Attachment_13_-_Revised_Drawings_dated_15_August_2018.pdf

PDF 2 MB Posted

Attached to
Repair HVAC Combat Camera Facility, B. 241 Federal contract opportunity
Solicitation number
FA4418-18-R-0010
Issued by
Department of the Air Force Air Mobility Command

About this file

Attachment 13 - Revised Drawings dated 15 August 2018 to Amendment 0002 - FA4418-18-R-0010-0002 Repair HVAC Combat Camera B241

View the file

Other files for this federal contract opportunity

Other files attached to Repair HVAC Combat Camera Facility, B. 241, newest first.
File Type Posted
Attachment_14_-_Addendum_5_dated_20_Aug_18.pdf PDF
Amendment_0003_-_FA4418-18-R-0010_Repair_HVAC_Combat_Camera_B241.pdf PDF
MFR_for_Adding_B247_Sketch_dated_17_Aug.pdf PDF
Response_to_Question__18_-_Sketch_of_B247.PDF PDF
Amendment_0002_-_FA4418-18-R-0010-0002_Repair_HVAC_Combat_Camera_B241.pdf PDF
Attendance_Sheet_B241.pdf PDF
FA441818R0010_Questions_and_Answers.pdf PDF
Conf_Site_Visit_Slides_3_Aug_18_B241.pptx PPTX presentation
Attachment_11_-_Addendum_4_dated_15_August_2018.pdf PDF
Attachment_12_-_Revised_Specification_Section_23_07_00_dated_15_Aug_18.pdf PDF
Attachment_10_-_Addendum_3_to_Statement_of_Work_dated_8_Aug_18.pdf PDF
Attachment_9_-_Amendment_1_to_Solicitation_dated_9_Aug_18.pdf PDF
Solicitation_FA441818R0010_Repair_HVAC_Combat_Camera_B241.pdf PDF
Attachment_7_-_Schedule_of_Materials_Submittals_dated_8_Jun_18.pdf PDF
Attachment_4_-_Drawings_dated_12_Aug_16.pdf PDF
Attachment_5_-_Wage_Determination,_SC30_dated_29_Jun_18.pdf PDF
Attachment_2_-_Addendum_1_dated_8_Jun_18.pdf PDF
Attachment_3_-_Addendum_2_dated_8_Jun_18.pdf PDF
Attachment_6_-_Green_Procurement_Plan_dated_8_Jun_18.pdf PDF
Attachment_8_-_ACM_LBP_Report,_B241_dated_9_Nov_15.pdf PDF
Attachment_1_-_Specifications_dated_12_Aug_16.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

R

No.

K

TU

S

A

M K

Y A. U

27045

RCAH OL INN

E

D

P

F E SS IO O

C

N

I L R

L

G

O

M

COM

MO

IT Y

B I L

W

B

A IR AS

I N 62 8T H

SEAL AREASEAL AREASEAL AREASEAL AREA

OFOFOFOFSHEETSHEETSHEETSHEET

DA

TE

PR

EP

AP

'D

RECORD DRAWING DATERECORD DRAWING DATERECORD DRAWING DATERECORD DRAWING DATE

DRAWING SIZE:DRAWING SIZE:DRAWING SIZE:DRAWING SIZE:

PROJECT NO.PROJECT NO.PROJECT NO.PROJECT NO.

DE

PA

RT

ME

NT

F

TH

AIR

OR

CE

PA

PA

PA

AI

BI

LIT

CO

MM

AN

LIT

LIT

LIT

RE

V.

SC

RI

PT

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

CH

BY

DR

AW

DS

GN

Y:

SU

PV

NG

R:

GL

IC

K/

BO

EH

AS

SO

CI

AT

ES

IN

ES

ES

ES

KI

TR

EE

T, ITE

AR

LE

ST

ON

LE

LE

LE

JO

T B A S E

C H A R

LE

S

TO

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

LE

LE

LE

LE

ANSI D(22X34)ANSI D(22X34)ANSI D(22X34)ANSI D(22X34)

33333333

M002M002M002M002

H

VA

C S C H

ED

U

LE

C S C H

ED

U

C S C H

ED

U

C S C H

ED

U

KT

MA

U

-1

2-

15132151321513215132

13131313

IR

MB

AM

ER

A

FA

CI

LIT

Y, A

FA

CI

A

FA

CI

A

FA

CI

BL

DG

1, A

1, A

1, A

1, A

08-12-1608-12-1608-12-1608-12-16

AIR DISTRIBUTION SCHEDULE

MARK DESCRIPTION FACE SIZE H FACE SIZE W NECK SIZE MANUFACTURER MODEL

Supply Air

LS106 LOUVERED FACE SUPPLY 10" 6" 10" x 6" PRICE 620

LS108 LOUVERED FACE SUPPLY 10" 8" 10" x 8" PRICE 620

LS1010 LOUVERED FACE SUPPLY 10" 10" 10" x 10" PRICE 620

PD106 PLAQUE FACE SUPPLY DIFFUSER 12" 12" 6"ø PRICE ASPD

PD206 PLAQUE FACE SUPPLY DIFFUSER 24" 24" 6"ø PRICE ASPD

PD208 PLAQUE FACE SUPPLY DIFFUSER 24" 24" 8"ø PRICE ASPD

PD210 PLAQUE FACE SUPPLY DIFFUSER 24" 24" 10"ø PRICE ASPD

PD212 PLAQUE FACE SUPPLY DIFFUSER 24" 24" 12"ø PRICE ASPD

Return Air

PF222 PERFORATED RETURN GRILLE 24" 24" 22" x 22" PRICE APDDR

SR1210 SIDEWALL RETURN GRILLE 12" 10" 12" x 10" PRICE 630

SR1616 SIDEWALL RETURN GRILLE 16" 16" 16" x 16" PRICE 630

SR3220 SIDEWALL RETURN GRILLE 32" 20" 32" x 20" PRICE 630

Exhaust Air

LE222 PERFORATED EXHAUST GRILLE 24" 24" 22" x 22" PRICE APDDR

EXHAUST FAN SCHEDULE

MARK

CAPACITY

CFM

ESP (INCHES

WG) TYPE FRPM SONES MANUFACTURER MODEL

EF-1 50 0.25 CABINET 675 1.1 GREENHECK SP-B70

EF-2 70 0.25 CABINET 700 1.3 GREENHECK SP-B90

EF-3 560 0.25 INLINE 1285 5.6 GREENHECK SQ-95-VG

EF-4 200 0.25 CABINET 900 2 GREENHECK SP-A200

EF-5 240 0.25 CABINET 1000 3 GREENHECK SP-A250

EF-6 150 0.25 INLINE 1457 3.8 GREENHECK SQ-70-VG

VAV AIR HANDLING UNIT SCHEDULE

AIR CAPACITY

CFM FAN COOLING COIL PRE-HEATING COIL

MANUFACTURER MODELCFM CFM OA HP BHP

EXTERNAL

STATIC

TOTAL

STATIC TOTAL MBH

SENSIBLE

MBH EAT DB EAT WB LAT DB LAT WB GPM EWT LWT COIL PD

MBH EAT DB LAT DB EWT LWT GPM COIL WPD

AHU-1 11,165 1,530 15.0 9.53 1.75 2.95 376.9 270.8 77.9 65.8 54.7 54.2 76.5 45 55 9.3 52.1 45 60 180 150 3.5 0.5 DAIKIN APPLIED CAH021GDAC

AHU-2 5870 1000 5.0 4.0 1.75 2.59 241.8 165.9 80 67 54.2 53.6 47.0 45 55 18.3 28.6 40 55 180 150 3.0 0.3 DAIKIN APPLIED CAH008GDAC

VAV TERMINAL UNIT SCHEDULE

PRIMARY INLET

(INCHES)

COOLING

DESIGN CFM

MIN CFM

AIR PD (IN.

W.G.)

HEATING

CFM TOTAL KW EAT °F LAT °F MANUFACTURER MODEL

VAV-1 8 575 175 0.25 410 3.9 55 85 PRICE SDV5

VAV-2 6 425 130 0.25 275 2.6 55 85 PRICE SDV5

VAV-3 6 300 100 0.25 205 1.9 55 85 PRICE SDV5

VAV-4 8 750 225 0.25 500 4.7 55 85 PRICE SDV5

VAV-5 6 250 75 0.25 230 2.2 55 85 PRICE SDV5

VAV-6 8 475 145 0.25 270 2.6 55 85 PRICE SDV5

VAV-7 10 825 250 0.25 490 4.7 55 85 PRICE SDV5

VAV-8 6 350 105 0.25 130 1.2 55 85 PRICE SDV5

VAV-9 8 500 150 0.25 335 3.2 55 85 PRICE SDV5

VAV-10 8 625 175 0.25 175 1.7 55 85 PRICE SDV5

VAV-11 6 350 105 0.25 190 1.8 55 85 PRICE SDV5

VAV-12 8 390 150 0.25 335 3.2 55 85 PRICE SDV5

VAV-13 10 1200 360 0.25 655 6.2 55 85 PRICE SDV5

VAV-14 10 1200 360 0.25 655 6.2 55 85 PRICE SDV5

VAV-15 12 1530 465 0.25 720 6.8 55 85 PRICE SDV5

VAV-16 6 300 105 0.25 210 2 55 85 PRICE SDV5

VAV-17 6 300 90 0.25 150 1.4 55 85 PRICE SDV5

VAV-18 6 300 90 0.25 150 1.4 55 85 PRICE SDV5

VAV-134 10 850 255 0.25 155 2.6 55 85 PRICE SDV5

VAV-135 4 200 100 0.25 120 1.1 55 85 PRICE SDV5

VAV-137 8 500 150 0.25 410 3.9 55 85 PRICE SDV5

VAV-210 14 2040 615 0.25 1570 15.0 55 85 PRICE SDV5

VAV-211 8 650 195 0.25 520 4.9 55 85 PRICE SDV5

VAV-215 8 650 195 0.25 520 4.9 55 85 PRICE SDV5

VAV-219 14 2040 615 0.25 1450 13.8 55 85 PRICE SDV5

NOTES:

1. REFER TO ELECTRICAL DRAWINGS FOR VOLTAGE INFORMATION.

2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

3. INLET SIZE PER MANUFACTURER. VAV BOX INLET SIZE SHALL BE SAME SIZE AS INLET UNLESS OTHERWISE NOTED ON DRAWINGS. PROVIDE

PROPER EQUIVALENT LENGTH DUCT DIAMETER PER MANUFACTURER'S REQUIREMENTS.

4. TERMINAL UNITS SHALL BE SUPPLIED WITH SINGLE POINT POWER CONNECTION WITH UNIT MOUNTED CONTROL TRANSFORMER.

5. CONTROLS FOR THE TERMINAL UNITS SHALL BE BACNET COMPLIANT AND SHALL BE FACTORY MOUNTED.

6. VAV BOXES SHALL HAVE SCR ELECTRIC COILS.

VRF MINI-SPLIT UNIT SCHEDULE

INDOOR

OUTDOOR

MBH

MBH

HEATING

MBH MANUFACTURER MODEL

AH-122 CU-121 7.5 6.4 8.5 DAIKIN FXAQ07PVJU /

RXYMQ48PVJU

AH-121 CU-121 7.5 6.4 8.5 DAIKIN FXAQ07PVJU /

AH-124 CU-121 7.5 6.4 8.5 DAIKIN FXAQ07PVJU /

AH-126 CU-121 7.5 6.4 8.5 DAIKIN FXAQ07PVJU /

AH-125 CU-121 7.5 6.4 8.5 DAIKIN FXAQ07PVJU /

AH-206 CU-121 7.5 6.4 8.5 DAIKIN FXAQ07PVJU /

EXPANSION TANK SCHEDULE

MARK SYSTEM

TANK VOLUME

(GALLONS)

ACCEPTANCE

VOLUME

WORKING

PRESSURE

(PSIG) MANUFACTURER MODEL

ET-1 CHILLED WATER 10.9 2.4 125 BELL & GOSSETT D-20

ET-2 HOT WATER 21.7 11.3 125 BELL & GOSSETT D-40

AIR SEPARATOR SCHEDULE

SYSTEM

CONNECTION GPM

PRESSURE DROP AT

MAX FLOW MANUFACTURER MODEL

AS-1 CHILLED WATER 108 2.0 FT OF HEAD BELL & GOSSETT ROLAIRTROL RL-3

AS-2 HOT WATER 22 2.0 FT OF HEAD BELL & GOSSETT ROLAIRTROL RL-3

COMPUTER ROOM AIR CONDITIONER SCHEDULE

OUTDOOR

MARK CFM

TOTAL

MOTOR

HP

COOLING COIL

MANUFACTURER MODELTOTAL MBH

MBH EAT DB EAT WB LAT DB LAT WB

CRAC-1 CRC-1 3080 0.5 32.5 28.5 80.0°F 64.0°F 58.5°F 55.5°F LIEBERT MMD36E/PFH037AL

2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

GAS DOMESTIC WATER HEATER SCHEDULE

STORAGE

INPUT CAPACITY

(MBH)

RECOVERY @

100°F (GPH) FUEL

GAS SUPPLY

SIZE

VENT

DIAMETER MIN. EFF. MANUFACTURER MODEL

WH-1 130 700 815 NG 1" 6" 96% PVI 70 L 130A-GCML

1. WATER HEATER SHALL INCLUDE AN ASME RATED T&P RELIEF VALVE AND DRAIN VALVE.

2. ALL ADDITIONAL APPURTENANCES INCLUDING PIPE, HANGERS, ADHESIVES ETC. SHALL BE INSTALLED TO PROVIDE A SAFE, SECURE AND OPERATING

SYSTEM.

3. SEE ELECTRICAL DOCUMENTS FOR VOLTAGE AND AMPERAGE REQUIREMENTS.

4. PROVIDE MANUFACTURER'S CONDENSATE NEUTRALIZATION KIT.

5. PROVIDE MANUFACTURER'S CONTROLS KIT FOR HIGH AND LOW GAS PRESSURE SWITCHES, AND CONNECTION TO BMS.

6. PROVIDE FACTORY AUTHORIZED STARTUP.

7. PROVIDE VENT AND DIRECT AIR INLET TERMINATION CAPS FOR SIDEWALL INSTALLATION.

8. PROVIDE UL LISTED CENTROTHERM INNOFLUE OR STAINLESS STEEL COMBUSTION PIPING PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

2. PROVIDE SEACOAST COATING ON OUTDOOR CONDENSING UNIT.

3. PROVIDE AIR HANDLING UNITS WITH CONDENSATE PUMPS.

1. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF ALL CEILING MOUNTED AIR DISTRIBUTION DEVICES.

2. COORDINATE MOUNTING TYPE AND ACCESSORIES WITH ARCHITECTURAL CEILING GRID.

3. COORDINATE AIR DISTRIBUTION LOCATIONS WITH ALL OTHER TRADES.

4. AIR DISTRIBUTION TO BE ALUMINUM CONSTRUCTION WITH BAKED ENAMEL "WHITE" FINISH.

5. SURFACE MOUNTED AIR DISTRIBUTION DEVICES SHALL BE MOUNTED WITHOUT VISIBLE FASTENERS.

6. ALL CEILING DIFFUSERS SHALL BE 4-WAY BLOW UNLESS NOTED OTHERWISE.

ELECTRIC HEATER SCHEDULE

MARK CAPACITY KW BASIS OF DESIGN MODEL

UH-1 5 MARKEL F2F503N

1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. FURNISH WITH ROOF CURB AND INSECT SCREEN.

3. GRAVITY DAMPER SHALL BE PROVIDED WITH A MOTORIZED DAMPER TIED INTO

BUILDING HVAC EMERGENCY SHUT-OFF SYSTEM.

1. SEE ELECTRICAL DRAWINGS FOR VOLTAGE INFORMATION.

2. FURNISH WITH MANUFACTURER PROVIDED SUPPORT BRACKET.

3. FURNISH WITH INTEGRAL THERMOSTAT.

4. FURNISH WITH INTEGRAL POWER DISCONNECT SWITCH.

GRAVITY VENTILATOR SCHEDULE

AIR FLOW

RATE (CFM)

MAX STATIC

PRESSURE LOSS SIZE BASIS OF DESIGN MODEL

GV-1 1150 0.011 24 GREENHECK GRSR

GV-2 120 0.011 8 GREENHECK GRSR

LOUVER SCHEDULE

AIR PRESSURE

DROP

VELOCITY CFM

DIMENSION

FREE AREA

HEIGHT

WIDTH

SCHEDULE

NOTES

BASIS OF

DESIGN MODEL

L-1 0.01 in-wg 286 FPM 1400 4.90 SF 24" 72" INTAKE RUSKIN EME520DD

L-2 0.04 in-wg 478 FPM 575 1.20 SF 24" 20" INTAKE RUSKIN EME520DD

1. LOUVERS SHALL BE EXTRUDED ALUMINUM.

2. COORDINATE FINISH WITH ARCHITECT DURING SUBMITTAL PHASE.

1. SEE SPECIFICATIONS FOR MORE INFORMATION.

2. SEE ELECTRICAL DRAWINGS FOR VOLTAGE INFORMATION.

3. DIRECT DRIVE FANS SHALL BE SUPPLIED WITH SPEED CONTROLLER.

4. EXHAUST FANS SHALL BE CONTROLLED BY OCCUPANCY SENSOR IN SPACE.

2. SEE ELECTRICAL DRAWINGS FOR VOLTAGE INFORMATION.

3. UNIT SHALL BE FURNISHED WITH VARIABLE FREQUENCY DRIVE TO ALLOW VARIABLE SPEED OPERATION.

4. FURNISH WITH SMOKE DETECTORS IN SUPPLY AND RETURN DUCTS.

V

IS

/8

/1

SEQUENCE OF OPERATION:AHU-1, 2

VARIABLE AIR VOLUME COOLING ONLY AHU – SEQUENCE OF OPERATION

A PROGRAMMABLE CONTROLLER CAPABLE OF STAND-ALONE OPERATION WILL CONTROL THE UNIT. THE VAV AIR HANDLER WILL BE ENABLED AND DISABLED AS REQUESTED BY ITS

ASSOCIATED VAV BOXES.

GENERAL: THIS UNIT IS A VARIABLE AIR VOLUME AHU WITH VARIABLE FREQUENCY DRIVES ON THE SUPPLY FAN, DEHUMIDIFICATION CONTROL, A CHILLED WATER COIL FOR COOLING, AND A HOT WATER COIL IN THE PREHEAT POSITION FOR HEATING. REHEAT, AS REQUIRED FOR SPACE TEMPERATURE CONTROL, WILL BE ACCOMPLISHED AT THE TERMINAL UNIT

(“VAV BOX”).

FAN CONTROL (GENERAL): THE SUPPLY FAN WILL BE CONTROLLED THROUGH A PANEL INTEGRAL WITH THE RESPECTIVE VARIABLE FREQUENCY DRIVE (VFD). WHEN THE RESPECTIVE VFD CONTROL PANEL SWITCH IS IN THE “REMOTE/AUTO” POSITION, THE SUPPLY FAN WILL BE STARTED AND STOPPED AND FAN SPEED WILL BE CONTROLLED THROUGH THE BAS. WHEN THE RESPECTIVE SWITCH IS IN THE “KEYPAD/HAND” POSITION, THE ASSOCIATED FAN WILL RUN AND THE FAN SPEED MAY BE CONTROLLED THROUGH A MANUAL SPEED ADJUSTMENT INTEGRAL TO THE VFD CONTROL PANEL. WHEN THE STARTING CIRCUIT IS ACTIVATED BY THE BAS OR BY PLACING THE SELECTOR SWITCH IN “KEYPAD/HAND” POSITION, THE VFD WILL START UNLOADED AND WILL RAMP UP TO SPEED AS PROGRAMMED INTO THE VFD’S SAFETY CIRCUIT.

UNOCCUPIED MODE: THE SUPPLY FAN WILL BE INDEXED OFF AND WILL REMAIN OFF UNTIL THE START OF NIGHT HIGH LIMIT, NIGHT LOW LIMIT, WARMUP, COOLDOWN, OR OCCUPIED MODE. THE RETURN AIR DAMPER WILL REMAIN OPEN AND THE OUTSIDE AIR DAMPER WILL REMAIN CLOSED.

NIGHT LOW LIMIT MODE (NLL): ON A REQUEST FOR NIGHT LOW LIMIT OPERATION FROM MINIMUM NUMBER OF VAV ZONES (ADJ.) THE SUPPLY FAN VFD’S AND SUPPLY AIR TEMPERATURE CONTROL WILL BE ENABLED. DURING NLL MODE THE SUPPLY AIR TEMPERATURE SETPOINT WILL BE SET TO THE WARMUP SUPPLY AIR TEMPERATURE SETPOINT (70° F, ADJ.). WHEN THE NUMBER OF VAV ZONES REQUESTING NLL DROPS BELOW THE MINIMUM REQUIRED OR OCCUPIED MODE BECOMES ACTIVE, NLL WILL BE DISABLED.

NIGHT HIGH LIMIT MODE (NHL): ON A REQUEST FOR NIGHT HIGH LIMIT OPERATION FROM A MINIMUM NUMBER OF VAV ZONES (ADJ.) THE SUPPLY FAN VFD’S AND SUPPLY AIR TEMPERATURE CONTROL WILL BE ENABLED. WHEN THE NUMBER OF VAV ZONES REQUESTING NHL DROPS BELOW THE MINIMUM REQUIRED OR OCCUPIED MODE BECOMES ACTIVE, NHL WILL BE DISABLED.

WARMUP MODE: ON A REQUEST FOR WARMUP OPERATION FROM A MINIMUM NUMBER OF VAV ZONES (ADJ.) THE SUPPLY FAN VFD’S AND SUPPLY AIR TEMPERATURE CONTROL WILL BE ENABLED. DURING WARMUP MODE THE SUPPLY AIR TEMPERATURE SETPOINT WILL BE SET TO THE WARMUP SUPPLY AIR TEMPERATURE SETPOINT (70°F, ADJ.). WHEN THE OCCUPIED MODE BECOMES ACTIVE WARMUP MODE WILL BE DISABLED AND THE UNIT WILL BEGIN OCCUPIED MODE CONTROL.

COOLDOWN MODE: ON A REQUEST FOR COOLDOWN OPERATION FROM A MINIMUM NUMBER OF VAV ZONES (ADJ.) THE SUPPLY FAN VFD’S AND SUPPLY AIR TEMPERATURE CONTROL WILL BE ENABLED. WHEN OCCUPIED MODE BECOMES ACTIVE THE COOLDOWN CONTROL LOOP WILL BE DISABLED AND THE UNIT WILL BEGIN OCCUPIED MODE CONTROL.

AFTERHOURS MODE: ON A REQUEST FOR AFTERHOURS OPERATION FROM ANY VAV ZONE, THE SUPPLY FAN VFD’S AND SUPPLY AIR TEMPERATURE CONTROL WILL BE ENABLED. ALL OTHER VAV’S ASSOCIATED WITH THAT AHU, WILL BE ENABLED IN OCCUPIED MODE. WHEN THE OVERRIDE TIMER EXPIRES OR OCCUPIED MODE BECOMES ACTIVE, AFTERHOURS MODE

WILL BE DISABLED.

OCCUPIED MODE: ON A REQUEST FOR OCCUPIED MODE OPERATION FROM A MINIMUM NUMBER OF VAV ZONES (ADJ.) THE SUPPLY FAN VFD’S AND SUPPLY AIR TEMPERATURE CONTROL WILL BE ENABLED. DURING OCCUPIED MODE THE OUTSIDE AIR DAMPER WILL MODULATE OPEN TO ITS MINIMUM POSITION (10%, ADJ.), AS SPECIFIED BY THE BALANCE

CONTRACTOR.

SUPPLY FAN SPEED MODULATION: THE SUPPLY FAN SPEED WILL MODULATE AS REQUIRED TO MAINTAIN THE STARTUP/MANUAL DUCT STATIC PRESSURE SETPOINT (1.5”WC. ADJ.).

ONCE ENABLED, THE MINIMUM SUPPLY FAN SPEED SIGNAL WILL BE 20% (ADJ.). IN MANUAL MODE, THE STATIC PRESSURE SETPOINT WILL REMAIN AT THE STARTUP/MANUAL SETPOINT.

IN AUTOMATIC MODE, THE STATIC PRESSURE SETPOINT WILL BE RESET LINEARLY BETWEEN 0.5”WC. (ADJ.) AND 2.0”WC. (ADJ.) BASED ON THE HIGHEST NEED MORE AIR SIGNAL FROM THE ASSOCIATED VAV BOXES. IF THE NEED MORE AIR SIGNAL IS HIGH, THEN THE STATIC PRESSURE SETPOINT WILL BE RESET TOWARD THE MAXIMUM. IF THE NEED MORE AIR SIGNAL IS LOW, THEN THE STATIC PRESSURE SETPOINT WILL BE RESET TOWARD THE MINIMUM.

SUPPLY AIR TEMPERATURE CONTROL: STAGES OF MECHANICAL COOLING WILL BE ENABLED AND DISABLED, AS REQUIRED, TO MAINTAIN THE CURRENT SUPPLY AIR TEMPERATURE SETPOINT. IN MANUAL MODE, THE SUPPLY AIR SETPOINT WILL REMAIN AT THE STARTUP/MANUAL SETPOINT. IN AUTOMATIC MODE, THE SUPPLY AIR TEMPERATURE SETPOINT WILL BE RESET LINEARLY BETWEEN 55°F (ADJ.) AND 65°F (ADJ.) BASED ON THE HIGHEST COOLING SIGNAL FROM THE ASSOCIATED VAV BOXES. IF THE COOLING SIGNAL IS HIGH, THEN THE SUPPLY AIR TEMPERATURE SETPOINT WILL BE RESET TOWARD THE MINIMUM. IF THE COOLING SIGNAL IS LOW, THEN THE SUPPLY AIR TEMPERATURE SETPOINT WILL BE RESET TOWARD THE MAXIMUM. ADDITIONAL STAGES OF COOLING WILL NOT BE ENABLED OR DISABLED IF THE SUPPLY AIR TEMPERATURE IS WITHIN +/- 5°F OF THE CURRENT SETPOINT.

THIS IS DONE TO PREVENT EXCESSIVE CYCLING OF MECHANICAL EQUIPMENT.

MINIMUM OUTSIDE AIRFLOW CONTROL: THE OUTSIDE AIR DAMPER WILL MODULATE AS REQUIRED TO MAINTAIN THE OUTSIDE AIRFLOW SETPOINT AS DETERMINED BY THE BALANCE CONTRACTOR. MINIMUM OUTSIDE AIRFLOW CONTROL WILL ONLY BE ENABLED DURING OCCUPIED OR AFTERHOURS MODE OPERATION. PROVIDE FULL MODULATING DAMPER

MOTORS.

ALARMS: THE FOLLOWING SOFTWARE ALARMS WILL BE GENERATED AND DISPLAYED AT THE OPERATOR’S WORKSTATION:

· HIGH SUPPLY AIR TEMP (5°F GREATER THAN CURRENT SETPOINT)

· LOW SUPPLY AIR TEMP (5°F LESS THAN CURRENT SETPOINT)

· BAD SUPPLY TEMP SENSOR (GREATER THAN 180°F OR LESS THAN -20°F)

· SUPPLY FAN FAILURE (COMMAND WITH NO STATUS)

· SUPPLY FAN “IN HAND” (STATUS WITH NO COMMAND)

· FILTER ALARM (WHEN RUNTIME EXCEEDS 3000 HOURS (ADJ.),

SAFETIES: THE FOLLOWING SAFETIES WILL BE MONITORED AS A STATUS INPUT AND WILL BE DISPLAYED AT THE OPERATOR’S WORKSTATION:

· HIGH PRESSURE SWITCH: A HIGH PRESSURE SWITCH WILL BE INSTALLED IN THE SUPPLY DUCTWORK TO SHUTDOWN THE SUPPLY FAN (HARDWIRE INTERLOCK) WHEN THE

SUPPLY DUCT PRESSURE EXCEEDS 4.0”WC. (MANUALLY ADJUSTABLE AND RESET).

EMERGENCY SHUT-OFF BUTTON SHALL TURN OFF AHU AND SHUT ALL OUTSIDE AIR DAMPERS AND GRAVITY VENTILATOR DAMPERS WITHIN 30 SECONDS OF SWITCHING.

UNIT SHUTDOWN HARDWARE POSITIONS: WHEN THE AHU IS COMMANDED OFF, THE COOLING AND HEATING COILS WILL BE DISABLED. DAMPERS WILL BE COMMANDED TO THEIR

NORMAL POSITIONS (BYPASS DAMPER “CLOSED”).

TS

VAV POINTS LISTAHU POINTS LIST

LEGEND

RETURN

AHU MIXING

BOX

VFD

FANC

EMCS

SUPPLY

AHU

SPACE

T

ENERGY MANAGEMENT CONTROL SYSTEM UNIT CONTROLLER

MOTORIZED ACTUATOR

TEMPERATURE SENSOR

CURRENT SWITCHC

VAV

BOX

FLOW RING SENSOR

(BY VAV BOX

MANUFACTURER)

VARIABLE FREQUENCY DRIVEVFD

ELECTRIC

REHEAT

COIL

LOCATE 2/3

OF THE WAY

DOWN THE

LENGTH OF

DUCT.

FIRE

ALARM

PANEL,

TYP.

PRESSURE SENSORP

AI-1 AIR FLOW SENSOR

AI-2 SPACE TEMP SENSOR

AI-3 DAMPER POSITION

AI-4 MINIMUM CFM

AI-5 MAXIMUM CFM

AO-1 DAMPER CONTROL

DI-1 AHU FAN STATUS (CURRENT)

AI-2 DISCHARGE AIR TEMP

AI-3 DUCT STATIC PRESSURE

DI-2 FIRE ALARM PANEL CONTACT

AI-1 MIXED AIR TEMP

AO-5 VARIABLE FREQUENCY DRIVE

DO-1 START/STOP AHU

AO-1 DISCHARGE STATIC PRESSURE SETPOINT

AO-2 SUPPLY AIR TEMP SETPOINT

AO-3 OA MOTORIZED DAMPER

AO-4 RA MOTORIZED DAMPER

AI-4 OUTDOOR AIR FLOWRATE

(CFM)

S SMOKE DETECTOR

SCHEMATIC DIAGRAM:AHU-1, 2

PRE-HEAT

TO CHILLER

TO BOILER

OUTSIDE

INTAKE

HIGH STATIC

SENSOR

EMERGENCY SHUTDOWNES

ES ES ES

LOBBY

MOBILITY

CORRIDOR

DUCT CONSTRUCTION SCHEDULE

DUCT TYPE DUCT LOCATION

MEDIUM

DOWNSTREAM OF AHU

AND UPSTREAM OF VAV'S

SEAL

CLASS

SEALING REQUIREMENTS

ALL TRANSVERSE JOINTS,

LONGITUDINAL SEAMS, AND

DUCT WALL PENETRATIONS

CLASS

4 in-wg

LEAKAGE CLASS

RECTANGULAR

ROUND

6 CFM PER 100 SF

3 CFM PER 100 SF

PA

PA

PA

LIT

LIT

LIT

LIT

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

ES

ES

ES

ES

LE

LE

LE

LE

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

LE

LE

LE

LE

M003M003M003M003

C S C H

ED

U

C S C H

ED

U

C S C H

ED

U

C S C H

ED

U

14141414

A

FA

CI

A

FA

CI

A

FA

CI

A

FA

CI

1, A

1, A

1, A

1, A

FAN COIL UNIT SCHEDULE

AIR CAPACITY

CFM

EXTERNAL

COOLING COIL HEATING COIL

MANUFACTURER MODELCFM CFM OA TOTAL MBH

MBH EAT DB EAT WB LAT DB LAT WB GPM EWT LWT COIL PD

MBH EAT DB LAT DB EWT LWT GPM

FCU-1 1000 125 0.75 30.5 23.4 75 63 54 53 6.1 45 55 0.13 44.8 70 110 180 160 4.6 ENVIRO-TEC HPP

NOT TO SCALE

M003

1 AHU-1, 2 SEQUENCE OF OPERATIONS

PUMP SCHEDULE

MARK GPM

PUMP

HEAD MOTOR HP RPM TYPE VFD MANUFACTURER MODEL

BP-1 10 17.5 1/12 2650 IN-LINE NO BELL & GOSSET PL-30

CWP-1 130 65 5 1750 END

SUCTION

YES BELL & GOSSET E-1510

CWP-2 130 65 5 1750 END

HWP-1 11 45 1.5 1750 END

HWP-2 11 45 1.5 1750 END

2. SEE ELECTRICAL DRAWINGS FOR VOLTAGE INFORMATION.

3. UNIT SHALL BE FURNISHED WITH THERMOSTAT FOR ADJUSTMENT AS SPACE IS OCCUPIED.

BOILER SCHEDULE

MARK CAPACITY GPM EWT °F LWT °F MANUFACTURER MODEL

B-1 175 MBH 11.1 150 180 LOCHINVAR KBN400

3. PROVIDE WITH CONDENSATE NEUTRALIZER KIT FOR DISCHARGE INTO FLOOR

DRAIN.

4. PROVIDE WITH MANUFACTURER PROVIDED CONCENTRIC VENT KIT FOR DIRECT

VENT INTAKE AND FLUE PENETRATIONS THROUGH WALL.

INFRARED ELECTRIC HEATER SCHEDULE

MARK BTU/h OUTPUT MANUFACTURER MODEL

IH-1 4947 MARKEL FSS-14

IH-2 4947 MARKEL FSS-14

IH-3 4947 MARKEL FSS-14

IH-4 4947 MARKEL FSS-14

3. INFRARED HEATERS SHALL BE PROVIDED WITH REMOTE LINE

VOLTAGE THERMOSTATS.

FEDCBA

(E) BOILER

(E) CHILLED WATER PUMPS

(E) HYDRONIC HEATING PUMPS

SHALL BE DEMOLISHED

(E)WH

FCU-4

FCU-1

FCU-2

EXISTING

CHILLER TO

REMAIN

EXISTING MINI-SPLIT

SHALL REMAIN

CONTRACTOR SHALL VERIFY WHICH

CONDENSING UNITS ARE SERVING THE

SIMULATION ROOM PRIOR TO DEMOLITION.

EXISTING CONDENSING UNITS SERVING

SIMULATION ROOM SHALL REMAIN AND

OTHERS SHALL BE DEMOLISHED.

EXISTING SPLIT SYSTEM HEAT

PUMPS SHALL BE REMOVED

AND RETURNED TO OWNER.

(E) WATER HEATER SHALL

BE DEMOLISHED

EXISTING CHILLED WATER

LINES SHALL BE CUT AND

CAPPED AT GRADE OR RIGHT

ABOVE SLAB AT CHILLER AND

IN MECHANICAL ROOM.

EXISTING DUCTWORK AND

AIR DICTRIBUTION SERVING

ROOMS 135 AND 136 SHALL

BE DEMOLISHED.

DISCONNECT EXISTING DUCTWORK FROM SPLIT

SYSTEM AIR HANDLING UNITS SERVING THESE

SPACES. AIR HANDLERS SHALL BE TURNED OVER

TO OWNER. DEMOLISH DUCTWORK, CONDENSATE

AND REFRIGERANT LINES. CAP AND SEAL ON BOTH

SIDES OF EXTERIOR WALL PENETRATION.

TEAM B

OFFICE

CONFERENCE

ROOM

114B

114A

1ST SGT.

CSS

UDM

DO

CHIEF

COMMANDER

COMMANDERS

MENS

SHOWER

LOCKER

DTS

STATIONS

BREAK RM

AVID 2

AVID 1

AVID 4

AVID 3

AVID

EIC

COORIDOR

WOMENS

MECH

SERVER

RM

133A

WORKOUT

SIMULATION

AREA

LOGISTICS

NCOIC

NETWORK

MAINTENANCE

COMSEC

119A

ARMORY

137A

BUDGET

FLYING OP.

UNITS AND ASSOCIATED

CONDENSER UNITS

SHALL BE REMOVED

AND RETURNED TO

OWNER. DEMOLISH

EXISTING REFRIGERANT

PIPING AND

CONDENSATE LINES

UNITS SHALL BE

DEMOLISHED.

SHALL REMAIN

(E) ROOF MOUNTED

EXHAUST FAN AND

CONTROLS SHALL REMAIN.

(E) EF-5 AND ALL ASSOCIATED

DUCTWORK AND ACCESSORIES

SHALL BE DEMOLISHED.

EXISTING VRF SYSTEM SHALL

BE DEMOLISHED.

CONTRACTOR SHALL REMOVE

ALL EXISTING AIR HANDLERS

FROM AVID ROOMS.

(E) ABANDONED AHU-3

SHALL BE DEMOLISHED

PA

PA

PA

LIT

LIT

LIT

LIT

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

ES

ES

ES

ES

LE

LE

LE

LE

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

LE

LE

LE

LE

8 16 24 32

SCALE: 1/8" = 1'-0"

M051M051M051M051

1S

FL

O O R H

VA

EM

LI

TI

O N P

LA

FL

O O R H

VA

LI

TI

O N P

FL

O O R H

VA

LI

TI

O N P

FL

O O R H

VA

LI

TI

O N P

19191919

A

FA

CI

A

FA

CI

A

FA

CI

A

FA

CI

1, A

1, A

1, A

1, A

SCALE: 1/8" = 1'-0"M051

1 1ST FLOOR HVAC DEMOLITION PLANGENERAL DEMOLITION NOTES

1. WHERE ROOF MOUNTED EQUIPMENT IS DEMOLISHED CONTRACTOR

SHALL PROVIDE A SHEET METAL COVER WITH R-20 INSULATION

ACROSS THE OPENING OF THE DEMOLISHED EQUIPMENT. SHEET

METAL COVER SHALL BE FASTENED TO SIDES OF EIXSTING CURB SO

THAT ALL JOINTS ARE MADE WATERTIGHT.

GFEDC

AHU-1

AHU-2

FCU-4

-3

ACCESS DOOR TO

PLATFORM CONTAINING

FCU'S LOCATED HERE

DEMOLISH ALL DUCTWORK AND AIR

DISTRIBUTION SERVING MODULAR

OFFICE SPACES. SUPPLY AND

RETURN DUCTWORK IS ROUTED

ABOVE MODULAR OFFICE SPACE

BETWEEN SHEET METAL PAN CEILING

STRUCTURE AND ROOF OF EXISTING

BUILDING. ACCESS IS LIMITED.

AHU-2 IS ON RAISED

PLATFORM ABOVE FLOOR.

DEMOLISH AIR HANDLING

UNIT AND REFRIGERANT

AND CONDENSATE LINES.

REMOVE EXISTING EXHAUST

FANS, ALL ASSOCIATED

DUCTWORK. SEAL FLOOR

PENETRATIONS AND CAP

ROOF OPENING.

EXISTING VRF SYSTEM SHALL BE

DEMOLISHED. CONTRACTOR SHALL

REMOVE ALL EXISTING AIR HANDLERS

AND ASSOCIATED REFRIGERANT AND

CONDENSATE PIPING FROM AVID ROOMS.

EXISTING AIR HANDLING UNITS ARE

LOCATED IN SECOND FLOOR

MECHANICAL ROOM. UNITS SHALL BE

REMOVED THROUGH DOUBLE-DOOR

ACCESS AT TOP OF STAIRS.

DEMOLISH ALL ASSOCIATED OUTSIDE

AIR, SUPPLY AND RETURN AIR WITH AIR

HANDLING UNITS LOCATED IN

MECHANICAL ROOM.

DEMOLISH EXISTING

LOUVER ABOVE DOOR.

ALL DUCTWORK AND AIR DISTRIBUTION

DEVICES ASSOCIATED WITH EXISTING HVAC

SYSTEMS SHALL BE DEMOLISHED, UNLESS

NOTED OTHERWISE.

GENERAL NOTES:

1.

PA

PA

PA

LIT

LIT

LIT

LIT

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

ES

ES

ES

ES

LE

LE

LE

LE

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

LE

LE

LE

LE

M052M052M052M052

2N

FL

O R H

VA

LI

TI

O N P

O R H

VA

LI

TI

O N P

O R H

VA

LI

TI

O N P

O R H

VA

LI

TI

O N P

20202020

A

FA

CI

A

FA

CI

A

FA

CI

A

FA

CI

1, A

1, A

1, A

1, A

SCALE: 1/8" = 1'-0"M052

1 2ND FLOOR AND MEZZANINE HVAC DEMOLITION PLAN

T T

T T

FEDCBA

TEAM B

110B

LATRINE

110A

1ST SGT.

DO

UDM

CSS

COMMANDERS

108 SPRINKLER

DTS

STATIONS

MAINTENANCE

FLYING OP.

ARMORY

COMSEC

119A

NETWORK

LOGISTICS

NCOIC

AREA

137A

BUDGET

AVID 1

122BREAK RM

WOMENS

MATERNITY

AVID 4

AVID 3

ID

AVID

EIC

MECH

SIMULATION

SERVER

RM

133A

WORKOUT

EXISTING GAS

METER LOCATION

PD208

PF222

PD210

PD210 250

PD106

PD206

VAV-5

VAV-6

-8

VAV-4

-7

VAV-3

VAV-2

VAV-15

VAV-11

VAV-12

VAV-10

LS108

EXISTING CONDITIONING

IN SIMULATION ROOM

SHALL REMAIN.

VAV-137

AH-122

AH-125

AH-126

AH-124

AH-121

(E) AH

(E) CU

EXISTING LADDER TO

MEZZANINE

PD212

EF-1

EF-2

EF-4 EF-5

40"x20"26"x20"

"x

20"x12"

18"x12"

"ø

14"x12"

"ø1

12"x12"

12"ø

10"ø

14"ø

10"ø8

8"ø

16"ø

10"ø 12"ø

12"ø2

18"ø

20"x20"

26"x20"

UH-1

3" CHWR

3" CHWS

TO AHU-2

2" CHWR

(E) CHILLER

TO FCU-1

1" CHWR

M500

3" CHWR

1 1/2" HWS

1 1/2" HWR

1" HWS

1" HWR

6"ø

EF-3

8"ø 1

14"x14"

GV-2

CU-121

8"ø12"ø

LE222

UP TO DUCTWORK

ROUTED ABOVE MODULAR

OFFICE SPACE.

LE222

EF-6

(E) AH

(E) CU

CRC-1

IH-2

IH-1

IH-3

IH-4

VAV-9

UP TO DUCTWORK

OVERHEAD (TYP.)

ALL PIPING IN

WORKOUT ROOM

SHALL BE ROUTED

TIGHT TO CEILING

MOUNT 9' AFF,

TYPICAL OF 4

PA

PA

PA

LIT

LIT

LIT

LIT

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

ES

ES

ES

ES

LE

LE

LE

LE

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

LE

LE

LE

LE

M101M101M101M101

FL

O O R H

VA

FL

O O R H

VA

FL

O O R H

VA

FL

O O R H

VA

21212121

A

FA

CI

A

FA

CI

A

FA

CI

A

FA

CI

1, A

1, A

1, A

1, A

SCALE: 1/8" = 1'-0"M101

1 1ST FLOOR HVAC PLAN

KEYED NOTES

SUPPLY AND RETURN DISTRIBUTION DEVICES LOCATED WITHIN

COMSEC AND ARMORY SHALL BE PROVIDED WITH OPENING

PROTECTION. REFER TO DETAIL FOR ADDITIONAL INFORMATION.

ROUTE CHILLED WATER PIPING ON STANDS AS CLOSE TO WALL AS

POSSIBLE, THEN TIGHT TO EXTERIOR WALL UP UNTIL PENETRATION

INTO CONDITIONED SPACE. PIPE PENETRATION SHALL BE 8" DIAMETER

OPENING FILLED WITH ELASTOMERIC MATERIAL, SEALED AND

COVERED WITH ESCUTCHEON.

GENERAL NOTES

1. MANUAL DAMPERS SHALL BE INSTALLED ON ALL DUCT RUNOUTS TO

AIR DISTRIBUTION DEVICES FOR BALANCING OF SYSTEM. REFER TO AIR

DISTRIBUTION INSTALLATION DETAIL FOR ADDITIONAL INFORMATION.

PROVIDE AN EMERGENCY SHUT-OFF BUTTON WITH COVER FOR THE

HVAC SYSTEM. SHUT-OFF DEVICE SHALL BE A DIFFERENT COLOR THAN

THE FIRE ALARM PULL STATION. SHUT OFF SWITCH SHALL TURN OFF

AHU-1, AHU-2, FCU-1, AND SHUT ALL OUTSIDE AIR DAMPERS AND

GRAVITY VENTILATOR DAMPERS WITHIN 30 SECONDS OF SWITCHING.

COORDINATE THE LOCATION OF INFRARED HEATERS WITH OCCUPIED

WORKING SPACES BELOW.

NEW CONDENSATE UNITS SHALL BE PROVIDED WITH 8" THICK

CONCRETE PADS EXTENDING 6" ON ALL SIDES.

GFEDC

MEZZ

OPEN

OPEN

ALPHA

FLIGHT

ELEMENT

LEADERS

ELEMENT

LEADERS

C FLIGHT

ALPHA

FLIGHT

MECHANICAL

STAIR

PHOTO FLT

CC

COORIDOR

AUI05

FCU-1

PF222 150

VAV-210

VAV-211

VAV-215

VAV-219

AH-206

ROUTE DUCT THROUGH

CHASE TO FLOOR BELOW

VAV-135

CRAC-1

ROUTE DUCT TO

FLOOR BELOW

VAV-18

VAV-16

VAV-14

VAV-13

VAV-17

SR3220

SR3220

40"x20"

32"x20"

24"ø

10"ø8"ø

12"x12" 10"ø 12"x12" 10"ø 8"ø

12"ø18"ø

AHU-1

1 1/2" HWR

1 1/2" HWS

"ø3

SR1616

LS106

GV-1

L-2

M3

SR1210

VAV-134

LS1010

12"ø 12"ø

8"ø 8"ø

ROUTE DUCT OUT OF

MECHANICAL ROOM

TO SPACE ABOVE

FIRST FLOOR CEILING

5 6

DOWN TO FIRST

FLOOR DIFFUSER

22"ø

L-1

PA

PA

PA

LIT

LIT

LIT

LIT

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

ES

ES

ES

ES

LE

LE

LE

LE

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

LE

LE

LE

LE

M201M201M201M201

FL

O O R

AN

D M

EZ

ZA

N

IN

E H

VA

C P

FL

O O R

AN

D M

EZ

ZA

N

IN

E H

VA

C P

FL

O O R

AN

D M

EZ

ZA

N

IN

E H

VA

C P

FL

O O R

AN

D M

EZ

ZA

N

IN

E H

VA

C P

22222222

A

FA

CI

A

FA

CI

A

FA

CI

A

FA

CI

1, A

1, A

1, A

1, A

SCALE: 1/8" = 1'-0"M201

1 2ND FLOOR AND MEZZANINE HVAC PLAN

CRAC-1 SHALL BE INSTALLED ON MEZZANINE ABOVE SERVER ROOM

PRIOR TO DEMOLITION OF EXISTING UNITS SERVING COMPUTER ROOM.

ONCE CRAC-1 IS OPERATIONAL, SERVICE OF THE SPACE SHOULD BE

SWITCHED TO NEW UNIT AND EXISTING UNITS SHALL BE REMOVED.

ACCESS LADDER LOCATION. REFER TO ARCHITECTURAL PLANS FOR

ADDITIONAL INFORMATION.

REFRIGERANT AND CONDENSATE PIPING FOR AH-206 SHALL BE ROUTED

THROUGH WALL INTO MECHANICAL ROOM, THEN TO OUTDOOR UNIT.

PROVIDE AN EMERGENCY SHUT-OFF BUTTON WITH COVER FOR THE HVAC

SYSTEM. SHUT-OFF DEVICE SHALL BE A DIFFERENT COLOR THAN THE FIRE

ALARM PULL STATION. SHUT OFF SWITCH SHALL TURN OFF AHU-1, AHU-2,

FCU-1, AND SHUT ALL OUTSIDE AIR DAMPERS AND GRAVITY VENTILATOR

DAMPERS WITHIN 30 SECONDS OF SWITCHING.

PROVIDE CONCRETE PAD BENEATH NEW AIR HANDLING UNIT LOCATED IN

SECOND FLOOR MECHANICAL ROOM. PAD SHALL EXTEND 6" BEYOND AIR

HANDLING UNIT ON EACH SIDE. PROVIDE A SECONDARY EMERGENCY

DRAIN PAN BENEATH THE ENTIRE AIR HANDLING UNIT.

AIR HANDLING UNIT INSTALLATION ACCESS IS LIMITED TO DOUBLE DOORS

AT THE TOP OF THE STAIRWELL. ALL SECTIONS SHALL BE COORDINATED

TO FIT IN THE EXISTING EXTERIOR OPENING AND UNIT SHALL BE

ASSEMBLED WITHIN THE MECHANICAL ROOM.

DUCTWORK FROM FCU-1 INTENDED TO SERVE THE WORK-OUT AREA ON

THE FIRST FLOOR. COORDINATE VERTICAL DUCTWORK DOWN SIDE OF

MODULAR OFFICE SPACE SO AS TO NOT INTERFERE WITH OPERATION OF

ROLL-UP DOORS.

COORDINATE ORIENTATION OF FCU-1 SUCH THAT FILTER CHANGE IS

POSSIBLE FROM EXISTING PLATFORM.

LOCATE NEW TRANE DDC CONTROLLER ON MECHANICAL ROOM WALL

ADJACENT TO ELECTRICAL PANELS.

CONTRACTOR SHALL VERIFY SIZE OF OPENING PRIOR TO ORDERING

LOUVER. PROVIDE 6" DEEP INSULATED SHEETMETAL PLENUM ON BACK

OF LOUVER. DUCT SHALL TRANSITION TO APPROXIMATELY 48" x 20"

BEFORE CONNECTING TO PLENUM.

1. DUCTWORK FOR AIR DISTRIBUTION IN MODULAR OFFICE SHALL BE

INSTALLED BETWEEN MODULAR OFFICE ROOF AND BUILDING ROOF.

REFER TO INSTALLATION DETAIL FOR ADDITIONAL INFORMATION ABOUT

ROUTING THROUGH THE MODULAR OFFICE ROOF.

2. MANUAL DAMPERS SHALL BE INSTALLED ON ALL DUCT RUNOUTS TO AIR

DISTRIBUTION DEVICES FOR BALANCING OF SYSTEM. REFER TO AIR

DISTRIBUTION INSTALLATION DETAIL FOR ADDITIONAL INFORMATION.

A B

C D E F G

GFEDCBA

MP

E1

3 3

PA

PA

PA

LIT

LIT

LIT

LIT

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

A W

IN

G

R E V

IS

IO

ES

ES

ES

ES

LE

LE

LE

LE

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

T B A S E

C H A R

LE

S

LE

LE

LE

LE

ED101ED101ED101ED101

FL

O

EL

EC

AL

LI

TI

O

FL

O

AL

TI

O

FL

O

AL

TI

O

FL

O

AL

TI

O

MR

32323232

A

FA

CI

A

FA

CI

A

FA

CI

A

FA

CI

1, A

1, A

1, A

1, A

SCALE: 1/8" = 1'-0"ED101

1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN

ALL PANELBOARDS ARE EXISTING TO REMAIN.

EXISTING SMOKE DETECTORS AND WIRING SHALL REMAIN. PROTECT

AND APPROPRIATELY CONTAIN TO PREVENT FALSE ALARMS DURING

CONSTRUCTION FOR INSTALLATION IN NEW CEILING.

2.

RETAIN EXISTING CEILING JUNCTION BOXES, CONDUIT, AND

CONDUCTORS IN THIS AREA FOR FUTURE INSTALLATION OF FUTURE

CEILING FANS.

SPEAKER SYSTEM IN THIS AREA SHALL BE DEMOLISHED AND WILL NOT BE

REPLACED.

DEMOLISH POWER TO SPLIT SYSTEMS SERVING THESE ROOMS.

OS OS OS OS

OSOSOSOS

OS

OS OS

OSOS

OS OS

OS OS OS

C D E F G

MECH.

MEZZANINE

REFLECTED CEILING PLAN NOTES

CEILING GRIDS AND/OR TILES TO BE CENTERED IN ALL

ROOMS IN BOTH DIRECTIONS UNLESS NOTED OTHERWISE.

PARTIAL TILES SHALL NOT BE LESS THAN 6 INCHES IN

EITHER DIMENSION.

SPRINKLER HEADS ARE TO BE CENTERED IN CEILING TILES.

NO EXCEPTIONS.

COORDINATE REFLECTED CEILING PLANS WITH

ELECTRICAL, MECHANICAL, STRUCTURAL, FIRE

PROTECTION AND ROOM FINISH SCHEDULE.

IN THE CASE OF MINOR DISCREPANCIES IN THE LOCATION

OF CEILING MOUNTED COMPONENTS THE REFLECTED

CEILING PLAN SHALL GOVERN. IN THE CASE OF MAJOR

DISCREPANCIES, THE CONTRACTING OFFICER SHALL BE

NOTIFIED PRIOR TO PROCEEDING WITH THE WORK.

REFER TO MECHANICAL AND/OR ELECTRICAL DRAWINGS

FOR MOUNTING LOCATIONS OF ITEMS WHERE NO CEILING

IS INDICATED OR REQUIRED.

LIGHTS, DIFFUSERS, EXIT SIGNS, SMOKE DETECTORS,

SPEAKERS, GENERAL ALARM SPEAKERS/STROBES AND

OTHER DEVICES SHALL BE CENTERED IN THE CEILING TILES

IN WHICH THEY OCCUR, UNLESS NOTED OTHERWISE.

REFER TO MECHANICAL AND ELECTRICAL FOR LOCATIONS.

CEILING SEISMIC DETAILS ARE PROVIDED TO ILLUSTRATE

THE GENERAL REQUIREMENTS OF CISCA GUIDELINES FOR

SEISMIC RESTRAIN AND IBC CHAPTER 16. CONTRACTOR IS

RESPONSIBLE FOR MEETING ALL APPLICABLE PROVISIONS

OF THE STANDARDS. IN CASE OF CONFLICT THE MORE

STRINGENT REQUIREMENT SHALL PREVAIL.

REFER TO A571 FOR RCP SEISMIC REQUIREMENTS AND

DETAILS.

ALL CEILING HEIGHTS SHOWN ON PLAN ARE +/-. CEILING

HEIGHTS SHALL MATCH EXISTING

3.

4.

5.

6.

7.

8.

9.

10.

KEYNOTE

RCP LEGEND

2'X2' ACT CEILING GRID SYSTEM

EXISTING 8" CMU WALL TO REMAIN

EXISTING CMU AND BRICK VENEER WALL TO

REMAIN

GYPSUM BOARD CEILING SYSTEM

2'x4' LIGHT

1'x4' CEILING MOUNTED LIGHT

RECESSED DOWNLIGHT

2'x2' LIGHT

CEILING MOUNTED SUPPLY GRILLES

CEILING MOUNTED RETURN GRILLES

2'X2' ACT CEILING GRID SYSTEM W/ FOIL

FACED BATT INSULATION INSTALLED

ABOVE CEILING. FOIL FACE UP TOWARDS

NON-CONDITIONED SPACE.

1' X 2' CEILING MOUNTED SUPPLY GRILLES

EXIT SIGN

CEILING MOUNTED SMOKE DETECTOR

CEILING MOUNTED HEAT SENSOR

CEILING MOUNTED SPEAKERSP

HD

SD

EXHAUST FAN

HIGH BAY LIGHT W/ DIA EMERGENCY

HIGH BAY LIGHT

OCCUPANCY SENSOROS

PROVIDE NEW DOOR/TRANSOM H.M. FRAME, H.M.

DOORS, AND DOOR HARDWARE

NEW KEYNOTES

2 PROVIDE STEEL SHIPS LADDER TO ACCESS PANEL

ABOVE

3 PROVIDE 3'X3' ACCESS PANEL BOTTOM OF ACCESS

PANEL 9' +/- ABOVE MECH. MEZZANINE FLOOR.

4 PROVIDE HASP DOOR HARDWARE FOR PADLOCK AT

EXISTING DOOR. PADLOCK TO BE PROVIDED BY

GOVERNMENT.

DOOR SCHEDULE

7'

0"

FI

IF

F1

D1

FRAME ELEVATIONS

DOOR ELEVATIONS

6' - 0"

PROVIDE SOLID

METAL LOUVER

SEALED AIR AND

WATER TIGHT, SEE

MECHANICAL DWGS.

1. INSTALL NEW FRAME IN EXISTING OPENING. FIELD VERIFY DIMENSIONS OF EXISTING OPENING.

CHARLESTON

NO. 2676

GARY J. BOEHMST

EOF SOUTH CAROLINA

REGISTERED A RCHITECT

A D

M AN

E W

BAIR AS

I N62 8T H

SEAL AREA

OFSHEET

RECORD DRAWING DATE

DRAWING SIZE:

PROJECT NO.

OB

ILI

TY

OM

ND

A W

IN

G

R E V

IS

IO

SO

CI

AT

ES

LE

T B

AS

E C H

AR

LE

S

LE

ANSI D(22X34)

A121

OO

C

EI

EW

GB

MC

SM

2/

DKFX 14-1065

A

FA

CI

1, A

SCALE: 1/8" = 1'-0"1 2ND FLOOR REFLECTED CEILING PLAN - NEW

0' 4' 8' 16'

TAG MATERIAL TYPE HEIGHT WIDTH THICKNESS FINISH

FRAMES FIRE

RATING

HARDWARE

SET NOTESTYPE FINISH

01 H.M. 01 7' - 0" 6' - 0" 1 3/4" PT F1 PT N/A 01 1.2 3'-0" EA.

LO

UV

EV

8/

Attachment 13 FA441818R0010

Revised Drawings Repair HVAC Combat Camera Facility – B241

15 August 2018

COVER PAGE

CEILING GRID CLIPS OR METAL

CLIPS FASTENED TO CEILING

GRID (MAIN TEES) TO SUPPORT

HVAC GRILLE

HVAC GRILLE

OR TERMINAL

No. 9 GAGE HANGER

WIRE, TYP. WHEN DEVICE

IS > 20 LBS. SUS'D ACT

CEILING GRID

SUSPENDED

CEILING TILE

LIGHT FIXTURE

MOUNTING

BRACKET

LIGHT FIXTURE

SEE ELECT. DWGS

SUSP'D CLG

GRID "TEE"

SUPPORT WIRE:

MAY BE SLACK

8" MAX.

MAIN "TEE"

POP RIVET WALL

ANGLE TO GRID

"RESTRAINED

CONDITION"

2" WIDE

WALL ANGLE

FASTEN TO

WALL

105/128" MAX.

HANGER WIRE, NOT

MORE THAN 1 IN 6

OUT OF PLUMB

STABILIZER

BAR

CROSS "TEE"

8" MAX.

"TEE" BAR TO FLOAT

FREE ON WALL ANGLE

"UNRESTRAINED

CONDITION"

2" WIDE

WALL ANGLE

FASTEN TO

WALL

105/128" MAX.

HANGER WIRE, NOT

MORE THAN 1 IN 6

OUT OF PLUMB

STABILIZER

BAR

MAIN OR CROSS

TEES, TYP.

FASTENER AS

REQ'D BY MANUF.

EXP. JOINT COVER

FASTEN ONE SIDE ONLY

SEE PLANS FOR LOCATION

MIN.

2" SLOT

WITHIN 8" OF JOINT

SUPPPORT WIRE

VERTICAL SUPPORT

WIRE @ 4' o.c. E.W.

SPLAY WIRES (LONG DASH)

@45d FROM VERTICAL IN ROOM

GRID N & S DIRECTIONS.

SECURE TO STRUCTURE

SPLAY WIRES (SHORT DASH)

@45d FROM VERTICAL IN ROOM

GRID E & W DIRECTIONS.

SECURE TO STRUCTURE

FASTEN CLIP

TO STRUCTURE

STRUCTURE ABOVE

1-1/2" COLD ROLLED

CHANNELS @ 48" o.c.

5/8" GYPSUM BOARD

7/8" METAL HAT

CHANNELS @ 16" o.c.

SUSPENSION WIRE TO

STRUCTURE ABOVE

NOTE: FOLLOW MANUFACTURER'S

RECOMMENDATIONS FOR GAGE OF

METAL FRAMING & SUPPORT WIRE

SEALANT AND

BACKER ROD

5/8" GYPSUM BOARD

1-1/2" COLD-ROLLED

CHANNELS @ 48"o.c.

7/8" METAL HAT CHANNEL

@ 16" o.c.

WALL STRUCTURE

1/4"

6 65/128"

1/2"

3"

6"

CONTROL JOINT

(CJ)

5/8" GYPSUM

BOARD

7/8" METAL HAT

CHANNELS @ 16" o.c.

1-1/2" COLD-ROLLED

CHANNELS @ 48" o.c.

(OVERLAP 12" AT CJ)

STAGGER CR CHANNELS

AT 24" EACH SIDE OF

CONTROL JOINT

WALL "A"

WALL "C"

AL

"B

"D

INTERSECTION STRENGTH AT MAIN / CROSS TEES

HANGER WIRE (MIN. OF 3 TWISTS)

CONNECTION @ WIRE / STRUCTURE ABOVE

MAIN TEE CLASSIFICATION

MAXIMUM OUT OF PLUMB

PERIMETER WIRE DISTANCE FROM WALLS

GRID CONNECTION TO PERIMETER WALLS

PERIMETER TEE ENDS TIED TOGETHER

SPLAY BRACING 90º APART @ 45º ANGLES

SPLAY BRACING CONNECTION STRENGTH

COMPRESSION POSTS

PARTITION ATTACHMENT

SEISMIC SEPARATION JOINT

RIGID BRACING AT CEILING PLANE CHANGES

ALL LIGHT FIXTURES ATTACHED TO GRID, TYPICAL

SURFACE MOUNTED LIGHT FIXTURE

PENDANT HUNG LIGHT FIXTURE

RECESSED LIGHT FIXTURE < 10 LBS.

LAY-IN OR RECESSED LIGHT FIXTURE, 10 TO 56 LBS.

LAY-IN OR RECESSED LIGHT FIXTURE > 56 LBS.

AIR TERMINALS < 20 LBS.

AIR TERMINALS, 20 TO 56 LBS.

AIR TERMINALS > 56 LBS.

SPRINKLER HEAD CLEARANCE

MISC. PENETRATION CLEARANCE

CABLE TRAYS

CONDUIT AND PIPING

PERIMETER MOLDING WIDTH

60 LBS.

12 GAUGE @ 4' o.c. EACH WAY

NO MINIMUM REQUIREMENT

INTERMEDIATE DUTY OR HEAVY DUTY

1 IN 6 MAXIMUM

IF WALL ANGLE < 7/8" THEN 8" MAXIMUM

NOT ALLOWED

YES, WITH STABILZER BAR

NOT REQUIRED

N/A

NOT REQUIRED

BRACE INDEPENDENT OF CEILING GRID

NOT REQUIRED

NOT REQUIRED

AT 2 POINTS UNLESS INDEPENDENTLY SUPPORTED

ATTACH TO GRID

SUPPORT DIRECTLY FROM STRUCTURE W/ 9 GA. WIRE

SUPPORT WITH ONE WIRE TO STRUCTURE

TWO WIRES TO STRUCTURE ON DIAGONAL

SUPPORT INDEPENDENTLY FROM STRUCTURE

POSITIVELY ATTACHED TO GRID

POSITIVELY ATTACH TO GRID + 2 WIRES TO STRUCTURE

SUPPORT DIRECTLY FROM STRUCTURE

3/8 INCH ON ALL SIDES

3/8 INCH ON ALL SIDES

MAY BE SUPPORTED BY GRID OR STRUCTURE

MAY BE SUPPORTED BY GRID OR STRUCTURE

7/8 INCH MINIMUM

IBC CATEGORY "C"

CISCA ZONES 0-2 UP TO 1,000 SF GREATER THAN 1,000 SF

180 LBS.

100 LBS. MINIMUM

HEAVY DUTY

1 IN 6 MAXIMUM

8" MAXIMUM

ATTACHED TO TWO ADJACENT WALLS

NOT REQUIRED

N/A

NOT REQUIRED

BRACE INDEPENDENT OF CEILING GRID

NOT REQUIRED

YES

AT 2 POINTS UNLESS INDEPENDEENTLY SUPPORTED

ATTACH TO GRID

SUPPORT DIRECTLY FROM STRUCTURE W/ 9 GA. WIRE

SUPPORT WITH ONE WIRE TO STRUCTURE

TWO WIRES TO STRUCTURE ON DIAGONAL

SUPPORT INDEPENDENTLY FROM STRUCTURE

POSITIVELY ATTACHED TO GRID

POSITIVELY ATTACH TO GRID + 2 WIRES TO STRUCTURE

SUPPORT DIRECTLY FROM STRUCTURE

2 INCH MINIMUM OPENING OR SWING JOINT

2 INCH MINIMUM OPENING OR FLEX JOINT

SUPPORT DIRECTLY FROM STRUCTURE

2 INCH MINIMUM

180 LBS.

100 LBS. MINIMUM

HEAVY DUTY

1 IN 6 MAXIMUM

8" MAXIMUM

ATTACHED TO TWO ADJACENT WALLS

REQ'D WITHIN 2" OF TEE INTERSECTION @ 12'-0" o. c. E.W.

GREATER OF 200 LBS. OR DESIGN LOAD

REQ'D @ 12' O.C. EACH WAY, STARTING 6' FROM WALLS

BRACE INDEPENDENT OF CEILING GRID

REQUIRED WHERE AREA IS > 2,500 SF

YES

AT 2 POINTS UNLESS INDEPENDENTLY SUPPORTED

ATTACH TO GRID

SUPPORT DIRECTLY FROM STRUCTURE W/ 9 GA. WIRE

SUPPORT WITH ONE WIRE TO STRUCTURE

TWO WIRES TO STRUCTURE ON DIAGONAL

SUPPORT INDEPENDENTLY FROM STRUCTURE

POSITIVELY ATTACHED TO GRID

POSITIVELY ATTACH TO GRID + 2 WIRES TO STRUCTURE

SUPPORT DIRECTLY FROM STRUCTURE

2 INCH MINIMUM OPENING OR SWING JOINT

2 INCH MINIMUM OPENING OR FLEX JOINT

2 INCH MINIMUM

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

27.

28.

29.

IBC CATEGORY "D", "E" OR "F" - CISCA ZONES 3 & 4

SEISMIC RESTRAINTS FOR SUSP'D AOUSTICAL CEILINGS

# CEILING COMPONENT

GRID / WALL CLEARANCE 3/8 INCH MINIMUM 3/4 INCH MINIMUM 3/4 INCH MINIMUM

TYPICAL

12' - 0"

MAX.

6' - 0"

PI

AX

6'

0"

WALL "A"

WALL "C"

"B

"D

LAY-IN FLUORESCENT

LIGHT TROFFER,

SEE ELECT. DWGS

SUSP'D CLG.

GRID TEE

TIE DOWN CLIP AT EACH CORNER OF

LIGHT FIXTURE, TYPICAL

SUPPORT WIRE SHALL

BE INSTALLED NOT MORE

THAN 1 IN 6 OUT OF PLUMB,

WIRE MAY BE SLACK

NOTE:

SEE SCHEDULE FOR # OF

SUPPORT WIRES BASED

ON WEIGHT OF FIXTURE

SUSP'D CLG

GRID "TEE"

MECHANICALLY

FASTEN

POST TO GRID PER

MANUFACTURER'S

INSTRUCTIONS

COMPRESSION

POST

VERTICAL SUPPORT

WIRE

SPRING CLIP OR

SIMILAR PER

MANUFACTUER

MECHANICALLY

FASTEN

TOP CLIP TO

STRUCTURE

CHARLESTON

NO. 2676

GARY J. BOEHMST

E OF SOUTH CAROLINA

REGISTERED A RCHITECT

A D

M AN

E W

BAIR AS

I N62 8T H

SEAL AREA

OFSHEET

RECORD DRAWING DATE

DRAWING SIZE:

PROJECT NO.

OB

ILI

OM

ND

A W

IN

G

R E V

IS

IO

SO

CI

AT

ES

LE

T B

AS

E C H

AR

LE

S

LE

ANSI D(22X34)

A571

AC

OU

EI

IL

E

SE

IS

M

IC

D

ET

LS

GB

MC

SM

2/

A

FA

CI

1, A

SCALE: NTSA571

4 AIR TERMINAL ATTACHMENT TO SUSP'D GRID

10 CAN LIGHT ATTACHMENT

13 ACT SEISMIC GRID AT WALL

12 UNRESTRAINED GRID / WALL

9 ACT EXPANSION JOINT

7 ACT SEISMIC SPLAY WIRE LAYOUT1

3 SUP'D GYPSUM BD. CEILING DETAIL

5 WALL / CLG INTERSECTION

6 GYP. BD. CLG CONTROL JOINT

1 GRID WHEN ROOM < 1,000 SF

A571A571

A571 A571

A571A571 A571

A571SCALE: 1/8" = 1'-0"A571

2 GRID WHEN ROOM > 1,000 SF

SCALE: 1/8" = 1'-0"A571

11 LAY-IN TROFFER ATTACHMENT

SCALE: 1/64" = 1'-0"A571

8 COMPRESSIONP POST

SE

LG

S.