trip capabilities ranging from 10 to 29.17 ampere multiples. The base operates an on-site diesel generator standby plant connected to the Bravo switching station to provide backup power during commercial outages. Medium voltage protection employs SEL and GE relays at the substation level, while low voltage distribution uses a combination of solid-state trip (SST) devices from manufacturers including Sentron, Digi-Trip, Seltronic, Micrologic, and Spectra RMS.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Dyess AFB

Electrical Distribution System Description

3-4

3.3.2 Available Short Circuit Current

The Utility provides the main source of short circuit currents available throughout the circuit. Refer to Table 3-1 for a summary of the available short circuit current. These values are used as the basis for the short circuit study.

Table 3-1 Utility Main Substation Short Circuit Current

Utility Short Circuit Type

Voltage Reference Fault Current

AEP Texas Alpha 69kV Line

Three Phase 69 kV 982.1 MVA

Single line to ground

69 kV 727.1 MVA

AEP Texas Bravo 69kV Line

Three Phase 69 kV 973.7 MVA

Single line to ground

69 kV 757.9 MVA

AEP Texas Charlie 69kV

Line

Three Phase 69 kV 808.9 MVA

Single line to ground

69 kV 574.6 MVA

3.3.3 Overcurrent Protection

Overcurrent protection is provided by a main breaker/relay on each feeder and/or distribution equipment. (Refer to Table 3-2, Table 3-3, and Table 3-4). For additional Neutral / Ground Overcurrent Protection settings, refer to Appendix R – Compiled OCPD Information Table.

Table 3-2 Dyess AFB Alpha Switchgear Overcurrent Protection Data

Relay FDR A1 FDR A2 Model GE SR 760 GE SR 760

CT ratio 1200/5 1200/5

Phase Settings Tap (pickup) 0.3 (360A) 0.3 (360A)

Dyess AFB Alpha Switchgear Overcurrent Protection Data

3-5

Time dial setting 1.2 1.2

Curve shape U4 Extremely Inverse

U4 Extremely Inverse

Instantaneous None None

Neutral Settings CT ratio 1000/5 1000/5

Tap (pickup) 0.15 (150A) 0.15 (150A)

Time dial setting 1.2 1.2

Curve shape U4 Extremely Inverse

U4 Extremely Inverse

Instantaneous None None

Table 3-3 Dyess AFB Bravo Switchgear Overcurrent Protection Data

Relay FDR B1 FDR B2 FDR B3 FDR B4 Model SEL-751 SEL-751 SEL-751 SEL-751

CT ratio 240/1 240/1 240/1 240/1

Phase Settings

Tap (pickup) 1.25 (173.205A)

1.25 (173.205A)

1.25 (173.205A)

1.25 (173.205A)

Time dial setting 2.85 2.85 2.85 2.85

Curve shape U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

Instantaneous 12 (1662.77A) 15 (2078.46A) 15 (2078.46A) 10 (1385.64A)

Neutral Settings Tap (pickup) 0.5 (69.282A) 0.5 (69.282A) 0.5 (69.282A) 0.5 (69.282A)

Time dial setting 2 2 2 2

3-6

Curve shape U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

U3 Very

Instantaneous None None None None

Relay RLY-S-G1-1 RLY-S-G1-2 RLY-SW-EG1-

UTILBKR

Model SEL-751 SEL-751 GE SR 750

CT ratio 240/1 240/1 1200/5

Phase Settings Tap (pickup) 2 (277.128A) 2 (277.128A) 0.68 (816A)

Time dial setting 2.5 2.5 6

Curve shape U3 Very Inverse

U3 Very Inverse

IAC Short Inverse

Instantaneous None None None

Neutral Settings Tap (pickup) 0.5 (69.282A) 0.5 (69.282A) 0.11 (132A)

Time dial setting 3.25 3.25 10.9

Curve shape U3 Very Inverse

U3 Very Inverse

U4 Extremely

Instantaneous None None None

Table 3-4 Dyess AFB Charlie Switchgear Overcurrent Protection Data

Relay FDR C1 FDR C2 FDR C3 FDR C4 Model SEL-751 SEL-751 SEL-751 SEL-751

CT ratio 120/1 120/1 120/1 120/1

Phase Settings Tap (pickup) 2.5 (300A) 2.5 (300A) 2.5 (300A) 2.5 (300A)

3-7

Time dial setting 2.85 3.23 3.1 3

Curve shape U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

Instantaneous 29.17 (3500.4A)

29.17 (3500.4A)

29.17 (3500.4A) 29.17

(3500.4A)

Neutral Settings Tap (pickup) 1 (120A) 1 (120A) 1 (120A) 1 (120A)

Time dial setting 4.8 4.8 4.8 4.8

Curve shape U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

Instantaneous 8.33 (999.6A)

0.2 sec Delay

8.33 (999.6A)

0.2 sec Delay

8.33 (999.6A)

0.2 sec Delay

8.33 (999.6A)

0.2 sec Delay

Relay FDR C5 FDR GPR-C- G1

FDR GPR-C-

G2

FDR IPR-C-

C7

Model SEL-751 SEL-751 SEL-751 SEL-751

CT ratio 120/1 1200/5 1200/5 1200/5

Phase Settings Tap (pickup) 2.5 (300A) 2.5 (600A) 2.5 (600A) 2.5 (600A)

Time dial setting 3 2.85 2.85 2.85

Curve shape U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

Instantaneous 29.17 (3500.4A)

29.17 (7000.8A)

29.17 (7000.8A) 29.17

(7000.8A)

Neutral Settings Tap (pickup) 1 (120A) 1 (120A) 1 (120A) 1 (120A)

Time dial setting 4.8 4.8 4.8 4.8

3-8

Curve shape U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

U3 Very Inverse

Instantaneous 8.33 (999.6A)

0.2 sec Delay

8.33 (1999.2A)

0.2 sec Delay

8.33 (1999.2A)

0.2 sec Delay

8.33 (1999.2A)

0.2 sec Delay

3.3.4 Utility Source (Substations)

Dyess Air Force Base (AFB) operates and maintains three on-site switching stations, designated Alpha, Bravo, and Charlie. These stations are powered by adjacent substations managed by American Electric Power Texas (AEP Texas). The base also features an on-site diesel generator (DG) standby plant, which is connected to the Bravo switching station. The DG plant serves as a standby power source for the main base, ensuring power supply to Bravo and Charlie in the event of a commercial power outage.

3.3.5 Switchgear Protection

At the Substation, SEL and GE relays are used for protection at the medium voltage level.

Throughout the rest of the distribution system, there is a combination of relays and fuses used for protection at the medium voltage level.

At the low voltage level, there are a combination of SSTs used. These include Sentron, Digi-Trip, Seltronic, Micrologic and Spectra RMS. Figure 3-4 shows an example of one of these relays. Some of these relays contain a ground element.

These relays fall into the Solid-State Trip (SST) category unlike an Intelligent Electronic Device (IED) category. SST provides no analytical assistance, historical databasing, or event recording.

File details come from the government source that posted it. Updated .