(ANS) XDAT 14-11031 PRE-BID 03 Multiple Conduits on exterior.pdf
PDF 243 KB Posted
- Attached to
- Repair Fuel System Generators Federal contract opportunity
- Solicitation number
- FA442721R0012
About this file
This document contains a request for information (RFI) related to a federal contract for repairing fuel systems generators. The RFI provides clarification on conduit details shown on sheets A2.0 and E3.3, detail 2 of the contract drawings. Specifically, it addresses conduits that will replace conduits that cannot be reused for the repair of fuel systems generators under Solicitation Number FA442721R0012 from the Department of the Air Force Air Mobility Command. A mandatory site visit is scheduled for February 23, 2021 at 9:00AM PST to inspect the work sites. Attendees must RSVP by February 22 at 4:00PM and provide identification and contact information for base access.
View the file
Other files for this federal contract opportunity
Show all 50
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Please wait...
If this message is not eventually replaced by the proper contents of the document, your PDF viewer may not be able to display this type of document.
You can upgrade to the latest version of Adobe Reader for Windows®, Mac, or Linux® by visiting http://www.adobe.com/go/reader_download.
For more assistance with Adobe Reader visit http://www.adobe.com/go/acrreader.
Windows is either a registered trademark or a trademark of Microsoft Corporation in the United States and/or other countries. Mac is a trademark of Apple Inc., registered in the United States and other countries. Linux is the registered trademark of Linus Torvalds in the U.S. and other countries.
REQUEST FOR INFORMATION
DATE
ACTIVITY ID
CONTRACT TITLE
CONTRACT NO
RFI NO
RFI SUBJECT
DWG NO
DWG DETAIL
DWG SHEET NO
SPEC SECTION
SPEC PARAGRAPH
SPEC PAGE NO
RFI PRIORITY?
POTENTIAL TIME/COST?
SCHEDULE REFERENCED?
CRITICAL PATH?
4296/2C (9/98)
SHEET
of
CONTRACTOR QUESTION AND PROPOSED SOLUTION
RFI QUESTION/ISSUE:
CONTRACTOR PROPOSED SOLUTION:
DATE
CONTRACTOR/PROJECT MANAGER
NOTE: If the determination of this RFI is "Answered - No Cost" then this reply is given with the expressed understanding that it does not constitute a basis for any change in the amount or time of subject contract. Information provided in this response does not authorize work not currently included in the contract. If determination of this RFI is "Answered - Pending PCO" then this response may require a change to the contract.
ANSWERS AND COMMENTS
RFI REASON CODE
RFI ACTION
COMMENTS FOR DETAILED REVIEWER:
DETAILED REVIEWER 1 RECOMMENDED RFI SOLUTION:
DETAILED REVIEWER 1 NAME/SIGNATURE
TITLE
RESPONSE DATE
DETAILED REVIEWER 2 RECOMMENDED RFI SOLUTION:
DETAILED REVIEWER 2 NAME/SIGNATURE
TITLE
RESPONSE DATE
RFI RESPONSE:
DATE
GOVERNMENT CONSTRUCTION MANAGER
8.0.1291.1.339988.308172
| DateTimeField2: 2021-02-25 |
| activityID: |
| contractTitle: REPAIR FUEL SYSTEMS GENERATORS |
| Enter Cnt # Here: XDAT 14-1031 |
| rfiNo: Pre-Bid 03 |
| rfiSubject: MULTIPLE CONDUITS |
| dwgNo: |
| dwgDetail: |
| dwSheetNo: |
| specSection: |
| specParagraph: |
| specPageNo: |
| : |
| PageNumber: |
| TextField: At both sites, there are multiple conduits on the exterior of the building installed for an explosive environment. Is there any classification level around the buildings, i.e. Class 1, Div. 2? |
| TextField: |
| TextField: Details on the conduits that will replace conduits that cannot be reused are detailed on sheet A2.0 and sheet E3.3, detail 2. |
| SignatureField1: |
| DateTimeField1: 2021-02-25 |
| rfiReason: |
| SignatureField3: |
| TextField1: |
| SignatureField2: |
File details come from the government source that posted it. Updated .