This document outlines a federal contract solicitation for repair services. The Department of the Air Force Air Mobility Command is seeking to engage a contractor to provide all materials, labor, supervision and equipment to complete Repair Fuel System Generators at a specified location. A mandatory site visit is scheduled for February 23, 2021 at 9:00AM PST, and interested parties must RSVP in advance. No more than two individuals from each company will be permitted to attend the site visit, and all attendees must comply with COVID-19 safety protocols including wearing face masks. The solicitation number is FA442721R0012 and responses are due based on the terms outlined in the document.
View the file
Other files for this federal contract opportunity
Show all 50
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
+4'-6" AFF
POWER LEGEND AND SYMBOLS
SYMBOL
MOUNTING HEIGHT FROM FINISHED FLOOR TO CENTERLINE OF
OUTLET OR EQUIPMENT. FOR LIGHT FIXTURES, IT IS TO BOTTOM OF
FIXTURE.
DESCRIPTION
UTILITY COMPANY PULL SECTION LUGS
GROUNDING CONNECTION TO MAIN BUILDING GROUND SYSTEM U.O.N.
CURRENT TRANSFORMER
MOLDED CASE SHUNT TRIP CIRCUIT BREAKER
DO NOT SCALE DRAWINGS
CONDUIT TURNED DOWN
CONDUIT TURNED UP
CONDUIT STUBBED AND CAPPED; LOAD BANK CONNECTED
RACEWAY CONCEALED IN WALLS OR ABOVE CEILING
UTILITY METER WITH CURRENT TRANSFORMERS (CT'S)
TRANSFORMER WITH SECONDARY GROUND
ON-SITE GENERATOR SET
OR
200-S
MOLDED CASE DRAW OUT TYPE POWER CIRCUIT BREAKER
GROUND ROD/WELL
SOLENOID KEY RELEASE UNIT
POWER METER
POWER QUALITY METER. SQAURE D PM500 SERIES.
CURRENT SENSOR
VOLTAGE SENSOR
MOLDED CASE CIRCUIT BREAKER
KIRK KEY
SYMBOL DESCRIPTION
OR
EXISTING (DASH INDICATES) ELECTRICAL EQUIPMENT
DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS)
MOUNTED +15" A.F.F. TO CENTER LINE U.O.N.
3/4" CONDUIT WITH 2 #12 & 1 #12 GND WIRES
3/4" CONDUIT WITH 3 #12 & 1 #12 GND WIRES
3/4" CONDUIT WITH 4 #12 & 1 #12 GND WIRES
3/4" CONDUIT WITH 5 #12 & 1 #12 GND WIRES
A-1,3
EQUIPMENT
ID. NO.
SHEET NO.
DETAIL NO.
EQUIPMENT REFERENCE
DETAIL REFERENCE
POWER LEGEND AND SYMBOLS
DESCRIPTIONSYMBOL DESCRIPTION
NOTE TO CONTRACTOR
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST CALIFORNIA CODE OF
REGULATIONS (CCR), NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL
CODES AND REGULATIONS.
2. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN
COMPLIANCE TO UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN.
3. WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE
INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND MAKE
FINAL CONNECTION AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING ELECTRICAL
CONNECTIONS.
5. LOCATION OF LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS. AT OR NEAR DOORS, INSTALL SWITCHES ON SIDE OPPOSITE TO DOOR HINGE. VERIFY FINAL HINGE LOCATION IN
FIELD PRIOR TO ANY WORK.
6. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND
WORK INCLUDED. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OR OTHER
TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN
HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES.
7. FURNISH APPROVED EXPANSION FITTINGS WHERE RACEWAY CROSSES BUILDING EXPANSION
JOINTS.
8. FURNISH PULL STRING IN EACH RACEWAY RUN OVER 10' IN LENGTH, IN WHICH PERMANENT
WIRING IS NOT INSTALLED.
9. PROVIDE PULL BOXES WHEREVER NECESSARY TO FACILITATE PULLING OF CONDUCTORS.
COORDINATE LOCATIONS OF BOXES WITH OTHER TRADES TO AVOID CONFLICT. PULL BOXES
SHALL BE ACCESSIBLE. THE SIZE OF PULL BOX SHALL COMPLY WITH N.E.C. REQUIREMENTS.
10. ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED
TO OUTSIDE ENVIRONMENT (UP TO 16') SHALL BE WEATHERPROOF TYPE, NEMA 3R.
11. NO CONDUIT RUNS SHALL BE ALLOWED IN CONCRETE SLABS. ALL CONDUITS WILL BE PLACED
ABOVE ACCESSIBLE CEILING SPACES UNLESS SPECIFICALLY INDICATED TO BE UNDERGROUND.
12. DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE
DIRECTLY ON EQUIPMENT, PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY.
13. ALL ELECTRICAL POWER OR SIGNAL WIRING IN FIRE RATED WALL IS TO BE INSTALLED IN A
METALLIC CONDUIT SYSTEM.
14. ALL ELECTRIC MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL"
LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT.
15. ALL DISTRIBUTION AND CONTROL EQUIPMENT (SUCH AS CB'S, SWITCHES, CONTACTORS, ETC.), TERMINATIONS SHALL BE FULLY RATED PER UL AS FOLLOWS:
A. 125A OR LESS : 60°C OR MORE;
B. MORE THAN 125A : 75°C OR MORE.
16. NO MC, BX, OR FLEX CABLE WILL BE ALLOWED (UNLESS PRIOR APPROVAL IS GRANTED); AS A
STANDARD, FLEX AND MC MUST BE ACCESSIBLE ON BOTH ENDS FOR REMOVAL AND SERVICE,
IF THEY WILL BE USED.
17. ALL RECEPTACLE OUTLETS TO BE SPECIFICATION GRADE - 125V 20AMP.
18. STANDARD COLOR FOR ALL SWITCHES AND RECEPTACLES TO BE IVORY.
19. ALL SWITCH AND RECEPTACLE FACE PLATES TO BE BRUSHED (SATIN) STAINLESS STEEL U.O.N.
CONTRACTOR SHALL LABEL EACH RECEPTACLE AND SWITCH WITH PANEL & BREAKER NUMBER
FROM WHICH IT IS FED FROM.
20. ALL CONDUIT SHALL BE 3/4" MIN. NON-METALLIC CONDUIT IS NOT ALLOWED IN INTERIOR
SPACES.
21. CONDUCTORS SHALL HAVE UNDERWRITER'S LABORATORIES, INC.(UL) LISTED, 600 VOLT
INSULATION OF TYPE SPECIFIED BELOW OR ELSEWHERE IN THE SPECIFICATIONS.
CONDUCTORS SHALL BE COPPER.
1. BRANCH CIRCUITS - LIGHTING AND POWER.
A. #10 AWG AND SMALLER, SOLID WIRE TYPE THW OR THHN/THWN, THHW(THHN FOR DRY
LOCATION ONLY).
B. #8 AWG TO #2 AWG, STRANDED TYPE THW OR THHN/THHW.
C. #1 AWG AND LARGER, STRANDED TYPE XHHW.
2. FEEDERS : TYPE THW OR THHN/THWN, OR XHHW.
22. PROVIDE GREEN INSULATED GROUNDING CONDUCTOR IN EACH RACEWAY INCLUDING
CONDUITS, PLUG STRIPS, WIREMOLD. SIZE OF GROUNDING SHALL BE IN ACCORDANCE WITH
NATIONAL ELECTRIC CODE ARTICLE 250.
23. WIRING METHOD SHALL BE EMT ABOVE GROUND AND MOUNTED IN CONCEALED SPACES AND
SCHEDULE-40 PVC FOR UNDERGROUND INSTALLATION. USE RIGID WHEN ENCASED IN
CONCRETE OR SUSCEPTIBLE TO DAMAGE.
24. CONTRACTOR TO USE THE FOLLOWING CONDUCTOR SIZES FOR BRANCH CIRCUITS:
#10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER THAN 75 FEET.
#10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER THAN 200 FEET.
GENERAL NOTES
SHEET DETAIL IS
SHOWN ON
SHEET FROM WHICH
DETAIL IS REFERENCED
15KV 6-WAY PADMOUNT SWITCH
PHOTO REFERENCE.
SHEET FROM WHICH PHOTO
IS REFERENCED
VIEW DIRECTION
OF PHOTO
DETAIL REFERENCE.
DETAIL NUMBER ON
SHEET
PHOTO NUMBER
ON SHEET
SHEET PHOTO
IS SHOWN ON
1FEEDER SCHEDULES
600V FEEDER SCHEDULE 1Ø 3W
SETSTYPELABEL PHASE GROUNDNEUTRAL CONDUIT
1 2 # 12
1 2 # 10
1 2 # 8
1 2 # 6
1 2 # 6
1 2 # 4
1 2 # 4
1 2 # 2
1 2 # 1
1 2 # 1
20A-3W
200A-3W
175A-3W
150A-3W
125A-3W
100A-3W
80A-3W
60A-3W
50A-3W
30A-3W
40A-3W
70A-3W
90A-3W
2 # 1/0
2 # 2/0
2 # 3/0
1 # 12
1 # 6
1 # 6
1 # 6
1 # 6
1 # 8
1 # 8
1 # 10
1 # 10
1 # 10
1 # 10
1 # 8
1 # 8
3/4"
3/4"
1"
1"
1"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
2"
2"
1 # 12
1 # 10
1 # 10
1 # 6
1 # 6
1 # 4
1 # 4
1 # 2
1 # 1
1 # 1
1 # 1/0
1 # 2/0
1 # 3/0
1-1/4"
1-1/2"
NOTE:
ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THE AMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).
20-B
30-B
40-B
50-B
60-B
70-B
80-B
90-B
100-B
125-B
150-B
175-B
200-B
SETSTYPELABEL PHASE GROUND CONDUIT
1 3 # 12 3/4"
1 3 # 10 3/4"
1 3 # 8 1"
1 3 # 6
1 3 # 6
1 3 # 4
1 3 # 4
1 3 # 2
1 3 # 1
1 3 # 1
3 # 250 KCM
1600A-4W
4000A-4W
1000A-4W
700A-4W
600A-4W
500A-4W
450A-4W
20A-4W
3000A-4W
2000A-4W
2500A-4W
800A-4W
1200A-4W
400A-4W
350A-4W
300A-4W
250A-4W
225A-4W
200A-4W
175A-4W
150A-4W
125A-4W
100A-4W
80A-4W
60A-4W
50A-4W
30A-4W
40A-4W
70A-4W
90A-4W
3 # 1/0
3 # 2/0
3 # 3/0
3 # 4/0
3 # 350 KCM
3 # 500 KCM
3 # 600 KCM
3 # 250 KCM
3 # 350 KCM
3 # 500 KCM
3 # 600 KCM
3 # 500 KCM
3 # 600 KCM
3 # 600 KCM
3 # 600 KCM
3 # 600 KCM
3 # 600 KCM
3 # 600 KCM
3 # 4/0
1"
1"
1"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
1-1/2"
1 # 4/0
1#500KCM
1 # 2/0
1 # 1/0
1 # 1/0
1 # 2
1 # 2
1 # 12
1#500KCM
1#250KCM
1#350KCM
1 # 1/0
1 # 3/0
1 # 2
1 # 2
1 # 4
1 # 4
1 # 4
1 # 6
1 # 6
1 # 6
1 # 6
1 # 8
1 # 8
1 # 10
1 # 10
1 # 10
1 # 10
1 # 8
1 # 8
4"
4"
4"
4"
4"
3"
3"
4"
4"
4"
4"
4"
4"
4"
3"
2 1/2"
2 1/2"
2"
2"
NEUTRAL
1 # 12
1 # 10
1 # 10
1 # 6
1 # 6
1 # 4
1 # 4
1 # 2
1 # 1
1 # 1
1 # 250 KCM
1 # 1/0
1 # 2/0
1 # 3/0
1 # 4/0
1 # 350 KCM
1 # 500 KCM
1 # 600 KCM
1 # 4/0
1 # 250 KCM
1 # 350 KCM
1 # 500 KCM
1 # 600 KCM
1 # 500 KCM
1 # 600 KCM
1 # 600 KCM
1 # 600 KCM
1 # 600 KCM
1 # 600 KCM
1 # 600 KCM
600V FEEDER SCHEDULE 3Ø 4W
20-Y
30-Y
40-Y
50-Y
60-Y
70-Y
80-Y
90-Y
100-Y
125-Y
150-Y
175-Y
200-Y
225-Y
250-Y
300-Y
350-Y
400-Y
450-Y
500-Y
600-Y
700-Y
800-Y
1000-Y
1200-Y
1600-Y
2000-Y
2500-Y
3000-Y
4000-Y
NOTE:
ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THE AMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).
600V FEEDER SCHEDULE 3Ø 3W
SETSTYPELABEL PHASE GROUNDNEUTRAL CONDUIT
1 3 # 12
1 3 # 10
1 3 # 8
1 3 # 6
1 3 # 6
1 3 # 4
1 3 # 4
1 3 # 2
1 3 # 1
1 3 # 1
3 # 250 KCM
1600A-3W
4000A-3W
1000A-3W
700A-3W
600A-3W
500A-3W
450A-3W
20A-3W
3000A-3W
2000A-3W
2500A-3W
800A-3W
1200A-3W
400A-3W
350A-3W
300A-3W
250A-3W
225A-3W
200A-3W
175A-3W
150A-3W
125A-3W
100A-3W
80A-3W
60A-3W
50A-3W
30A-3W
40A-3W
70A-3W
90A-3W
3 # 1/0
3 # 2/0
3 # 3/0
3 # 4/0
3 # 350 KCM
3 # 500 KCM
3 # 600 KCM
3 # 250 KCM
3 # 350 KCM
3 # 500 KCM
3 # 600 KCM
3 # 500 KCM
3 # 600 KCM
3 # 600 KCM
3 # 600 KCM
3 # 600 KCM
3 # 600 KCM
3 # 600 KCM
3 # 4/0
1 # 4/0
1#500KCM
1 # 2/0
1 # 1/0
1 # 1/0
1 # 2
1 # 2
1 # 12
1#500KCM
1#250KCM
1#350KCM
1 # 1/0
1 # 3/0
1 # 2
1 # 2
1 # 4
1 # 4
1 # 4
1 # 6
1 # 6
1 # 6
1 # 6
1 # 8
1 # 8
1 # 10
1 # 10
1 # 10
1 # 10
1 # 8
1 # 8
3/4"
3/4"
1"
1"
1"
1"
1-1/4"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
4"
4"
4"
4"
4"
3"
3"
4"
4"
4"
4"
4"
4"
4"
3"
2 1/2"
2 1/2"
2"
2"
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
20-D
30-D
40-D
50-D
60-D
70-D
80-D
90-D
100-D
125-D
150-D
175-D
200-D
225-D
250-D
300-D
350-D
400-D
450-D
500-D
600-D
700-D
800-D
1000-D
1200-D
1600-D
2000-D
2500-D
3000-D
4000-D
NOTE:
ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THE AMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).
600V FEEDER SCHEDULE 1Ø 2W
SETSTYPELABEL PHASE GROUNDNEUTRAL CONDUIT
1 2 # 12
1 2 # 10
1 2 # 8
1 2 # 6
1 2 # 6
1 2 # 4
1 2 # 4
1 2 # 2
1 2 # 1
1 2 # 1
20A-2W
200A-2W
175A-2W
150A-2W
125A-2W
100A-2W
80A-2W
60A-2W
50A-2W
30A-2W
40A-2W
70A-2W
90A-2W
2 # 1/0
2 # 2/0
2 # 3/0
1 # 12
1 # 6
1 # 6
1 # 6
1 # 6
1 # 8
1 # 8
1 # 10
1 # 10
1 # 10
1 # 10
1 # 8
1 # 8
3/4"
3/4"
1"
1"
1"
1"
1-1/4"
1-1/4"
1-1/4"
1-1/2"
1-1/2"
2"
2"
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
20-S
30-S
40-S
50-S
60-S
70-S
80-S
90-S
100-S
125-S
150-S
175-S
200-S
NOTE:
ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THE AMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).
GROUNDING CONNECTION AT SWITCHGEAR/DISTRIBUTION BOARD
WITH NEUTRAL BONDING.
SOLID STATE DEVICE CONNECTED TO THE POWER DISTRIBUTION
SYSTEM
GROUND FAULT PROTECTION DEVICE CONNECTED TO THE POWER
DISTRIBUTION SYSTEM
TRANSIENT VOLTAGE SURGE SUPPRESSION
UL 1449, 3RD EDITION
CONDUIT WIRING DESCRIPTION PER FEEDER SCHEDULE ON OTHER
PLAN
CONCRETE ELECTRICAL PULL BOX WITH LID APPROPRIATE FOR
INSTALLATION LOCATION. LID SHALL BE LABELED "ELECTRICAL" OR
"COMM" ACCORDING TO USE.
CONDUIT UNDERGROUND IN SCHEDULE - 40 PVC UNLESS NOTED
OTHERWISE. VERIFY DEPTH AND TRENCHING WITH G.C.
DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS,
GFCI TYPE) MOUNTED +15" A.F.F. TO CENTER U.O.N.
WEATHERPROOF DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20
AMPS, 125 VOLTS) MOUNTED +15" A.F.F. TO CENTER LINE U.O.N.
SURFACE MOUNTED DUPLEX RECEPTACLE OUTLET, CONVENIENCE.
(20 AMPS, 125 VOLTS) MOUNTED +15" A.F.F. TO BOTTOM OF DEVICE
U.O.N.
ABOVE CEILING, CONCEALED, JUNCTION BOX, WITH COVER, PER
NATIONAL ELECTRICAL CODE (NEC) TABLE 370-b(a), 4" SQUARE DEEP, WITH PLASTER RING.
RECESSED WALL MOUNTED JUNCTION BOX, WITH COVER, PER
NATIONAL ELECTRICAL CODE (NEC) TABLE 370-b(a), 4" SQUARE DEEP, WITH PLASTER RING.
BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE.
(SURFACE MOUNTED)
MAIN SWITCHBOARD, POWER OR LIGHT, FLOOR STANDING
ENCLOSURE, (SEE SINGLE LINE DIAGRAM AND LOAD SUMMARY)
DISCONNECT SWITCH H.P. RATED 600 VOLTS RATED. "F" INDICATES
FUSE TYPE. FUSES PER APPROVED MANUFACTURERS SHOP
DRAWINGS.
COMBINATION STARTER DISCONNECT SWITCH H.P. RATED 600 VOLTS
RATED. "F" INDICATES FUSE TYPE. FUSES PER APPROVED
MANUFACTURERS SHOP DRAWINGS.
HOMERUN TO CIRCUITS #1 AND #3 IN PANEL "A". (CROSSMARKS
INDICATE NUMBER OF PHASES AND NEUTRAL. PROVIDE GROUND
WIRE.)*
3/4" CONDUIT WITH 2 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE
SIZE)
3/4" CONDUIT WITH 3 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE
SIZE)
REMOTE CONTROLLED, ELECTRONICALLY OPERATED CIRCUIT
BREAKER
CONTRACTOR SHALL VERIFY PLANS AND EXISTING DIMENSIONS AND CONDITIONS ON THE JOB
SITE AND SHALL IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES
BEFORE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR THE SAME.
GENERAL DEMOLITION NOTES
1. THE DEMOLITION NOTE REFERENCE PERTAINS TO ALL RELATED SHEETS WHERE EXISTING ELECTRICAL WORK IS INDICATED.
2. THE CONTRACTOR SHALL VISIT THE PROJECT SITE AND MAKE THEMSELVES COMPLETELY FAMILIAR WITH THE EXISTING INSTALLED CONDITIONS.
3. ALL EQUIPMENT OR WORK REQUIRED TO CARRY OUT THE DEMOLITION SCOPE OF WORK IS CONSIDERED TO BE PART OF THE CONTRACTOR SCOPE OF WORK. NO EXTRAS WILL BE CONSIDERED TO PERFORM THE REQUIRED WORK.
4. THE CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM PROJECT MANAGER PRIOR TO THE SCHEDULING OF ANY SHUTDOWN. SUCH PERMISSION MUST BE OBTAINED IN WRITING AND BE GRANTED AT LEAST 14 DAYS PRIOR TO ANY
SCHEDULED SHUTDOWN.
5. DISPOSITION OF EQUIPMENT:
DEMOLISHED EQUIPMENT SHALL BECOME THE PROPERTY OF THE INSTALLING CONTRACTOR AND SHALL BE DISPOSED IN ACCORDANCE WITH PRESIDENTIAL EXECUTIVE ORDER 13514. CONTRACTOR SHALL DISPOSE OF EQUIPMENT AND PROVIDE A CERTIFICATE OF DISPOSAL. CONTRACTOR TO PROVIDE DIGITAL HIGH RESOLUTION PHOTOGRAPH OF TAGS ON ALL EQUIPMENT PRIOR TO DEMOLITION OR REMOVAL FROM THE SITE.
6. THE CONTRACTOR SHALL REMOVE ALL CONDUITS AND CONDUCTORS SERVING DEVICES, PANELBOARDS, SWITCHBOARDS, ETC., WHICH ARE DESIGNATED AS EXISTING TO BE REMOVED, BACK TO THE SOURCE WHEN POSSIBLE. IF THE NATURE OF THE EXISTING INSTALLATION WILL NOT ALLOW REMOVAL OF CONDUIT, THE CONTRACTOR SHALL REMOVE ALL EXPOSED CONDUIT AND ABANDON THE REMAINDER AFTER REMOVING ALL CONDUCTORS ONLY WITH WRITTEN PERMISSION.
7. DEMOLITION AND/OR REMOVAL OF ELECTRICAL EQUIPMENT IN AREAS TO BE REMODELED SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
8. WHERE OUTLETS ARE REMOVED IN EXISTING WALL, REMOVE DEVICES, OUTLETS AND WIRING BACK TO PANELBOARD OR BACK TO NEAREST OUTLET WITH OTHER EXISTING LOAD TO REMAIN.
9. REMOVE ALL CONTROL PANELS, PULL-BOXES, TERMINAL CABINETS, ETC. FOR SYSTEMS TO BE DEMOLISHED EXCEPT WHERE ANY OF THE EXISTING DEVICES, SYSTEMS, CONSOLES, ETC. ARE TO BE REUSED FOR UPGRADE.
10. WHERE DEMO OF EXISTING ELECTRICAL EQUIPMENT IS SHOWN, ALL ASSOCIATED CONDUITS, CONDUCTORS, BOXES, AND ELECTRICAL DEVICES ARE TO BE REMOVED, U.O.N.
11. WHERE REMOVAL OF CONDUIT, PANELBOARDS AND ELECTRICAL DEVICES IS SHOWN, PROVIDE PATCH AND PAINT PER ARCHITECTURAL DETAILS AND SPECIFICATIONS.
12. CONTRACTOR TO INCLUDE RE-USE OR RECYCLING OPTIONS WHERE APPROPRIATE VICE DISPOSAL. THIS IS TO COMPLY WITH PRESIDENTIAL EXECUTIVE ORDER 13514 WHICH REQUIRES REDUCING DISPOSAL OF CONSTRUCTION AND DEMOLITION DEBRIS. CONTRACTOR TO DISPOSE OF ANY EXISTING ITEMS THAT MEET DEFINITION OF HAZARDOUS WASTE OR UNIVERSAL WASTE PER FEDERAL AND STATE ENVIRONMENTAL REGULATIONS.
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E0.1
ELECTRICAL LEGENDS & NOTES
GENERATOR LOAD CALCULATIONSGENERATOR STARTING CALCULATIONSABBREVIATIONS
A AMPERE
AF AMPERE FRAME RATING (CIRCUIT BREAKER)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFU AMPERE FUSE RATING (FUSE)
AIC AMPERE INTERRUPTING CAPACITY
AS AMPERE SWITCH RATING (FUSE)
AT AMPERE TRIP RATING (CIRCUIT BREAKER)
AWG AMERICAN WIRE GAUGE
BKBD BACKBOARD
BLDG BUILDING
BKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CFSD COMBINATION FIRE SMOKE DAMPER
CO CONDUIT ONLY
CONC CONCRETE
CT CURRENT TRANSFORMER
CU COPPER
CL CENTERLINE
DISC DISCONNECT
DSBN DISTRIBUTION SECTION
DN DOWN
DWG DRAWING
EA EACH
EC ELECTRICAL CONTRACTOR
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EXIST, (E) EXISTING
EXO EXTERNAL OPERABLE DISCONNECT
F FUSE
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FF FINISHED FLOOR
FG FINISHED GRADE
FLA FULL LOAD CURRENT
FLUOR FLUORESCENT
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HV HIGH VOLTAGE
IDF INTERMEDIATE DISTRIBUTION FRAME
IG ISOLATED/INSULATED GROUND
INCAND INCANDESCENT
ISC SHORT CIRCUIT CURRENT AVAILABLE IN RMS
SYMMETRICAL AMPERES
J-BOX JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KW KILOWATT
KV KILO VOLT
KVA KILO VOLT-AMPERE
LDC LOCAL DISTRIBUTION CABINET
LDF LOCAL DISTRIBUTION FRAME
LCL LONG CONTINUOUS LOAD
LTG LIGHTING
LV LOW VOLTAGE
MFR MANUFACTURER
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MH MANHOLE / METAL HALIDE
M/M METER AND MAIN SECTION
MULTI MULTI-METER SECTION
MV MEDIUM VOLTAGE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NEW (N) NEW, TO BE FURNISHED AND INSTALLED BY
CONTRACTOR
NF NON-FUSED
NIC NOT IN CONTRACT
N/L NIGHT LIGHT
NO NUMBER, NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
P POLE
PB PULL BOX
PF POWER FACTOR
PNL PANEL
POC POINT OF CONNECTION
PP POWER POLE
PWR POWER
PVC POLYVINYL CHLORIDE
QUAD QUADRUPLEX
QTY QUANTITY
REQD REQUIRED
REQMT REQUIREMENT
RGS RIGID GALVANIZED STEEL
RMC RIGID METALLIC CONDUIT
RM ROOM
RNC RIGID NONMETALLIC CONDUIT
SHT SHEET
SN SOLID NEUTRAL
SPEC SPECIFICATIONS
SPDT SINGLE POLE, DOUBLE THROW
SPST SINGLE POLE, SINGLE THROW
SW SWITCH
SWBD SWITCHBOARD
TC TIME CLOCK
TEL TELEPHONE
TERM TERMINAL
TP TEMPORARY POLE
TYP TYPICAL
UGPS UNDERGROUND PULL SECTION
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UON UNLESS OTHERWISE NOTED
V VOLT, VOLTAGE
VA VOLT-AMPERE
VFC VARIABLE FREQUENCY CONTROLLER
VFD VARIABLE FREQUENCY DRIVE
W WATT
WH WATT-HOUR
WP WEATHERPROOF
WT WEATHERTIGHT
WW WIREWAY
XP EXPLOSION PROOF
Z IMPEDANCE
4W FOUR-WIRE
3W THREE-WIRE
5S JUNCTION BOX
(4 11/16" SQUARED X2 1/8" DEEP)
Ø DIAMETER, PHASE
# NUMBER
°C DEGREE CELSIUS
(ETR) EXISTING TO REMAIN
(R) REMOVE EXISTING DEVICE AND ASSOCIATED
CONDUIT AND WIRE
(E) REMOVE EXISTING DEVICE.
REPLACE/RELOCATE AS SHOWN ON PLAN
(N) NEW LOCATION OF RELOCATED DEVICE
SEQUENCE OF OPERATIONS
NOTE: THE SEQUENCE OF OPERATIONS LISTED BELOW REPRESENTS A
GENERAL OVERVIEW OF HOW THE SYSTEM IS EXPECTED TO
OPERATE. THE ELECTRICAL EQUIPMENT MANUFACTURER SHALL
PROVIDE A DETAILED SEQUENCE OF OPERATIONS.
MANUAL TRANSFER TO PERMANENT GENERATOR POWER
MANUAL TRANSFER TO PERMANENT GENERATOR POWER - (CLOSED
TRANSITION):
1. THE OPERATOR STARTS THE GENERATOR AND WAITS UNTIL IT IS
UP TO RATED VOLTAGE AND FREQUENCY.
2. AT THE 3-WAY MANUAL TRANSFER SWITCH, CONFIRM
CONFIGURATION BETWEEN CIRCUIT BREAKERS CONTROLLING THE
PERMANENT GENERATOR AND TRANSFER SWITCHGEAR
CONNECTIONS ARE PROPERLY SET TO SUPPLY THE SWITCHGEAR
WITH GENERATOR POWER.
3. TURN OFF ALL INDIVIDUAL POL PUMP BREAKERS.
4. AFTER GENERATOR ATTAINS RATED VOLTAGE AND FREQUENCY,
SWITCH TO GENERATOR INCOMING POWER VIA KIRK-KEY
INTERLOCK BREAKERS
a. TURN KEY AND OPEN THE UTILITY MAIN BREAKER; RELEASE KEY.
b. TURN KEY AND CLOSE THE GENERATOR MAIN BREAKER; RELEASE
KEY.
5. TURN ON CIRCUIT BREAKER AT SWITCHGEAR FEEDING PANEL 'PA'
TO POWER CIRCUITS FEEDING THE GENERATOR'S CONTROL
PANEL, JACKET WATER HEATER, AND BATTERY CHARGER. PANEL
'PA' IS LOCATED INSIDE THE BUILDING.
6. TURN ON POL PUMP BREAKERS #1, #2, AND #3. ALLOW AT LEAST
FIVE SECONDS BETWEEN START-UP OF EACH PUMP.
7. YOU ARE NOW ON THE GENERATOR SUPPLY.
MANUAL RETURN TO UTILITY POWER - (CLOSED TRANSITION):
1. AFTER UTILITY SUPPLY POWER IS RESTORED, THE OPERATOR
MEASURES AND WAITS UNTIL UTILITY POWER IS UP TO PROPER
VOLTAGE AND FREQUENCY.
2. TURN OFF ALL INDIVIDUAL POL PUMP BREAKERS.
3. TURN OFF CIRCUIT BREAKER AT SWITCHGEAR FEEDING PANEL 'PA'.
4. SWITCH TO UTILITY INCOMING POWER VIA KIRK-KEY INTERLOCK
BREAKERS
a. TURN KEY AND OPEN THE GENERATOR MAIN BREAKER; RELEASE
KEY.
b. TURN KEY AND CLOSE THE UTILITY MAIN BREAKER; RELEASE KEY.
5. YOU ARE NOW ON UTILITY SUPPLY.
6. TURN ON ALL INDIVIDUAL POL PUMP BREAKERS.
LOAD BANK CONNECTION
ENTRY:
1. A LOAD BANK IS CONNECTED TO THE 3-WAY MANUAL TRANSFER
SWITCH.
2. CONNECT THE LOAD BANK CABLES TO THE TRANSFER SWITCH
LOCATED ON THE EXTERIOR OF BUILDING. PER THE TRANSFER
SWITCH CONNECTION SEQUENCE LABEL, CLOSE THE LOAD BANK
TO GENERATOR CIRCUIT BREAKER AND OPEN THE REMAINING
BREAKERS. VERIFY EACH PHASE IS PROPERLY CONNECTED.
3. THE GENERATOR IS STARTED.
4. LOAD CAN NOW BE ADDED FROM THE LOAD BANK CONTROLS.
EXIT:
1. LOADS ARE REMOVED WITH LOAD BANK CONTROLS.
2. SWITCH CIRCUIT BREAKERS CONTROLLING THE PERMANENT
GENERATOR AND TRANSFER SWITCHGEAR CONNECTIONS TO
SUPPLY THE SWITCHGEAR WITH PERMANENT GENERATOR POWER,
PER THE TRANSFER SWITCH CONNECTION SEQUENCE LABEL.
3. ENGINES ARE RUN FOR A COOL DOWN PERIOD THEN SHUTDOWN.
4. DISCONNECT THE LOAD BANK CABLES FROM THE TRANSFER
SWITCH.
TEMPORARY GENERATOR CONNECTION
IN CASE OF A TOTAL LOSS OF ALL ENGINES, THE 3-WAY MANUAL
TRANSFER SWITCH SHALL BE USED TO FEED THE MAIN
SWITCHGEAR BUS BY CONNECTING A TEMPORARY GENERATOR.
THIS SHALL BE A MANUAL OPERATION BY THE OPERATOR.
ENTRANCE INTO UTILITY FAIL:
1. AT THE 3-WAY MANUAL TRANSFER SWITCH, CONFIRM
CONFIGURATION BETWEEN CIRCUIT BREAKERS CONTROLLING THE
TEMPORARY GENERATOR AND TRANSFER SWITCHGEAR
CONNECTIONS ARE PROPERLY SET TO SUPPLY THE SWITCHGEAR
WITH TEMP GENERATOR POWER.
2. TURN OFF ALL INDIVIDUAL POL PUMP BREAKERS.
3. SWITCH TO GENERATOR INCOMING POWER VIA KIRK-KEY
INTERLOCK BREAKERS
a. TURN KEY AND OPEN THE UTILITY MAIN BREAKER; RELEASE KEY.
b. TURN KEY AND CLOSE THE GENERATOR MAIN BREAKER; RELEASE
KEY.
4. TURN ON POL PUMP BREAKERS #1, #2, AND #3. ALLOW AT LEAST
FIVE SECONDS BETWEEN START-UP OF EACH PUMP.
5. THE OPERATOR WILL START THE TEMPORARY GENERATOR.
6. YOU ARE NOW ON THE TEMP GENERATOR SUPPLY.
EXIT FROM UTILITY FAIL:
1. AFTER UTILITY SUPPLY POWER IS RESTORED, THE OPERATOR
MEASURES AND WAITS UNTIL UTILITY POWER IS UP TO PROPER
VOLTAGE AND FREQUENCY.
2. TURN OFF ALL INDIVIDUAL POL PUMP BREAKERS.
3. SWITCH TO UTILITY INCOMING POWER VIA KIRK-KEY INTERLOCK
BREAKERS
a. TURN KEY AND OPEN THE GENERATOR MAIN BREAKER; RELEASE
KEY.
b. TURN KEY AND CLOSE THE UTILITY MAIN BREAKER; RELEASE KEY.
4. YOU ARE NOW ON UTILITY SUPPLY.
5. TURN ON ALL INDIVIDUAL POL PUMP BREAKERS.
6. AFTER ALL LOADS ARE BACK ON UTILITY POWER, THE TEMPORARY
GENERATOR IS MANUALLY SHUT DOWN.
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E0.2
ELECTRICAL NOTES & GEN CALCS
2B1733 - PARTIAL SINGLE LINE DIAGRAM
GENERAL NOTES
DEMOLITION NOTES
1B1733 - PARTIAL DEMOLITION SINGLE LINE DIAGRAM
(E) XFMR
G
N
800AT
3P
1000AT
3P
1000AT
3P
K K
(N) TRANSFER
SWITCHGEAR 1200A
480Y/277V 3Ø 4W
EXISTING
(E) 200A 3P
(E) 200A 3P
(E) 200A 3P
(E) 200A 3P
(E) 200A 3P
(E) 200A 3P800-Y
(E) XFMR
G
N
1000AT
3P
800AT
3P
K K
(E) TRANSFER SWITCHGEAR
1200A 480Y/277V 3Ø 4W 'MS'
(E) 200A 3P
(E) 200A 3P
(E) 200A 3P
(E) 200A 3P
(E) 200A 3P
(E) 200A 3P
EXISTING INCOMING
POWER UTILITY SERVICE
(E) 1200A 480V 3Ø 3W MCC
1000-Y
(1) #3/O CU. BOND TO
EXISTING SERVICE
GROUND.
(E) (E)
SINGLE LINE NOTES
1. ELECTRICAL SERVICE MUST BE MAINTAINED 7-DAYS PER WEEK, 24-HOURS PER DAY (7/24). NO SERVICE INTERRUPTION TO THE EQUIPMENT WILL OCCUR DURING REMOVAL OF THE EXISTING SYSTEM AND INSTALLATION OF THE NEW
SYSTEM.
2. THE TERM HAZARDOUS CONDITION (HAZCON) IS USED TO DESCRIBE WHEN A GIVEN FACILITY IS OPERATING IN A DECREASED STATE OF RELIABILITY OR OPERATIONAL ABILITY. A HAZCON IS DEFINED AS A CONDITION IN WHICH THE NORMAL, ALTERNATE, BACKUP, OR REDUNDANT POWER SOURCE OR MECHANICAL EQUIPMENT IS NOT AVAILABLE, BUT POWER AND COOLING IS NOT INTERRUPTED TO THE LOAD. IT IS THEREFORE NOT A TRUE OUTAGE AT THE LOAD, ALTHOUGH IT MAY BE A PARTIAL OUTAGE OF ONE BUS, CIRCUIT, MECHANICAL SYSTEM ETC.
3. THE CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM THE PROJECT MANAGER PRIOR TO THE SCHEDULING OF ANY HAZCON CONDITION. SUCH PERMISSION MUST BE OBTAINED IN WRITING AND BE GRANTED AT LEAST 30 DAYS
PRIOR TO ANY SCHEDULED HAZCON.
4. PROVIDE TEMPORARY POWER FOR ANY PLANNED OUTAGES AS REQUIRED DURING DEMOLITION OF EQUIPMENT.
EXISTING SWITCHBOARD TO BE DEMO'D.
EXISTING MCC TO BE REFED.
EXISTING FEEDERS AND CONDUITS TO BE DEMO'D BACK TO SOURCE.
EXISTING GENERATOR TO BE DEMO'D.
G 1200A 3P
(E) GENERATOR
(E)
EXISTING
EXISTING
EXISTING SERVICE
GROUND
1200AF 1200AF
N.C. N.O.
1200AF 1200AF 1200AF
(N) (N) (N)N.O. N.C.
1 PROVIDE NEW SWITCHGEAR.
PROVIDE NEW 3-WAY MANUAL TRANSFER SWITCH 'ESL TRIPLE SWITCH' WITH CAM-STYLE RECEPTACLES. PART # ESL
T3D12 X-800C-800H-800H-480-311-S-C OR APPROVED EQUAL.
PROVIDE NEW 562KVA/450KW GENERATOR (MANUFACTURER: MTU 12V1600 DS SERIES OR APPROVED EQUAL).
EXISTING MOTOR CONTROL CENTER TO BE REFED FROM NEW SWITCHGEAR.
EXISTING LOADS TO BE REFED FROM NEW SWITCHGEAR.
PROVIDE CONTROL WIRES FROM GENERATOR TO ANNUNCIATOR PANEL IN 1"C. QUANTITY OF LOW VOLTAGE
CONDUCTORS ARE TO BE PER MANUFACTURER REQUIREMENTS.
CONTRACTOR IS TO PROVIDE NEW GENERATOR ANNUNCIATOR PANEL. COORDINATE EXACT LOCATION WITH
REPRESENTATIVE PRIOR TO INSTALLATION.
PROVIDE 4#6, 2#10, 1#10GRD IN 1"C. FOR GENERATOR BATTERY CHARGER, JACKET WATER HEATER AND
CONTROLLER CIRCUITS.
(1)#1/0 C.U. BOND TO DRIVEN GROUND ROD PER CEC 250.30 AND DO NOT BOND NEUTRAL AND GROUND TERMINALS
INSIDE 250.102(C). OF GENERATOR (NO GROUND LOOP). SIZE PER TABLE 250.66 .
NEW BREAKER LSIG RATED FOR 100% GENERATOR OUTPUT.
CABLING PER MANUFACTURER'S REQUIREMENTS.
EXISTING
ALL EXISTING IS TO REMAIN UNLESS OTHERWISE NOTED.
20A 3P
150A 3P
40A 3P
LEAK DET. SYSTEM TRLR
EXISTING TRANSF/PANEL 'PB'
BOUNDARY LIGHTS
600AT
3P
(E)
1200AF
FUEL
TRANSFER
PUMP
FTP-1 FP-5 FP-4 FP-3 FP-2 FP-1
PUMP #5 PUMP #4 PUMP #3 PUMP #2 PUMP #1
PUMP #5 PUMP #4 PUMP #3 PUMP #2 PUMP #1
EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
FUEL
TRANSFER
PUMP
A
3P
0A
3P
A
3P
LE
AK
D
ET
. S
YS
TE
M
TR
LR
EX
IS
TI
NG
T
RA
NS
F/
PA
NE
L '
PB
BO
UN
DA
RY
LI
GH
TS
PQM
(E) 1200A 480V 3Ø 3W MCC
EXISTING
EXISTING
EXISTING
GENERATOR FUEL CALCULATION
SUB BASE FUEL TANK CAPACITY: 1000 GALLONS
DIESEL FUEL CONSUMPTION RATE @ FULL LOAD: 30.5 GALLONS/HR.
APPROX. RUN TIME @ FULL LOAD: 1000/30.5 = 32.7 HRS.
TEMP
GENERATOR
CONNECTION
800A 3P
800-Y
3 (N) GENERATOR 'G1733'
450KW (562KVA) 480V 3Ø 4W
800A MAIN OUTPUT CIRCUIT BREAKER
WEATHERPROOF LEVEL 2 SOUND
ATTENUATED ENCLOSURE
AFC= 4,894
AIC=30,000
REMOTE
ANUNCIATOR
PANEL
PB-22,24,29 8
LOAD BANK
CONNECTION
ESL TRIPLE SWITCH
NEMA 3R
AFC=27940
AIC=30,000
L=50' V.D.=0.12%
L=70' V.D.=0.17%
L=10' V.D.=0.02%
G
30,000 AFC
30,000 AIC
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E0.3
B1733 SINGLE LINE DIAGRAMS
1PANEL SCHEDULES
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E0.5
PANEL SCHEDULES
(ETR) 1200A MCC
(E) 1200A SWITCHGEAR
(E) 550KW GENSET
(ETR) TRANSFORMER
B1733
(ETR) TRANSF.
(ETR) PANEL PB
E1.0 E3.4
E1.0 E3.4
E1.0 E3.4
(ETR) AC UNIT
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E1.0
PROJECT
NORTH
TRUE NORTH
08 8
4 164
GENERAL NOTES
DEMOLITION PLAN NOTES
1. PROVIDE TEMPORARY POWER FOR ANY PLANNED OUTAGES AS REQUIRED DURING DEMOLITION OF EQUIPMENT.
DEMOLISH EXISTING SWITCHGEAR. REFER TO SINGLE LINE DIAGRAM.
DEMOLISH EXISTING GENERATOR.
DEMOLISH EXISTING ABOVE GROUND FUEL TANK.
SCALE: 1/8" = 1'-0"B1733 DEMOLITION SITE PLAN
B1733 DEMOLITION SITE PLAN
(E) 1200A MCC
(N) 1200A TRANSFER SWITCHGEAR
(N) TRIPLE SWITCH
(N) 450KW GENSET
(E) TRANSFORMER
B1733
(E) TRANSF.
(E) PANEL PB1000-Y
1000-Y
(N) ANNUNCIATOR
(E) AC UNIT
1000-Y64
PULLBOX
E2.0 E3.3
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E2.0
B1733 ELECTRICAL SITE PLAN
PROJECT
NORTH
TRUE NORTH
08 8
4 164
GENERAL NOTES
PLAN NOTES
1. EXISTING ELECTRICAL EQUIPMENT TO BE PROTECTED IN PLACE, U.O.N.
2. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE NEMA 3R.
3. ALL EXTERIOR RECEPTACLE OUTLETS SHALL BE GFCI TYPE.
4. PROVIDE HEAVY DUTY DISCONNECT SWITCHES WITH DUAL ELEMENT FUSES TO MATCH MOTOR H.P. RATING.
PROVIDE NEW 1200A TRANSFER SWITCHGEAR. REFER TO SINGLE LINE DIAGRAM.
PROVIDE NEW ESL TRIPLE SWITCH, WITH CAM-STYLE RECEPTACLES. PART # ESL T4D X-1200A H-1000A H-480-311-S-C OR APPROVED EQUAL.
PROVIDE NEW GENERATOR ON NEW CONCRETE PAD FOUNDATION. NEW GENERATOR TO BE 450KW/562KVA, MANUFACTURER: MTU 12V1600 DS SERIES
OR APPROVED EQUAL. REFER TO DETAIL 5 ON SHEET E3.3.
CONCRETE TRENCH FOR CABLE ROUTING BETWEEN EQUIPMENT. TRENCH TO EXTEND BELOW EQUIPMENT. REFER TO DETAIL 2 ON SHEET E3.3.
PROVIDE 4#6, 2#10, 1#10GRD IN 1"C. FOR GENERATOR BATTERY CHARGER, JACKET WATER HEATER AND CONTROLLER CIRCUITS.
PROVIDE CONTROL WIRES FROM GENERATOR TO ANNUNCIATOR PANEL. QUANTITY OF LOW VOLTAGE CONDUCTORS ARE TO BE PER MANUFACTURER
REQUIREMENTS.
CONTRACTOR IS TO TRANSITION FROM NONMETALLIC CONDUIT TO RIGID STEEL CONDUIT AFTER RISING ABOVE GROUND LEVEL.
SCALE: 1/8" = 1'-0"B1733 ELECTRICAL SITE PLAN
3.5 29 7 17 3.5
36 24
SWITCHGEAR ELEVATION - BLDG 1733 1
NOTE:
EQUIPMENT SHOWN IS BASED ON IEM EQUIPMENT
DIMENSIONS. CONTRACTOR SHALL PROVIDE SHOP
DRAWINGS OF ALL ELECTRICAL EQUIPMENT LAYOUTS IN
BUILDING 1733, SHOWING THAT THE EQUIPMENT WILL FIT
AND MEET ALL REQUIRED CLEARANCES PRIOR TO
ORDERING EQUIPMENT.
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E3.0
SWITCHGEAR ELEVATIONS
GENERATOR ELEVATION 2
GENERATOR FUEL TANK ELEVATION 1
NOTE:
EQUIPMENT SHOWN IS BASED ON MTU EQUIPMENT
DIMENSIONS. CONTRACTOR SHALL PROVIDE SHOP
DRAWINGS OF ALL ELECTRICAL EQUIPMENT LAYOUTS AT
BUILDING 1733 AND 1041 AREAS, SHOWING THAT THE
EQUIPMENT WILL FIT AND MEET ALL REQUIRED
CLEARANCES PRIOR TO ORDERING EQUIPMENT.
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E3.1
GENERATOR ELEVATIONS
APPROVED
BY:
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN
OR WHEREWITH IS NOT TO BE REPRODUCED, USED
OR DISCLOSED IN WHOLE OR IN PART TO ANYONE
WITHOUT THE PERMISSION OF ESL.
24.13
DATE:
FOR FABRICATION BY ESL
CONDUIT ENTRY
AREA
NOTES:
1. FINISH POWDER COAT SERIES W49. SEE TITLE
BLOCK FOR COLOR.
2. WIRING DIAGRAM: 0901-311215
TOP VIEW
104.00
TRIPLE SWITCH
LOGO
PRODUCT LABEL
DANGER LABEL
(2X)
PADLOCKABLE
HANDLE WITH
3-POINT LATCH
(2X)
HINGED DOOR
(2X)
INCOMING &
OUTGOING
WIREWAY
SECTION
CONDUIT ENTRY
AREA
ESL LOGO
PLATE
REMOVABLE
LIFTING EYE
(4X)
3. USE LABEL DRAWING 3112-LBL-480-3P4W
CONDUIT ENTRY
AREA
HINGED SEPARATE
DOOR FOR EMERGENCY
GENERATOR CABLES
VENTILATION LOUVERS
(2X)
LEFT SIDE VIEW
FRONT VIEW
RIGHT SIDE VIEW
C
POWER SYSTEMS
18.58
1200A 480Y/277VAC 50/60Hz 3ɸ +N +G
TRIPLE TRANSFER SWITCH
SOLID BOTTOM
BOTTOM VIEW
QTY=
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN INCHES
TOLERANCES:
A GT
12/01/16
3 GL
REV. BY
9/8/2016
DATE
AS BUILT
ES 9/22/2016 ADD 2ND GRND CAMS, ADDED NOTE 3, REVISED LABELING ON DOORS & DEAD FRONTS ON SHT 2
CHG ATS LUGS TO 750kcmil
DESCRIPTION
DECIMALS
.x .03
.XX .01
.XXX .005
BREAK ALL SHARP EDGES
.005 - .010
DIMENSIONS TO BE HELD AFTER
PLATING AND HEAT TREATING
COLOR: WRINKLE GRAY
RAL 7035
REFERENCE:
1050-20A-ASSY
APPROVAL
DATE
DO NOT SCALE DRAWING
ANGULAR
1/2
THICKNESS:
MATERIAL: GALV STEEL
12 GAUGE
ENGINEER
CHECKED
POWER SYSTEMS, INC.
CORONA, CALIFORNIA 92880
(951) 739-7000 (800) 922-4188 eslpwr.com - info@eslpwr.com
PATH
L:\DWG\REEFPART\FABRIC\3112\
DRAWING NUMBER
3112-15
SHEET
ESL CAT.# T3D12-1200C-1200C-1200C-480-311-S-C-X311215
TYPE:3R
EST. WEIGHT: 2310
1200A, 480Y/277VAC
3 PHASE + N + G
TRIPLESWITCH
Lbs.
Corona, CA 92880 <> (800)922-4188 <> (951)739-7000 <> info@eslpwr.com
MFG. DATE:
SHORT CIRCUIT CURRENT RATING: 50,000 RMS SYMMETRICAL AMPS
UL US
R
3NZT
LISTED
.75
(4X)
INCOMING &
OUTGOING
WIREWAY
SECTION
M O
D
EL:
3112-15
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN
OR WHEREWITH IS NOT TO BE REPRODUCED, USED
OR DISCLOSED IN WHOLE OR IN PART TO ANYONE
WITHOUT THE PERMISSION OF ESL.
TOP VIEW
REMOVABLE DEADFRONT
FOR OPERATOR SAFETY
B
TERMINATION LUGS FOR
FEEDER CABLES FROM
PERMANENT GENERATOR.
ACCEPTS (6) #6AWG-300kcmil
WIRES PER PHASE, NEUTRAL
1200A, 3-POLE
CIRCUIT BREAKER
80% RATED
(3X)
SAFETY INTERLOCK
MECHANISM ALLOWS
ONLY ONE CIRCUIT
BREAKER TO BE "ON"
AT A TIME.
INTERLOCK MECHANISM
FEMALE OUTPUT CAMS FOR
(2) GREEN - GROUND
LOAD BANK CONNECTION
(3) YELLOW - PHASE C
(3) ORANGE - PHASE B
(3) BROWN - PHASE A
(3) WHITE - NEUTRAL
B
(DOORS AND DEADFRONTS REMOVED)
FRONT VIEW
SCALE 1 : 26
SECTION B-B
MALE INPUT CAMS FOR
EMERGENCY GENERATOR
CONNECTION
(2) GREEN - GROUND
(3) WHITE - NEUTRAL
(3) BROWN - PHASE A
(3) ORANGE - PHASE B
(3) YELLOW - PHASE C
GROUND LUG
ACCEPTS:
(4) #2-600kcmil (2X)
(2) #2-600kcmil (1X)
FAN
TRANSFORMER
WIRES PER PHASE, NEUTRAL
ACCEPTS (4) 1/0-750kcmil
OUTPUT CABLES TO ATS.
TERMINATION LUGS FOR
20.66
TOP FEED
WIRE BENDING
SPACE
OPERATING
INSTRUCTIONS
(2X)
INTERLOCKED
(3X)
DISCONNECT
HANDLES
HINGED DEADFRONT
WHILE CONNECTING AND
FOR OPERATOR SAFETY
DISCONNECTING WIRING.
PROTECTION
BARRIER
WHILE CONNECTING AND
DISCONNECTING WIRING.
FRONT VIEW
(DOORS REMOVED)
QTY=
UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN INCHES
TOLERANCES:
A GT
12/01/16
3 GL
REV. BY
9/8/2016
DATE
AS BUILT
ES 9/22/2016 ADD 2ND GRND CAMS, ADDED NOTE 3, REVISED LABELING ON DOORS & DEAD FRONTS ON SHT 2
CHG ATS LUGS TO 750kcmil
DESCRIPTION
DECIMALS
.x .03
.XX .01
.XXX .005
BREAK ALL SHARP EDGES
.005 - .010
DIMENSIONS TO BE HELD AFTER
PLATING AND HEAT TREATING
COLOR: WRINKLE GRAY
RAL 7035
REFERENCE:
1050-20A-ASSY
ANGULAR
1/2
MATERIAL:
THICKNESS:
GALV STEEL
12 GAUGE
ENGINEER
CHECKED
APPROVAL
DATE
DO NOT SCALE DRAWING
1 EST. WEIGHT:
POWER SYSTEMS, INC.
CORONA, CALIFORNIA 92880
(951) 739-7000 (800) 922-4188 eslpwr.com -
PATH
L:\DWG\REEFPART\FABRIC\3112\
info@eslpwr.com
DRAWING NUMBER
3112-15
SHEET
1200A, 480Y/277VAC
3 PHASE + N + G
TRIPLESWITCH
Lbs.
M O
D
EL:
3112-15
TRIPLE TRANSFER SWITCH ELEVATIONS & WIRING DIAGRAM 1
NOTE:
EQUIPMENT SHOWN IS BASED ON ESL EQUIPMENT
DIMENSIONS. CONTRACTOR SHALL PROVIDE SHOP
DRAWINGS OF ALL ELECTRICAL EQUIPMENT LAYOUTS AT
BUILDING 1733 AND 1041 AREAS, SHOWING THAT THE
EQUIPMENT WILL FIT AND MEET ALL REQUIRED
CLEARANCES PRIOR TO ORDERING EQUIPMENT.
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E3.2
TRIPLE TRANSFER SWITCH
ELEVATIONS & WIRING DIAGRAM
FINISH GRADE
CADWELD
GROUND ROD DETAIL
CONDUIT & WIRE TO
ADDITIONAL
GROUND (AS
REQUIRED).
NOTES:
1. SIZE OF CONDUCTORS SHALL COMPLY W/CEC 250.66.
2. CHECK RESISTANCE TO GROUND. IF RESISTANCE
EXCEEDS 25 OHMS, INSTALL ADDITIONAL GROUND
RODS W/CONDUCTORS AS SHOWN. SEPARATE AT
LEAST 6'-0" UNTIL RESISTANCE IS REDUCED TO 25
OHMS OR LESS (CEC 250.56)
CONDUIT & WIRE SIZE AS
REQUIRED SEE PLANS.
CONCRETE COVER WITH LIFTING
EYES LABEL "ELECTRICAL"
PRECAST 19-3/4"L X 14-1/4"W
X 12"D. YARD BOX. BROOKS
PRODUCTS #3 1/2PB-21
QUICKSET #EC-17
CONDUIT HUB FOR GROUNDING
BY "THOMAS & BETTS"
3/4" X 10'-0" DRIVEN
"COPPERWELD" GROUND ROD.
GENERATOR SIGNAGE
GENERAL NOTES:
1. PROVIDE OSHA DANGER SIGN. "NO SMOKING WITHIN 50 FEET" SEE SAMPLE ABOVE. SIGN TO BE 20"X24" PRESSURE SENSITIVE VINYL. CHAMPION AMERICA INC. (1-800-521-7000) PN 30612HF. MOUNT ON BOTH
SIDES OF GENERATOR ENCLOSURE.
2. PROVIDE OSHA DANGER SIGN. "THIS EQUIPMENT STARTS AND STOPS AUTOMATICALLY" SEE SAMPLE ABOVE.
SIGN TO BE 14"X10" CHAMPION AMERICA INC. (1-800-521-7000) SENSITIVE VINYL. PN 51368HF, OR APPROVED EQUIVALENT. MOUNT ON BOTH SIDES OF GENERATOR ENCLOSURE. SIGN IS TO BE INSTALLED SO IT IS
VISIBLE TO PEDESTRIANS AT ALL TIMES.
THIS EQUIPMENT
AUTOMATICALLY
STARTS AND STOPS
CAUTION
DANGER
NO SMOKING
WITHIN 50 FEET
GENERATOR
3 5
GENERATOR POWER FEEDER TO TRIPLE TRANSFER SWITCH. SEE
SINGLELINE DIAGRAM FOR MORE INFORMATION.
OUTPUT CIRCUIT BREAKER FEEDER SHALL BE ROUTED BELOW GRADE
AND 'SEALTITE' FLEX CONDUIT PROVIDED FROM GROUND STUB TO
CIRCUIT BREAKER ENCLOSURE.
GENERATOR INSIDE NEMA 3R ENCLOSURE.
FAN-COOLED RADIATOR AND COOLING AIR DISCHARGE.
ENGINE EXHAUST MANIFOLD VERIFY OVERALL HEIGHT OF CRITICAL
SILENCER AND NOTIFY ARCHITECT.
CONTROL PANEL MOUNTED INSIDE GENERATOR SET NEMA 3R
ENCLOSURE.
BATTERY AND CHARGER MOUNTED INSIDE GENERATOR SET NEMA 3R
ENCLOSURE.
JACKET WATER HEATER.
ROUTE CIRCUITS TO 208Y/120V PANEL AS INDICATED ON PLAN.
ROUTE MINIMUM 6#14 IN 1"C FOR TRANSFER SIGNAL.
3/4"C. (1)#3/0 BARE COPPER WIRE TO GROUND ROD. SEE DETAIL 1,
SHEET E3.3
3/4"C. X 10' COPPER GROUND ROD. SEE DETAIL 1, SHEET E3.3
GENERAL NOTES:
1. VERIFY FINAL GENERATOR SET DIMENSIONS WITH SHOP DRAWINGS.
2. MAINTAIN MINIMUM CLEARANCES AS INDICATED.
3. GENERATOR SET ENCLOSURE DOORS SHALL BE FULLY OPENABLE
SIDES WITH CLEARANCES MAINTAINED.
4. SEE DIMENSIONED ARCHITECTURAL PLANS FOR GENERATOR YARD
LAYOUT.
CONSTRUCTION NOTES:
SCHEMATIC GENERATOR PLAN-OUTDOOR
TO TRANSFER
SWITCH
PA-19
PB-22
PA-29
PB-29
SIGNAL
CONDUITS BANK
POWER
CONDUITS BANK
6" WIDE WARNING TAPE
RIGID NONMETALLIC
SIGNAL CONDUIT(S) TYP.
EXACT QUANTITY PER
SINGLE LINE DIAGRAM
AND SITE PLAN.3" MIN.
" M
IN
3" MIN.
6" MIN.
3" MIN.
3" MIN.
3" MIN.
CONCRETE
RIGID NONMETALLIC POWER CONDUIT(S).
EXACT QUANTITY PER SINGLE LINE
DIAGRAM AND SITE PLAN(S).
95% COMPACTED BACK FILL
AC PAVING OR LANDSCAPE TO
EXISTING SURROUNDING AREA
CONDUIT SPACER TYP. ALL
CONDUITS IN TRENCH
BASE CONDUIT
SPACER TYP.
7.5" MIN.
NOTE: MINIMUM TRENCH WIDTH TO BE 24".
3" MIN.
POWER & SIGNAL CONDUIT DUCT BANK
E3.3 E3.3
E2.0 E3.3 E2.1
E3.1 E3.3
E2.0 E3.3
E2.0 E3.3 E2.1
PULLBOX CONSTRUCTION DETAILS
E2.1
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E3.3
ELECTRICAL DETAILS
B1733 - PHOTO DETAIL
EXISTING GENERATOR TO BE DEMO'D
EXISTING FUEL TANK
TO BE DEMO'D
EXISTING SWITCHGEAR
TO BE DEMO'D
EXISTING MOTOR CONTROL
CENTER TO REMAIN
E1.0 E3.4
B1733 - PHOTO DETAIL
E1.0 E3.4
B1733 - PHOTO DETAIL
E1.0 E3.4
E1.1 E3.4
E1.1 E3.4
E1.1 E3.4
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100
Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com
Architecture | Project Management
E3.4
PHOTO DETAILS