Atch 3 - AMENDED Equipment Salient Characteristics_8 Jun 26.pdf

PDF 127 KB Posted

Attached to
Purchase and installation of two (2) Closed-Circuit Fluid Coolers and Associated Pumps
Solicitation number
FA301626Q0120
Issued by

About this file

This is an Amended Salient Characteristics document specifying equipment requirements for the replacement of fluid coolers and pumps in Buildings 590 and 591.

The solicitation requires three categories of equipment to meet existing infrastructure compatibility and facility cooling loads. For the fluid cooler (cooling tower), proposed equipment must meet or exceed the cooling capacity of the existing SPX ReCold MW-30C model, fit the existing structural support pad, operate on 208/230V 3-Phase power, include dual fans of approximately 3.0 HP each or equivalent configuration to achieve required cooling performance, and incorporate an internal basin heater of approximately 4.0 KW. Circulation pumps must deliver a minimum flow rate of 110 GPM, feature a 5 HP continuous duty motor with standard 4-pole speed rated at approximately 1750-1760 RPM, and operate on 208/230V 3-Phase power. The disconnect panel must be rated for 208/120V 3-Phase 4-Wire power, include a 100A 3-pole main disconnect breaker with two 20A 3-pole breakers to isolate the cooler and pump, and be housed in a NEMA 3R outdoor-rated enclosure. All proposed equipment must strictly adhere to these physical dimensions, electrical requirements, and performance specifications to be considered acceptable.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDED SALIENT CHARACTERISTICS

FLUID COOLERS AND PUMPS REPLACEMENT (BLDGS 590 & 591)

To be considered an acceptable product, all proposed equipment must strictly adhere to the physical dimensions, electrical requirements, and performance capabilities outlined below to ensure compatibility with existing infrastructure and meet required facility cooling loads.

1. Fluid Cooler (Cooling Tower)

• Performance: Must meet or exceed the cooling capacity/tonnage of the existing SPX ReCold MW-30C.

• Footprint: Size must fit the existing structural support/pad.

• Electrical: Must operate on 208/230V, 3-Phase power.

• Fans: Dual fans (approx. 3.0 HP each) or an equivalent fan configuration that meets the required cooling performance.

• Heater: Must include an internal basin heater (approx. 4.0 KW).

2. Circulation Pumps

• Flow Rate: Minimum 110 GPM.

• Motor: 5 HP, continuous duty, standard 4-pole speed (approx. 1750-1760 RPM)

• Electrical: Must operate on 208/230V, 3-Phase power.

3. Disconnect Panel

• Power: Rated for 208/120V, 3-Phase, 4-Wire.

• Protection: Includes a 100A, 3-pole main disconnect breaker (including two 20A 3-pole breakers) to isolate the cooler and pump

• Enclosure: NEMA 3R (outdoor rated).