1. On page FP-10 it shows a one line riser for the foam releasing system, but the device symbols on the riser does not match the device symbols and description as shown on page FP-5 or does not match devices shown on the floor plan. Can we get a corrected system riser.
Response: See updated drawings on addendum
2. Specification Section 21 13 39; Appendix B; Item 13. Where a Mass Notification System is provided, delete Amber Strobes… and provide Text signs..
Response: Mass Notification System is not part of this system.
On this project will the existing amber strobe need to be removed and Text Signs added?
Response: No, not part of this scope.