Attch 2 - Drawings for Bldg 91262 (Includes Addendum 1).pdf
PDF 14 MB Posted
- Attached to
- Alter A/C Hangar, Bldg. 91262 Federal contract opportunity
- Solicitation number
- FA441722B0001
About this file
This document provides details for a federal contract opportunity with the Department of the Air Force Special Operations Command. The solicitation number FA441722B0001 seeks proposals to alter and improve Air Conditioning System within Hangar Building 91262 at an unspecified location. Attachments include drawings and plans for the building renovation project. Interested contractors should review the solicitation and accompanying documents for specifications and requirements related to renovating and upgrading the HVAC system in the hangar to meet the needs of the Air Force Special Operations Command. The response due date and anticipated award date are not provided in this document.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
90918
92470
90043
90308
92006 92007
90434
93660
90600
92431
92081
90101
90761
91048
99045
91307
90325
90106
90032
92469
90359
91159
93542
92427
90716
92550
91401
90030
92085
91265
90053
90439
92046
90416
90225
91301
92093
91148
91303
99042
92429
91364
90366
91056
90304
91254
90051
90531
91045
90636
90062
90426
92449
92519
90115
90370
90064
92403
90713
93589
90438
90326
92028
92019 92021
91047
90063
90138
92060
90352
91029
93618
90371
93469
90137
92472
90748
90128
90618
90208
90035
90619
90532
90369
93422
92065
93597
92438
90033
90702
91255
91520
93557
90521
92091
90510
93414
90302
93386
90232
92404
90382
90215
92080
93653
90617
92059
91137
92513
92057
92042 92043
92037
92551
90419
92017 92016
92107
91142
90300
90374
92546
92084
92099
99059
90621
92105
90339
91300
90008
92102
91163
90347
92098
90358
99022
99145
99126
99044
90390
99056
99055
99007
99105
91016
90552
90131
99001
93341
93381
92090
92050
90334
91050
91350
90410
91363
91130
90337
92538
92061 92082
90760
90375
93613
90229
90707
92052
92035
90615
93477
92406
90105
90616
90928
91039
91009
90015
92432
92039
90121
91031
90610
92275
92420
90759
92430
91151
91023
91140
92011
91037
90802
91055
91252
92013
92000
90703
92528
92455
93509
90005
90084
92024
92069
90328
90731
90372
92032 92030
90717
90145
91054
92436
91155 90606
92452
93573
92451
90378
92022
91012
93581
90223
90642
90054
90377
90436
9202792026
93522
91146
90230
93373
93486
90056
92055
92010
92072
92076
92071
92068
92058
90058
91053
90333
93556
90320
93500
92004
92100
90207
92522
92087
90413
91104
93586
91103
93444
93650
93596
91105
92437
90432
90809
91330
93365
92553
90701
92548
93645
90327
93453
92435
92549
92001
92008
92051
90724
91122
93608
93445
92434
90511
92009
92461
90085
90609
99023
99716
9971799718
99719
99127 99051
99025
99024
90210
91546
92034
91032
92023
99058
92505
93538
90522
90509
90747
92089
91154
92426 92419
92463
92501
92516
92541
90607
99104
99090
99048
99020
90340
90075
93485
93368
92048
90711
90430
90409
92094
91133
90523
91112
90388
99057
91510
99041
90068
90069
93397
90392
92064
90037
93517
90141
99004
90362
93629
93493
92537
90613
90134
92014
93501
92529
90052
91162
92464
92025
92446
92515
91161
90381
90387
92103
99053
91057
90729
99094
99146
92502
92450
92033
91132
91030
91152
92556
90076
91145
93354
93317
93304
90102
92441
92471
90357
90111
90070
92054
90355
93309
93510
90601
92527
91099
92407
92015
92079
90916
91108
90811
90743
91007
91360
91325
90081
93398
92038
92533
92095
90368
91052
91164
93349
90742
92083
92555
93325
92514
90627
92047
90361
99010
93541
90714
90763
90109
92503
90329
91135
91310
93566
92460
92428
91266
91500
92044
90213
92539
93389
93637
90039
90073
90074
93421
91035
90505
92466
91120
91601
93432
90926
91025
91603
91365
90538
90535
91351
92062
91020
90417
90036
90518
91370
92088
92063
93429
92544
93476
90402
90140
92521
99031
92473
91361
92518
92433
91027
91024
91515
92523
93461
92545
93301
93549
90373
91147
92445
92530
90117
92092
90705
90517
92511
90331
92444
90079
91000
92401
91033
90838
90431
93640
91538
91119
91114
90203
92045
90632
90720
90404
92067
92097
9254392506
92535
92524
92070
92056
92053
9204192104
92106
92074
91268
93413
92459
92508
91036
90624
92517
90625
93437
91260
90553
90066
90061
90057
91028
90423
91021
92525
92440
99141
92468
91144
90755
90310
90220
92086
90551
90050
90367
90407
90323
92402
93464
92467
90055
92018
91257
90029
92020
9200292003
92073
90519
93626
99065
90420
92101
92463
90712
93454
91013
92442
92096
90135
91049
92465
92408
90231
90603
91250
90322
92507
92066
90718
93565
92049
93530
90501
90640
90353
91041
92542
91153
92552
90002
92108
92276
90428
93346
92531
90758
90700
92439
93332
93333
90113
93621
92564
91302
90708
91126
90010
92077
90060
91136
91042
90332
93701
91258
90630
90206
90421
90028
90020
92075
92078
92031
90408
93405
92500
91259
90067
90059
92485
92509
90425
93357
92536
90349
90365
90065
90612
99049
90228
90433
90221
91625
92418
99005
93318
91141
90710
93576
99009
90502
90412
90427
90038
92540
90209
90414
92557
91537
90503
90021
99077
99154
90628
92547
90506
91101
90507
90380
90379
93605
91149
91124
90734
91043
90360
90363
91278
90364
90730
90611
90500
90508
90311
90086
91058
91059
99958
90917
90905
90306
91168
91107
91157
90534
90536
90727
99326
91404
90108
90539
99147
91362
90050
90296
9990299901
91177 91178
91158
91006
90639
91065
91064
91070
91062
368 366 364
1223122112191217121512131211120912071205
1204 1206 1208 1210 1212 1214 1216
369 367
1070/1072
1066/1068 1062/1064
1058/1060
1056/1054
1052/1050
1048/1046
1044/1042
1047/1045
1043/1041
1039/1037
1040/1038
1036/1034
1035/1033
1032/1030
1028/1026 1047/1045
1024/1022 1043/1041
1020/1018 1039/1037
1016/1014 1035/1033
1012/1010
1008/1006 1002/1000
998/996
992/994
988/990
984/986
980/982
976/978
972/974
968/970
618/616
614/612
610/608 606/604 602/600
609/607 605/603
99155
93261
91272
91061
99030
99029
99904
99903 99043
90201
90538
90540
99052
90599
90839
90077
90437
90590
91285
L e to ur n e a u C irc le
L e to ur n e au C irc le
F o xx A ve n u e
Tully Street
S im pso n A venue
Tully Street
Red Horse Road
Tupelo Circle
Bakke Street
M a yo S tre e t
Bakke Street
Red H orse
R oad
Tully Street
Grimm Lane
Hume Drive
Bland Street
Galvan Street
Hume Drive
Lewis Drive
Hodges Street
Walters Drive
H u m e
D riv e
Acha Drive
Harrison Dr ive
Hume Drive
McIntosh Court
US98
O 'N e il
A ve n u e
Independence Road
US98
C o dy A v e n u e
Purcell Drive
C a m p ai g n e
S tr e et
Whitbeck Street
Gelshlager Street
Clark Road
Hume Drive
Schmauss Lane
W ea ve r
A ve nu e
US98
McMillan Street
Corlew Road
W alkup W ay
Independen ce Road
Bedel Street
B e n n et t
A ve n u e
Frazier Street
C ru z A ve n u e
Red Horse Road
Benn ett
A ve nue
T u lly Street
T u lly S tr e e t
Bedel Street
Westfal l C ircl e
Ham by Place
Tully Street
Lukasik Avenue
Cod y
Ave nu e
K e rw oo d R o a d
US98
Lielmanis Avenue
Howie W alters W ay
US98
M a in te na n c e H a u l
R o a
Tully Street
US98
Harts on S tre et
McClean Stre et
T e rr y
Av en u e
Independence Road
Mitchell Road
Bartley Street
Blessinger D r iv e
Kanu ha D riv e
Downs Road
M artin
L uther K ing
W alkup W ay
Downs R oad
M A
Y S
TR
E
E T
Kissam Street
Spooky Ln.
Broadway Dr.
B ro a dw a y D r.
B roadw ay D r.
Piccadilly Dr.
Thursday Dr.
T h u r s d a y
D r .
Dagger D r.
T h u rs d ay
D r.
91266
91147
91268
91250
91258
91259
91278
91157
91272 91285
HIGHWAY 98
HIGHWAY 98
MARTIN LUTHER KING JR. BLVD
INTERSECTION ENTRANCE
COMMERCIAL VEHICLE INSPECTION
ENTRANCE PASS & ID OFFICE
HURLBURT EAST GATE, NO
COMMERCIAL ENTRANCE
FIRE DEPARTMENT BLDG 90734
CONTRACTOR HAUL ROUTE
NORTH
BASE MAP
IN
DEPENDENCE R
D
BLDG 90053
1 SPEC OPS CIVIL ENG SQ
BLDG 90337
1 SPEC OPS CONTRACTING SQ
MAIN GATE
PASS ID OFFICE
PROJECT SITE
(EXISTING BLDG)
LAYDOWN
AREA
91262
AR94997
DERETSI
G
E R
A R C H
IT
E C
T
FOETAT
S
FL O R ID
A
R ICE
ACREBO
R
RLT
08/18/2021
IA
R
E
OF
RC
SP
EC
IA
AN
N
P
ER
L O
A
TI
O
M M
S
CO
D
SHEET REFERENCE:
D A
T E
SHEET NUMBER:
OF
D E
S C
R
IP
T
IO
N R
E V
A
IR
F O
R C
E
SP
EC
IA
L O
PE
R
A
TI
O N
S C
O M
M A
N D
S
P
EC
IA
L
O
PE
R A
TI
O
N S
C
IV
IL
E
N G
IN
E
ER
S
Q U
A D
R O
N
H U
R
LB
U R
T
FI
EL
D
, F
LO
R
ID
A
PROJECT NUMBER:
BUILDING NUMBER:
DRAWN BY:
DESIGNED BY:
DATE:
91262
G-001
FINAL SUBMITTAL
8/18/2021
T
IT
LE
S
H E
E T
GJD
LCS
CP1038344
A L T
E R
A C
M A
IN
T
E N
A N
C E
H A
N G
A R
S O
A M
X S
B
ALTER AC MAINTENANCE HANGAR
801 SOAMXS, BLDG. 91262
HURLBURT FIELD, FLORIDA
CP1038344
PROJECT
SITE
PLAN
NORTH
AR94997
DERETSI
G
E R
A R C H
IT
E C
T
FOETAT
S
FL O R ID
A
R ICE
ACREBO
R
RLT
08/18/2021
IA
R
E
OF
RC
SP
EC
IA
AN
N
P
ER
L O
AT
IO
M M
S
CO
D
SHEET REFERENCE:
D A
T E
SHEET NUMBER:
OF
D E
S C
R
IP
T
IO
N R
E V
A
IR
F O
R C
E
SP
EC
IA
L O
PE
R
A
TI
O N
S C
O M
M A
N D
S
P
EC
IA
L
O
PE
R A
TI
O
N S
C
IV
IL
E
N G
IN
E
ER
S
Q U
A D
R O
N
H U
R
LB
U R
T
FI
EL
D
, F
LO
R
ID
A
PROJECT NUMBER:
BUILDING NUMBER:
DRAWN BY:
DESIGNED BY:
DATE:
91262
G-002
FINAL SUBMITTAL
8/18/2021
D R
A W
IN
G
IN
D
E X
Author
Designer
CP1038344
A L T
E R
A C
M A
IN
T
E N
A N
C E
H A
N G
A R
S O
A M
X S
B
INDEX OF DRAWINGS
SHEET
NUMBER SHEET NAME
FIRE PROTECTION
FX-111 1ST FLOOR DEMO PLAN - FIRE PROTECTION
FX-121 1ST FLOOR PLAN - FIRE PROTECTION
FX-122 2ND FLOOR PLAN - FIRE PROTECTION
FX-201 FIRE PROTECTION DETAILS
FIRE ALARM
F-101 FIRE ALARM NOTES, LEGEND AND MATRIX
F-121 1ST FLOOR PLAN - FIRE ALARM
F-122 2ND FLOOR PLAN - FIRE ALARM
MECHANICAL
M-001 GENERAL MECHANICAL INFORMATION
M-101 DEMOLITION - 1ST FLOOR HVAC
M-201 1ST FLOOR HVAC
M-202 2ND FLOOR HVAC
M-501 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES AND CONTROLS
ELECTRICAL
E-001 LEGEND, GENERAL NOTES, POWER RISER DIAGRAM
E-002 LIGHTING FIXTURE SCHEDULE AND DETAILS
E-003 DIAGRAMS AND DETAILS
E-101 1ST FLOOR ELECTRICAL DEMOLITION PLAN
E-102 2ND FLOOR ELECTRICAL DEMOLITION PLAN
E-103 1ST FLOOR LIGHTING PLAN
E-104 2ND FLOOR LIGHTING PLAN
E-105 1ST FLOOR POWER PLAN
E-106 2ND FLOOR POWER PLAN
TELECOMMUNICATIONS
T-001 1ST FLOOR COMMUNICATIONS PLAN
T-101 1ST FLOOR COMMUNICATIONS PLAN
T-102 2ND FLOOR COMMUNICATIONS PLAN
INDEX OF DRAWINGS
SHEET
NUMBER SHEET NAME
GENERAL
G-001 TITLE SHEET
G-002 DRAWING INDEX
L-121 1ST FLOOR PLAN - LIFE SAFETY
L-122 2ND FLOOR PLAN - LIFE SAFETY
STRUCTURAL
S-001 GENERAL NOTES
S-002 GENERAL NOTES
S-100 SLAB-ON-GRADE PLAN
S-101 ENLARGED SLAB-ON-GRADE PLANS
S-110 MEZZANINE FRAMING PLAN
S-201 ELEVATIONS
S-202 ELEVATIONS
S-301 MEZZANINE SECTIONS
S-302 MEZZANINE SECTIONS
S-303 CMU OPENING SECTIONS
S-401 FOUNDATION SECTIONS
S-501 TYPICAL STEEL DETAILS
S-502 TYPICAL CMU DETAILS
S-503 TYPICAL SLAB-ON-GRADE DETAILS
ARCHITECTURAL
A-001 WALL TYPES, SYMBOLS & ABBREVIATIONS
A-100 OVERALL PLAN
A-111 1ST FLOOR PLAN - DEMOLITION
A-112 2ND FLOOR PLAN - DEMOLITION
A-121 1ST FLOOR PLAN - NEW WORK
A-122 2ND FLOOR PLAN - NEW WORK
A-151 1ST FLOOR RCP - DEMOLITION
A-152 2ND FLOOR RCP - DEMOLITION
A-161 1ST FLOOR RCP - NEW WORK
A-162 2ND FLOOR RCP - NEW WORK
A-201 ELEVATIONS & PARTIAL BUILDING SECTION
A-401 STAIRS & DETAILS
A-402 STAIRS, STAIR DETAILS & OHCD DETAILS
A-601 OPENING SCHEDULE AND DETAILS
A-602 OPENING DETAILS
A-701 CASEWORK & SECTION DETAILS
INTERIOR
I-101 1ST FLOOR PLAN - FINISH AND FURNITURE
I-102 2ND FLOOR PLAN - FINISH AND FURNITURE
I-103 1ST FLOOR PLAN - SIGNAGE
I-104 2ND FLOOR PLAN - SIGNAGE
I-601 FINISH SCHEDULE, NOTES, AND DETAILS
1.00 GENERAL NOTES
1.01 THESE DRAWINGS ADDRESS ONLY THE STRUCTURAL DESIGN OF THE STRUCTURE. THE DIMENSIONAL LAYOUT OF THE STRUCTURE HAS BEEN DICTATED TO JOE DEREUIL ASSOCIATES IN ORDER TO PRODUCE STRUCTURAL DESIGN DOCUMENTS. NO REPRESENTATION IS MADE REGARDING CODE CONFORMANCE OF NON-STRUCTURAL ASPECTS OF THE STRUCTURE.
1.02 THESE STRUCTURAL NOTES SHALL BE APPLIED WITH THE TECHNICAL SPECIFICATIONS IN THE SPECIFICATIONS MANUAL. ANY CONFLICTING REQUIREMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER-OF-RECORD FOR RESOLUTION
BEFORE PROCEEDING WITH FABRICATION OR CONSTRUCTION.
1.03 DRAWINGS SHOW TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY. FOR DETAILS NOT SPECIFICALLY SHOWN, PROVIDE
DETAILS SIMILAR TO THOSE SHOWN.
1.04 VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE STARTING WORK. NOTIFY STRUCTURAL ENGINEER OF
ANY DISCREPANCY.
1.05 THE DESIGN, ADEQUACY, AND SAFETY OF ERECTION BRACING, SHORING, TEMPORARY SUPPORTS, ETC., ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. TAKE NECESSARY PRECAUTIONS TO PROTECT THE EXISTING STRUCTURE AND ITS FOUNDATION AND TO LIMIT, TO THE EXTENT POSSIBLE, THE EFFECTS OF CONSTRUCTION THAT THE NEW STRUCTURE HAS ON THE
EXISTING STRUCTURE.
1.06 COORDINATE STRUCTURAL CONTRACT DOCUMENTS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND CIVIL.
NOTIFY STRUCTURAL ENGINEER OF ANY CONFLICT AND/OR OMISSION. CONTRACTOR SHALL MAKE NO DEVIATION FROM DESIGN DRAWINGS WITHOUT WRITTEN APPROVAL OF THE ARCHITECT. FOR ADDITIONAL OPENINGS NOT SHOWN ON THE STRUCTURAL
DRAWINGS, SEE ARCHITECTURAL, MECHANICAL, AND PLUMBING DRAWINGS.
1.07 DESIGN CRITERIA:
THE STRUCTURE HAS BEEN DESIGNED UTILIZING THE FOLLOWING REFERENCES:
A. UFC 1-200-01, GENERAL BUILDING REQUIREMENTS
B. UFC 3-301-01, STRUCTURAL ENGINEERING
C. INTERNATIONAL BUILDING CODE, 2018
D. ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
E. ACI 302.1 R-15, CONCRETE FLOOR AND SLAB CONSTRUCTION
F. ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
G. ACI 360 R-10, DESIGN OF SLABS-ON-GROUND
H. AISC STEEL CONSTRUCTION MANUAL 15TH EDITION
I. ANSI/SDI, AMERICAN NATIONAL STANDARDS INSTITUTE/STEEL DECK INSTITUTE, RD-2010 STANDARD FOR STEEL FLOOR
DECK
J. TMS 402/602-16, BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES
1.08 DESIGN LOADS
A. DEAD LOADS:
1. MECHANICAL, ELECTRICAL, PLUMBING: 5 PSF
2. MISCELLANEOUS: 5 PSF
B. LIVE LOADS: (MAY BE REDUCED PER CODE)
1. STAIRS: 100 PSF
2. EXISTING MEZZANINE (OFFICE SPACE): 100 PSF
3. SLAB-ON-GRADE: 250 PSF
4. HEAVY STORAGE: 250 PSF
C. WIND LOADS - STRUCTURE HAS BEEN DESIGNED TO CONFORM TO THE WIND PROVISIONS OF ASCE 7-16. SEE WIND
PRESSURE DIAGRAM & CHART FOR THE FOLLOWING:
1. BASIC WIND SPEED (3-SEC GUST)
2. BUILDING RISK CATEGORY
3. WIND EXPOSURE CATEGORY
4. INTERNAL PRESSURE COEFFICIENT
5. COMPONENT & CLADDING WIND PRESSURES
D. EARTHQUAKE LOADS:
1. SEISMIC IMPORTANCE FACTOR (Ie): 1.25
2. OCCUPANCY CATEGORY: III
3. SEISMIC DESIGN CATEGORY: B
4. MAPPED SPECTRAL RESPONSE ACCELERATIONS & PARAMETERS
Ss = 0.075g Sds = 0.080g S1 = 0.053g Sd1 = 0.085g
5. SITE CLASSIFICATION: D
6. BASIC SEISMIC-FORCE-RESISTING SYSTEM: ORDINARY REINFORCED MASONRY SHEAR WALLS
7. DESIGN BASE SHEAR: 7.7 KIPS
8. SEISMIC RESPONSE COEFFICIENT, Cs = 0.050
9. RESPONSE MODIFICATION FACTOR(S): 2
10. ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE
1.09 SHOP DRAWING SUBMITTALS:
A. THE REVIEW OF SUBMITTALS AND/OR SHOP DRAWINGS DONE BY THE STRUCTURAL ENGINEER DOES NOT RELIEVE THE
CONTRACTOR OF THE RESPONSIBILITY TO REVIEW AND CHECK SHOP DRAWINGS BEFORE SUBMITTAL TO THE STRUCTURAL ENGINEER. THE REVIEW BY THE STRUCTURAL ENGINEER IS FOR GENERAL CONFORMANCE ONLY. IF SHOP DRAWINGS HAVE NOT BEEN REVIEWED AND APPROVED BEFORE SUBMITTAL TO THE STRUCTURAL ENGINEER, THEY SHALL
BE RETURNED WITHOUT APPROVAL.
B. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ANY AND ALL ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF ALL SHOP DRAWINGS AS THEY PERTAIN TO MEMBER SIZES, DETAILS, AND DIMENSIONS SPECIFIED IN
THE CONSTRUCTION DOCUMENTS.
C. ALL MODIFICATIONS MADE FOR SUBMITTALS THAT ARE RE-SUBMITTED SHALL CLEARLY NOTE ALL CHANGES.
D. REPRODUCING THE CONTRACT DOCUMENTS FOR USE AS SHOP DRAWINGS IS NOT ALLOWED, AND SHOP DRAWINGS WILL
BE RETURNED WITHOUT APPROVAL.
E. GENERAL SHOP DRAWING REQUIREMENTS:
1. SUBMIT SHOP DRAWINGS AND ANY OTHER SPECIAL INFORMATION NECCESSARY FOR PROPER FABRICATION, ERECTION, AND PLACEMENT OF STRUCTURAL FABRICATIONS. INCLUDE PLANS, ELEVATIONS, AND SECTIONS.
CLEARLY SHOW ANCHORAGES, CONNECTIONS, AND ACCESSORY ITEMS. THE DETAILER MUST INTERPRET THE CONTRACT DOCUMENTS AND CLEARLY CONVEY THIS INTERPRETATION TO THE FIELD IN THE FORM OF PLACING OR
ERECTION DRAWINGS.
2. CONCRETE REINFORCING DETAILER - PROVIDE PLACING DRAWINGS FOR FABRICATION AND PLACING OF REINFORCING STEEL. THESE DRAWINGS SHALL INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: BAR LISTS, SCHEDULES, BENDING DETAILS, PLACING DETAILS, PLACING PLANS, AND PLACING ELEVATIONS. CLEARLY SHOW FOUNDATION REINFORCING. INDICATE BAR LENGTHS, LOCATION AND SPLICES OF CONTINUOUS BARS, AND BAR
SUPPORTS. CLEARLY SHOW LOCATIONS OF ALL DOWELS ON PLAN.
1.10 SHOP DRAWINGS BY SPECIALTY ENGINEER:
A. THE FOLLOWING SYSTEMS AND COMPONENTS AS A MINIMUM REQUIRE SPECIALTY ENGINEERED ERECTION AND
FABRICATION DRAWINGS WITH INPUT BY A SPECIALTY ENGINEER, BUT ARE NOT LIMITED TO: WINDOW SYSTEMS, STOREFRONT SYSTEM, ROOF SYSTEMS, AWNINGS, LOUVERS, LADDERS, AND ALL EXTERIOR SOFFIT FRAMING.
B. THE SPECIALTY ENGINEER OR SUPPLIER SHALL DESIGN AND INSTALL THEIR COMPLETED SYSTEM IN ITS ENTIRETY TO THE PRIMARY STRUCTURE PER THE CRITERIA NOTED ON THESE CONSTRUCTION DOCUMENTS. THE SPECIALTY ENGINEER SHALL ADHERE TO ALL REQUIREMENTS OF THE APPLICABLE BUILDING CODE OR THESE NOTES, WHICHEVER IS MORE
STRINGENT.
C. SHOP DRAWINGS SHALL BE PROVIDED TO THE ARCHITECT/E.O.R. AND CALCULATIONS SHALL REQUIRE THE SEAL, DATE, AND SIGNATURE OF THE SPECIALTY ENGINEER REGISTERED IN THE PROJECT STATE.
2.00 FOUNDATIONS AND SLAB-ON-GRADE
2.01 REFER TO SECTION 7.00 FOR HELICAL PILES.
2.02 SIDES OF FOUNDATIONS SHALL BE FORMED. SLOPE SIDES OF EXCAVATIONS AS APPROVED BY GEOTECHNICAL ENGINEER AND
CLEAN UP SLOUGHING BEFORE AND DURING CONCRETE PLACEMENT.
2.03 CONTRACTOR IS RESPONSIBLE FOR ADEQUATELY PROTECTING ALL EXCAVATION SLOPES.
2.04 DEWATER TO AT LEAST TWO FEET BELOW BOTTOM OF LOWEST FOUNDATION IF GROUNDWATER IS ENCOUNTERED. REFER TO DIVISION 1 SPECIFICATIONS FOR ENVIRONMENTAL CONTROLS & DEWATERING. THE SITE IS KNOWN TO HAVE CONTAMINATED
GROUNDWATER WHICH MAY BE ENCOUNTERED.
2.05 SEE SPECIFICATIONS FOR VAPOR RETARDER MATERIAL VAPOR RETARDER SHALL CONFORM TO ASTM E1745, CLASS A, B, & C AND A MINIMUM OF 15 MIL. THICKNESS. VAPOR RETARDER SHOULD BE PLACED OVER THE COMPACTED SUBGRADE. IF THE VAPOR BARRIER/RETARDER IS TO BE PLACED OVER A ROUGH GRANULAR FILL A THIN LAYER OF APPROXIMATELY 1/2 IN. OF FINE-GRADED MATERIAL SHOULD BE ROLLED OR COMPACTED OVER THE FILL PRIOR TO INSTALLATION OF THE VAPOR BARRIER/RETARDER TO REDUCE THE POSSIBILITY OF PUNCTURE. VAPOR RETARDER SHOULD BE OVERLAPPED 8 IN. AND TAPED AT THE JOINTS AND CAREFULLY
FITTED AROUND SERVICE OPENINGS.
3.00 REINFORCED CONCRETE
3.01 ALL CONCRETE WORK SHALL CONFORM TO ACI 301-16, SPECIFICATIONS FOR STRUCTURAL CONCRETE. DESIGN IS BASED ON ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE. DETAIL CONCRETE REINFORCEMENT AND ACCESSORIES IN ACCORDANCE WITH ACI 315R-18, GUIDE TO PRESENTING REINFORCING STEEL DESIGN DETAILS. DETAIL ALL CONCRETE WALLS AND BEAMS ON THE SHOP DRAWINGS IN ELEVATION UNLESS SPECIFICALLY APPROVED OTHERWISE. SUBMIT SHOP DRAWINGS FOR APPROVAL, SHOWING ALL FABRICATION DIMENSIONS AND LOCATIONS FOR PLACING REINFORCING STEEL AND ACCESSORIES. DO NOT
BEGIN FABRICATION UNTIL SHOP DRAWINGS ARE COMPLETED AND REVIEWED.
3.02 UNLESS NOTED OTHERWISE, ALL CONCRETE SHALL BE NORMAL WEIGHT AND HAVE THE FOLLOWING MINIMUM 28 DAY COMPRESSIVE STRENGTHS (Fc’), WATER TO CEMENTITIOUS CONTENT (W/CM) AND AIR CONTENT ACCORDING TO EXPOSURE CLASS (EC):
Fc’ MAX. W/CM AIR CONTENT
A. FOUNDATIONS
(EC)-F0, S0, W0, C0) 3500 PSI 0.50 N/A
B. FRAMED (ELEVATED) FLOOR SLABS - INTERIOR
(EC-F0, S0, W0, C0) 3500 PSI 0.50 N/A
C. SLAB-ON-GRADE - INTERIOR & EXTERIOR
(EC-F0, S0, W0, C0) 3500 PSI 0.50 N/A
CONCRETE MAY CONTAIN A PROPERLY DESIGNED SUPERPLASTICIZER FOR WORKABILITY.
3.03 REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60 UNLESS NOTED OTHERWISE.
3.04 REASONABLE MEASURES HAVE BEEN TAKEN TO MITIGATE SHRINKAGE CRACKING THROUGH THE USE OF JUDICIOUS DETAILING AND REINFORCING. HOWEVER SOME VISIBLE CRACKING IS TO BE EXPECTED AS A RESULT OF CONCRETE SHRINKAGE RESTRAINT.
FURTHER MEASURES COULD BE TAKEN TO ELIMINATE ALL VISIBLE CRACKING, BUT THESE WOULD COME AT A COST IN THE FORM OF ADDITIONAL REINFORCING. ANY CRACKING THAT DOES OCCUR SHALL BE REPAIRED WITH APPROPRIATE PROCEDURES.
3.05 THE PROPOSED MATERIALS AND MIX DESIGN SHALL BE FULLY DOCUMENTED AND REVIEWED BY THE OWNER'S TESTING LABORATORY. RESPONSIBILITY FOR OBTAINING THE REQUIRED DESIGN STRENGTH IS THE CONTRACTOR'S.
3.06 USE OF CALCIUM CHLORIDE, CHLORIDE IONS, OR OTHER SALTS IN CONCRETE IS NOT PERMITTED.
3.07 CHAMFER OR ROUND ALL EXPOSED CORNERS A MINIMUM OF 3/4".
3.08 TIE ALL REINFORCING STEEL AND EMBEDMENTS SECURELY IN PLACE PRIOR TO PLACING CONCRETE. PROVIDE SUFFICIENT SUPPORTS TO MAINTAIN THE POSITION OF REINFORCEMENT WITHIN SPECIFIED TOLERANCE DURING ALL CONSTRUCTION ACTIVITIES.
"STICKING” DOWELS INTO WET CONCRETE IS NOT PERMITTED.
3.09 PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE; SPLICE ONLY AS SHOWN OR APPROVED; STAGGER SPLICE WHERE POSSIBLE; USE FULL TENSION SPLICE (CLASS "B") UNLESS NOTED OTHERWISE. DOWELS SHALL MATCH THE SIZE AND SPACING OF THE SPECIFIED REINFORCEMENT AND SHALL BE LAPPED WITH FULL TENSION SPLICES (CLASS "B") UNLESS NOTED OTHERWISE.
TERMINATE BARS WITH STANDARD HOOKS.
3.10 REINFORCING STEEL SHALL HAVE THE FOLLOWING CONCRETE COVER UNLESS NOTED OTHERWISE (PER ACI 318-14 TABLE 20.6.1.3.1):
A. CONCRETE AGAINST EARTH (NOT FORMED): 3"
B. FORMED CONCRETE EXPOSED TO THE EARTH OR WEATHER:
1. #6 THROUGH #18 BARS: 2"
2. #5 BARS AND SMALLER: 1-1/2"
C. CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
1. SLABS AND WALLS: 3/4"
3.11 DO NOT WELD OR TACK WELD REINFORCING STEEL UNLESS APPROVED OR DIRECTED BY THE STRUCTURAL ENGINEER.
3.12 THE DESIGN AND CONSTRUCTION OF FORMS SHALL CONFORM TO THE FOLLOWING REQUIREMENTS:
A. FORMS SHALL CONFORM TO SHAPE, FORM AND LINES ON DRAWINGS.
B. ADEQUATE BRACING SHALL BE USED.
C. FORMS SUPPORTED ON GROUND SHALL HAVE ADEQUATE MUDSILLS.
D. QUALIFIED WORKMEN SHALL CONSTANTLY OBSERVE AND ADJUST, AS REQUIRED, ALL SHORES DURING CONCRETE
PLACING.
E. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE ADEQUATE DESIGN AND CONSTRUCTION OF ALL FORMS.
F. SPECIAL ATTENTION IS DIRECTED TO THE REQUIREMENT THAT THE CONTRACTOR MUST ADJUST THE SHORING, USING
SURVEYING INSTRUMENTS, DURING AND IMMEDIATELY AFTER PLACING OF CONCRETE FOR SLABS; THIS ADJUSTMENT
MUST NOT BE ATTEMPTED AFTER THE INITIAL SET OF CONCRETE.
3.13 SHORING SHALL REMAIN IN PLACE UNTIL CONCRETE HAS ATTAINED 75% OF ITS 28-DAY STRENGTH.
3.14 THE LICENSED DESIGN PROFESSIONAL, A PERSON UNDER THE SUPERVISION OF A LICENSED DESIGN PROFESSIONAL, OR A QUALIFIED INSPECTOR SHALL VERIFY COMPLIANCE WITH CONSTRUCTION DOCUMENTS. (ACI 318-14 PAR. 26.13.1.3)
3.15 ALL REINFORCING STEEL PLACEMENTS SHALL BE REVIEWED BY THE CONTRACTING OFFICER, OR BY A REPRESENTATIVE
RESPONSIBLE TO HIM. (RE: ACI 318 PAR. 26.13.1)
3.16 FOR CONCRETE PADS SEE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS.
4.00 STRUCTURAL STEEL, STEEL DECK
4.01 STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED ACCORDING TO AISC 360-10 SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS.
4.02 SUBMIT SHOP DRAWINGS PREPARED IN ACCORDANCE WITH AISC MANUAL "DETAILING
FOR STEEL CONSTRUCTION", LATEST EDITION. STEEL FABRICATOR SHALL SUPPLY ANCHOR
BOLT LOCATION DRAWINGS. DO NOT BEGIN FABRICATION UNTIL SHOP DRAWINGS ARE
COMPLETED AND REVIEWED.
4.03 STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992.
STRUCTURAL STEEL SHAPES, PLATES, ANGLES, AND CHANNELS SHALL CONFORM TO ASTM
A36 UNLESS NOTED OTHERWISE. STEEL GUSSET PLATES USED IN BRACED FRAME
CONNECTIONS SHALL CONFORM TO ASTM A572, GRADE 50. HOLLOW STRUCTURAL STEEL
SHAPES SHALL CONFORM TO ASTM A500, GRADE C, FY = 50 KSI, UNLESS NOTED OTHERWISE.
4.04 BOLTS SHALL CONFORM TO ASTM A325, 3/4-INCH DIAMETER MINIMUM, UNLESS NOTED
OTHERWISE. BOLTS IN BEARING CONNECTIONS SHALL BE DESIGNATED TYPE N, TENSIONED,
SNUG-TIGHT AS DEFINED BY AISC. BOLTS IN MOMENT CONNECTIONS AND IN TRUSSES SHALL BE DESIGNATED SLIP-CRITICAL (SC). FULLY TENSION SLIP-CRITICAL CONNECTIONS WITH DIRECT TENSION INDICATOR WASHERS INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTION.
4.05 HEADED ANCHOR RODS: ASTM F 1554, GRADE 36 ASTM F 1554, GRADE 55, WELDABLE, STRAIGHT.NUTS: ASTM A 563 (ASTM A 563M) HEAVY-HEX CARBON STEEL, PLATE WASHERS: ASTM A 36/A 36M CARBON STEEL, WASHERS: ASTM F 436 (ASTM F 436M), TYPE 1, HARDENED CARBON STEEL. FINISH: HOT-DIP ZINC COATING, ASTM A 153/A 153M, CLASS C MECHANICALLY DEPOSITED ZINC COATING, ASTM B 695, CLASS 50.
4.06 ALL COLUMNS, UNLESS NOTED OTHERWISE, SHALL BEAR ON 1 ½” GROUT BED. GROUT SHALL BE NON-SHRINK, NON-METALLIC
AND SHALL BE PLACED PRIOR TO POURING OF UPPER FLOOR LEVELS.
4.07 HEADED STUD SHEAR CONNECTORS: ASTM A 108, GRADES 1010 THROUGH 1020, HEADED-STUD TYPE, COLD-FINISHED CARBON STEEL; AWS D1.1, TYPE B. USE AUTOMATIC END WELDING OF HEADED-STUD SHEAR CONNECTORS ACCORDING TO AWS D1.1 AND
MANUFACTURER’S WRITTEN INSTRUCTIONS.
4.08 USE PRE-QUALIFIED WELDED JOINTS AS PER AISC, AND AWS D1.1 "STRUCTURAL WELDING CODE." USE ONLY CERTIFIED WELDERS; ALL ELECTRODES SHALL CONFORM TO AWS A5 GRADE E70XX. BARE ELECTRODE AND GRANULAR FLUX SHALL CONFORM TO AWS A5, F70 AWS FLUX CLASSIFICATION. MINIMUM WELD SIZE TO BE 3/16" FILLET WELD, U.N.O.
4.09 CUTS, BOLTS, COPING, ETC. REQUIRED FOR WORK OR OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS AND MADE IN THE SHOP. CUTS OR BURNING HOLES IN STRUCTURAL STEEL MEMBERS IN THE FIELD WILL NOT BE PERMITTED.
4.10 SHOP CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS MAY BE WELDED OR BOLTED. FIELD CONNECTIONS NOT
SPECIFICALLY DETAILED ON THE DRAWINGS SHALL BE BOLTED, WHERE POSSIBLE.
4.11 WHEN SPECIFICALLY NOT DETAILED ON THE DESIGN DRAWINGS PROVIDE THE FOLLOWING BEAM CONNECTIONS:
A. USE TWO-SIDE ANGLE CONNECTIONS PER AISC SPECIFICATIONS, LATEST EDITION.
B. WHERE BEAM REACTIONS ARE SHOWN, CONNECTIONS SHALL DEVELOP THE REACTION GIVEN.
C. WHEN BEAM REACTIONS ARE NOT SHOWN, CONNECTIONS SHALL BE DESIGNED TO SUPPORT ONE HALF THE TOTAL
UNIFORM LOAD CAPACITIES SHOWN IN THE ALLOWABLE UNIFORM LOAD TABLES, PARTS 2 OF THE AISC MANUAL, FOR THE
GIVEN BEAM, SPAN, AND GRADE OF STEEL SPECIFIED.
D. WHERE REACTIONS ARE SUBJECT TO ECCENTRICITY, SUCH ECCENTRICITY SHALL BE TAKEN INTO ACCOUNT.
4.12 FIELD SPLICES SHALL BE DESIGNED TO DEVELOP THE FULL CAPACITY OF MEMBER AT THE POINT OF SPLICE IN BENDING, SHEAR
AND AXIAL LOAD (COMPRESSION AND TENSION).
4.13 ALTERNATE CONNECTION DETAILS MAY BE USED IF SUCH DETAILS ARE SUBMITTED TO THE ENGINEER FOR REVIEW AND ACCEPTANCE IS GRANTED. HOWEVER, THE ENGINEER SHALL BE THE SOLE JUDGE OF ACCEPTABILITY AND THE CONTRACTOR'S BID SHALL ANTICIPATE THE USE OF THE SPECIFIC DETAILS SHOWN ON THE DRAWINGS. IN ANY EVENT, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE DESIGN OF SUCH ALTERNATE DETAILS, WHICH HE PROPOSES.
4.14 PROVIDE STIFFENER PLATES ON EACH SIDE OF WEB OF BEAM OR GIRDER AT POINTS OF CONCENTRATED LOADS. MINIMUM STIFFENER PLATE THICKNESS SHALL BE 1/2" OR FLANGE THICKNESS OF COLUMNS ABOVE OR BELOW, WHICHEVER IS THICKER.
4.15 PROVIDE TEMPORARY BRACING OF STRUCTURAL FRAMING TO PROVIDE LATERAL SUPPORT UNTIL ALL PERMANENT BRACING MOMENT CONNECTIONS AND FLOOR AND ROOF DECKS (DIAPHRAGMS) ARE COMPLETELY INSTALLED.
4.16 STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL AND MECHANICAL DRAWINGS AND DRAWINGS RELATED TO OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE TO CHECK AND COORDINATE DIMENSIONS, CLEARANCES, ETC.
WITH THE WORK OF OTHER TRADES. THE STRUCTURAL STEEL CONTRACTOR SHALL PROVIDE FRAMING AROUND OPENINGS IN FLOOR
AND ROOF SLAB AS INDICATED IN THE MECHANICAL AND ARCHITECTURAL DRAWINGS.
4.17 THE STRUCTURAL STEEL CONTRACTOR SHALL PROVIDE WEB REINFORCEMENT AT OPENINGS IN STEEL BEAMS AND GIRDERS FOR MECHANICAL AND ELECTRICAL PENETRATIONS. WEB OPENINGS SHALL BE LOCATED IN THE MIDDLE 1/3 OF BEAM DEPTH. WEB REINFORCEMENT IS NOT REQUIRED FOR WEB OPENINGS LESS THAN 4" DIAMETER OR 3" X 3". A MAXIMUM OF ONE WEB OPENING IS
PERMITTED FOR EACH BEAM NOT HAVING WEB REINFORCEMENT.
4.18 STRUCTURAL STEEL CONTRACTOR SHALL COORDINATE THE BOTTOM OF BASE PLATE ELEVATION WITH THE TOP OF CONCRETE ELEVATION. IN CASE OF CONFLICT, THE CONTRACTOR SHALL MAKE ALLOWANCE IN HIS BID FOR MORE STRINGENT REQUIREMENTS.
4.19 COMPOSITE CONSTRUCTION SHEAR CONNECTORS: SOLID FLUXED SHEAR CONNECTORS STUDS AUTOMATICALLY WELDED THROUGH THE METAL DECK AS SHOWN ON THE DRAWINGS AND IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE
MANUFACTURER (NELSON DIVISION OF TRW OR APPROVED EQUAL).
4.20 ALL STUD WELDING SHALL BE INSPECTED AND FIELD-TESTED. ALL STUDS FAILING THE TEST SHALL BE REPLACED AT THE
CONTRACTORS EXPENSE.
4.21 PAINT STRUCTURAL STEEL IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. DO NOT PAINT STEEL SURFACES TO BE ENCASED IN CONCRETE OR RECEIVE SPRAYED ON FIREPROOFING, CONNECTIONS DESIGNATED AS SLIP CRITICAL, OR TO BE WELDED.
STEEL SURFACES RECEIVING AUTOMATICALLY WELDED SHEAR CONNECTORS STUDS IN THE FIELD SHALL NOT BE PAINTED.
4.22 PRIMER: SSPC-PAINT 25, TYPE I, ZINC OXIDE, ALKYD, LINSEED OIL PRIMER.
D
EU
SOJ
R E
G
ISTERE
R E
E
NIGNED
EPH
ER
IL
SI
U
OL
A
DIOL
F R
STATE OF
No. 54319
E T
ACFIT
C R
E
I
301 West Cervantes St.301 West Cervantes St.301 West Cervantes St.301 West Cervantes St. Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951 Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501
JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA
IA
R
E
OF
RC
SP
EC
IA
AN
N
P
ER
L O
AT
IO
M M
S
CO
D
SHEET REFERENCE:
D A
T E
SHEET NUMBER:
OF
D E
S C
R
IP
T
IO
N R
E V
A
IR
F O
R C
E
SP
EC
IA
L O
PE
R
A
TI
O N
S C
O M
M A
N D
SP
EC
IA
L O
PE
RA
TI
ON
S
CI
VI
L
EN
GI
NE
ER
S
QU
AD
RO
N
H U
R
LB
U R
T
FI
EL
D
, F
LO
R
ID
A
PROJECT NUMBER:
BUILDING NUMBER:
DRAWN BY:
DESIGNED BY:
DATE:
91262
STATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDA
P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515
JDA JOB #18163
S-001
FINAL SUBMITTAL
8/18/2021
G E
N E
R A
L N
O T
E S
WEC
WEC
CP1038344
A L T
E R
A C
M A
IN
T
E N
A N
C E
H A
N G
A R
S O
A M
X S
B
8/18/20218/18/20218/18/20218/18/2021
4.23 HIGH PERFORMANCE PAINT SYSTEM SHALL BE USED FOR ALL EXTERIOR STEEL STRUCTURES. EQUIVALENT SYSTEM BY OTHER MANUFACTURERS MAY BE PROPOSED. HOWEVER, THE ENGINEER SHALL BE THE SOLE JUDGE OF ACCEPTABILITY AND THE
CONTRACTOR'S BID SHALL ANTICIPATE THE USE OF THE SPECIFIC SYSTEM.
A. HIGH PERFORMANCE ZINC RICH URETHANE PRIMER/ EPOXY INTERMEDIATE/ FLOUROPOLYMER URTETHANE FINISH PAINTSYSTEM: SURFACE PREPARATION REMOVE ALL GREASE AND OTHER SOLUBLE CONTAMINANTS IN ACCORDANCE
WITH SSPC-SP1 SOLVENT CLEANING.
B. SHOP SURFACE PREPARATION SHALL BE CLEANED IN ACCORDANCE WITH SSPC-SP10 NEAR WHITE BLAST CLEANING.
PRIME ANY BARE STEEL THE SAME DAYAS IT IS CLEANED AND BEFORE ANY RUST BLOOM HAS FORMED. SURFACE PROFILE
SHALL BE 1.5-2.5
C. PRIMER: TNEMEC SERIES 90-97 TNEME-ZINC (2.5 – 3.5 MILS DFT)
FIELD TOUCH UP REPAIR SHALL BE CLEANED IN ACCORDANCE WITH SSPC-SP11 POWER TOOL CLEANING TO BARE METAL.
FIELD TOUCH UP: TOUCH UP FIELD WELDS AND SCRATCHES WITH 90-97 TNEMEC ZINC PRIMER (2.5- 3.5 MILS DFT)
D. STRIPE COAT: ALL SHARP EDGES, BOLTED CONNECTIONS, WELDED CONNECTIONS AND OTHER DIFFICULT TO COAT AREAS SHALL RECEIVE ONE COAT, APPLIED BY BRUSH, OF TNEMEC SERIES 66 EPOXOLINE (4.0-6.0 MILS DFT) PREPARATION PRIOR TO APPLICATION OF FINISH COATS: ALL SURFACES TO BE COATED SHALL BE HIGH PRESSURE WATER WASHED USING CHLOR*RID TO REMOVE ALL CHLORIDES, DIRT, DUST, AND OTHER FOREIGN MATTER.
2ND COAT: TNEMEC SERIES 66 EPOXOLINE (4.0-6.0 MILS DFT)
3RD COAT: TNEMEC 1070 FLOURONAR (2.0 – 3.0 MILS DFT)
STEEL DECKING:
4.24 FABRICATION AND ERECTION OF STEEL DECKING SHALL CONFORM TO THE LATEST EDITION OF THE STEEL DECK INSTITUTE'S (SDI) "SPECIFICATION AND COMMENTARY FOR COMPOSITE STEEL FLOOR DECK, NON-COMPOSITE STEEL DECK, AND STEEL ROOF DECK"
AS APPLICABLE TO THIS PROJECT.
4.25 MATERIAL FOR STEEL DECKING SHALL CONFORM TO ASTM A1008 OR A653 WITH 50 KSI MINIMUM YEILD STRENGTH. SEE
DRAWINGS FOR STEEL DECK TYPE, GAUGE, AND SECTION PROPERTIES.
4.26 FLOOR DECK SHALL BE COMPOSITE FLOOR DECK.
4.27 UNLESS NOTED OTHERWISE ALL STEEL DECKING SHALL HAVE A GALVANIZED COATING CONFORMING TO ASTM A653, G90.
4.28 THE BELOW PRODUCTS ARE THE DESIGN BASIS FOR THIS PROJECT. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTED BELOW MAY BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER-OF-RECORD (EOR) FOR REVIEW. SUBSTITUTIONS WILL ONLY BE CONSIDERED FOR PRODUCTS THAT MEET THE CODE REQUIREMENT FOR DECK ATTACHMENT, POSSESS A FM GLOBAL APPROVAL AND POSSESS A CODE REPORT RECOGNIZING THE PRODUCT FOR THE APPROPRIATE APPLICATION. SUBSTITUTION REQUESTS SHALL INCLUDE CALCULATIONS THAT DEMONSTRATE THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE EQUIVALENT PERFORMANCE VALUES OF THE DESIGN BASIS PRODUCT. CONTRACTOR SHALL CONTACT MANUFACTURER’S REPRESENTATIVE FOR PRODUCT INSTALLATION TRAINING, AND A LETTER SHALL BE SUBMITTED TO THE EOR INDICATING TRAINING HAS TAKEN PLACE. REFER TO THE BUILDING CODE AND THE MANUFACTURER’S LITERATURE FOR ANY OTHER REQUIREMENTS. FASTENERS SHALL BE COLLATED AND INSTALLED USING THE MANUFACTURER’S DELIVERY TOOL AND FOLLOWING MANUFACTURER’S INSTRUCTIONS. REFER TO PLAN NOTES, DETAILS OR SCHEDULES FOR THE SPECIFIC FASTENER PATTERN FOR VARIOUS ZONES OF THE
DECK.
4.29 STEEL FLOOR DECK ANCHORAGE (UNLESS NOTED OTHERWISE ON PLANS OR DETAILS):
A. WELDING: ANCHOR STEEL DECKING TO THE SUPPORTING STRUCTURE INCLUDING BEARING WALLS WITH NOMINAL 5/8
INCH DIAMETER PUDDLE WELDS OR EQUIVALENT, AT ALL EDGE RIBS PLUS INTERIOR RIBS AT A MINIMUM SPACING OF 24 INCHES. WHERE SHEAR STUDS ARE USED FOR COMPOSITE CONSTRUCTION, THE STUDS MAY REPLACE THE WELDS.
B. SCREWS: AS AN ALTERNATE TO WELDING, DECK MAY BE ANCHORED TO SUPPORTING STRUCTURE USING #12 SELF- TAPPING STRONG-DRIVE XL LARGE-HEAD METAL SCREWS BY SIMPSON (OR APPROVED EQUAL), AT ALL EDGE RIBS PLUS INTERIOR RIBS AT A MINIMUM SPACING OF 24 INCHES. CONTRACTOR HAS THE OPTION TO USE POWDER ACTUATED
FASENTERS BY HILTI (OR APPROVED EQUAL):
BASE STEEL THICKNESS HILTI P.A.F.
<3/8” X-EDN 19 THQ 12
>3/8” X-ENP-19 L15
C. FASTEN SIDE LAPS OF ADJACENT UNITS AT A MAXIMUM SPACING OF 24 INCHES WITH #10 SELF-TAPPING XJ METAL
SCREWS BY SIMPSON (OR APPROVED EQUAL)..
4.30 PROVIDE DECKING CONTINUOUS OVER 3 SPANS MINIMUM WHERE SUPPORTING STRUCTURE PERMITS.
4.31 STEEL DECKING SHALL BE ERECTED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S RECOMMENDATIONS
5.00 MASONRY
5.01 CONCRETE MASONRY DESIGN, CONSTRUCTION AND TESTING SHALL CONFORM TO TMS 402/602-16, BUILDING CODE
REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES.
5.02 PROVIDE LIGHTWEIGHT, HOLLOW, LOAD-BEARING CONCRETE MASONRY UNITS (CMU) CONFORMING TO ASTM C90, UNLESS
NOTED OTHERWISE.
5.03 PROVIDE MASONRY CONSTRUCTION WITH MINIMUM COMPRESSIVE STRENGTH, f'm = 2,000 PSI.
5.04 PROVIDE TYPE "M" OR “S” MORTAR IN ACCORDANCE WITH ASTM C270 BY PROPORTION REQUIREMENTS, UNLESS NOTED
OTHERWISE.
5.05 VERTICAL CELLS SHALL BE REINFORCED AS INDICATED IN THE CONTRACT DRAWINGS. VERTICAL REINFORCING SHALL BE CONTINUOUS (LAPPED 48 BAR DIAMETERS MINIMUM AT SPLICES, U.N.O.) AND HELD IN POSITION AT THE TOP AND BOTTOM OF THE
GROUT POUR. U.N.O., POSITION VERTICAL REINFORCING IN THE CENTER OF THE CELL.
5.06 PROVIDE GROUT FOR REINFORCED MASONRY IN ACCORDANCE WITH ASTM C476. GROUT SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3,000 PSI UNLESS NOTED OTHERWISE. GROUT SHALL BE FLUID CONSISTENCY. FLUID CONSISTENCY SHALL MEAN THAT CONSISTENCY IS AS FLUID AS POSSIBLE FOR POURING WITHOUT SEGREGATION OF THE CONSTITUENT PARTS. FILL ALL CELLS BELOW GRADE WITH GROUT. ALL GROUT SHALL BE CONSOLIDATED AT THE TIME OF POURING BY VIBRATING AND THEN RECONSOLIDATED BY AGAIN PUDDLING LATER, BEFORE PLASTICITY IS LOST. WHEN GROUTING IS STOPPED FOR ONE HOUR OR LONGER, CONSTRUCTION JOINTS SHALL BE FORMED BY STOPPING THE POUR OF THE GROUT 1-1/2 INCHES BELOW THE TOP OF THE UPPERMOST
UNIT.
5.07 PROVIDE HORIZONTAL JOINT REINFORCEMENT COMPLYING WITH ASTM A82, NO. 9 GAUGE OR HEAVIER, ZINC COATED, PLACED 16
INCHES ON CENTER UNLESS NOTED OTHERWISE.
5.08 PROVIDE RUNNING BONDS WITH VERTICAL JOINTS LOCATED AT CENTER OF MASONRY UNITS IN THE ALTERNATE COURSE BELOW, UNLESS NOTED OTHERWISE.
5.09 ALL MASONRY UNITS SHALL BE FREE OF EXCESSIVE DUST AND DIRT AT THE TIME THEY ARE LAYED BY THE MASON.
5.10 ALL REINFORCED HOLLOW UNIT MASONRY SHALL BE BUILT TO PRESERVE THE UNOBSTRUCTED VERTICAL CONTINUITY OF THE CELLS TO BE FILLED. WALLS AND CROSS WEBS IN ALL REINFORCED MASONRY WALLS SHALL BE FULLY BEDDED IN MORTAR. ALL HEAD (OR END) JOINTS SHALL BE SOLIDLY FILLED WITH MORTAR FOR A DISTANCE IN FROM EACH FACE OF THE UNIT NOT LESS THAN THE THICKNESS OF THE LONGITUDINAL FACE SHELLS, BOND SHALL BE PROVIDED BY LAPPING UNITS IN SUCCESSIVE VERTICAL COURSES.
5.11 PROVIDE VERTICAL CONTROL JOINTS BETWEEN REINFORCED MASONRY WALLS AND MASONRY PARTITION WALLS, AND AT A
MINIMUM OF 20’-0” O.C.
5.12 SAMPLE AND TEST MASONRY MATERIAL IN ACCORDANCE WITH TMS 602-16, TABLE 3, QUALITY ASSURANCE LEVEL 2.
5.13 INSPECT MASONRY CONSTRUCTION IN ACCORDANCE WITH TMS 602-16, TABLE 4, QUALITY ASSURANCE LEVEL 2 .
6.00 POST-INSTALLED ANCHORS
6.01 EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS SHALL CONSIST OF THE FOLLOWING ANCHOR TYPES AS PROVIDED BY HILTI, INC. CONTACT HILTI AT (800) 879-8000 FOR PRODUCT RELATED QUESTIONS.
A. REBAR DOWELING INTO CONCRETE
1. ADHESIVE ANCHORS FOR CRACKED AND UNCRACKED CONCRETE USE:
a. HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HOLLOW DRILL BIT SYSTEM WITH CONTINUOUSLY DEFORMED
REBAR PER ICC ESR-3187.
B. ANCHORAGE TO SOLID GROUTED MASONRY
1. ADHESIVE ANCHORS USE:
a. HILTI HIT-HY 70 MASONRY ADHESIVE ANCHORING SYSTEM (ICC PENDING).
b. STEEL ANCHOR ELEMENT SHALL BE HILTI HAS-E CONTINUOUSLY THREADED ROD OR CONTINUOUSLY
DEFORMED STEEL REBAR
2. MECHANICAL ANCHORS USE:
a. HILTI KWIK HUS-EZ SCREW ANCHOR PER ICC ESR-3056
b. HILTI KWIK BOLT-TZ2 MASONRY ANCHOR PER ICC ESR-4561
C. ANCHORAGE TO HOLLOW / MULTI-WYTHE MASONRY
1. ADHESIVE ANCHORS USE:
a. HILTI HIT-HY 270 MASONRY ADHESIVE ANCHORING SYSTEM PER ICC ESR-4144.
6.02 ANCHOR CAPACITY USED IN DESIGN SHALL BE BASED ON THE TECHNICAL DATA PUBLISHED BY HILTI OR SUCH OTHER METHOD AS APPROVED BY THE STRUCTURAL ENGINEER OF RECORD. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. CONTRACTOR SHALL PROVIDE CALCULATIONS DEMONSTRATING THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT. SUBSTITUTIONS WILL BE EVALUATED BY THEIR HAVING AN ICC ESR SHOWING COMPLIANCE WITH THE RELEVANT BUILDING CODE FOR SEISMIC USES, LOAD RESISTANCE, INSTALLATION CATEGORY, AND AVAILABILITY OF COMPREHENSIVE INSTALLATION INSTRUCTIONS. ADHESIVE ANCHOR EVALUATION WILL ALSO CONSIDER CREEP, IN-SERVICE TEMPERATURE AND INSTALLATION
TEMPERATURE.
6.03 INSTALL ANCHORS PER THE MANUFACTURER INSTRUCTIONS, AS INCLUDED IN THE ANCHOR PACKAGING AND IN STRICT
ACCORDANCE WITH THE CURRENT ICC ESR.
6.04 THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR’S PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE
COMMENCEMENT OF INSTALLING ANCHORS.
6.05 ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE CLEARANCES INDICATED ON THE DRAWINGS.
6.06 EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. UNLESS NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT, THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF THE REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE ANCHORS, BY HILTI
FERROSCAN, GPR, X-RAY, CHIPPING OR OTHER MEANS.
6.07 ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT THE TIME OF ANCHOR
INSTALLATION IN ACCORDANCE WITH ACI 318-14 17.4.5.2.
6.08 PROVIDE SPECIAL INSPECTION FOR ALL MECHANICAL AND ADHESIVE ANCHORS PER THE APPLICABLE BUILDLING CODE AND PER
THE CURRENT ICC-ES REPORT FOR THE ANCHOR.
7.00 HELICAL PIERS
7.01 PIERS SHALL BE INSTALLED BY AN AUTHORIZED INSTALLING CONTRACTOR WHO HAS SATISFIED THE CERTIFICATION REQUIREMENTS RELATING TO THE TECHNICAL ASPECTS OF THE PRODUCT AND THE ASCRIBED INSTALLATION TECHNIQUES. PROOF OF
CURRENT CERTIFICATION BY THE HELICAL PILE MANUFACTURER MUST BE PRESENTED.
7.02 ALL WORK AS DESCRIBED HEREIN SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE SAFETY CODES IN EFFECT AT
THE TIME OF INSTALLATION.
7.03 HELICAL PIERS AS SPECIFIED SHALL CONFORM TO THE INTERNATIONAL BUILDING CODE. AN OFFICIAL EVALUATION REPORT WITH ASSIGNED NUMBER SHALL BE PRESENTED UPON REQUEST TO THE OWNER AND/OR THEIR REPRESENTATIVE.
7.04 THE HELICAL LEAD SECTIONS AND EXTENSION SECTIONS SHALL BE SOLID STEEL, ROUND CORNERED SQUARE SHAFT, OR ROUND STEEL PIPE SHAFT, OR COMPOSITE STEEL AND GROUT SHAFT CONFIGURED WITH ONE OR MORE HELICAL BEARING PLATES WELDED TO
THE SHAFT.
7.05 ALL PIERS MUST BE CORROSION PROTECTED BY HOT DIP GALVANIZATION.
7.06 INSTALLATION UNITS SHALL CONSIST OF A ROTARY TYPE TORQUE MOTOR WITH FORWARD AND REVERSE CAPABILITIES. THESE
UNITS ARE TYPICALLY POWERED.
7.07 INSTALLATION UNITS SHALL BE CAPABLE OF DEVELOPING THE MINIMUM TORQUE AS REQ'D.
7.08 INSTALLATION UNITS SHALL BE CAPABLE OF POSITIONING THE HELICAL PIER AT THE PROPER INSTALLATION ANGLE. THIS ANGLE MAY VARY BETWEEN VERTICAL AND 5 DEGREES DEPENDING UPON APPLICATION AND TYPE OF LOAD TRANSFER DEVICE SPECIFIED OR
REQUIRED.
7.09 INSTALLATION TORQUE SHALL BE MONITORED THROUGHOUT THE INSTALLATION PROCESS.
7.10 HELICAL PIERS SHALL BE INSTALLED TO THE MINIMUM TORQUE VALUE REQUIRED TO PROVIDE THE LOAD CAPACITIES SHOWN ON
THE PLANS.
7.11 THE APPROPRIATE STEEL NEW CONSTRUCTION LOAD TRANSFER DEVICE SHALL BE USED.
7.12 APPROPRIATE HELICAL PIER SELECTION WILL CONSIDER DESIGN LOAD PLUS SAFETY FACTOR, SOIL PARAMETERS AND THE INSTALLATION TORQUE VS. CAPACITY EQUATION AS PER THE MANUFACTURER'S RECOMMENDATIONS.
7.13 DESIGN OF HELICAL SCREW PILES AND ANCHORS SHALL BE PERFORMED BY AN ENTITY AS REQUIRED IN ACCORDANCE WITH EXISTING LOCAL CODE REQUIREMENTS OR ESTABLISHED LOCAL PRACTICES. THIS DESIGN WORK SHALL BE PERFORMED BY A
LICENSED PROFESSIONAL ENGINEER.
WIND LOAD DETERMINATION ASSUMPTIONS - INTERNATIONAL BUILDING CODE 2018
ROOF SLOPE
157 C 27 1 ON 12 III ENCLOSED
ULT. WIND
VELOCITY (MPH)
EXPOSURE
CATEGORY
MEAN ROOF
HEIGHT (FT.)
RISK
CATEGORY
ENCLOSURE
CATEGORY
ULTIMATE DESIGN WIND PRESSURES FOR COMPONENTS AND CLADDING (PSF)
ROOF
ZONE 1
ROOF
ZONE 2
ROOF
ZONE 2'
ROOF
ZONE 3
ROOF
ZONE 3'
24.6 -65.7 -76.0 -101.6 -142.7
50 21.0 -65.7 -72.4 -80.1 -106.8
19.5 -65.7 -70.8 -70.8 -91.4
-91.4
-87.8
-86.2
NOTES:
1. FOR EFFECTIVE AREAS BETWEEN THOSE GIVEN ABOVE THE LOAD MAY BE INTERPOLATED,
OTHERWISE USE THE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREA.
2. THE EDGE STRIP, a = 10.6 FT.
3. PRESSURES SHALL BE APPLIED IN ACCORDANCE WITH THE FIGURE SHOWN ON THIS SHEET.
4. PRESSURES GIVEN ARE ULTIMATE LOADS TO BE USED WITH STRENGTH DESIGN. FOR SERVICE
LOADS TO BE USED WITH ALLOWABLE STRESS DESIGN, MULTIPLY THE PRESSURES BY 0.60.
SEE TABLES 2.3 AND 2.4 IN ASCE 7-16 FOR MORE INFORMATION ON LOAD COMBINATIONS.
< 10
> 100
EFF.
AREA
(SQ. FT.)
REPRESENTATIVE DIAGRAM
a a
2'
3' a a
EXISTING HANGAR
3'
2'
2'
2a
4a
2a
2a
ZONE
115.9 131.7 184.4
50 106.4 122.2 141.7
102.3 118.1 123.3
-113.8
-96.2
-88.7
< 10
> 100
EFF.
AREA
(SQ. FT.)
142.2
114.3
102.3
-99.6
-87.9
-82.8
PARAPET CASE A PARAPET CASE B
ZONE
2'
ZONE
ZONE
3'
INTERIOR
ZONE
WALL
ZONE 4
-60.1
-54.3
-51.9
WALL
ZONE 5
-73.9
-62.5
-57.6
55.4
-49.7
-47.3
CORNER
ZONE
24.6
21.0
19.5
24.6
21.0
19.5
24.6
21.0
19.5
24.6
21.0
19.5
55.4
-49.7
-47.3
D
EU
SOJ
R E
G
ISTERE
R E
E
NIGNED
EPH
ER
IL
SI
U
OL
A
DIOL
F R
STATE OF
No. 54319
E T
ACFIT
C R
E
I
301 West Cervantes St.301 West Cervantes St.301 West Cervantes St.301 West Cervantes St. Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951 Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501
JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA
IA
R
E
OF
RC
SP
EC
IA
AN
N
P
ER
L O
AT
IO
M M
S
CO
D
SHEET REFERENCE:
D A
T E
SHEET NUMBER:
OF
D E
S C
R
IP
T
IO
N R
E V
A
IR
F O
R C
E
SP
EC
IA
L O
PE
R
A
TI
O N
S C
O M
M A
N D
SP
EC
IA
L O
PE
RA
TI
ON
S
CI
VI
L
EN
GI
NE
ER
S
QU
AD
RO
N
H U
R
LB
U R
T
FI
EL
D
, F
LO
R
ID
A
PROJECT NUMBER:
BUILDING NUMBER:
DRAWN BY:
DESIGNED BY:
DATE:
91262
STATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDA
P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515
JDA JOB #18163
S-002
FINAL SUBMITTAL
8/18/2021
G E
N E
R A
L N
O T
E S
WEC
WEC
CP1038344
A L T
E R
A C
M A
IN
T
E N
A N
C E
H A
N G
A R
S O
A M
X S
B
8/18/20218/18/20218/18/20218/18/2021
X19
XF
S-401
12" SLAB
2'-0"x2'-0" TURNDOWN
W/ (2) #6 CONT. BOT.
3'-6" 11'-0 1/2" 3'-6"
1' -0
5'
-8
/2
2' -9
2'-0"x2'-0" TURNDOWN
W/ (2) #6 CONT. BOT.
2'-0"x3'-6" TURNDOWN
W/ (4) #6 CONT. BOT.
1' -0
5'
-1 0"
3' -3
4'-0" 12'-1" 4'-0"
12" SLAB
S-401
X15
D
3' -0
7'
-9
3' -0
1'-0" 8'-1 5/8" 2'-3"
-0' 5-1/4"
12" SLAB
2'-1 5/8" 8'-6" 9"
6' -2
S-401
S-401
HOLD THIS PILE 5 1/4" LOWER
THAN THE TYPICAL TO ACHIEVE
THE SAME EMBEDMENT INTO THE SLAB
18 TON HELICAL PILE.
12" THICK CONCRETE SLAB-ON-GRADE REINFORCED WITH #5@8" O.C. E.W., TOP AND BOTTOM.
SLAB SHALL BE PLACED OVER A VAPOR BARRIER AND CAPILLARY BREAK AS INDICATED IN THE
GENERAL NOTES SECTION 2.05 ON SHEET S-001.
SLAB RECESS
BRACED FRAME; L3-1/2X3-1/2X1/4 X-BRACING, SEE ELEVATIONS
12" SLAB
LEGEND
-X' X"
B.F.
D
EU
SOJ
R E
G
ISTERE
R E
E
NIGNED
EPH
ER
IL
SI
U
OL
A
DIOL
F R
STATE OF
No. 54319
E T
ACFIT
C R
E
I
301 West Cervantes St.301 West Cervantes St.301 West Cervantes St.301 West Cervantes St. Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951 Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501
JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA
IA
R
E
OF
RC
SP
EC
IA
AN
N
P
ER
L O
AT
IO
M M
S
CO
D
SHEET REFERENCE:
D A
T E
SHEET NUMBER:
OF
D E
S C
R
IP
T
IO
N R
E V
A
IR
F O
R C
E
SP
EC
IA
L O
PE
R
A
TI
O N
S C
O M
M A
N D
SP
EC
IA
L O
PE
RA
TI
ON
S
CI
VI
L
EN
GI
NE
ER
S
QU
AD
RO
N
H U
R
LB
U R
T
FI
EL
D
, F
LO
R
ID
A
PROJECT NUMBER:
BUILDING NUMBER:
DRAWN BY:
DESIGNED BY:
DATE:
91262
STATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDA
P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515
JDA JOB #18163
S-101
FINAL SUBMITTAL
8/18/2021
E N
LA
R
G E
D S
LA
B
-O N
-G R
A D
E P
LA
N
S
WEC
WEC
CP1038344
A L T
E R
A C
M A
IN
T
E N
A N
C E
H A
N G
A R
S O
A M
X S
B
8/18/20218/18/20218/18/20218/18/2021
3/8" = 1'-0"S-101
1 EXTERIOR STAIRS FOUNDATION PLAN
3/8" = 1'-0"S-101
2 INTERIOR STAIRS PILE PLAN
3/8" = 1'-0"S-101
3 LIFT PILE PLAN
0 1' 2' 4'
SCALE 3/8":1'-0"
8'
SECOND FLOOR
12' - 0"
XFXF.2
EXIST. BOND BEAM
EXIST. REINF.
AROUND OPENING
EXIST. BOND BEAM
23' - 4"
T/EXIST. BOND BEAM
#5 VERT. REINF. FULL HEIGHT W/ #5x3'-0"
DOWELS DRILLED & EPOXIED 6" INTO EXIST.
BOND BEAMS TOP & BOTTOM; POSITION
BARS IN CENTER OF CELLS & GROUT FILL,
TYP. WHERE VERT. REINF. IS SHOWN
NEW GROUT FILLED HORIZONTAL
BOND BEAMS IN OPEN BOTTOM
LINTEL BLOCKS REINF. W/ (2) #5 x
(OPENING WIDTH - 6") IN CENTER
OF GROUT FILLED CELLS, DRILL &
EPOXY 6" INTO EXIST. GROUT
FILLED CMU JAMB
12" CMU INFILL
DEMOLISH
EXIST. CMU
FOR NEW
OPENING
ANTICIPATED EXIST. GROUT
FILLED & REINFORCED
CELLS, TYP. WHERE SHOWN
S-303
SLAB-ON-GRADE
0"
C
EXIST. BOND BEAM
#5 VERT. REINF. FULL HEIGHT
W/ #5x3'-0" DOWELS DRILLED &
EPOXIED 6" INTO EXIST. BOND
BEAMS TOP & BOTTOM;
POSITION BARS IN CENTER OF
CELLS & GROUT FILL, TYP.
WHERE VERT. REINF. IS SHOWN
DEMOLISH
EXIST. CMU
FOR NEW
OPENING
ANTICIPATED EXIST.
GROUT FILLED &
REINFORCED CELLS,
TYP. WHERE SHOWN
28' - 0"
T/EXIST. BOND BEAM
S-303
Sim
SLAB-ON-GRADE
0"
DEMOLISH
EXIST. CMU
FOR NEW
OPENING
ANTICIPATED EXIST.
GROUT FILLED &
REINFORCED CELLS,
TYP. WHERE SHOWN
DEMOLISH
EXIST. CMU
FOR NEW
OPENING
S-303
SLAB-ON-GRADE
0"
C
EXIST. BOND BEAM
23' - 4"
T/EXIST. BOND BEAM
#5 VERT. REINF. FULL HEIGHT
W/ #5x3'-0" DOWELS DRILLED &
EPOXIED 6" INTO EXIST. BOND
BEAMS TOP & BOTTOM;
POSITION BARS IN CENTER OF
CELLS & GROUT FILL, TYP.
WHERE VERT. REINF. IS SHOWNDEMOLISH
EXIST. CMU
FOR NEW
OPENING
ANTICIPATED EXIST.
GROUT FILLED &
REINFORCED CELLS,
TYP. WHERE SHOWN
S-303
TO INSTALL REINF.
AS REQ'D
STEP 1: CUT OUT EXISTING FACE SHELL & WEB AS REQ'D
EXIST. CMU TYPES MAY VARY,
REQUIRING ADDITIONAL
CUTTING & CHIPPING
EFFORTS AS WELL AS GROUT
FUTURE CUT FOR
NEW OPENING
STEP 2: CUT IN NEW OPENING AS SHOWN
NEW OPENING
CONTRACTOR SHALL POINT &
RUB OUT SAWCUT FACE TO
PROVIDE A SMOOTH FINAL FINISH
2" MIN.
SLAB-ON-GRADE
0"
SECOND FLOOR
12' - 0"
XF
EXIST. BOND BEAM
DEMOLISH
EXIST. CMU
FOR NEW
OPENING
#5 VERT. REINF. FULL HEIGHT W/ #5x3'-0"
DOWELS DRILLED & EPOXIED 6" INTO EXIST.
BOND BEAMS TOP & BOTTOM; POSITION
BARS IN CENTER OF CELLS & GROUT FILL,
TYP. WHERE VERT. REINF. IS SHOWN
ANTICIPATED EXIST. GROUT
FILLED & REINFORCED
CELLS, TYP. WHERE SHOWN
S-303
Sim
D
EU
SOJ
R E
G
ISTERE
R E
E
NIGNED
EPH
ER
IL
SI
U
OL
A
DIOL
F R
STATE OF
No. 54319
E T
ACFIT
C R
E
I
301 West Cervantes St.301 West Cervantes St.301 West Cervantes St.301 West Cervantes St. Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951 Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501
JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA
IA
R
E
OF
RC
SP
EC
IA
AN
N
P
ER
L O
AT
IO
M M
S
CO
D
SHEET REFERENCE:
D A
T E
SHEET NUMBER:
OF
D E
S C
R
IP
T
IO
N R
E V
A
IR
F O
R C
E
SP
EC
IA
L O
PE
R
A
TI
O N
S C
O M
M A
N D
SP
EC
IA
L O
PE
RA
TI
ON
S
CI
VI
L
EN
GI
NE
ER
S
QU
AD
RO
N
H U
R
LB
U R
T
FI
EL
D
, F
LO
R
ID
A
PROJECT NUMBER:
BUILDING NUMBER:
DRAWN BY:
DESIGNED BY:
DATE:
91262
STATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDA
P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515
JDA JOB #18163
S-201
FINAL SUBMITTAL
8/18/2021
E
LE
V A
T
IO
N S
WEC
WEC
CP1038344
A L T
E R
A C
M A
IN
T
E N
A N
C E
H A
N G
A R
S O
A M
X S
B
8/18/20218/18/20218/18/20218/18/2021
1/2" = 1'-0"S-201
1 2ND FLOOR EXTERIOR WALL ELEVATION
1/2" = 1'-0"S-201
5 NEW HANGAR WALL OPENING ELEVATION
1/2" = 1'-0"S-201
2 INTERIOR WINDOWS ELEVATION
1/2" = 1'-0"S-201
4 EAST EXTERIOR MAN DOOR ELEVATION
1 1/2" = 1'-0"S-201
6 NEW OPENING JAMB @ PARTIAL CELL
1/2" = 1'-0"S-201
3 WEST EXTERIOR MAN DOOR ELEVATION
0 3" 6" 1'
SCALE 1-1/2":1'-0"
2' 0 1' 2' 4'
SCALE 1/2":1'-0"
6"
SLAB-ON-GRADE
0"
BXG
S-302
FULLY GROUTED 12" CMU
INFILL W/ (2) #5 TOP,
CENTER & BOT.
G.C. VERIFY
14'-0"
G .C
. V E
R
IF
Y
4' -8
U-BLOCK AT
BOTTOM OF HEADER
EXIST. CONC.
LINTEL
8" MIN.
DEMO EXIST. CMU (CHIP
CAREFULLY AROUND EXIST.
REINFORCING BARS) FOR
BEARING OF NEW CMU
SLAB-ON-GRADE
0"
X17.5X16X15.9
S-302
FULLY GROUTED 8"
CMU INFILL W/ (1) #5
TOP, CENTER, & BOT.
U-BLOCK AT
BOTTOM OF HEADER
G .C
. V E
R
IF
Y
4' -8
G.C. VERIFY
15'-0"
EXIST. CONC.
LINTEL
8" MIN.
DEMO EXIST. CMU (CHIP
CAREFULLY AROUND EXIST.
REINFORCING BARS) FOR
BEARING OF NEW CMU
D
EU
SOJ
R E
G
ISTERE
R E
E
NIGNED
EPH
ER
IL
SI
U
OL
A
DIOL
F R
STATE OF
No. 54319
E T
ACFIT
C R
E
I
301 West Cervantes St.301 West Cervantes St.301 West Cervantes St.301 West Cervantes St. Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951Tel. 850.429.1951 Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501Pensacola, FL 32501
JOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLCJOE DEREUIL ASSOCIATES, LLC S T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SS T R U C T U R A L E N G I N E E R SJDA
IA
R
E
OF
RC
SP
EC
IA
AN
N
P
ER
L O
AT
IO
M M
S
CO
D
SHEET REFERENCE:
D A
T E
SHEET NUMBER:
OF
D E
S C
R
IP
T
IO
N R
E V
A
IR
F O
R C
E
SP
EC
IA
L O
PE
R
A
TI
O N
S C
O M
M A
N D
SP
EC
IA
L O
PE
RA
TI
ON
S
CI
VI
L
EN
GI
NE
ER
S
QU
AD
RO
N
H U
R
LB
U R
T
FI
EL
D
, F
LO
R
ID
A
PROJECT NUMBER:
BUILDING NUMBER:
DRAWN BY:
DESIGNED BY:
DATE:
91262
STATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDASTATE OF FLORIDA
P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515P.E. NO. 54319 / C.A. NO. 9515
JDA JOB #18163
S-202
FINAL SUBMITTAL
8/18/2021
E
LE
V A
T
IO
N S
WEC
WEC
CP1038344
A L T
E R
A C
M A
IN
T
E N
A N
C E
H A
N G
A R
S O
A M
X S
B
8/18/20218/18/20218/18/20218/18/2021
1/2" = 1'-0"S-202
1 EXTERIOR OHCD ELEVATION
1/2" = 1'-0"S-202
2 INTERIOR OHCD ELEVATION
0 1' 2' 4'
SCALE 1/2":1'-0"
6"
XF.2
#4x2'-0" REINF. BAR AT 12"
O.C. DOWELED & EPOXIED
INTO EXIST. CONC. DECK
ELEV. SLAB,
SEE PLAN
SHEAR STUD, SEE PLAN
W-BEAM, SEE PLAN
EXIST. W-BEAM,
SEE PLAN
EXIST. JOIST,
SEE PLAN
EXIST. CONC. DECK
1'-0"1'-0"
SEE DET. /2 S-501
SECOND FLOOR
12' - 0"
D
CONT. L6X4X5/16 LLV W/ 5/8" x
3-1/4" EMBED. HILTI KWIK HUS-
EZ (OR EQUIV.) AT 24" O.C.
ELEV. SLAB,
SEE PLAN
EXIST. CMU WALL
1/
2"
1/ 2"
CONTINUOUSL…