Attach 4 - B1733 - Final Drawings.pdf

PDF 27 MB Posted

Attached to
Repair Fuel System Generators Federal contract opportunity
Solicitation number
FA442721R0012
Issued by
Department of the Air Force Air Mobility Command

About this file

This document outlines a federal contract solicitation for repair services. The Department of the Air Force Air Mobility Command is seeking to engage a contractor to provide all materials, labor, supervision and equipment to complete Repair Fuel System Generators at a specified location. A mandatory site visit is scheduled for February 23, 2021 at 9:00AM PST, and interested parties must RSVP in advance. No more than two individuals from each company will be permitted to attend the site visit, and all attendees must comply with COVID-19 safety protocols including wearing face masks. The solicitation number is FA442721R0012 and responses are due based on the terms outlined in the document.

View the file

Other files for this federal contract opportunity

Other files attached to Repair Fuel System Generators, newest first.
File Type Posted
(ANS) XDAT 14-1031 PRE-BID RFI 12 -Follow Up RFI_Battery.pdf PDF
(ANS) XDAT 14-1031 PRE-BID RFI 13 -Switchgear.pdf PDF
(ANS) XDAT 14-1031 PRE-BID 09 Triple Switch Elevations.pdf PDF
(ANS) XDAT 14-1031 PRE-BID 05 B1733 Wire Designation.pdf PDF
(ANS) XDAT 14-1031 PRE-BID 04 B1041 Wire Designation.pdf PDF
(ANS) XDAT 14-1031 PRE-BID 06 Specified Generator Manufacturer (2.0).pdf PDF
(ANS) XDAT 14-1031 PRE-BID 06 Specified Generator Manufacturer.pdf PDF
(ANS) XDAT 14-1031 PRE-BID 07 Requirements for Utilizing Crane.pdf PDF
(ANS) XDAT 14-11031 PRE-BID 03 Multiple Conduits on exterior.pdf PDF
Questions and Answers - Round 3.pdf PDF
Solicitation Amendment FA442721R00120001 SF 30.pdf PDF
(ANS) XDAT 14-1031 PRE-BID 08 Contractors Responsibility in Demolished Equipment.pdf PDF
(ANS) XDAT 14-1031 PRE-BID 02 Drivers Training_Driving Privileges_Security Escorts.pdf PDF
(ANS) XDAT 14-1031 PRE-BID 01 Fuel Tank Responsibility.pdf PDF
XDAT 14-1031 PRE-BID RFI 10 Demolished Items.pdf PDF
XDAT 14-1031 PRE-BID RFI 11 Removal of Fuel.pdf PDF
43 - EU-1 - ELECTRICAL SITE PLAN AREA A.pdf PDF
20 - S-1 - VALVE VAULT DETAILS.pdf PDF
0 - C - 1 EXISTING SITE CONDITIONS AREA A.pdf PDF
4 - B-4 - PUMPHOUSE BUILDING SECTION.pdf PDF
8 - B-8 - CONNECTION DETAILS.pdf PDF
Questions and Answers - Round 2.pdf PDF
48 - ED-2 - TANK DETAILS.pdf PDF
6 - B-6 - PUMPHOUSE ELEVATIONS.pdf PDF
3 - B-3 - PUMPHOUSE BUILDING SECTION.pdf PDF
1 - B - 1 PUMPHOUSE FLOOR PLAN AND DETAILS.pdf PDF
7 - B-7 - CONNECTION DETAILS.pdf PDF
2 - B-2 - PUMPHOUSE BUILDING PLAN.pdf PDF
33 - T-2 - APPURTENANCES AND FITTINGS.pdf PDF
5 - B-5 - PUMPHOUSE BUILDING SECTION.pdf PDF
29 - T-1 - FOUNDATION DETAILS.pdf PDF
Attendance Sheet - Site Visit - Signed.pdf PDF
Questions and Answers - Round 1.pdf PDF
Attach 7 - Travis Facilities Excellence Guide.pdf PDF
Attach 9 - Travis Specifications Section 01000.pdf PDF
Attach 1 - B1733 SOW Dated 23 Mar 2020.pdf PDF
Attach 6a - Bid Schedule B1041.xlsx XLSX spreadsheet
Attach 6 - Bid Schedule B1733.xlsx XLSX spreadsheet
Attach 1a - B1041 SOW Dated 23 Mar 2020.pdf PDF
Attach 4a - B1041 Final Drawings.pdf PDF
Attach 2 - B1733 Final Design Analysis Report.pdf PDF
Attach 2a. - B1041 Final Design Analysis Report.pdf PDF
Attach 8 - WD CA20200007 27 November 2020.pdf PDF
Attach 5a - Submittal Register Generator B1041.pdf PDF
Attach 3 - B1733 - Final Specifications.pdf PDF
Attach 5 - Submittal Register Generator B1733.pdf PDF
Attach 10 - Past Performance Questionnaire.docx DOCX document
Attach 3a - B1041 Final Specifications.pdf PDF
Attach 11 - Contract Security Clause 29 Apr 19.pdf PDF
Solicitation - FA442721R0012.pdf PDF
Show all 50

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

+4'-6" AFF

POWER LEGEND AND SYMBOLS

SYMBOL

MOUNTING HEIGHT FROM FINISHED FLOOR TO CENTERLINE OF

OUTLET OR EQUIPMENT. FOR LIGHT FIXTURES, IT IS TO BOTTOM OF

FIXTURE.

DESCRIPTION

UTILITY COMPANY PULL SECTION LUGS

GROUNDING CONNECTION TO MAIN BUILDING GROUND SYSTEM U.O.N.

CURRENT TRANSFORMER

MOLDED CASE SHUNT TRIP CIRCUIT BREAKER

DO NOT SCALE DRAWINGS

CONDUIT TURNED DOWN

CONDUIT TURNED UP

CONDUIT STUBBED AND CAPPED; LOAD BANK CONNECTED

RACEWAY CONCEALED IN WALLS OR ABOVE CEILING

UTILITY METER WITH CURRENT TRANSFORMERS (CT'S)

TRANSFORMER WITH SECONDARY GROUND

ON-SITE GENERATOR SET

OR

200-S

MOLDED CASE DRAW OUT TYPE POWER CIRCUIT BREAKER

GROUND ROD/WELL

SOLENOID KEY RELEASE UNIT

POWER METER

POWER QUALITY METER. SQAURE D PM500 SERIES.

CURRENT SENSOR

VOLTAGE SENSOR

MOLDED CASE CIRCUIT BREAKER

KIRK KEY

SYMBOL DESCRIPTION

OR

EXISTING (DASH INDICATES) ELECTRICAL EQUIPMENT

DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS)

MOUNTED +15" A.F.F. TO CENTER LINE U.O.N.

3/4" CONDUIT WITH 2 #12 & 1 #12 GND WIRES

3/4" CONDUIT WITH 3 #12 & 1 #12 GND WIRES

3/4" CONDUIT WITH 4 #12 & 1 #12 GND WIRES

3/4" CONDUIT WITH 5 #12 & 1 #12 GND WIRES

A-1,3

EQUIPMENT

ID. NO.

SHEET NO.

DETAIL NO.

EQUIPMENT REFERENCE

DETAIL REFERENCE

POWER LEGEND AND SYMBOLS

DESCRIPTIONSYMBOL DESCRIPTION

NOTE TO CONTRACTOR

1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST CALIFORNIA CODE OF

REGULATIONS (CCR), NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL

CODES AND REGULATIONS.

2. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN

COMPLIANCE TO UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN.

3. WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE

INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND MAKE

FINAL CONNECTION AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING ELECTRICAL

CONNECTIONS.

5. LOCATION OF LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS. AT OR NEAR DOORS, INSTALL SWITCHES ON SIDE OPPOSITE TO DOOR HINGE. VERIFY FINAL HINGE LOCATION IN

FIELD PRIOR TO ANY WORK.

6. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND

WORK INCLUDED. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OR OTHER

TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN

HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES.

7. FURNISH APPROVED EXPANSION FITTINGS WHERE RACEWAY CROSSES BUILDING EXPANSION

JOINTS.

8. FURNISH PULL STRING IN EACH RACEWAY RUN OVER 10' IN LENGTH, IN WHICH PERMANENT

WIRING IS NOT INSTALLED.

9. PROVIDE PULL BOXES WHEREVER NECESSARY TO FACILITATE PULLING OF CONDUCTORS.

COORDINATE LOCATIONS OF BOXES WITH OTHER TRADES TO AVOID CONFLICT. PULL BOXES

SHALL BE ACCESSIBLE. THE SIZE OF PULL BOX SHALL COMPLY WITH N.E.C. REQUIREMENTS.

10. ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED

TO OUTSIDE ENVIRONMENT (UP TO 16') SHALL BE WEATHERPROOF TYPE, NEMA 3R.

11. NO CONDUIT RUNS SHALL BE ALLOWED IN CONCRETE SLABS. ALL CONDUITS WILL BE PLACED

ABOVE ACCESSIBLE CEILING SPACES UNLESS SPECIFICALLY INDICATED TO BE UNDERGROUND.

12. DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE

DIRECTLY ON EQUIPMENT, PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY.

13. ALL ELECTRICAL POWER OR SIGNAL WIRING IN FIRE RATED WALL IS TO BE INSTALLED IN A

METALLIC CONDUIT SYSTEM.

14. ALL ELECTRIC MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL"

LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT.

15. ALL DISTRIBUTION AND CONTROL EQUIPMENT (SUCH AS CB'S, SWITCHES, CONTACTORS, ETC.), TERMINATIONS SHALL BE FULLY RATED PER UL AS FOLLOWS:

A. 125A OR LESS : 60°C OR MORE;

B. MORE THAN 125A : 75°C OR MORE.

16. NO MC, BX, OR FLEX CABLE WILL BE ALLOWED (UNLESS PRIOR APPROVAL IS GRANTED); AS A

STANDARD, FLEX AND MC MUST BE ACCESSIBLE ON BOTH ENDS FOR REMOVAL AND SERVICE,

IF THEY WILL BE USED.

17. ALL RECEPTACLE OUTLETS TO BE SPECIFICATION GRADE - 125V 20AMP.

18. STANDARD COLOR FOR ALL SWITCHES AND RECEPTACLES TO BE IVORY.

19. ALL SWITCH AND RECEPTACLE FACE PLATES TO BE BRUSHED (SATIN) STAINLESS STEEL U.O.N.

CONTRACTOR SHALL LABEL EACH RECEPTACLE AND SWITCH WITH PANEL & BREAKER NUMBER

FROM WHICH IT IS FED FROM.

20. ALL CONDUIT SHALL BE 3/4" MIN. NON-METALLIC CONDUIT IS NOT ALLOWED IN INTERIOR

SPACES.

21. CONDUCTORS SHALL HAVE UNDERWRITER'S LABORATORIES, INC.(UL) LISTED, 600 VOLT

INSULATION OF TYPE SPECIFIED BELOW OR ELSEWHERE IN THE SPECIFICATIONS.

CONDUCTORS SHALL BE COPPER.

1. BRANCH CIRCUITS - LIGHTING AND POWER.

A. #10 AWG AND SMALLER, SOLID WIRE TYPE THW OR THHN/THWN, THHW(THHN FOR DRY

LOCATION ONLY).

B. #8 AWG TO #2 AWG, STRANDED TYPE THW OR THHN/THHW.

C. #1 AWG AND LARGER, STRANDED TYPE XHHW.

2. FEEDERS : TYPE THW OR THHN/THWN, OR XHHW.

22. PROVIDE GREEN INSULATED GROUNDING CONDUCTOR IN EACH RACEWAY INCLUDING

CONDUITS, PLUG STRIPS, WIREMOLD. SIZE OF GROUNDING SHALL BE IN ACCORDANCE WITH

NATIONAL ELECTRIC CODE ARTICLE 250.

23. WIRING METHOD SHALL BE EMT ABOVE GROUND AND MOUNTED IN CONCEALED SPACES AND

SCHEDULE-40 PVC FOR UNDERGROUND INSTALLATION. USE RIGID WHEN ENCASED IN

CONCRETE OR SUSCEPTIBLE TO DAMAGE.

24. CONTRACTOR TO USE THE FOLLOWING CONDUCTOR SIZES FOR BRANCH CIRCUITS:

#10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER THAN 75 FEET.

#10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER THAN 200 FEET.

GENERAL NOTES

SHEET DETAIL IS

SHOWN ON

SHEET FROM WHICH

DETAIL IS REFERENCED

15KV 6-WAY PADMOUNT SWITCH

PHOTO REFERENCE.

SHEET FROM WHICH PHOTO

IS REFERENCED

VIEW DIRECTION

OF PHOTO

DETAIL REFERENCE.

DETAIL NUMBER ON

SHEET

PHOTO NUMBER

ON SHEET

SHEET PHOTO

IS SHOWN ON

1FEEDER SCHEDULES

600V FEEDER SCHEDULE 1Ø 3W

SETSTYPELABEL PHASE GROUNDNEUTRAL CONDUIT

1 2 # 12

1 2 # 10

1 2 # 8

1 2 # 6

1 2 # 6

1 2 # 4

1 2 # 4

1 2 # 2

1 2 # 1

1 2 # 1

20A-3W

200A-3W

175A-3W

150A-3W

125A-3W

100A-3W

80A-3W

60A-3W

50A-3W

30A-3W

40A-3W

70A-3W

90A-3W

2 # 1/0

2 # 2/0

2 # 3/0

1 # 12

1 # 6

1 # 6

1 # 6

1 # 6

1 # 8

1 # 8

1 # 10

1 # 10

1 # 10

1 # 10

1 # 8

1 # 8

3/4"

3/4"

1"

1"

1"

1-1/4"

1-1/4"

1-1/2"

1-1/2"

2"

2"

1 # 12

1 # 10

1 # 10

1 # 6

1 # 6

1 # 4

1 # 4

1 # 2

1 # 1

1 # 1

1 # 1/0

1 # 2/0

1 # 3/0

1-1/4"

1-1/2"

NOTE:

ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THE AMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).

20-B

30-B

40-B

50-B

60-B

70-B

80-B

90-B

100-B

125-B

150-B

175-B

200-B

SETSTYPELABEL PHASE GROUND CONDUIT

1 3 # 12 3/4"

1 3 # 10 3/4"

1 3 # 8 1"

1 3 # 6

1 3 # 6

1 3 # 4

1 3 # 4

1 3 # 2

1 3 # 1

1 3 # 1

3 # 250 KCM

1600A-4W

4000A-4W

1000A-4W

700A-4W

600A-4W

500A-4W

450A-4W

20A-4W

3000A-4W

2000A-4W

2500A-4W

800A-4W

1200A-4W

400A-4W

350A-4W

300A-4W

250A-4W

225A-4W

200A-4W

175A-4W

150A-4W

125A-4W

100A-4W

80A-4W

60A-4W

50A-4W

30A-4W

40A-4W

70A-4W

90A-4W

3 # 1/0

3 # 2/0

3 # 3/0

3 # 4/0

3 # 350 KCM

3 # 500 KCM

3 # 600 KCM

3 # 250 KCM

3 # 350 KCM

3 # 500 KCM

3 # 600 KCM

3 # 500 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 4/0

1"

1"

1"

1-1/4"

1-1/4"

1-1/2"

1-1/2"

1-1/2"

1 # 4/0

1#500KCM

1 # 2/0

1 # 1/0

1 # 1/0

1 # 2

1 # 2

1 # 12

1#500KCM

1#250KCM

1#350KCM

1 # 1/0

1 # 3/0

1 # 2

1 # 2

1 # 4

1 # 4

1 # 4

1 # 6

1 # 6

1 # 6

1 # 6

1 # 8

1 # 8

1 # 10

1 # 10

1 # 10

1 # 10

1 # 8

1 # 8

4"

4"

4"

4"

4"

3"

3"

4"

4"

4"

4"

4"

4"

4"

3"

2 1/2"

2 1/2"

2"

2"

NEUTRAL

1 # 12

1 # 10

1 # 10

1 # 6

1 # 6

1 # 4

1 # 4

1 # 2

1 # 1

1 # 1

1 # 250 KCM

1 # 1/0

1 # 2/0

1 # 3/0

1 # 4/0

1 # 350 KCM

1 # 500 KCM

1 # 600 KCM

1 # 4/0

1 # 250 KCM

1 # 350 KCM

1 # 500 KCM

1 # 600 KCM

1 # 500 KCM

1 # 600 KCM

1 # 600 KCM

1 # 600 KCM

1 # 600 KCM

1 # 600 KCM

1 # 600 KCM

600V FEEDER SCHEDULE 3Ø 4W

20-Y

30-Y

40-Y

50-Y

60-Y

70-Y

80-Y

90-Y

100-Y

125-Y

150-Y

175-Y

200-Y

225-Y

250-Y

300-Y

350-Y

400-Y

450-Y

500-Y

600-Y

700-Y

800-Y

1000-Y

1200-Y

1600-Y

2000-Y

2500-Y

3000-Y

4000-Y

NOTE:

ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THE AMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).

600V FEEDER SCHEDULE 3Ø 3W

SETSTYPELABEL PHASE GROUNDNEUTRAL CONDUIT

1 3 # 12

1 3 # 10

1 3 # 8

1 3 # 6

1 3 # 6

1 3 # 4

1 3 # 4

1 3 # 2

1 3 # 1

1 3 # 1

3 # 250 KCM

1600A-3W

4000A-3W

1000A-3W

700A-3W

600A-3W

500A-3W

450A-3W

20A-3W

3000A-3W

2000A-3W

2500A-3W

800A-3W

1200A-3W

400A-3W

350A-3W

300A-3W

250A-3W

225A-3W

200A-3W

175A-3W

150A-3W

125A-3W

100A-3W

80A-3W

60A-3W

50A-3W

30A-3W

40A-3W

70A-3W

90A-3W

3 # 1/0

3 # 2/0

3 # 3/0

3 # 4/0

3 # 350 KCM

3 # 500 KCM

3 # 600 KCM

3 # 250 KCM

3 # 350 KCM

3 # 500 KCM

3 # 600 KCM

3 # 500 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 600 KCM

3 # 4/0

1 # 4/0

1#500KCM

1 # 2/0

1 # 1/0

1 # 1/0

1 # 2

1 # 2

1 # 12

1#500KCM

1#250KCM

1#350KCM

1 # 1/0

1 # 3/0

1 # 2

1 # 2

1 # 4

1 # 4

1 # 4

1 # 6

1 # 6

1 # 6

1 # 6

1 # 8

1 # 8

1 # 10

1 # 10

1 # 10

1 # 10

1 # 8

1 # 8

3/4"

3/4"

1"

1"

1"

1"

1-1/4"

1-1/4"

1-1/4"

1-1/2"

1-1/2"

4"

4"

4"

4"

4"

3"

3"

4"

4"

4"

4"

4"

4"

4"

3"

2 1/2"

2 1/2"

2"

2"

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

20-D

30-D

40-D

50-D

60-D

70-D

80-D

90-D

100-D

125-D

150-D

175-D

200-D

225-D

250-D

300-D

350-D

400-D

450-D

500-D

600-D

700-D

800-D

1000-D

1200-D

1600-D

2000-D

2500-D

3000-D

4000-D

NOTE:

ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THE AMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).

600V FEEDER SCHEDULE 1Ø 2W

SETSTYPELABEL PHASE GROUNDNEUTRAL CONDUIT

1 2 # 12

1 2 # 10

1 2 # 8

1 2 # 6

1 2 # 6

1 2 # 4

1 2 # 4

1 2 # 2

1 2 # 1

1 2 # 1

20A-2W

200A-2W

175A-2W

150A-2W

125A-2W

100A-2W

80A-2W

60A-2W

50A-2W

30A-2W

40A-2W

70A-2W

90A-2W

2 # 1/0

2 # 2/0

2 # 3/0

1 # 12

1 # 6

1 # 6

1 # 6

1 # 6

1 # 8

1 # 8

1 # 10

1 # 10

1 # 10

1 # 10

1 # 8

1 # 8

3/4"

3/4"

1"

1"

1"

1"

1-1/4"

1-1/4"

1-1/4"

1-1/2"

1-1/2"

2"

2"

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

20-S

30-S

40-S

50-S

60-S

70-S

80-S

90-S

100-S

125-S

150-S

175-S

200-S

NOTE:

ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THE AMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C).

GROUNDING CONNECTION AT SWITCHGEAR/DISTRIBUTION BOARD

WITH NEUTRAL BONDING.

SOLID STATE DEVICE CONNECTED TO THE POWER DISTRIBUTION

SYSTEM

GROUND FAULT PROTECTION DEVICE CONNECTED TO THE POWER

DISTRIBUTION SYSTEM

TRANSIENT VOLTAGE SURGE SUPPRESSION

UL 1449, 3RD EDITION

CONDUIT WIRING DESCRIPTION PER FEEDER SCHEDULE ON OTHER

PLAN

CONCRETE ELECTRICAL PULL BOX WITH LID APPROPRIATE FOR

INSTALLATION LOCATION. LID SHALL BE LABELED "ELECTRICAL" OR

"COMM" ACCORDING TO USE.

CONDUIT UNDERGROUND IN SCHEDULE - 40 PVC UNLESS NOTED

OTHERWISE. VERIFY DEPTH AND TRENCHING WITH G.C.

DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS,

GFCI TYPE) MOUNTED +15" A.F.F. TO CENTER U.O.N.

WEATHERPROOF DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20

AMPS, 125 VOLTS) MOUNTED +15" A.F.F. TO CENTER LINE U.O.N.

SURFACE MOUNTED DUPLEX RECEPTACLE OUTLET, CONVENIENCE.

(20 AMPS, 125 VOLTS) MOUNTED +15" A.F.F. TO BOTTOM OF DEVICE

U.O.N.

ABOVE CEILING, CONCEALED, JUNCTION BOX, WITH COVER, PER

NATIONAL ELECTRICAL CODE (NEC) TABLE 370-b(a), 4" SQUARE DEEP, WITH PLASTER RING.

RECESSED WALL MOUNTED JUNCTION BOX, WITH COVER, PER

NATIONAL ELECTRICAL CODE (NEC) TABLE 370-b(a), 4" SQUARE DEEP, WITH PLASTER RING.

BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE.

(SURFACE MOUNTED)

MAIN SWITCHBOARD, POWER OR LIGHT, FLOOR STANDING

ENCLOSURE, (SEE SINGLE LINE DIAGRAM AND LOAD SUMMARY)

DISCONNECT SWITCH H.P. RATED 600 VOLTS RATED. "F" INDICATES

FUSE TYPE. FUSES PER APPROVED MANUFACTURERS SHOP

DRAWINGS.

COMBINATION STARTER DISCONNECT SWITCH H.P. RATED 600 VOLTS

RATED. "F" INDICATES FUSE TYPE. FUSES PER APPROVED

MANUFACTURERS SHOP DRAWINGS.

HOMERUN TO CIRCUITS #1 AND #3 IN PANEL "A". (CROSSMARKS

INDICATE NUMBER OF PHASES AND NEUTRAL. PROVIDE GROUND

WIRE.)*

3/4" CONDUIT WITH 2 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE

SIZE)

3/4" CONDUIT WITH 3 #10 & 1 #10 GND WIRES (#10 INDICATING WIRE

SIZE)

REMOTE CONTROLLED, ELECTRONICALLY OPERATED CIRCUIT

BREAKER

CONTRACTOR SHALL VERIFY PLANS AND EXISTING DIMENSIONS AND CONDITIONS ON THE JOB

SITE AND SHALL IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES

BEFORE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR THE SAME.

GENERAL DEMOLITION NOTES

1. THE DEMOLITION NOTE REFERENCE PERTAINS TO ALL RELATED SHEETS WHERE EXISTING ELECTRICAL WORK IS INDICATED.

2. THE CONTRACTOR SHALL VISIT THE PROJECT SITE AND MAKE THEMSELVES COMPLETELY FAMILIAR WITH THE EXISTING INSTALLED CONDITIONS.

3. ALL EQUIPMENT OR WORK REQUIRED TO CARRY OUT THE DEMOLITION SCOPE OF WORK IS CONSIDERED TO BE PART OF THE CONTRACTOR SCOPE OF WORK. NO EXTRAS WILL BE CONSIDERED TO PERFORM THE REQUIRED WORK.

4. THE CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM PROJECT MANAGER PRIOR TO THE SCHEDULING OF ANY SHUTDOWN. SUCH PERMISSION MUST BE OBTAINED IN WRITING AND BE GRANTED AT LEAST 14 DAYS PRIOR TO ANY

SCHEDULED SHUTDOWN.

5. DISPOSITION OF EQUIPMENT:

DEMOLISHED EQUIPMENT SHALL BECOME THE PROPERTY OF THE INSTALLING CONTRACTOR AND SHALL BE DISPOSED IN ACCORDANCE WITH PRESIDENTIAL EXECUTIVE ORDER 13514. CONTRACTOR SHALL DISPOSE OF EQUIPMENT AND PROVIDE A CERTIFICATE OF DISPOSAL. CONTRACTOR TO PROVIDE DIGITAL HIGH RESOLUTION PHOTOGRAPH OF TAGS ON ALL EQUIPMENT PRIOR TO DEMOLITION OR REMOVAL FROM THE SITE.

6. THE CONTRACTOR SHALL REMOVE ALL CONDUITS AND CONDUCTORS SERVING DEVICES, PANELBOARDS, SWITCHBOARDS, ETC., WHICH ARE DESIGNATED AS EXISTING TO BE REMOVED, BACK TO THE SOURCE WHEN POSSIBLE. IF THE NATURE OF THE EXISTING INSTALLATION WILL NOT ALLOW REMOVAL OF CONDUIT, THE CONTRACTOR SHALL REMOVE ALL EXPOSED CONDUIT AND ABANDON THE REMAINDER AFTER REMOVING ALL CONDUCTORS ONLY WITH WRITTEN PERMISSION.

7. DEMOLITION AND/OR REMOVAL OF ELECTRICAL EQUIPMENT IN AREAS TO BE REMODELED SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

8. WHERE OUTLETS ARE REMOVED IN EXISTING WALL, REMOVE DEVICES, OUTLETS AND WIRING BACK TO PANELBOARD OR BACK TO NEAREST OUTLET WITH OTHER EXISTING LOAD TO REMAIN.

9. REMOVE ALL CONTROL PANELS, PULL-BOXES, TERMINAL CABINETS, ETC. FOR SYSTEMS TO BE DEMOLISHED EXCEPT WHERE ANY OF THE EXISTING DEVICES, SYSTEMS, CONSOLES, ETC. ARE TO BE REUSED FOR UPGRADE.

10. WHERE DEMO OF EXISTING ELECTRICAL EQUIPMENT IS SHOWN, ALL ASSOCIATED CONDUITS, CONDUCTORS, BOXES, AND ELECTRICAL DEVICES ARE TO BE REMOVED, U.O.N.

11. WHERE REMOVAL OF CONDUIT, PANELBOARDS AND ELECTRICAL DEVICES IS SHOWN, PROVIDE PATCH AND PAINT PER ARCHITECTURAL DETAILS AND SPECIFICATIONS.

12. CONTRACTOR TO INCLUDE RE-USE OR RECYCLING OPTIONS WHERE APPROPRIATE VICE DISPOSAL. THIS IS TO COMPLY WITH PRESIDENTIAL EXECUTIVE ORDER 13514 WHICH REQUIRES REDUCING DISPOSAL OF CONSTRUCTION AND DEMOLITION DEBRIS. CONTRACTOR TO DISPOSE OF ANY EXISTING ITEMS THAT MEET DEFINITION OF HAZARDOUS WASTE OR UNIVERSAL WASTE PER FEDERAL AND STATE ENVIRONMENTAL REGULATIONS.

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E0.1

ELECTRICAL LEGENDS & NOTES

GENERATOR LOAD CALCULATIONSGENERATOR STARTING CALCULATIONSABBREVIATIONS

A AMPERE

AF AMPERE FRAME RATING (CIRCUIT BREAKER)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFU AMPERE FUSE RATING (FUSE)

AIC AMPERE INTERRUPTING CAPACITY

AS AMPERE SWITCH RATING (FUSE)

AT AMPERE TRIP RATING (CIRCUIT BREAKER)

AWG AMERICAN WIRE GAUGE

BKBD BACKBOARD

BLDG BUILDING

BKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CFSD COMBINATION FIRE SMOKE DAMPER

CO CONDUIT ONLY

CONC CONCRETE

CT CURRENT TRANSFORMER

CU COPPER

CL CENTERLINE

DISC DISCONNECT

DSBN DISTRIBUTION SECTION

DN DOWN

DWG DRAWING

EA EACH

EC ELECTRICAL CONTRACTOR

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EXIST, (E) EXISTING

EXO EXTERNAL OPERABLE DISCONNECT

F FUSE

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FF FINISHED FLOOR

FG FINISHED GRADE

FLA FULL LOAD CURRENT

FLUOR FLUORESCENT

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

GND GROUND

HOA HAND-OFF-AUTOMATIC

HP HORSE POWER

HV HIGH VOLTAGE

IDF INTERMEDIATE DISTRIBUTION FRAME

IG ISOLATED/INSULATED GROUND

INCAND INCANDESCENT

ISC SHORT CIRCUIT CURRENT AVAILABLE IN RMS

SYMMETRICAL AMPERES

J-BOX JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILS

KW KILOWATT

KV KILO VOLT

KVA KILO VOLT-AMPERE

LDC LOCAL DISTRIBUTION CABINET

LDF LOCAL DISTRIBUTION FRAME

LCL LONG CONTINUOUS LOAD

LTG LIGHTING

LV LOW VOLTAGE

MFR MANUFACTURER

MAX MAXIMUM

MCC MOTOR CONTROL CENTER

MIN MINIMUM

MH MANHOLE / METAL HALIDE

M/M METER AND MAIN SECTION

MULTI MULTI-METER SECTION

MV MEDIUM VOLTAGE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NEW (N) NEW, TO BE FURNISHED AND INSTALLED BY

CONTRACTOR

NF NON-FUSED

NIC NOT IN CONTRACT

N/L NIGHT LIGHT

NO NUMBER, NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

P POLE

PB PULL BOX

PF POWER FACTOR

PNL PANEL

POC POINT OF CONNECTION

PP POWER POLE

PWR POWER

PVC POLYVINYL CHLORIDE

QUAD QUADRUPLEX

QTY QUANTITY

REQD REQUIRED

REQMT REQUIREMENT

RGS RIGID GALVANIZED STEEL

RMC RIGID METALLIC CONDUIT

RM ROOM

RNC RIGID NONMETALLIC CONDUIT

SHT SHEET

SN SOLID NEUTRAL

SPEC SPECIFICATIONS

SPDT SINGLE POLE, DOUBLE THROW

SPST SINGLE POLE, SINGLE THROW

SW SWITCH

SWBD SWITCHBOARD

TC TIME CLOCK

TEL TELEPHONE

TERM TERMINAL

TP TEMPORARY POLE

TYP TYPICAL

UGPS UNDERGROUND PULL SECTION

UL UNDERWRITERS LABORATORY

UPS UNINTERRUPTIBLE POWER SUPPLY

UON UNLESS OTHERWISE NOTED

V VOLT, VOLTAGE

VA VOLT-AMPERE

VFC VARIABLE FREQUENCY CONTROLLER

VFD VARIABLE FREQUENCY DRIVE

W WATT

WH WATT-HOUR

WP WEATHERPROOF

WT WEATHERTIGHT

WW WIREWAY

XP EXPLOSION PROOF

Z IMPEDANCE

4W FOUR-WIRE

3W THREE-WIRE

5S JUNCTION BOX

(4 11/16" SQUARED X2 1/8" DEEP)

Ø DIAMETER, PHASE

# NUMBER

°C DEGREE CELSIUS

(ETR) EXISTING TO REMAIN

(R) REMOVE EXISTING DEVICE AND ASSOCIATED

CONDUIT AND WIRE

(E) REMOVE EXISTING DEVICE.

REPLACE/RELOCATE AS SHOWN ON PLAN

(N) NEW LOCATION OF RELOCATED DEVICE

SEQUENCE OF OPERATIONS

NOTE: THE SEQUENCE OF OPERATIONS LISTED BELOW REPRESENTS A

GENERAL OVERVIEW OF HOW THE SYSTEM IS EXPECTED TO

OPERATE. THE ELECTRICAL EQUIPMENT MANUFACTURER SHALL

PROVIDE A DETAILED SEQUENCE OF OPERATIONS.

MANUAL TRANSFER TO PERMANENT GENERATOR POWER

MANUAL TRANSFER TO PERMANENT GENERATOR POWER - (CLOSED

TRANSITION):

1. THE OPERATOR STARTS THE GENERATOR AND WAITS UNTIL IT IS

UP TO RATED VOLTAGE AND FREQUENCY.

2. AT THE 3-WAY MANUAL TRANSFER SWITCH, CONFIRM

CONFIGURATION BETWEEN CIRCUIT BREAKERS CONTROLLING THE

PERMANENT GENERATOR AND TRANSFER SWITCHGEAR

CONNECTIONS ARE PROPERLY SET TO SUPPLY THE SWITCHGEAR

WITH GENERATOR POWER.

3. TURN OFF ALL INDIVIDUAL POL PUMP BREAKERS.

4. AFTER GENERATOR ATTAINS RATED VOLTAGE AND FREQUENCY,

SWITCH TO GENERATOR INCOMING POWER VIA KIRK-KEY

INTERLOCK BREAKERS

a. TURN KEY AND OPEN THE UTILITY MAIN BREAKER; RELEASE KEY.

b. TURN KEY AND CLOSE THE GENERATOR MAIN BREAKER; RELEASE

KEY.

5. TURN ON CIRCUIT BREAKER AT SWITCHGEAR FEEDING PANEL 'PA'

TO POWER CIRCUITS FEEDING THE GENERATOR'S CONTROL

PANEL, JACKET WATER HEATER, AND BATTERY CHARGER. PANEL

'PA' IS LOCATED INSIDE THE BUILDING.

6. TURN ON POL PUMP BREAKERS #1, #2, AND #3. ALLOW AT LEAST

FIVE SECONDS BETWEEN START-UP OF EACH PUMP.

7. YOU ARE NOW ON THE GENERATOR SUPPLY.

MANUAL RETURN TO UTILITY POWER - (CLOSED TRANSITION):

1. AFTER UTILITY SUPPLY POWER IS RESTORED, THE OPERATOR

MEASURES AND WAITS UNTIL UTILITY POWER IS UP TO PROPER

VOLTAGE AND FREQUENCY.

2. TURN OFF ALL INDIVIDUAL POL PUMP BREAKERS.

3. TURN OFF CIRCUIT BREAKER AT SWITCHGEAR FEEDING PANEL 'PA'.

4. SWITCH TO UTILITY INCOMING POWER VIA KIRK-KEY INTERLOCK

BREAKERS

a. TURN KEY AND OPEN THE GENERATOR MAIN BREAKER; RELEASE

KEY.

b. TURN KEY AND CLOSE THE UTILITY MAIN BREAKER; RELEASE KEY.

5. YOU ARE NOW ON UTILITY SUPPLY.

6. TURN ON ALL INDIVIDUAL POL PUMP BREAKERS.

LOAD BANK CONNECTION

ENTRY:

1. A LOAD BANK IS CONNECTED TO THE 3-WAY MANUAL TRANSFER

SWITCH.

2. CONNECT THE LOAD BANK CABLES TO THE TRANSFER SWITCH

LOCATED ON THE EXTERIOR OF BUILDING. PER THE TRANSFER

SWITCH CONNECTION SEQUENCE LABEL, CLOSE THE LOAD BANK

TO GENERATOR CIRCUIT BREAKER AND OPEN THE REMAINING

BREAKERS. VERIFY EACH PHASE IS PROPERLY CONNECTED.

3. THE GENERATOR IS STARTED.

4. LOAD CAN NOW BE ADDED FROM THE LOAD BANK CONTROLS.

EXIT:

1. LOADS ARE REMOVED WITH LOAD BANK CONTROLS.

2. SWITCH CIRCUIT BREAKERS CONTROLLING THE PERMANENT

GENERATOR AND TRANSFER SWITCHGEAR CONNECTIONS TO

SUPPLY THE SWITCHGEAR WITH PERMANENT GENERATOR POWER,

PER THE TRANSFER SWITCH CONNECTION SEQUENCE LABEL.

3. ENGINES ARE RUN FOR A COOL DOWN PERIOD THEN SHUTDOWN.

4. DISCONNECT THE LOAD BANK CABLES FROM THE TRANSFER

SWITCH.

TEMPORARY GENERATOR CONNECTION

IN CASE OF A TOTAL LOSS OF ALL ENGINES, THE 3-WAY MANUAL

TRANSFER SWITCH SHALL BE USED TO FEED THE MAIN

SWITCHGEAR BUS BY CONNECTING A TEMPORARY GENERATOR.

THIS SHALL BE A MANUAL OPERATION BY THE OPERATOR.

ENTRANCE INTO UTILITY FAIL:

1. AT THE 3-WAY MANUAL TRANSFER SWITCH, CONFIRM

CONFIGURATION BETWEEN CIRCUIT BREAKERS CONTROLLING THE

TEMPORARY GENERATOR AND TRANSFER SWITCHGEAR

CONNECTIONS ARE PROPERLY SET TO SUPPLY THE SWITCHGEAR

WITH TEMP GENERATOR POWER.

2. TURN OFF ALL INDIVIDUAL POL PUMP BREAKERS.

3. SWITCH TO GENERATOR INCOMING POWER VIA KIRK-KEY

INTERLOCK BREAKERS

a. TURN KEY AND OPEN THE UTILITY MAIN BREAKER; RELEASE KEY.

b. TURN KEY AND CLOSE THE GENERATOR MAIN BREAKER; RELEASE

KEY.

4. TURN ON POL PUMP BREAKERS #1, #2, AND #3. ALLOW AT LEAST

FIVE SECONDS BETWEEN START-UP OF EACH PUMP.

5. THE OPERATOR WILL START THE TEMPORARY GENERATOR.

6. YOU ARE NOW ON THE TEMP GENERATOR SUPPLY.

EXIT FROM UTILITY FAIL:

1. AFTER UTILITY SUPPLY POWER IS RESTORED, THE OPERATOR

MEASURES AND WAITS UNTIL UTILITY POWER IS UP TO PROPER

VOLTAGE AND FREQUENCY.

2. TURN OFF ALL INDIVIDUAL POL PUMP BREAKERS.

3. SWITCH TO UTILITY INCOMING POWER VIA KIRK-KEY INTERLOCK

BREAKERS

a. TURN KEY AND OPEN THE GENERATOR MAIN BREAKER; RELEASE

KEY.

b. TURN KEY AND CLOSE THE UTILITY MAIN BREAKER; RELEASE KEY.

4. YOU ARE NOW ON UTILITY SUPPLY.

5. TURN ON ALL INDIVIDUAL POL PUMP BREAKERS.

6. AFTER ALL LOADS ARE BACK ON UTILITY POWER, THE TEMPORARY

GENERATOR IS MANUALLY SHUT DOWN.

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E0.2

ELECTRICAL NOTES & GEN CALCS

2B1733 - PARTIAL SINGLE LINE DIAGRAM

GENERAL NOTES

DEMOLITION NOTES

1B1733 - PARTIAL DEMOLITION SINGLE LINE DIAGRAM

(E) XFMR

G

N

800AT

3P

1000AT

3P

1000AT

3P

K K

(N) TRANSFER

SWITCHGEAR 1200A

480Y/277V 3Ø 4W

EXISTING

(E) 200A 3P

(E) 200A 3P

(E) 200A 3P

(E) 200A 3P

(E) 200A 3P

(E) 200A 3P800-Y

(E) XFMR

G

N

1000AT

3P

800AT

3P

K K

(E) TRANSFER SWITCHGEAR

1200A 480Y/277V 3Ø 4W 'MS'

(E) 200A 3P

(E) 200A 3P

(E) 200A 3P

(E) 200A 3P

(E) 200A 3P

(E) 200A 3P

EXISTING INCOMING

POWER UTILITY SERVICE

(E) 1200A 480V 3Ø 3W MCC

1000-Y

(1) #3/O CU. BOND TO

EXISTING SERVICE

GROUND.

(E) (E)

SINGLE LINE NOTES

1. ELECTRICAL SERVICE MUST BE MAINTAINED 7-DAYS PER WEEK, 24-HOURS PER DAY (7/24). NO SERVICE INTERRUPTION TO THE EQUIPMENT WILL OCCUR DURING REMOVAL OF THE EXISTING SYSTEM AND INSTALLATION OF THE NEW

SYSTEM.

2. THE TERM HAZARDOUS CONDITION (HAZCON) IS USED TO DESCRIBE WHEN A GIVEN FACILITY IS OPERATING IN A DECREASED STATE OF RELIABILITY OR OPERATIONAL ABILITY. A HAZCON IS DEFINED AS A CONDITION IN WHICH THE NORMAL, ALTERNATE, BACKUP, OR REDUNDANT POWER SOURCE OR MECHANICAL EQUIPMENT IS NOT AVAILABLE, BUT POWER AND COOLING IS NOT INTERRUPTED TO THE LOAD. IT IS THEREFORE NOT A TRUE OUTAGE AT THE LOAD, ALTHOUGH IT MAY BE A PARTIAL OUTAGE OF ONE BUS, CIRCUIT, MECHANICAL SYSTEM ETC.

3. THE CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM THE PROJECT MANAGER PRIOR TO THE SCHEDULING OF ANY HAZCON CONDITION. SUCH PERMISSION MUST BE OBTAINED IN WRITING AND BE GRANTED AT LEAST 30 DAYS

PRIOR TO ANY SCHEDULED HAZCON.

4. PROVIDE TEMPORARY POWER FOR ANY PLANNED OUTAGES AS REQUIRED DURING DEMOLITION OF EQUIPMENT.

EXISTING SWITCHBOARD TO BE DEMO'D.

EXISTING MCC TO BE REFED.

EXISTING FEEDERS AND CONDUITS TO BE DEMO'D BACK TO SOURCE.

EXISTING GENERATOR TO BE DEMO'D.

G 1200A 3P

(E) GENERATOR

(E)

EXISTING

EXISTING

EXISTING SERVICE

GROUND

1200AF 1200AF

N.C. N.O.

1200AF 1200AF 1200AF

(N) (N) (N)N.O. N.C.

1 PROVIDE NEW SWITCHGEAR.

PROVIDE NEW 3-WAY MANUAL TRANSFER SWITCH 'ESL TRIPLE SWITCH' WITH CAM-STYLE RECEPTACLES. PART # ESL

T3D12 X-800C-800H-800H-480-311-S-C OR APPROVED EQUAL.

PROVIDE NEW 562KVA/450KW GENERATOR (MANUFACTURER: MTU 12V1600 DS SERIES OR APPROVED EQUAL).

EXISTING MOTOR CONTROL CENTER TO BE REFED FROM NEW SWITCHGEAR.

EXISTING LOADS TO BE REFED FROM NEW SWITCHGEAR.

PROVIDE CONTROL WIRES FROM GENERATOR TO ANNUNCIATOR PANEL IN 1"C. QUANTITY OF LOW VOLTAGE

CONDUCTORS ARE TO BE PER MANUFACTURER REQUIREMENTS.

CONTRACTOR IS TO PROVIDE NEW GENERATOR ANNUNCIATOR PANEL. COORDINATE EXACT LOCATION WITH

REPRESENTATIVE PRIOR TO INSTALLATION.

PROVIDE 4#6, 2#10, 1#10GRD IN 1"C. FOR GENERATOR BATTERY CHARGER, JACKET WATER HEATER AND

CONTROLLER CIRCUITS.

(1)#1/0 C.U. BOND TO DRIVEN GROUND ROD PER CEC 250.30 AND DO NOT BOND NEUTRAL AND GROUND TERMINALS

INSIDE 250.102(C). OF GENERATOR (NO GROUND LOOP). SIZE PER TABLE 250.66 .

NEW BREAKER LSIG RATED FOR 100% GENERATOR OUTPUT.

CABLING PER MANUFACTURER'S REQUIREMENTS.

EXISTING

ALL EXISTING IS TO REMAIN UNLESS OTHERWISE NOTED.

20A 3P

150A 3P

40A 3P

LEAK DET. SYSTEM TRLR

EXISTING TRANSF/PANEL 'PB'

BOUNDARY LIGHTS

600AT

3P

(E)

1200AF

FUEL

TRANSFER

PUMP

FTP-1 FP-5 FP-4 FP-3 FP-2 FP-1

PUMP #5 PUMP #4 PUMP #3 PUMP #2 PUMP #1

PUMP #5 PUMP #4 PUMP #3 PUMP #2 PUMP #1

EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING

EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING

FUEL

TRANSFER

PUMP

A

3P

0A

3P

A

3P

LE

AK

D

ET

. S

YS

TE

M

TR

LR

EX

IS

TI

NG

T

RA

NS

F/

PA

NE

L '

PB

BO

UN

DA

RY

LI

GH

TS

PQM

(E) 1200A 480V 3Ø 3W MCC

EXISTING

EXISTING

EXISTING

GENERATOR FUEL CALCULATION

SUB BASE FUEL TANK CAPACITY: 1000 GALLONS

DIESEL FUEL CONSUMPTION RATE @ FULL LOAD: 30.5 GALLONS/HR.

APPROX. RUN TIME @ FULL LOAD: 1000/30.5 = 32.7 HRS.

TEMP

GENERATOR

CONNECTION

800A 3P

800-Y

3 (N) GENERATOR 'G1733'

450KW (562KVA) 480V 3Ø 4W

800A MAIN OUTPUT CIRCUIT BREAKER

WEATHERPROOF LEVEL 2 SOUND

ATTENUATED ENCLOSURE

AFC= 4,894

AIC=30,000

REMOTE

ANUNCIATOR

PANEL

PB-22,24,29 8

LOAD BANK

CONNECTION

ESL TRIPLE SWITCH

NEMA 3R

AFC=27940

AIC=30,000

L=50' V.D.=0.12%

L=70' V.D.=0.17%

L=10' V.D.=0.02%

G

30,000 AFC

30,000 AIC

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E0.3

B1733 SINGLE LINE DIAGRAMS

1PANEL SCHEDULES

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E0.5

PANEL SCHEDULES

(ETR) 1200A MCC

(E) 1200A SWITCHGEAR

(E) 550KW GENSET

(ETR) TRANSFORMER

B1733

(ETR) TRANSF.

(ETR) PANEL PB

E1.0 E3.4

E1.0 E3.4

E1.0 E3.4

(ETR) AC UNIT

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E1.0

PROJECT

NORTH

TRUE NORTH

08 8

4 164

GENERAL NOTES

DEMOLITION PLAN NOTES

1. PROVIDE TEMPORARY POWER FOR ANY PLANNED OUTAGES AS REQUIRED DURING DEMOLITION OF EQUIPMENT.

DEMOLISH EXISTING SWITCHGEAR. REFER TO SINGLE LINE DIAGRAM.

DEMOLISH EXISTING GENERATOR.

DEMOLISH EXISTING ABOVE GROUND FUEL TANK.

SCALE: 1/8" = 1'-0"B1733 DEMOLITION SITE PLAN

B1733 DEMOLITION SITE PLAN

(E) 1200A MCC

(N) 1200A TRANSFER SWITCHGEAR

(N) TRIPLE SWITCH

(N) 450KW GENSET

(E) TRANSFORMER

B1733

(E) TRANSF.

(E) PANEL PB1000-Y

1000-Y

(N) ANNUNCIATOR

(E) AC UNIT

1000-Y64

PULLBOX

E2.0 E3.3

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E2.0

B1733 ELECTRICAL SITE PLAN

PROJECT

NORTH

TRUE NORTH

08 8

4 164

GENERAL NOTES

PLAN NOTES

1. EXISTING ELECTRICAL EQUIPMENT TO BE PROTECTED IN PLACE, U.O.N.

2. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE NEMA 3R.

3. ALL EXTERIOR RECEPTACLE OUTLETS SHALL BE GFCI TYPE.

4. PROVIDE HEAVY DUTY DISCONNECT SWITCHES WITH DUAL ELEMENT FUSES TO MATCH MOTOR H.P. RATING.

PROVIDE NEW 1200A TRANSFER SWITCHGEAR. REFER TO SINGLE LINE DIAGRAM.

PROVIDE NEW ESL TRIPLE SWITCH, WITH CAM-STYLE RECEPTACLES. PART # ESL T4D X-1200A H-1000A H-480-311-S-C OR APPROVED EQUAL.

PROVIDE NEW GENERATOR ON NEW CONCRETE PAD FOUNDATION. NEW GENERATOR TO BE 450KW/562KVA, MANUFACTURER: MTU 12V1600 DS SERIES

OR APPROVED EQUAL. REFER TO DETAIL 5 ON SHEET E3.3.

CONCRETE TRENCH FOR CABLE ROUTING BETWEEN EQUIPMENT. TRENCH TO EXTEND BELOW EQUIPMENT. REFER TO DETAIL 2 ON SHEET E3.3.

PROVIDE 4#6, 2#10, 1#10GRD IN 1"C. FOR GENERATOR BATTERY CHARGER, JACKET WATER HEATER AND CONTROLLER CIRCUITS.

PROVIDE CONTROL WIRES FROM GENERATOR TO ANNUNCIATOR PANEL. QUANTITY OF LOW VOLTAGE CONDUCTORS ARE TO BE PER MANUFACTURER

REQUIREMENTS.

CONTRACTOR IS TO TRANSITION FROM NONMETALLIC CONDUIT TO RIGID STEEL CONDUIT AFTER RISING ABOVE GROUND LEVEL.

SCALE: 1/8" = 1'-0"B1733 ELECTRICAL SITE PLAN

3.5 29 7 17 3.5

36 24

SWITCHGEAR ELEVATION - BLDG 1733 1

NOTE:

EQUIPMENT SHOWN IS BASED ON IEM EQUIPMENT

DIMENSIONS. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS OF ALL ELECTRICAL EQUIPMENT LAYOUTS IN

BUILDING 1733, SHOWING THAT THE EQUIPMENT WILL FIT

AND MEET ALL REQUIRED CLEARANCES PRIOR TO

ORDERING EQUIPMENT.

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E3.0

SWITCHGEAR ELEVATIONS

GENERATOR ELEVATION 2

GENERATOR FUEL TANK ELEVATION 1

NOTE:

EQUIPMENT SHOWN IS BASED ON MTU EQUIPMENT

DIMENSIONS. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS OF ALL ELECTRICAL EQUIPMENT LAYOUTS AT

BUILDING 1733 AND 1041 AREAS, SHOWING THAT THE

EQUIPMENT WILL FIT AND MEET ALL REQUIRED

CLEARANCES PRIOR TO ORDERING EQUIPMENT.

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E3.1

GENERATOR ELEVATIONS

APPROVED

BY:

THIS DOCUMENT AND THE DATA DISCLOSED HEREIN

OR WHEREWITH IS NOT TO BE REPRODUCED, USED

OR DISCLOSED IN WHOLE OR IN PART TO ANYONE

WITHOUT THE PERMISSION OF ESL.

24.13

DATE:

FOR FABRICATION BY ESL

CONDUIT ENTRY

AREA

NOTES:

1. FINISH POWDER COAT SERIES W49. SEE TITLE

BLOCK FOR COLOR.

2. WIRING DIAGRAM: 0901-311215

TOP VIEW

104.00

TRIPLE SWITCH

LOGO

PRODUCT LABEL

DANGER LABEL

(2X)

PADLOCKABLE

HANDLE WITH

3-POINT LATCH

(2X)

HINGED DOOR

(2X)

INCOMING &

OUTGOING

WIREWAY

SECTION

CONDUIT ENTRY

AREA

ESL LOGO

PLATE

REMOVABLE

LIFTING EYE

(4X)

3. USE LABEL DRAWING 3112-LBL-480-3P4W

CONDUIT ENTRY

AREA

HINGED SEPARATE

DOOR FOR EMERGENCY

GENERATOR CABLES

VENTILATION LOUVERS

(2X)

LEFT SIDE VIEW

FRONT VIEW

RIGHT SIDE VIEW

C

POWER SYSTEMS

18.58

1200A 480Y/277VAC 50/60Hz 3ɸ +N +G

TRIPLE TRANSFER SWITCH

SOLID BOTTOM

BOTTOM VIEW

QTY=

UNLESS OTHERWISE SPECIFIED:

DIMENSIONS ARE IN INCHES

TOLERANCES:

A GT

12/01/16

3 GL

REV. BY

9/8/2016

DATE

AS BUILT

ES 9/22/2016 ADD 2ND GRND CAMS, ADDED NOTE 3, REVISED LABELING ON DOORS & DEAD FRONTS ON SHT 2

CHG ATS LUGS TO 750kcmil

DESCRIPTION

DECIMALS

.x .03

.XX .01

.XXX .005

BREAK ALL SHARP EDGES

.005 - .010

DIMENSIONS TO BE HELD AFTER

PLATING AND HEAT TREATING

COLOR: WRINKLE GRAY

RAL 7035

REFERENCE:

1050-20A-ASSY

APPROVAL

DATE

DO NOT SCALE DRAWING

ANGULAR

1/2

THICKNESS:

MATERIAL: GALV STEEL

12 GAUGE

ENGINEER

CHECKED

POWER SYSTEMS, INC.

CORONA, CALIFORNIA 92880

(951) 739-7000 (800) 922-4188 eslpwr.com - info@eslpwr.com

PATH

L:\DWG\REEFPART\FABRIC\3112\

DRAWING NUMBER

3112-15

SHEET

ESL CAT.# T3D12-1200C-1200C-1200C-480-311-S-C-X311215

TYPE:3R

EST. WEIGHT: 2310

1200A, 480Y/277VAC

3 PHASE + N + G

TRIPLESWITCH

Lbs.

Corona, CA 92880 <> (800)922-4188 <> (951)739-7000 <> info@eslpwr.com

MFG. DATE:

SHORT CIRCUIT CURRENT RATING: 50,000 RMS SYMMETRICAL AMPS

UL US

R

3NZT

LISTED

.75

(4X)

INCOMING &

OUTGOING

WIREWAY

SECTION

M O

D

EL:

3112-15

THIS DOCUMENT AND THE DATA DISCLOSED HEREIN

OR WHEREWITH IS NOT TO BE REPRODUCED, USED

OR DISCLOSED IN WHOLE OR IN PART TO ANYONE

WITHOUT THE PERMISSION OF ESL.

TOP VIEW

REMOVABLE DEADFRONT

FOR OPERATOR SAFETY

B

TERMINATION LUGS FOR

FEEDER CABLES FROM

PERMANENT GENERATOR.

ACCEPTS (6) #6AWG-300kcmil

WIRES PER PHASE, NEUTRAL

1200A, 3-POLE

CIRCUIT BREAKER

80% RATED

(3X)

SAFETY INTERLOCK

MECHANISM ALLOWS

ONLY ONE CIRCUIT

BREAKER TO BE "ON"

AT A TIME.

INTERLOCK MECHANISM

FEMALE OUTPUT CAMS FOR

(2) GREEN - GROUND

LOAD BANK CONNECTION

(3) YELLOW - PHASE C

(3) ORANGE - PHASE B

(3) BROWN - PHASE A

(3) WHITE - NEUTRAL

B

(DOORS AND DEADFRONTS REMOVED)

FRONT VIEW

SCALE 1 : 26

SECTION B-B

MALE INPUT CAMS FOR

EMERGENCY GENERATOR

CONNECTION

(2) GREEN - GROUND

(3) WHITE - NEUTRAL

(3) BROWN - PHASE A

(3) ORANGE - PHASE B

(3) YELLOW - PHASE C

GROUND LUG

ACCEPTS:

(4) #2-600kcmil (2X)

(2) #2-600kcmil (1X)

FAN

TRANSFORMER

WIRES PER PHASE, NEUTRAL

ACCEPTS (4) 1/0-750kcmil

OUTPUT CABLES TO ATS.

TERMINATION LUGS FOR

20.66

TOP FEED

WIRE BENDING

SPACE

OPERATING

INSTRUCTIONS

(2X)

INTERLOCKED

(3X)

DISCONNECT

HANDLES

HINGED DEADFRONT

WHILE CONNECTING AND

FOR OPERATOR SAFETY

DISCONNECTING WIRING.

PROTECTION

BARRIER

WHILE CONNECTING AND

DISCONNECTING WIRING.

FRONT VIEW

(DOORS REMOVED)

QTY=

UNLESS OTHERWISE SPECIFIED:

DIMENSIONS ARE IN INCHES

TOLERANCES:

A GT

12/01/16

3 GL

REV. BY

9/8/2016

DATE

AS BUILT

ES 9/22/2016 ADD 2ND GRND CAMS, ADDED NOTE 3, REVISED LABELING ON DOORS & DEAD FRONTS ON SHT 2

CHG ATS LUGS TO 750kcmil

DESCRIPTION

DECIMALS

.x .03

.XX .01

.XXX .005

BREAK ALL SHARP EDGES

.005 - .010

DIMENSIONS TO BE HELD AFTER

PLATING AND HEAT TREATING

COLOR: WRINKLE GRAY

RAL 7035

REFERENCE:

1050-20A-ASSY

ANGULAR

1/2

MATERIAL:

THICKNESS:

GALV STEEL

12 GAUGE

ENGINEER

CHECKED

APPROVAL

DATE

DO NOT SCALE DRAWING

1 EST. WEIGHT:

POWER SYSTEMS, INC.

CORONA, CALIFORNIA 92880

(951) 739-7000 (800) 922-4188 eslpwr.com -

PATH

L:\DWG\REEFPART\FABRIC\3112\

info@eslpwr.com

DRAWING NUMBER

3112-15

SHEET

1200A, 480Y/277VAC

3 PHASE + N + G

TRIPLESWITCH

Lbs.

M O

D

EL:

3112-15

TRIPLE TRANSFER SWITCH ELEVATIONS & WIRING DIAGRAM 1

NOTE:

EQUIPMENT SHOWN IS BASED ON ESL EQUIPMENT

DIMENSIONS. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS OF ALL ELECTRICAL EQUIPMENT LAYOUTS AT

BUILDING 1733 AND 1041 AREAS, SHOWING THAT THE

EQUIPMENT WILL FIT AND MEET ALL REQUIRED

CLEARANCES PRIOR TO ORDERING EQUIPMENT.

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E3.2

TRIPLE TRANSFER SWITCH

ELEVATIONS & WIRING DIAGRAM

FINISH GRADE

CADWELD

GROUND ROD DETAIL

CONDUIT & WIRE TO

ADDITIONAL

GROUND (AS

REQUIRED).

NOTES:

1. SIZE OF CONDUCTORS SHALL COMPLY W/CEC 250.66.

2. CHECK RESISTANCE TO GROUND. IF RESISTANCE

EXCEEDS 25 OHMS, INSTALL ADDITIONAL GROUND

RODS W/CONDUCTORS AS SHOWN. SEPARATE AT

LEAST 6'-0" UNTIL RESISTANCE IS REDUCED TO 25

OHMS OR LESS (CEC 250.56)

CONDUIT & WIRE SIZE AS

REQUIRED SEE PLANS.

CONCRETE COVER WITH LIFTING

EYES LABEL "ELECTRICAL"

PRECAST 19-3/4"L X 14-1/4"W

X 12"D. YARD BOX. BROOKS

PRODUCTS #3 1/2PB-21

QUICKSET #EC-17

CONDUIT HUB FOR GROUNDING

BY "THOMAS & BETTS"

3/4" X 10'-0" DRIVEN

"COPPERWELD" GROUND ROD.

GENERATOR SIGNAGE

GENERAL NOTES:

1. PROVIDE OSHA DANGER SIGN. "NO SMOKING WITHIN 50 FEET" SEE SAMPLE ABOVE. SIGN TO BE 20"X24" PRESSURE SENSITIVE VINYL. CHAMPION AMERICA INC. (1-800-521-7000) PN 30612HF. MOUNT ON BOTH

SIDES OF GENERATOR ENCLOSURE.

2. PROVIDE OSHA DANGER SIGN. "THIS EQUIPMENT STARTS AND STOPS AUTOMATICALLY" SEE SAMPLE ABOVE.

SIGN TO BE 14"X10" CHAMPION AMERICA INC. (1-800-521-7000) SENSITIVE VINYL. PN 51368HF, OR APPROVED EQUIVALENT. MOUNT ON BOTH SIDES OF GENERATOR ENCLOSURE. SIGN IS TO BE INSTALLED SO IT IS

VISIBLE TO PEDESTRIANS AT ALL TIMES.

THIS EQUIPMENT

AUTOMATICALLY

STARTS AND STOPS

CAUTION

DANGER

NO SMOKING

WITHIN 50 FEET

GENERATOR

3 5

GENERATOR POWER FEEDER TO TRIPLE TRANSFER SWITCH. SEE

SINGLELINE DIAGRAM FOR MORE INFORMATION.

OUTPUT CIRCUIT BREAKER FEEDER SHALL BE ROUTED BELOW GRADE

AND 'SEALTITE' FLEX CONDUIT PROVIDED FROM GROUND STUB TO

CIRCUIT BREAKER ENCLOSURE.

GENERATOR INSIDE NEMA 3R ENCLOSURE.

FAN-COOLED RADIATOR AND COOLING AIR DISCHARGE.

ENGINE EXHAUST MANIFOLD VERIFY OVERALL HEIGHT OF CRITICAL

SILENCER AND NOTIFY ARCHITECT.

CONTROL PANEL MOUNTED INSIDE GENERATOR SET NEMA 3R

ENCLOSURE.

BATTERY AND CHARGER MOUNTED INSIDE GENERATOR SET NEMA 3R

ENCLOSURE.

JACKET WATER HEATER.

ROUTE CIRCUITS TO 208Y/120V PANEL AS INDICATED ON PLAN.

ROUTE MINIMUM 6#14 IN 1"C FOR TRANSFER SIGNAL.

3/4"C. (1)#3/0 BARE COPPER WIRE TO GROUND ROD. SEE DETAIL 1,

SHEET E3.3

3/4"C. X 10' COPPER GROUND ROD. SEE DETAIL 1, SHEET E3.3

GENERAL NOTES:

1. VERIFY FINAL GENERATOR SET DIMENSIONS WITH SHOP DRAWINGS.

2. MAINTAIN MINIMUM CLEARANCES AS INDICATED.

3. GENERATOR SET ENCLOSURE DOORS SHALL BE FULLY OPENABLE

SIDES WITH CLEARANCES MAINTAINED.

4. SEE DIMENSIONED ARCHITECTURAL PLANS FOR GENERATOR YARD

LAYOUT.

CONSTRUCTION NOTES:

SCHEMATIC GENERATOR PLAN-OUTDOOR

TO TRANSFER

SWITCH

PA-19

PB-22

PA-29

PB-29

SIGNAL

CONDUITS BANK

POWER

CONDUITS BANK

6" WIDE WARNING TAPE

RIGID NONMETALLIC

SIGNAL CONDUIT(S) TYP.

EXACT QUANTITY PER

SINGLE LINE DIAGRAM

AND SITE PLAN.3" MIN.

" M

IN

3" MIN.

6" MIN.

3" MIN.

3" MIN.

3" MIN.

CONCRETE

RIGID NONMETALLIC POWER CONDUIT(S).

EXACT QUANTITY PER SINGLE LINE

DIAGRAM AND SITE PLAN(S).

95% COMPACTED BACK FILL

AC PAVING OR LANDSCAPE TO

EXISTING SURROUNDING AREA

CONDUIT SPACER TYP. ALL

CONDUITS IN TRENCH

BASE CONDUIT

SPACER TYP.

7.5" MIN.

NOTE: MINIMUM TRENCH WIDTH TO BE 24".

3" MIN.

POWER & SIGNAL CONDUIT DUCT BANK

E3.3 E3.3

E2.0 E3.3 E2.1

E3.1 E3.3

E2.0 E3.3

E2.0 E3.3 E2.1

PULLBOX CONSTRUCTION DETAILS

E2.1

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E3.3

ELECTRICAL DETAILS

B1733 - PHOTO DETAIL

EXISTING GENERATOR TO BE DEMO'D

EXISTING FUEL TANK

TO BE DEMO'D

EXISTING SWITCHGEAR

TO BE DEMO'D

EXISTING MOTOR CONTROL

CENTER TO REMAIN

E1.0 E3.4

B1733 - PHOTO DETAIL

E1.0 E3.4

B1733 - PHOTO DETAIL

E1.0 E3.4

E1.1 E3.4

E1.1 E3.4

E1.1 E3.4

DESIGN WEST ENGINEERING

MECHANICAL ELECTRICAL ENERGY CONSULTANTS

San Bernardino, CA 92408 275 W. Hospitality Lane, Suite #100

Phone: 909.890.3700 Fax: 909.890.3770 Email: cadd@designwesteng.com

Architecture | Project Management

E3.4

PHOTO DETAILS

File details come from the government source that posted it. Updated .