RFI's_FA4417-17-R-0001_FTEV_13-1001-Answered_3.docx

DOCX document 12 KB Posted

Attached to
Upgrade Fire Suppression, Hangar 90225
Solicitation number
FA4417-17-R-0001
Issued by

About this file

This is response number 3 to questions submitted.

View the file

Other files

File Type Posted
Amend_6_Addendum_4.doc DOC document
Amend_6_FA4417-17-R-0001-0006.docx DOCX document
Amend_5_FA4417-17-R-0001-0005.docx DOCX document
Amend_5_ADDENDUM_3.doc DOC document
Additional_Question_and_Answer.docx DOCX document
sprinkler_pipe_sizes.pdf PDF
RFI's_FA4417-17-R-0001_FTEV_13-1001-Answered_12_Jan_17.docx DOCX document
FTEV13-1001Specifications_Rev-1-3-17.pdf PDF
FTEV_13-1001_revised_drawings_1-3-17_.pdf PDF
ADDENDUM__2.doc DOC document
Amendment_4.docx DOCX document
RFI's_FA4417-17-R-0001_FTEV_13-1001-Answered.docx DOCX document
FA4417-17-R-0001-0003_Amendment_3.pdf PDF
Site_Visit_Minutes_and_Sign_In_sheet.pdf PDF
FA4417-17-R-000102.docx DOCX document
02_FTEV13-1001Specifications_1_Dec_16.pdf PDF
Amendment_FA4417-17-R-0001-0001.docx DOCX document
FTEV_13-1001_drawings_1_Dec_16.pdf PDF
Atch_2_-_FTEV_13-1001 _DrawingsFinal.pdf PDF
Atch_4_-_PPQ _17R0001.docx DOCX document
Atch_1_-_FTEV_13-1001 SpecificationsFinal.pdf PDF
Solicitation_FA4417-17-R-0001.docx DOCX document
Atch_5_-_Financial_Worksheet _17R0001.docx DOCX document
Atch_3_-_Wage_Det _17R0001.docx DOCX document
Atch_6 _ _Add_Contract_Reqs _17R0001.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Page FP-10 references Optical Fire Detectors on the one line riser, but they are not shown on the floor plan. Please advise.

Response: Optical flame detectors are to be installed per notes on drawing sheet FP-10 and specification section 21 13 39. The number and location of the detectors is to be determine by the manufacture of the detectors.

File details come from the government source that posted it. Updated .