ASBESTOS SURVEY REPORT
FOR
VANDENBERG AIR FORCE BASE, CALIFORNIA
BUILDING NO. 860
Prepared for:
Mr. Joseph Naputi
30 CES/CEVCC
1028 Iceland Avenue Vandenberg Air Force Base, California 93437-6010
Ms. Carol Cromer
CESAM-EN-GE
U.S. Army Engineer District, Mobile Post Office Box 2288
Mobile, Alabama 36628-0001
Prepared by:
TETRA TECH EM, INC.
10860 GOLD CENTER DR. SUITE 200
RANCHO CORDOVA, CALIFORNIA 95670
Contract No. FA4890-04-D-0006, ECAS Log No. 658, Task Order CK 18, FY08 Environmental Compliance and Miscellaneous Technical Support for AFSPC
March 7, 2009 i
CONTENTS
Section Page
1.0 SITE STRUCTURE
2.0 FINDINGS
3.0 ASSUMPTIONS AND DEVIATIONS
APPENDICES
Appendix
A FIGURES
B PHOTOLOG
C LABORATORY REPORTS AND CHAIN-OF-CUSTODY FORMS
TABLES
Table
1 ACM SAMPLE SUMMARY
2 NON-ACM SAMPLE SUMMARY
1.0 SITE STRUCTURE
Building 860 is a single-story, approximately 7,740 sq. ft. structure; built in 1959. The building is constructed of concrete masonry with a stucco finish. Interior finishes include drywall with skim coat walls. Flooring materials include carpet, floor tile, ceramic tile, and mastic. Bathrooms have ceramic tile and grout on the walls and floors. The occupants of this building have recently remodeled (still in-progress) the interior of this building.
The building was split up into three areas; the office area, the annex area and the attic area. The office area is represented by the main section of the building and includes offices, a kitchen, restroom, a fitness room and locker room. The annex area is attached on the east side to the office area and includes classrooms and a conference room. The attic area is located above the main office area. Homogenous materials were identified in each section and sampled accordingly.
2.0 FINDINGS
Six homogenous materials were identified in the assessment areas with a total of 6 samples being analyzed by the laboratory. Samples that exceed the EPA-defined asbestos containing material (ACM) level of 1.0% by polarized light microscopy (PLM) testing are summarized in Table 1 for all areas. Table
2 identifies all samples taken in each area that according to laboratory results do not contain asbestos.
The laboratory report shown in Appendix C contains the PLM results for all the suspect ACM samples collected from the building.
TABLE 1
ACM SAMPLE SUMMARY
Sample No. Material Description
Material Locations and Room Condition (G, P, or S)
Analytical Result
(% ACM)
Quantity (Sq.
Ft. or Lin. Ft.)
Friable (Yes/No)
Material Condition (G, P, or S) and Potential for
Disturbance (L, M, or H)
860-115-NF-CA
Yellow/Black Mastic under
Carpet
Throughout the office area of the building* – G 2% - Chry 7,740 Sq. Ft. No G – L
NA TSI - Joints Throughout the attic area of the building – G PACM Unknown Yes G – L
Notes:
ACM Asbestos-containing material PACM Presumed asbestos-containing material Chry Chrysotile asbestos Sq. Ft. Square feet Lin Ft Linear feet NA Not applicable G Good Condition P Poor Condition S Significant Damage L Low Possibility of Disturbance M Medium Possibility of Disturbance H High Possibility of Disturbance
* Sample number 860-115-NF-CA was taken as a carpet adhesive material sample, but it is this assessors professional opinion that the 2% Chry lab result is not the carpet adhesive, but mastic residue mixed in with the carpet adhesive left on the concrete from 9” x 9” floor tile taken out during a renovation that had asbestos present as stated in a previous survey.
Based on survey observations or the sample analytical results, Tetra Tech recommends removal of all
ACM listed in Table 1 by a licensed asbestos abatement contractor before any work disturbs the materials. If the ACM is not disturbed during any renovation processes, the ACM may be left in place.
TABLE 2
NON-ACM SAMPLE SUMMARY
Figure ID Number* Sample No. Material Description Analytical Result
(% ACM)
1 860-11-NW-CBM Cove Base Mastic ND 2 860-113-EW-CT Ceiling Tile ND 3 860-113-EW-DW Drywall ND 4 860-111-NW-SC Skim Coat ND 5 860-E-NW-WC Window Caulk ND
Notes:
ACM Asbestos-containing material ND Non-Detect for Asbestos
* This ID number corresponds to the ID numbers listed on the figure identifying where the sample was taken.
Based on these sample analytical results, Tetra Tech recommends no further action be taken if the non-
ACMs listed in Table 2 are disturbed.
3.0 ASSUMPTIONS AND DEVIATIONS
The following suspect and/or assumed ACMs were identified but not sampled for one or more of the following reasons: limitations on access; limitation on destructive sampling in a specific area because of use; prospect of damage unable to be repaired, thus leaving the possibility of a future asbestos fiber release; or previous analytical reports identifying the material as containing asbestos (PACM).
• Destructive Sampling Limitations: Stucco on the exterior walls; joint compound associated with the drywall in the office area; possible electrical wiring wrap throughout all areas of the building (safety issue); and ceramic tile and associated grout and mastic in the office area, specifically the bathrooms.
• PACM: Thermal system insulation (TSI) in the attic area on the joints of the domestic water pipes.
• Limitations on Access: The annex area was not accessible; all three rooms were occupied and were not to be disturbed.
The previous survey identifies the following materials as containing asbestos; the current survey did not identify these materials. Renovations have occurred since the previous survey; therefore the materials may have been removed.
• 9x9 floor tile and associated mastic in the office area
The roof was not accessible but appeared to be covered with gravel, a previous survey indicated that roofing sealant was present and contained asbestos. The previous survey also indicates that the wallboard in rooms 104 and 105 of the annex area contains 2% chrysotile asbestos. This area was inaccessible due to a class in session.
Samples of the suspect ACMs not sampled during this survey should be taken by a licensed asbestos inspector, prior to any disturbance of the materials to determine if the material contains asbestos.
APPENDIX A
FIGURES
Figure 1 Building 860
X :\S
\0
0\
FH
\F ig ur e1 _8
.F
H
Asbestos Survey Vandenberg Air Force Base near Lompoc, California
Date: 01/30/09 Drawn By: Ingrid Tobar Project No: 103I0770.001
Not to Scale
Legend
Asbestos Containing Material Sample Location Non-asbestos Containing Material (sample number corresponds to sample’s taken listed in Table 2 of the report, that do not contain asbestos) Pressumed Asbestos Containing Materials PACM (TSI-Joints)
PACM
Classroom 1
860-115-NF-CA
(Mastic from previous 9x9 floor tile)
Classroom 2
Conference Room
Training Simulator Room
Men’s Restroom
Women’s Restroom
Physical Fitness Room
Crew Office
Supt’s Office
Dayroom
Kitchen
Tool Room
Supply Room
Locker Room
APPENDIX B
PHOTOLOG
Asbestos Survey Report Building No. 860
Vandenberg Air Force Base, California
TETRA TECH
This photograph shows the carpet over previously abated 9” x 9” floor tile and mastic in the physical fitness room 115 of the office area that has asbestos present mixed in with the carpet adhesive.
Date 1/27/09
DESCRIPTION
APPENDIX C
LABORATORY REPORTS AND CHAIN-OF-CUSTODY FORMS
| 1.0 SITE STRUCTURE |
| 2.0 FINDINGS |
| 3.0 ASSUMPTIONS AND DEVIATIONS |