Repair_CP_Rectifiers_Amendment-1_Summary.docx

DOCX document 16 KB Posted

Attached to
Repair Cathodic Protection Federal contract opportunity
Solicitation number
FA4626-18-R-0014
Issued by
Department of the Air Force Global Strike Command

View the file

Other files for this federal contract opportunity

Other files attached to Repair Cathodic Protection, newest first.
File Type Posted
Clarification.docx DOCX document
Repair_CP_Rectifiers_Question_Sets.docx DOCX document
Repair_CP_Rectifiers_Sheet_E3.3_Amendment1.pdf PDF
Repair_CP_Rectifiers_B-01,_Sheet_E1.1_Amendment1.pdf PDF
Questions_set_1.docx DOCX document
Repair_CP_Rectifiers__H-01,_Sheet_E1.7_Amendment1.pdf PDF
Amendment_2_conform_document.pdf PDF
Amendment_2.pdf PDF
Amendment_1.pdf PDF
Attach_1_Cathodic_Specifications.pdf PDF
Attach_3_Schedule_of_Drawings.pdf PDF
Attach_6_Installation_Perimeter_Access.pdf PDF
Attach_8_Past_Performance_Questionaire.pdf PDF
Attach_7_Special_Contract_Requirements.pdf PDF
Attach_9_Subcontractor_Consent.pdf PDF
Attach_5_Wage_Determinations_MT_67,_76,78.pdf PDF
Solicitation.pdf PDF
Attach_2_Material_Submittal_Schedule.pdf PDF
Attach_4_Drawings_all.pdf PDF
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT ONE SUMMARY

CATHODIC PROTECTION AT 15 MAFs & SELECT LFs

PN: NZAS 02-2030

3 July, 2018

Amended Drawing Sheets:

1) Revise Sheets E1.0, E1.2, E1.3, E1.4, E1.5, E1.6, E1.8, E1.9, E1.10, E1.11, E1.12, E1.13, and E1.14. Replace Specific Sheet Hex Note “6” as follows: “HORIZONTAL DIRECTIONAL BORE UNDER ACCESS ROAD FOR (1) 1” SCH. 80 PVC CONDUIT AND (1) 2” SPARE CONDUIT. ALL CONDUITS SHALL BE SLEEVED, SEE DETAIL 6, SHEET E3.3.”

2) Replace Sheet E1.1with New Sheet E1.1, Bravo 1: revises Hex Note “6” and adds Hex Note “6a”.

3) Replace Sheet E1.7 with New Sheet E1.7, Hotel 1: deletes Hex note “6” and adds Hex Notes “6a” and “6b”.

4) Replace Sheet E3.3 with New Sheet E3.3, Misc Electrical & Fence Details: revises the “NOTE” for Detail “6”.

Amended Specification Pages:

5) Page 72, SECTION 099000 3.4.D.2:

Add line “c” to SECTION 099000 3.4.D.2: “c. Unless noted otherwise on the drawings, PVC coated or galvanized conduit shall not be painted.”

6) Page 92, SECTION 264200 2.1.B:

Replace: …a self-contained circuit breaker with a thermal and magnetic time delay trip element and an instantaneous magnetic trip element in the AC input circuits.

With: …a self-contained magnetic circuit breaker with an instantaneous trip element in the AC input circuits.

7) Page 93, SECTION 264200 2.1.E:

Delete the following sentence: “Use fast/spun pin type hinge, welded on.”

8) Page 94, SECTION 264200 2.2.A:

Replace: “Use fast/spun-pin type hinges, welded on.”

With: “Hinges must be welded on.”

File details come from the government source that posted it.