This Statement of Work (SOW) details requirements for the 60th Civil Engineer Squadron's Medium Shelter System (MSS) and Electrical Distribution System (EDS) to support Prime BEEF training and exercises. The procurement includes a 30'W x 52'L x 15'H medium shelter system with specific components such as mil-spec vinyl cover, insulated end panels, flooring system, equipment and personnel doors, windows, ECU ports, LED lighting, and a 30kW diesel generator. The electrical system encompasses four primary distribution panels (25kW, 30kW, and 200kW) with various power input/output specifications, and one secondary distribution center with complex power input/output characteristics supporting multiple voltage and frequency configurations.
Key technical requirements include operating temperature ranges from -25°F to +125°F, ability to accept and distribute 120/208 VAC power, specific circuit breaker configurations, and comprehensive power distribution capabilities. The SOW specifies a brand name or equal requirement, with the Alaska Medium Shelter System (Part # AK-3052-MSS-2) as the reference model. Additional procurement terms include included freight and handling, no mandatory vendor training, and a minimum 12-month equipment warranty. The overall objective is to provide deployable shelter and power distribution equipment that enables realistic training for Airmen in expeditionary environments.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
9/19/2025 Rev 2
Statement of Work
For
60 CES/CEX Medium Shelter System and Electrical Distribution System
Description: The 60th Civil Engineer Squadron requires a Medium Shelter System (MSS) and an Electrical Distribution System (EDS) to support Prime BEEF training and exercises. Together, these systems provide deployable shelter capability and safe, reliable power distribution, enabling realistic training and mission readiness.
Currently, the squadron has neither medium shelters nor an organic power distribution system, creating a critical gap in preparing Airmen for expeditionary requirements. Prime BEEF teams are expected to be subject matter experts in the setup, operation, and sustainment of both MSS and EDS equipment.
Without access to these systems, Airmen cannot receive the hands-on training needed to build proficiency in shelter deployment, power distribution, and sustainment of operations in austere environments.
POC: 1Lt Daniel Cunningham
This is a brand name or equal requirement.
Medium Shelter System
- Alaska Medium Shelter System Part # AK-3052-MSS-2
Primary Distribution Panels
- 25K Part # PDSYS-PDP-25
- 30K Part # PDSYS-PDP-30
- 200K Part # PDSYS-PDP-200
Secondary Distribution Center (SDC)-2/20
- Part # PDSYS-SDC-150-2/200
The contractor shall provide the above brand name or an equal item following the below specifications:
1. Equipment.
1.1. Must include:
1.1.1. 1x Medium Shelter System 30’W x 52’L x 15’H
1.1.1.1. Mil-spec vinyl cover
1.1.1.2. Insulated end panels
1.1.1.3. Integrated liner system
1.1.1.4. Flooring system
1.1.1.5. (2) 11ft wide x 10.5ft high equipment doors
1.1.1.6. (2) 32in wide x 80in high personnel doors
1.1.1.7. 30in wide x 42in high windows
1.1.1.8. (4) ECU ports and plenums sets
1.1.1.9. LED high bay lighting kit
1.1.1.10. (1) 60-amp power distribution box with 24 outlets
1.1.1.11. (1) 100ft 60-amp power cable with Class L connectors
1.1.1.12. (1) installation kit that includes ladders, sledgehammers, come-a-longs, and anchoring equipment.
1.1.1.13. (2) 5-Ton Environmental Control Units
1.1.1.14. (1) cart mounted 30kW Diesel Generator
1.1.1.15. (1) Storage container that must be fork-liftable, stackable, and made from a durable long-lasting material.
1.1.2. (4) Primary Distribution Panel (PDP), 25kW
1.1.2.1. Dimensions: Width: 18in, Length: 23in, Height: 18in
1.1.2.2. Operating Temperature Range: -25°F to +125°F
1.1.2.3. Storage Temperature: -65°F to +150°
1.1.2.4. Accepts power at 120/208 VAC, 3-phase, 60-amp connectors
1.1.2.5. Distributes at 120/208 VAC 3-phase and 120 VAC 1-phase
1.1.2.6. Input: One 60-amp, 4-pole, 5-wire connector and is protected by an appropriately sized main circuit breaker.
1.1.2.7. Output: One 60-amp, 4-pole, 5-wire, output connector, one 15-amp (NEMA 5-15R), and four 20-amp (NEMA L5-20R) receptacles. The output connector and receptacles are protected by an appropriately sized circuit breaker.
1.1.2.8. Thermal magnetic circuit breakers, 3-phase circuit breakers need to be 3-pole, molded case, common trip with a single operating toggle.
1.1.2.9. Must provide power to equipment requiring 120/208 VAC power
1.1.3. (1) Power Distribution Panel (PDP), 30kW
1.1.3.1. Dimensions: Width: 18in, Length: 36in, Height: 18in
1.1.3.2. Operating Temperature Range: -25°F to +125°F
1.1.3.3. Storage Temperature: -65°F to +150°
1.1.3.4. Accepts power at 120/208 VAC, 3-phase, 100-amp Class-L connectors
1.1.3.5. Distributes at 120/208 VAC 3-phase and 120 VAC 1-phase
1.1.3.6. Input: One 100-amp, 4-pole, 5-wire connector and is protected by an appropriately sized main circuit breaker.
1.1.3.7. Output: Two 60-amp, 4-pole, 5-wire, output connector and five 20-amp (NEMA L5-20R) receptacles.
1.1.3.8. Thermal magnetic circuit breakers, 3-phase circuit breakers need to be 3-pole, molded case, common trip with a single operating toggle, and 1-phase circuit breakers need to be single pole, molded case, with a single operating toggle.
1.1.3.9. Must provide power to equipment requiring 120/208 VAC power
1.1.4. 1.1.2. (1) Primary Distribution Panel (PDP), 200kW
1.1.4.1. Dimensions: Width: 32in, Length: 75in, Height: 33in
1.1.4.2. Operating Temperature Range: -25°F to +125°F
1.1.4.3. Storage Temperature: -65°F to +150°
1.1.4.4. Accepts power at 120/208 VAC, 3-phase, 400-amp input terminals
1.1.4.5. Distributes at 120/208 VAC 3-phase using an 800 Amp bus to individual breaker and output connectors.
1.1.4.6. Input: Two 400-amp, rated input terminals for a 3-phase, 5-wire input termination. Must be protected by appropriately sized main circuit breaker that is mechanically interlocked with the other so only one input may be closed at a time.
1.1.4.7. Output: Six 100-amp and eight 60-amp outputs, each a 120/208 VAC, 3-phase MIL-C-22992 style receptacle with protective cover. The output receptacles are protected by an individual, appropriately sized circuit breaker.
1.1.4.8. Thermal magnetic circuit breakers, 3-phase circuit breakers need to be 3-pole, molded case, common trip with a single operating toggle.
1.1.4.9. Must provide power to equipment requiring 120/208 VAC power
1.1.5. (1) Secondary Distribution Center (SDC)
1.1.5.1. Dimensions: Width: 48in, Length: 61in, Height: 72in
1.1.5.2. Operating Temperature Range: -25°F to +125°F
1.1.5.3. Storage Temperature: -65°F to +150°
1.1.5.4. Output Connections:
1.1.5.4.1. Output Convenience Receptables: (2) 15-Amp
1.1.5.4.2. MEP Input Connectors: (1) 200-Amp
1.1.5.4.3. Load break Elbow Input Connectors: (9) 200-Amp
1.1.5.5. Power Characteristics
1.1.5.5.1. Input: 4160VAC/3-phase/60Hz
3800VAC/3-phase/50Hz
208YVAC/3-phase/60Hz
1.1.5.5.2. Output: 208Y/120VAC/3-phase, 60/50Hz 3-wire
208Y/120VAC/3-phase, 60/50Hz 4-wire
1.1.5.5.3. Power Ratings: 150kVA; 416 Amps
2. All freight and handling must be included.
3. No vendor training required.
4. Equipment warranty (12-months or greater) must be included
| Medium Shelter System |
| Primary Distribution Panels |
| Secondary Distribution Center (SDC)-2/20 |
| 1.1.1. 1x Medium Shelter System 30’W x 52’L x 15’H |
| 1.1.2. (4) Primary Distribution Panel (PDP), 25kW |
| 1.1.3. (1) Power Distribution Panel (PDP), 30kW |
| 1.1.4. 1.1.2. (1) Primary Distribution Panel (PDP), 200kW |
| 1.1.5. (1) Secondary Distribution Center (SDC) |