Repair_CP_Rectifiers_Amendment-1_Summary.docx
DOCX document 16 KB Posted
- Attached to
- Repair Cathodic Protection Federal contract opportunity
- Solicitation number
- FA4626-18-R-0014
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Clarification.docx | DOCX document | |
| Repair_CP_Rectifiers_Question_Sets.docx | DOCX document | |
| Repair_CP_Rectifiers_Sheet_E3.3_Amendment1.pdf | ||
| Repair_CP_Rectifiers_B-01,_Sheet_E1.1_Amendment1.pdf | ||
| Questions_set_1.docx | DOCX document | |
| Repair_CP_Rectifiers__H-01,_Sheet_E1.7_Amendment1.pdf | ||
| Amendment_2_conform_document.pdf | ||
| Amendment_2.pdf | ||
| Amendment_1.pdf | ||
| Attach_1_Cathodic_Specifications.pdf | ||
| Attach_3_Schedule_of_Drawings.pdf | ||
| Attach_6_Installation_Perimeter_Access.pdf | ||
| Attach_8_Past_Performance_Questionaire.pdf | ||
| Attach_7_Special_Contract_Requirements.pdf | ||
| Attach_9_Subcontractor_Consent.pdf | ||
| Attach_5_Wage_Determinations_MT_67,_76,78.pdf | ||
| Solicitation.pdf | ||
| Attach_2_Material_Submittal_Schedule.pdf | ||
| Attach_4_Drawings_all.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT ONE SUMMARY
CATHODIC PROTECTION AT 15 MAFs & SELECT LFs
PN: NZAS 02-2030
3 July, 2018
Amended Drawing Sheets:
1) Revise Sheets E1.0, E1.2, E1.3, E1.4, E1.5, E1.6, E1.8, E1.9, E1.10, E1.11, E1.12, E1.13, and E1.14. Replace Specific Sheet Hex Note “6” as follows: “HORIZONTAL DIRECTIONAL BORE UNDER ACCESS ROAD FOR (1) 1” SCH. 80 PVC CONDUIT AND (1) 2” SPARE CONDUIT. ALL CONDUITS SHALL BE SLEEVED, SEE DETAIL 6, SHEET E3.3.”
2) Replace Sheet E1.1with New Sheet E1.1, Bravo 1: revises Hex Note “6” and adds Hex Note “6a”.
3) Replace Sheet E1.7 with New Sheet E1.7, Hotel 1: deletes Hex note “6” and adds Hex Notes “6a” and “6b”.
4) Replace Sheet E3.3 with New Sheet E3.3, Misc Electrical & Fence Details: revises the “NOTE” for Detail “6”.
Amended Specification Pages:
5) Page 72, SECTION 099000 3.4.D.2:
Add line “c” to SECTION 099000 3.4.D.2: “c. Unless noted otherwise on the drawings, PVC coated or galvanized conduit shall not be painted.”
6) Page 92, SECTION 264200 2.1.B:
Replace: …a self-contained circuit breaker with a thermal and magnetic time delay trip element and an instantaneous magnetic trip element in the AC input circuits.
With: …a self-contained magnetic circuit breaker with an instantaneous trip element in the AC input circuits.
7) Page 93, SECTION 264200 2.1.E:
Delete the following sentence: “Use fast/spun pin type hinge, welded on.”
8) Page 94, SECTION 264200 2.2.A:
Replace: “Use fast/spun-pin type hinges, welded on.”
With: “Hinges must be welded on.”