RFQ Attach 6 - Pricing Workbook.xlsx

XLSX spreadsheet 41 KB Posted

Attached to
FY26 Fire Suppression
Solicitation number
FA440726QBM01
Issued by

About this file

This is a pricing workbook attachment for an RFQ solicitation for fire suppression system maintenance and testing services at Scott Air Force Base. The contract covers a base year plus four option years and a six-month extension, with services performed for 24 commercial kitchen fire suppression systems across 12 facilities and 18 non-commercial fire suppression systems across 17 facilities.

The pricing workbook details seven Contract Line Item Numbers (CLINs): CLIN 0001 and 0002 require semi-annual preventive maintenance services for commercial and non-commercial systems respectively (2 services per year), with work performed to manufacturer specifications and NFPA 96/17A standards including inspection, testing, discharge cap replacement, and battery replacement; CLIN 0003 covers fusible link replacement services on an as-needed basis (maximum 400 units per year) billed per individual link with depleted links returned to Scott AFB Fire Prevention Section; CLIN 0004 addresses 12-year wet chemical cylinder maintenance and hydrostatic testing (maximum 7 cylinders per year) billed per-cylinder upon completion and only on an as-used basis; CLIN 0005 provides reimbursable replacement parts including discharge nozzles, micro-switches, CO2 cartridges, wet chemical cylinders, piping, and actuation devices, billed on an itemized, as-needed basis; CLIN 0006 allocates eight pre-authorized labor hours (four hours in the six-month extension) for corrective maintenance and emergency repairs billed at the established hourly rate; and CLIN 0007 covers replacement of nitrogen expellant cylinders (maximum 2 per year) billed per unit upon successful installation and safety verification. The workbook includes a facility breakout identifying 12 commercial kitchen systems using ANSUL R-102 or Pyro Chem models and 17 non-commercial systems using Guardian III models, with specific building locations, room assignments, system quantities, and fusible link counts detailed for each facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Overall Fire Suppression / Fusible Link

Item No Cost

Base Year
Option Year 1
Option Year 2
Option Year 3
Option Year 4
6 Month Extension

Total Cost

Base Year Fire Suppression / Fusible Link Base Year

Item No Cost

Base Year
Option Year 1
Option Year 2
Option Year 3
Option Year 4
6 Month Extension

Total Cost

CLINTOPICREQUIREMENTCostUnitQuantityYearly total
CLIN 0001Semi-Annual Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for twenty-four (24) commercial kitchen fire suppression systems across twelve (12) facilities. Work shall be performed in accordance with manufacturer specifications and NFPA 96/17A standards. Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status.EA2.00
CLIN 0002Semi-Annual Non-Commercial Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for eighteen (18) non-commercial cooking facility fire suppression systems across seventeen (17) designated facilities. All work shall be performed in strict accordance with manufacturer specifications, NFPA 17A (Standard for Wet Chemical Extinguishing Systems), and NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations). Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status and code compliance.EA2.00
CLIN 0003Fusible Link Replacement (NTE 400 Units)Provide replacement services for fusible links on an as-needed basis in strict accordance with NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) and NFPA 17A (Standard for Wet Chemical Extinguishing Systems). This is a unit-priced service billed per individual link utilized. To ensure compliance and strict accountability, all replaced (depleted/old) links must be retained and delivered directly to the Scott AFB Fire Prevention Section prior to invoice approval. Total performance under this CLIN shall not exceed a cumulative maximum of 400 fusible links across both services.EA400.00
CLIN 000412-Year Wet Chemical Cylinder Maintenance and Hydrostatic TestingProvide 12-year maintenance and hydrostatic testing services for fire suppression system cylinders on an as-needed, "when required" basis. All services, testing, and safety inspections shall be performed in strict accordance with NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10 (Standard for Portable Fire Extinguishers), and applicable Department of Transportation (DOT) hydrostatic testing regulations. This is a unit-priced service billed on a "per-cylinder" basis. The contractor shall only bill against this CLIN upon successful completion of the hydrostatic test and service for each authorized cylinder. No advance billing or flat-rate monthly billing is authorized; charges shall be incurred strictly on an as-used basis.EA7.00
CLIN 0005Reimbursable Fire Suppression System Replacement Parts (As-Needed)Contractor shall provide reimbursable replacement parts and components required to repair, maintain, or restore fire suppression systems to a fully operational status in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This comprehensive CLIN encompasses all necessary fire suppression system replacement parts, including, but not limited to: discharge nozzles, micro-switches, CO2 expellant/charging cartridges, wet chemical agent cylinders, piping, actuation devices, and detection linkages. Parts shall be billed strictly on an as-needed, reimbursable basis. For billing approval, the contractor must provide a fully itemized invoice that lists each specific part utilized separately alongside its associated unit cost.Unit1.00Not Priced
CLIN 0006Additional Corrective Maintenance Labor Hours (8 Hours)Additional Labor Hours (8 hours). Provide up to eight (8) additional, pre-authorized direct labor hours to perform corrective maintenance, emergency repairs, and the installation of replacement components. All labor-driven tasks—including the installation of replacement nozzles, mechanical or electrical switches, the swap-out of pressurized agent/CO2 charging cylinders, and system recertification—shall be executed in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This labor CLIN shall be billed at the established hourly rate, strictly on an as-needed, actual-hours-worked basis, and only when corrective actions exceed the baseline preventive maintenance scope.Hours8
CLIN 0007As-Needed Replacement of Nitrogen Expellant Cylinders (NTE 2 Cylinders/Year)Provide replacement services for overcharged, depleted, or physically damaged nitrogen expellant cylinders on an as-needed basis. All replacement cylinders, installation procedures, and safety testing shall strictly conform to NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10, and applicable DOT specifications. This is a unit-priced service billed at a fixed rate per cylinder, restricted to a maximum allowable quantity of two (2) cylinders per contract year. The contractor shall bill against this line item strictly upon successful installation, safety verification, and completion of the service.EA2.00

TOTAL

Option Year 1 Fire Suppression / Fusible Link Base Year

Item No Cost

Base Year
Option Year 1
Option Year 2
Option Year 3
Option Year 4
6 Month Extension

Total Cost

CLINTOPICREQUIREMENTCostUnitQuantityYearly total
CLIN 0001Semi-Annual Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for twenty-four (24) commercial kitchen fire suppression systems across twelve (12) facilities. Work shall be performed in accordance with manufacturer specifications and NFPA 96/17A standards. Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status.EA2.00
CLIN 0002Semi-Annual Non-Commercial Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for eighteen (18) non-commercial cooking facility fire suppression systems across seventeen (17) designated facilities. All work shall be performed in strict accordance with manufacturer specifications, NFPA 17A (Standard for Wet Chemical Extinguishing Systems), and NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations). Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status and code compliance.EA2.00
CLIN 0003Fusible Link Replacement (NTE 400 Units)Provide replacement services for fusible links on an as-needed basis in strict accordance with NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) and NFPA 17A (Standard for Wet Chemical Extinguishing Systems). This is a unit-priced service billed per individual link utilized. To ensure compliance and strict accountability, all replaced (depleted/old) links must be retained and delivered directly to the Scott AFB Fire Prevention Section prior to invoice approval. Total performance under this CLIN shall not exceed a cumulative maximum of 400 fusible links across both services.EA400.00
CLIN 000412-Year Wet Chemical Cylinder Maintenance and Hydrostatic TestingProvide 12-year maintenance and hydrostatic testing services for fire suppression system cylinders on an as-needed, "when required" basis. All services, testing, and safety inspections shall be performed in strict accordance with NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10 (Standard for Portable Fire Extinguishers), and applicable Department of Transportation (DOT) hydrostatic testing regulations. This is a unit-priced service billed on a "per-cylinder" basis. The contractor shall only bill against this CLIN upon successful completion of the hydrostatic test and service for each authorized cylinder. No advance billing or flat-rate monthly billing is authorized; charges shall be incurred strictly on an as-used basis.EA7.00
CLIN 0005Reimbursable Fire Suppression System Replacement Parts (As-Needed)Contractor shall provide reimbursable replacement parts and components required to repair, maintain, or restore fire suppression systems to a fully operational status in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This comprehensive CLIN encompasses all necessary fire suppression system replacement parts, including, but not limited to: discharge nozzles, micro-switches, CO2 expellant/charging cartridges, wet chemical agent cylinders, piping, actuation devices, and detection linkages. Parts shall be billed strictly on an as-needed, reimbursable basis. For billing approval, the contractor must provide a fully itemized invoice that lists each specific part utilized separately alongside its associated unit cost.Unit1.00Not Priced
CLIN 0006Additional Corrective Maintenance Labor Hours (8 Hours)Additional Labor Hours (8 hours). Provide up to eight (8) additional, pre-authorized direct labor hours to perform corrective maintenance, emergency repairs, and the installation of replacement components. All labor-driven tasks—including the installation of replacement nozzles, mechanical or electrical switches, the swap-out of pressurized agent/CO2 charging cylinders, and system recertification—shall be executed in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This labor CLIN shall be billed at the established hourly rate, strictly on an as-needed, actual-hours-worked basis, and only when corrective actions exceed the baseline preventive maintenance scope.Hours8
CLIN 0007As-Needed Replacement of Nitrogen Expellant Cylinders (NTE 2 Cylinders/Year)Provide replacement services for overcharged, depleted, or physically damaged nitrogen expellant cylinders on an as-needed basis. All replacement cylinders, installation procedures, and safety testing shall strictly conform to NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10, and applicable DOT specifications. This is a unit-priced service billed at a fixed rate per cylinder, restricted to a maximum allowable quantity of two (2) cylinders per contract year. The contractor shall bill against this line item strictly upon successful installation, safety verification, and completion of the service.EA2.00

TOTAL

Option Year 2 Fire Suppression / Fusible Link Base Year

Item No Cost

Base Year
Option Year 1
Option Year 2
Option Year 3
Option Year 4
6 Month Extension

Total Cost

CLINTOPICREQUIREMENTCostUnitQuantityYearly total
CLIN 0001Semi-Annual Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for twenty-four (24) commercial kitchen fire suppression systems across twelve (12) facilities. Work shall be performed in accordance with manufacturer specifications and NFPA 96/17A standards. Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status.EA2.00
CLIN 0002Semi-Annual Non-Commercial Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for eighteen (18) non-commercial cooking facility fire suppression systems across seventeen (17) designated facilities. All work shall be performed in strict accordance with manufacturer specifications, NFPA 17A (Standard for Wet Chemical Extinguishing Systems), and NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations). Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status and code compliance.EA2.00
CLIN 0003Fusible Link Replacement (NTE 400 Units)Provide replacement services for fusible links on an as-needed basis in strict accordance with NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) and NFPA 17A (Standard for Wet Chemical Extinguishing Systems). This is a unit-priced service billed per individual link utilized. To ensure compliance and strict accountability, all replaced (depleted/old) links must be retained and delivered directly to the Scott AFB Fire Prevention Section prior to invoice approval. Total performance under this CLIN shall not exceed a cumulative maximum of 400 fusible links across both services.EA400.00
CLIN 000412-Year Wet Chemical Cylinder Maintenance and Hydrostatic TestingProvide 12-year maintenance and hydrostatic testing services for fire suppression system cylinders on an as-needed, "when required" basis. All services, testing, and safety inspections shall be performed in strict accordance with NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10 (Standard for Portable Fire Extinguishers), and applicable Department of Transportation (DOT) hydrostatic testing regulations. This is a unit-priced service billed on a "per-cylinder" basis. The contractor shall only bill against this CLIN upon successful completion of the hydrostatic test and service for each authorized cylinder. No advance billing or flat-rate monthly billing is authorized; charges shall be incurred strictly on an as-used basis.EA7.00
CLIN 0005Reimbursable Fire Suppression System Replacement Parts (As-Needed)Contractor shall provide reimbursable replacement parts and components required to repair, maintain, or restore fire suppression systems to a fully operational status in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This comprehensive CLIN encompasses all necessary fire suppression system replacement parts, including, but not limited to: discharge nozzles, micro-switches, CO2 expellant/charging cartridges, wet chemical agent cylinders, piping, actuation devices, and detection linkages. Parts shall be billed strictly on an as-needed, reimbursable basis. For billing approval, the contractor must provide a fully itemized invoice that lists each specific part utilized separately alongside its associated unit cost.Unit1.00Not Priced
CLIN 0006Additional Corrective Maintenance Labor Hours (8 Hours)Additional Labor Hours (8 hours). Provide up to eight (8) additional, pre-authorized direct labor hours to perform corrective maintenance, emergency repairs, and the installation of replacement components. All labor-driven tasks—including the installation of replacement nozzles, mechanical or electrical switches, the swap-out of pressurized agent/CO2 charging cylinders, and system recertification—shall be executed in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This labor CLIN shall be billed at the established hourly rate, strictly on an as-needed, actual-hours-worked basis, and only when corrective actions exceed the baseline preventive maintenance scope.Hours8
CLIN 0007As-Needed Replacement of Nitrogen Expellant Cylinders (NTE 2 Cylinders/Year)Provide replacement services for overcharged, depleted, or physically damaged nitrogen expellant cylinders on an as-needed basis. All replacement cylinders, installation procedures, and safety testing shall strictly conform to NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10, and applicable DOT specifications. This is a unit-priced service billed at a fixed rate per cylinder, restricted to a maximum allowable quantity of two (2) cylinders per contract year. The contractor shall bill against this line item strictly upon successful installation, safety verification, and completion of the service.EA2.00

TOTAL

Option Year 3 Fire Suppression / Fusible Link Base Year

Item No Cost

Base Year
Option Year 1
Option Year 2
Option Year 3
Option Year 4
6 Month Extension

Total Cost

CLINTOPICREQUIREMENTCostUnitQuantityYearly total
CLIN 0001Semi-Annual Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for twenty-four (24) commercial kitchen fire suppression systems across twelve (12) facilities. Work shall be performed in accordance with manufacturer specifications and NFPA 96/17A standards. Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status.EA2.00
CLIN 0002Semi-Annual Non-Commercial Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for eighteen (18) non-commercial cooking facility fire suppression systems across seventeen (17) designated facilities. All work shall be performed in strict accordance with manufacturer specifications, NFPA 17A (Standard for Wet Chemical Extinguishing Systems), and NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations). Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status and code compliance.EA2.00
CLIN 0003Fusible Link Replacement (NTE 400 Units)Provide replacement services for fusible links on an as-needed basis in strict accordance with NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) and NFPA 17A (Standard for Wet Chemical Extinguishing Systems). This is a unit-priced service billed per individual link utilized. To ensure compliance and strict accountability, all replaced (depleted/old) links must be retained and delivered directly to the Scott AFB Fire Prevention Section prior to invoice approval. Total performance under this CLIN shall not exceed a cumulative maximum of 400 fusible links across both services.EA400.00
CLIN 000412-Year Wet Chemical Cylinder Maintenance and Hydrostatic TestingProvide 12-year maintenance and hydrostatic testing services for fire suppression system cylinders on an as-needed, "when required" basis. All services, testing, and safety inspections shall be performed in strict accordance with NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10 (Standard for Portable Fire Extinguishers), and applicable Department of Transportation (DOT) hydrostatic testing regulations. This is a unit-priced service billed on a "per-cylinder" basis. The contractor shall only bill against this CLIN upon successful completion of the hydrostatic test and service for each authorized cylinder. No advance billing or flat-rate monthly billing is authorized; charges shall be incurred strictly on an as-used basis.EA7.00
CLIN 0005Reimbursable Fire Suppression System Replacement Parts (As-Needed)Contractor shall provide reimbursable replacement parts and components required to repair, maintain, or restore fire suppression systems to a fully operational status in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This comprehensive CLIN encompasses all necessary fire suppression system replacement parts, including, but not limited to: discharge nozzles, micro-switches, CO2 expellant/charging cartridges, wet chemical agent cylinders, piping, actuation devices, and detection linkages. Parts shall be billed strictly on an as-needed, reimbursable basis. For billing approval, the contractor must provide a fully itemized invoice that lists each specific part utilized separately alongside its associated unit cost.Unit1.00Not Priced
CLIN 0006Additional Corrective Maintenance Labor Hours (8 Hours)Additional Labor Hours (8 hours). Provide up to eight (8) additional, pre-authorized direct labor hours to perform corrective maintenance, emergency repairs, and the installation of replacement components. All labor-driven tasks—including the installation of replacement nozzles, mechanical or electrical switches, the swap-out of pressurized agent/CO2 charging cylinders, and system recertification—shall be executed in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This labor CLIN shall be billed at the established hourly rate, strictly on an as-needed, actual-hours-worked basis, and only when corrective actions exceed the baseline preventive maintenance scope.Hours8
CLIN 0007As-Needed Replacement of Nitrogen Expellant Cylinders (NTE 2 Cylinders/Year)Provide replacement services for overcharged, depleted, or physically damaged nitrogen expellant cylinders on an as-needed basis. All replacement cylinders, installation procedures, and safety testing shall strictly conform to NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10, and applicable DOT specifications. This is a unit-priced service billed at a fixed rate per cylinder, restricted to a maximum allowable quantity of two (2) cylinders per contract year. The contractor shall bill against this line item strictly upon successful installation, safety verification, and completion of the service.EA2.00

TOTAL

Option Year 4 Fire Suppression / Fusible Link Base Year

Item No Cost

Base Year
Option Year 1
Option Year 2
Option Year 3
Option Year 4
6 Month Extension

Total Cost

CLINTOPICREQUIREMENTCostUnitQuantityYearly total
CLIN 0001Semi-Annual Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for twenty-four (24) commercial kitchen fire suppression systems across twelve (12) facilities. Work shall be performed in accordance with manufacturer specifications and NFPA 96/17A standards. Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status.EA2.00
CLIN 0002Semi-Annual Non-Commercial Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for eighteen (18) non-commercial cooking facility fire suppression systems across seventeen (17) designated facilities. All work shall be performed in strict accordance with manufacturer specifications, NFPA 17A (Standard for Wet Chemical Extinguishing Systems), and NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations). Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status and code compliance.EA2.00
CLIN 0003Fusible Link Replacement (NTE 400 Units)Provide replacement services for fusible links on an as-needed basis in strict accordance with NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) and NFPA 17A (Standard for Wet Chemical Extinguishing Systems). This is a unit-priced service billed per individual link utilized. To ensure compliance and strict accountability, all replaced (depleted/old) links must be retained and delivered directly to the Scott AFB Fire Prevention Section prior to invoice approval. Total performance under this CLIN shall not exceed a cumulative maximum of 400 fusible links across both services.EA400.00
CLIN 000412-Year Wet Chemical Cylinder Maintenance and Hydrostatic TestingProvide 12-year maintenance and hydrostatic testing services for fire suppression system cylinders on an as-needed, "when required" basis. All services, testing, and safety inspections shall be performed in strict accordance with NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10 (Standard for Portable Fire Extinguishers), and applicable Department of Transportation (DOT) hydrostatic testing regulations. This is a unit-priced service billed on a "per-cylinder" basis. The contractor shall only bill against this CLIN upon successful completion of the hydrostatic test and service for each authorized cylinder. No advance billing or flat-rate monthly billing is authorized; charges shall be incurred strictly on an as-used basis.EA7.00
CLIN 0005Reimbursable Fire Suppression System Replacement Parts (As-Needed)Contractor shall provide reimbursable replacement parts and components required to repair, maintain, or restore fire suppression systems to a fully operational status in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This comprehensive CLIN encompasses all necessary fire suppression system replacement parts, including, but not limited to: discharge nozzles, micro-switches, CO2 expellant/charging cartridges, wet chemical agent cylinders, piping, actuation devices, and detection linkages. Parts shall be billed strictly on an as-needed, reimbursable basis. For billing approval, the contractor must provide a fully itemized invoice that lists each specific part utilized separately alongside its associated unit cost.Unit1.00Not Priced
CLIN 0006Additional Corrective Maintenance Labor Hours (8 Hours)Additional Labor Hours (8 hours). Provide up to eight (8) additional, pre-authorized direct labor hours to perform corrective maintenance, emergency repairs, and the installation of replacement components. All labor-driven tasks—including the installation of replacement nozzles, mechanical or electrical switches, the swap-out of pressurized agent/CO2 charging cylinders, and system recertification—shall be executed in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This labor CLIN shall be billed at the established hourly rate, strictly on an as-needed, actual-hours-worked basis, and only when corrective actions exceed the baseline preventive maintenance scope.Hours8
CLIN 0007As-Needed Replacement of Nitrogen Expellant Cylinders (NTE 2 Cylinders/Year)Provide replacement services for overcharged, depleted, or physically damaged nitrogen expellant cylinders on an as-needed basis. All replacement cylinders, installation procedures, and safety testing shall strictly conform to NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10, and applicable DOT specifications. This is a unit-priced service billed at a fixed rate per cylinder, restricted to a maximum allowable quantity of two (2) cylinders per contract year. The contractor shall bill against this line item strictly upon successful installation, safety verification, and completion of the service.EA2.00

TOTAL

6 Month Emergency Fire Suppression / Fusible Link Base Year

Item No Cost

Base Year
Option Year 1
Option Year 2
Option Year 3
Option Year 4
6 Month Extension

Total Cost

CLINTOPICREQUIREMENTCostUnitQuantityYearly total
CLIN 0001Semi-Annual Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for twenty-four (24) commercial kitchen fire suppression systems across twelve (12) facilities. Work shall be performed in accordance with manufacturer specifications and NFPA 96/17A standards. Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status.EA1.00
CLIN 0002Semi-Annual Non-Commercial Fire Suppression System Preventive MaintenanceProvide semi-annual preventive maintenance (PM) services for eighteen (18) non-commercial cooking facility fire suppression systems across seventeen (17) designated facilities. All work shall be performed in strict accordance with manufacturer specifications, NFPA 17A (Standard for Wet Chemical Extinguishing Systems), and NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations). Scope of work includes, but is not limited to, the inspection, testing, and replacement of all system discharge caps, and the replacement of system batteries as required to ensure fully operational status and code compliance.EA1.00
CLIN 0003Fusible Link Replacement (NTE 400 Units)Provide replacement services for fusible links on an as-needed basis in strict accordance with NFPA 96 (Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations) and NFPA 17A (Standard for Wet Chemical Extinguishing Systems). This is a unit-priced service billed per individual link utilized. To ensure compliance and strict accountability, all replaced (depleted/old) links must be retained and delivered directly to the Scott AFB Fire Prevention Section prior to invoice approval. Total performance under this CLIN shall not exceed a cumulative maximum of 400 fusible links across both services.EA200.00
CLIN 000412-Year Wet Chemical Cylinder Maintenance and Hydrostatic TestingProvide 12-year maintenance and hydrostatic testing services for fire suppression system cylinders on an as-needed, "when required" basis. All services, testing, and safety inspections shall be performed in strict accordance with NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10 (Standard for Portable Fire Extinguishers), and applicable Department of Transportation (DOT) hydrostatic testing regulations. This is a unit-priced service billed on a "per-cylinder" basis. The contractor shall only bill against this CLIN upon successful completion of the hydrostatic test and service for each authorized cylinder. No advance billing or flat-rate monthly billing is authorized; charges shall be incurred strictly on an as-used basis.EA7.00
CLIN 0005Reimbursable Fire Suppression System Replacement Parts (As-Needed)Contractor shall provide reimbursable replacement parts and components required to repair, maintain, or restore fire suppression systems to a fully operational status in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This comprehensive CLIN encompasses all necessary fire suppression system replacement parts, including, but not limited to: discharge nozzles, micro-switches, CO2 expellant/charging cartridges, wet chemical agent cylinders, piping, actuation devices, and detection linkages. Parts shall be billed strictly on an as-needed, reimbursable basis. For billing approval, the contractor must provide a fully itemized invoice that lists each specific part utilized separately alongside its associated unit cost.Unit1.00Not Priced
CLIN 0006Additional Corrective Maintenance Labor Hours (8 Hours)Additional Labor Hours (8 hours). Provide up to eight (8) additional, pre-authorized direct labor hours to perform corrective maintenance, emergency repairs, and the installation of replacement components. All labor-driven tasks—including the installation of replacement nozzles, mechanical or electrical switches, the swap-out of pressurized agent/CO2 charging cylinders, and system recertification—shall be executed in strict accordance with NFPA 17A, NFPA 96, and NFPA 72. This labor CLIN shall be billed at the established hourly rate, strictly on an as-needed, actual-hours-worked basis, and only when corrective actions exceed the baseline preventive maintenance scope.Hours4
CLIN 0007As-Needed Replacement of Nitrogen Expellant Cylinders (NTE 2 Cylinders/Year)Provide replacement services for overcharged, depleted, or physically damaged nitrogen expellant cylinders on an as-needed basis. All replacement cylinders, installation procedures, and safety testing shall strictly conform to NFPA 17A (Standard for Wet Chemical Extinguishing Systems), NFPA 10, and applicable DOT specifications. This is a unit-priced service billed at a fixed rate per cylinder, restricted to a maximum allowable quantity of two (2) cylinders per contract year. The contractor shall bill against this line item strictly upon successful installation, safety verification, and completion of the service.EA1.00

TOTAL

Facility Breakout Facility Owner Bldg # LOCATION ROOM # # of Systems System Type System Model Location of Nitrogen # of Links Hydro Date REMARKS

AES468In-Flight KitchenKitchen1CommercialPyro Chem10
FSS1192Golf CourseKitchen1CommercialANSUL R-10210
FSS1560SECKitchen3CommercialANSUL R-10232
AAFES1640ShoppetteKitchen1CommercialANSUL R-1026
AAFES1649Burger KingKitchen3CommercialANSUL R-1028
CCC1700Asian Joe'sKitchen2CommercialANSUL R-10210
FSS1800DFACKitchen5CommercialANSUL R-10238
FSS1805CDCKitchen1CommercialANSUL R-1026
FSS1807CDCKitchen1CommercialANSUL R-1024
FSS1934Bowling AlleyKitchen1CommercialANSUL R-10210
AAFES1981Base ExchangeFood Court4CommercialANSUL R-10238Food Court, Dominos, Charleys, Qdoba, Panda Express
FSS4780Youth CenterKitchen1CommercialPyro Chem10
CES57GOCESS1Non-CommercialGuardian III1
CES60HVAC1Non-CommercialGuardian III1
FSS382ALS1Non-CommercialGuardian III1
CES460Fire Station #1Kitchen1Non-CommercialAccurex2
CES504EOD1Non-CommercialGuardian III1
CES513heavy Equip1Non-CommercialGuardian III1
CES514Utilities1Non-CommercialGuardian III1
CES516Electric1Non-CommercialGuardian III1
CES528CES HQBreak Room1Non-CommercialGuardian III1
CES543WFMS1Non-CommercialGuardian III1
CES549Structures1Non-CommercialGuardian III1
WSA1620Chapel 11Non-CommercialGuardian III1
TRANSCOM1961USTRANSCOM Law1Non-CommercialGuardian III1
CES3300Waste Water Treat1Non-CommercialGuardian III1
CES3901Fire Station #3Kitchen1Non-CommercialGuardian III1
CES4560Fire Station #2Kitchen1Non-CommercialGuardian III1
SFS5490Dog Kennel1Non-CommercialGuardian III1

41 200