RFI's_FA4417-17-R-0001_FTEV_13-1001-Answered.docx

DOCX document 12 KB Posted

Attached to
Upgrade Fire Suppression, Hangar 90225
Solicitation number
FA4417-17-R-0001
Issued by

About this file

Answers from the RFI's received from the Site Visit held 13 Dec 16.

View the file

Other files

File Type Posted
Amend_6_Addendum_4.doc DOC document
Amend_6_FA4417-17-R-0001-0006.docx DOCX document
Amend_5_FA4417-17-R-0001-0005.docx DOCX document
Amend_5_ADDENDUM_3.doc DOC document
Additional_Question_and_Answer.docx DOCX document
RFI's_FA4417-17-R-0001_FTEV_13-1001-Answered_3.docx DOCX document
sprinkler_pipe_sizes.pdf PDF
RFI's_FA4417-17-R-0001_FTEV_13-1001-Answered_12_Jan_17.docx DOCX document
FTEV13-1001Specifications_Rev-1-3-17.pdf PDF
FTEV_13-1001_revised_drawings_1-3-17_.pdf PDF
ADDENDUM__2.doc DOC document
Amendment_4.docx DOCX document
FA4417-17-R-0001-0003_Amendment_3.pdf PDF
Site_Visit_Minutes_and_Sign_In_sheet.pdf PDF
FA4417-17-R-000102.docx DOCX document
02_FTEV13-1001Specifications_1_Dec_16.pdf PDF
Amendment_FA4417-17-R-0001-0001.docx DOCX document
FTEV_13-1001_drawings_1_Dec_16.pdf PDF
Atch_2_-_FTEV_13-1001 _DrawingsFinal.pdf PDF
Atch_4_-_PPQ _17R0001.docx DOCX document
Atch_1_-_FTEV_13-1001 SpecificationsFinal.pdf PDF
Solicitation_FA4417-17-R-0001.docx DOCX document
Atch_5_-_Financial_Worksheet _17R0001.docx DOCX document
Atch_3_-_Wage_Det _17R0001.docx DOCX document
Atch_6 _ _Add_Contract_Reqs _17R0001.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. On page FP-10 it shows a one line riser for the foam releasing system, but the device symbols on the riser does not match the device symbols and description as shown on page FP-5 or does not match devices shown on the floor plan. Can we get a corrected system riser.

Response: See updated drawings on addendum

2. Specification Section 21 13 39; Appendix B; Item 13. Where a Mass Notification System is provided, delete Amber Strobes… and provide Text signs..

Response: Mass Notification System is not part of this system.

On this project will the existing amber strobe need to be removed and Text Signs added?

Response: No, not part of this scope.

File details come from the government source that posted it. Updated .