RFI's_FA4417-17-R-0001_FTEV_13-1001-Answered_3.docx
DOCX document 12 KB Posted
- Attached to
- Upgrade Fire Suppression, Hangar 90225
- Solicitation number
- FA4417-17-R-0001
About this file
This is response number 3 to questions submitted.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. Page FP-10 references Optical Fire Detectors on the one line riser, but they are not shown on the floor plan. Please advise.
Response: Optical flame detectors are to be installed per notes on drawing sheet FP-10 and specification section 21 13 39. The number and location of the detectors is to be determine by the manufacture of the detectors.